| Plan Review Stops For Permit 08110356 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2009-01-26 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2009-01-26 |
Time |
08:08 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2009-01-26 |
Time |
07:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-12-08 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-12-01 |
Time |
15:51 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-12-01 |
Time |
15:51 |
Sent To |
PC |
|
| Notes |
| 2008-12-01 15:52:35 | 1) FBC* 106.3.5.1.1(5) FLORIDA STATUTES 553.79(2) NOW | | | THE SPACE IS BEING ALTERED, PROVIDE THE LAYOUT OF THE | | | SPRINKLER HEADS IN RELATION TO THE NEW CONSTRUCTED | | | WALLS. THIS INFORMATION CAN BE SHOWN ON THE REFLECTED | | | CEILING PLANS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2009-03-06 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2009-03-06 |
Time |
11:29 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2009-03-06 |
Time |
11:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2009-01-23 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2009-01-23 |
Time |
12:05 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2009-01-23 |
Time |
11:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2008-12-08 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-12-08 |
Time |
11:18 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-12-08 |
Time |
10:46 |
Sent To |
|
|
| Notes |
| 2008-12-08 11:18:16 | | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 | | | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED, | | | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} AHU AND CU #S 1 & 2 SHEET E-2.01 DO NOT CORRELATE | | | WITH THE MECHANICAL SPECIFICATIONS ON SHEET M-2 | | | | | | .IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2009-01-26 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-01-26 |
Time |
10:07 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-01-26 |
Time |
09:54 |
Sent To |
|
|
| Notes |
| 2009-01-26 10:03:30 | *****APPROVED****** | | | | | | | | | PLAN SHEETS A-1.01, A-2.01, AND E-1.01 (PREVIOUSLY FIRE | | | STAMPED ON 12/08/2008) WERE RE-STAMPED, INITIALED, AND | | | DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2008-12-08 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-12-08 |
Time |
11:53 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-12-08 |
Time |
11:34 |
Sent To |
|
|
| Notes |
| 2008-12-08 11:47:44 | *****APPROVED****** | | | | | | | | | PLAN SHEETS A-1.01, A-2.01, AND E-1.01 WERE STAMPED, | | | INITIALED, AND DATED. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2009-02-27 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2009-02-27 |
Time |
10:45 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2009-02-27 |
Time |
10:45 |
Sent To |
|
|
| Notes |
| 2009-02-27 10:45:37 | TO "BOB"#15 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2009-02-04 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2009-02-04 |
Time |
11:02 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2009-02-04 |
Time |
11:02 |
Sent To |
P |
|
| Notes |
| 2009-02-04 11:02:55 | TO "P" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2009-01-20 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2009-01-20 |
Time |
14:03 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2009-01-20 |
Time |
14:03 |
Sent To |
|
|
| Notes |
| 2009-01-20 14:04:10 | TO "BOB"#7 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2008-12-08 |
Time |
|
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-11-18 |
Time |
14:15 |
Sent To |
|
|
| Notes |
| 2008-11-20 11:37:52 | TO "BOB" #9 | | 2008-11-18 14:16:01 | WAITING FOR "BOB" |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2009-03-25 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-03-25 |
Time |
15:23 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-03-25 |
Time |
14:12 |
Sent To |
PC |
|
| Notes |
| 2009-03-25 15:23:35 | REVISED M1 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2009-01-29 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-01-29 |
Time |
19:22 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-01-29 |
Time |
19:14 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2008-12-06 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-12-06 |
Time |
16:30 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-12-06 |
Time |
16:25 |
Sent To |
|
|
| Notes |
| 2008-12-06 16:30:25 | REVIEW #: 1ST | | | ACTION: PASSED WITH CONDITIONS (SEE BELOW) | | | | | | REVIEWED FOR COMPLIANCE WITH THE FOLLOWING: | | | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. PAGE M-2 CALLS FOR CU ATTACHMENT TO SLAB IN | | | ACCORDANCE WITH 301.13.1. THIS SECTION AND PRESCRIPTIVE | | | METHOD IS ONLY APPLICABLE TO R-3 OCCUPANCIES. PLEASE | | | PROVIDE DETAIL WITH WIND CALCULATIONS OR MANUFACTURER'S | | | INFORMATION FOR WIND LOAD ATTACHMENT IN ACCORDANCE WITH | | | FBCM 301.13. | | | | | | 2. PLANS HAVE BEEN MODIFIED WITH WHITE-OUT. WHEN | | | REVISING PLANS TO ADDRESS THE ABOVE COMMENT, PLEASE | | | MAKE NECESSARY CORRECTIONS WITHOUT ALTERING THE PLANS | | | IN ACCORDANCE WITH FBCB 106.1.3. | | | | | | NOTE: ENERGY CALCULATIONS WILL BE SIGNED/STAMPED WHEN | | | PLUMBING COMMENTS HAVE BEEN ADDRESSED. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2009-02-13 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-02-13 |
Time |
16:34 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-02-13 |
Time |
16:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2009-01-27 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-01-27 |
Time |
12:20 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-01-27 |
Time |
12:20 |
Sent To |
|
|
| Notes |
| 2009-01-27 12:33:26 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 BUILDING | | | FBC-2004 CHAPTER 1 | | | | | | ****FROM PREVIOUS REVIEW: | | | | | | 1. OK | | | | | | 2. THE ENERGY EFFICIENCY CALCULATIONS INDICATE "N/A" | | | FOR THE HOT WATER, BUT THE PLANS INDICATE A TANKLESS | | | WATER HEATER FOR THE P-4 SINK IN THE BREAK ROOM. PLEASE | | | CLARIFY/CORRELATE. SECTION 13. | | | ****RESPONSE NOTED, BUT THE NEW ENERGY CALCULATIONS | | | STILL INDICATE "N/A" ON THE SYSTEMS INFORMATION AND ON | | | THE CHECK LIST FOR PRESCRIPTIVE MEASURES. PLANS STILL | | | SHOW A TANKLESS WATER HEATER. PLEASE CORRELATE. | | | | | | 3. OK | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2008-12-02 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-12-02 |
Time |
09:59 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-12-02 |
Time |
09:59 |
Sent To |
|
|
| Notes |
| 2008-12-02 10:08:40 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 BUILDING | | | FBC-2004 CHAPTER 1 | | | | | | 1. SUBMIT A SANITARY AND WATER RISER DIAGRAM TO REFLECT | | | ALL WORK SHOWN ON THE FLOOR PLAN. FOR THE SANITARY SHOW | | | ALL PIPE SIZES, TRAPS, VENTS, CONNECTIONS TO WASTE | | | STACKS & VENT THRU THE ROOF. FOR WATER SHOW ALL PIPE | | | SIZES, VALVES AND, (WHERE REQUIRED BY SECTION 604.9), | | | WATER HAMMER ARRESTORS. SECTIONS | | | 106.3.5.1.3(3)(4)(5)(6)(10)(13) 601.1, 604.1, 604.5, | | | 701.1, 704.1, 708, 709, 710, 901.1, 904, 905 & 916. | | | | | | 2. THE ENERGY EFFICIENCY CALCULATIONS INDICATE "N/A" | | | FOR THE HOT WATER, BUT THE PLANS INDICATE A TANKLESS | | | WATER HEATER FOR THE P-4 SINK IN THE BREAK ROOM. PLEASE | | | CLARIFY/CORRELATE. SECTION 13. | | | | | | 3. SHT A-1.01 HAS WHITE OUT FOR THE APPLICABLE CODES ON | | | THE DATE FOR THE 2007 SUPPLEMENTS. PER SECTION 106.1.3 | | | WHITE OUT IS NOT APPROVED ON PLANS SUBMITTED FOR PUBLIC | | | RECORD. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2008-11-21 |
|
|
Cont ID |
|
| Sent By |
kdfreema |
Date |
2008-11-21 |
Time |
11:21 |
Rev Time |
0.00 |
| Received By |
kdfreema |
Date |
2008-11-21 |
Time |
11:21 |
Sent To |
|
|
| Notes |
|
|