Plan Review Details - Permit 08110356
Plan Review Stops For Permit 08110356
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-01-26 Cont ID  
Sent By mjacobs Date 2009-01-26 Time 08:08 Rev Time 0.00
Received By mjacobs Date 2009-01-26 Time 07:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-12-08 Cont ID  
Sent By mjacobs Date 2008-12-01 Time 15:51 Rev Time 0.00
Received By mjacobs Date 2008-12-01 Time 15:51 Sent To PC
Notes
2008-12-01 15:52:351) FBC* 106.3.5.1.1(5) FLORIDA STATUTES 553.79(2) NOW
 THE SPACE IS BEING ALTERED, PROVIDE THE LAYOUT OF THE
 SPRINKLER HEADS IN RELATION TO THE NEW CONSTRUCTED
 WALLS. THIS INFORMATION CAN BE SHOWN ON THE REFLECTED
 CEILING PLANS.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-03-06 Cont ID  
Sent By btrobaug Date 2009-03-06 Time 11:29 Rev Time 0.00
Received By btrobaug Date 2009-03-06 Time 11:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-01-23 Cont ID  
Sent By btrobaug Date 2009-01-23 Time 12:05 Rev Time 0.00
Received By btrobaug Date 2009-01-23 Time 11:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-12-08 Cont ID  
Sent By btrobaug Date 2008-12-08 Time 11:18 Rev Time 0.00
Received By btrobaug Date 2008-12-08 Time 10:46 Sent To  
Notes
2008-12-08 11:18:16 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} AHU AND CU #S 1 & 2 SHEET E-2.01 DO NOT CORRELATE
 WITH THE MECHANICAL SPECIFICATIONS ON SHEET M-2
  
 .IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-01-26 Cont ID  
Sent By mawillia Date 2009-01-26 Time 10:07 Rev Time 0.00
Received By mawillia Date 2009-01-26 Time 09:54 Sent To  
Notes
2009-01-26 10:03:30*****APPROVED******
  
  
 PLAN SHEETS A-1.01, A-2.01, AND E-1.01 (PREVIOUSLY FIRE
 STAMPED ON 12/08/2008) WERE RE-STAMPED, INITIALED, AND
 DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2008-12-08 Cont ID  
Sent By mawillia Date 2008-12-08 Time 11:53 Rev Time 0.00
Received By mawillia Date 2008-12-08 Time 11:34 Sent To  
Notes
2008-12-08 11:47:44*****APPROVED******
  
  
 PLAN SHEETS A-1.01, A-2.01, AND E-1.01 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-02-27 Cont ID  
Sent By adarroug Date 2009-02-27 Time 10:45 Rev Time 0.00
Received By adarroug Date 2009-02-27 Time 10:45 Sent To  
Notes
2009-02-27 10:45:37TO "BOB"#15

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-02-04 Cont ID  
Sent By adarroug Date 2009-02-04 Time 11:02 Rev Time 0.00
Received By adarroug Date 2009-02-04 Time 11:02 Sent To P
Notes
2009-02-04 11:02:55TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-01-20 Cont ID  
Sent By adarroug Date 2009-01-20 Time 14:03 Rev Time 0.00
Received By adarroug Date 2009-01-20 Time 14:03 Sent To  
Notes
2009-01-20 14:04:10TO "BOB"#7

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2008-12-08 Time   Rev Time 0.00
Received By adarroug Date 2008-11-18 Time 14:15 Sent To  
Notes
2008-11-20 11:37:52TO "BOB" #9
2008-11-18 14:16:01WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-03-25 Cont ID  
Sent By rregueir Date 2009-03-25 Time 15:23 Rev Time 0.00
Received By rregueir Date 2009-03-25 Time 14:12 Sent To PC
Notes
2009-03-25 15:23:35REVISED M1

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-01-29 Cont ID  
Sent By rregueir Date 2009-01-29 Time 19:22 Rev Time 0.00
Received By rregueir Date 2009-01-29 Time 19:14 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-12-06 Cont ID  
Sent By rregueir Date 2008-12-06 Time 16:30 Rev Time 0.00
Received By rregueir Date 2008-12-06 Time 16:25 Sent To  
Notes
2008-12-06 16:30:25REVIEW #: 1ST
 ACTION: PASSED WITH CONDITIONS (SEE BELOW)
  
 REVIEWED FOR COMPLIANCE WITH THE FOLLOWING:
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE M-2 CALLS FOR CU ATTACHMENT TO SLAB IN
 ACCORDANCE WITH 301.13.1. THIS SECTION AND PRESCRIPTIVE
 METHOD IS ONLY APPLICABLE TO R-3 OCCUPANCIES. PLEASE
 PROVIDE DETAIL WITH WIND CALCULATIONS OR MANUFACTURER'S
 INFORMATION FOR WIND LOAD ATTACHMENT IN ACCORDANCE WITH
 FBCM 301.13.
  
 2. PLANS HAVE BEEN MODIFIED WITH WHITE-OUT. WHEN
 REVISING PLANS TO ADDRESS THE ABOVE COMMENT, PLEASE
 MAKE NECESSARY CORRECTIONS WITHOUT ALTERING THE PLANS
 IN ACCORDANCE WITH FBCB 106.1.3.
  
 NOTE: ENERGY CALCULATIONS WILL BE SIGNED/STAMPED WHEN
 PLUMBING COMMENTS HAVE BEEN ADDRESSED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-02-13 Cont ID  
Sent By kstevens Date 2009-02-13 Time 16:34 Rev Time 0.00
Received By kstevens Date 2009-02-13 Time 16:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2009-01-27 Cont ID  
Sent By kstevens Date 2009-01-27 Time 12:20 Rev Time 0.00
Received By kstevens Date 2009-01-27 Time 12:20 Sent To  
Notes
2009-01-27 12:33:26DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
  
 2. THE ENERGY EFFICIENCY CALCULATIONS INDICATE "N/A"
 FOR THE HOT WATER, BUT THE PLANS INDICATE A TANKLESS
 WATER HEATER FOR THE P-4 SINK IN THE BREAK ROOM. PLEASE
 CLARIFY/CORRELATE. SECTION 13.
 ****RESPONSE NOTED, BUT THE NEW ENERGY CALCULATIONS
 STILL INDICATE "N/A" ON THE SYSTEMS INFORMATION AND ON
 THE CHECK LIST FOR PRESCRIPTIVE MEASURES. PLANS STILL
 SHOW A TANKLESS WATER HEATER. PLEASE CORRELATE.
  
 3. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-12-02 Cont ID  
Sent By kstevens Date 2008-12-02 Time 09:59 Rev Time 0.00
Received By kstevens Date 2008-12-02 Time 09:59 Sent To  
Notes
2008-12-02 10:08:40DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
  
 1. SUBMIT A SANITARY AND WATER RISER DIAGRAM TO REFLECT
 ALL WORK SHOWN ON THE FLOOR PLAN. FOR THE SANITARY SHOW
 ALL PIPE SIZES, TRAPS, VENTS, CONNECTIONS TO WASTE
 STACKS & VENT THRU THE ROOF. FOR WATER SHOW ALL PIPE
 SIZES, VALVES AND, (WHERE REQUIRED BY SECTION 604.9),
 WATER HAMMER ARRESTORS. SECTIONS
 106.3.5.1.3(3)(4)(5)(6)(10)(13) 601.1, 604.1, 604.5,
 701.1, 704.1, 708, 709, 710, 901.1, 904, 905 & 916.
  
 2. THE ENERGY EFFICIENCY CALCULATIONS INDICATE "N/A"
 FOR THE HOT WATER, BUT THE PLANS INDICATE A TANKLESS
 WATER HEATER FOR THE P-4 SINK IN THE BREAK ROOM. PLEASE
 CLARIFY/CORRELATE. SECTION 13.
  
 3. SHT A-1.01 HAS WHITE OUT FOR THE APPLICABLE CODES ON
 THE DATE FOR THE 2007 SUPPLEMENTS. PER SECTION 106.1.3
 WHITE OUT IS NOT APPROVED ON PLANS SUBMITTED FOR PUBLIC
 RECORD.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status N Date 2008-11-21 Cont ID  
Sent By kdfreema Date 2008-11-21 Time 11:21 Rev Time 0.00
Received By kdfreema Date 2008-11-21 Time 11:21 Sent To  
Notes
***NONE***