Plan Review Details - Permit 08110335
Plan Review Stops For Permit 08110335
Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2009-08-13 Cont ID  
Sent By mawillia Date 2009-08-13 Time 15:55 Rev Time 0.00
Received By mawillia Date 2009-08-13 Time 15:15 Sent To  
Notes
2009-08-13 15:55:49*****REVSIONS #1 AND #2, APPROVED*****
  
 REVISED PLAN SHEET FP2 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2009-07-30 Cont ID  
Sent By mawillia Date 2009-07-30 Time 15:12 Rev Time 0.00
Received By mawillia Date 2009-07-30 Time 14:31 Sent To  
Notes
2009-07-30 15:08:19*****UNSAT*****
  
 1. IN THE HYDRAULIC DESIGN INFORMATION, THE HYDRAULIC
 SUMMARY SHOWS THE SAFETY MARGIN AS 2.84 PSI; AS PER THE
 WEST PALM BEACH BUREAU OF FIRE PREVENTION, A SAFETY
 MARGIN OF AT LEAST 5.0 PSI IS REQUIRED.
  
 2. PROVIDE CUT SHEETS/SPECS/SUBMITTALS FOR THE VARIOUS
 FIRE SPRINKLERS.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-03-04 Cont ID  
Sent By mwennerg Date 2009-03-04 Time 15:17 Rev Time 0.00
Received By mwennerg Date 2009-03-04 Time 15:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-12-11 Cont ID  
Sent By mwennerg Date 2008-12-11 Time 10:15 Rev Time 0.00
Received By mwennerg Date 2008-12-11 Time 10:15 Sent To  
Notes
2008-12-11 10:40:48***DENIED***
  
 1) PLEASE CLARIFY THE LOCATION OF THE DOUBLE CHECK
 DETECTOR ASSEMBY AND FIRE DEPARTMENT CONNECTION ON THE
 SITE PLAN. A PREVIOUS FIELD VISIT SHOWED THE PROPOSED
 EQUIPMENT ON THE SOUTH SIDE OF THE PROJECT. THIS
 INFORMATION CAN'T BE VERIFIED WITHOUT THE DIRECTION
 ILLUSTRATED ON THE FIRE LINE SITE DRAWING.
  
 2) ALL CALCULATION SUBMITTALS, DRAWINGS AND PERMIT
 APPLICATION SHOW THE PROJECT ADDRESS AS 1501 N.
 AUSTRALIAN AVE. IT IS MY UNDERSTANDING THAT THE
 EXISTING BUILDING IS 1501 AND THE NEW BUILDING IS 1505.
 PLEASE VERIFY ADDRESS AND MAKE APPROPRIATE CORRECTIONS.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-02-09 Cont ID  
Sent By adarroug Date 2009-02-09 Time 11:09 Rev Time 0.00
Received By adarroug Date 2009-02-09 Time 11:09 Sent To FIRE
Notes
2009-02-09 11:09:31TO "F" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-12-11 Cont ID  
Sent By mwennerg Date 2008-12-11 Time 10:41 Rev Time 0.00
Received By mwennerg Date 2008-11-18 Time 09:41 Sent To  
Notes
2008-11-18 09:42:04TO "F" BOX