| Plan Review Stops For Permit 08110332 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2009-05-12 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2009-05-12 |
Time |
13:53 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2009-05-12 |
Time |
13:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2009-04-29 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2009-04-29 |
Time |
10:10 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2009-04-29 |
Time |
10:10 |
Sent To |
|
|
| Notes |
| 2009-04-29 10:15:22 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FS FLORIDA STATUTE | | | | | | FROM PREVIOUS LIST: | | | | | | 6. ALL INFORMATION REQUIRED BY FAC61G1-15.003, 004, IS | | | REQUIRED ON EACH SHEET (CERTIFICATE OF AUTHORIZATION | | | FOR T. Y. LIN INTERNATIONAL). | | | | | | 2ND REVIEW, PLEASE INCLUDE CERTIFICATE OF AUTHORIZATION | | | IN TITLE BLOCK. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2009-04-01 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2009-04-01 |
Time |
15:27 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2009-04-01 |
Time |
15:27 |
Sent To |
|
|
| Notes |
| 2009-04-01 15:28:24 | ****REVISED COMMENT LIST 4/1/09**** | | | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FS FLORIDA STATUTE | | | | | | 1. N/A; PER A. JONES, LOT SUBDIVIDED PRIOR TO | | | CONSTRUCTION. | | | | | | 2. FBC EB 301.5, DECLARE LEVEL OF ALTERATION. | | | | | | 3. INFORMATIONAL ONLY - THE ADDRESS DOES NOT MATCH PAPA | | | RECORDS. THE CITY IS WORKING WITH THE COUNTY TO GET | | | PAPA RECORDS CHANGED TO REFLECT THE CORRECT ADDRESS. | | | | | | 4. SHEET SP1, A03, DOCUMENTS PREPARED BY AN ARCHITECT | | | AND SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, | | | SEALED, DATED ORIGINALS FS481. IT IS LIKELY THAT THIS | | | WAS SUBMITTED FOR INFORMATIONAL PURPOSES ONLY, BUT DUE | | | TO COMMENT #1 THIS IS REQUIRED TO SHOW CODE COMPLIANCE. | | | PLEASE ALSO BE ADVISED THAT, EVEN IF SUBMITTED AS | | | INFORMATIONAL ONLY, THE FLORIDA STATUTE STILL APPLIES | | | (NO EXEMPTION TO BEING SIGNED AND SEALED). | | | | | | 5. THE SITE PLAN SUBMITTED SHOWS A RAMP IN THE ACCESS | | | AISLE. FBC11-4.6.3 REGARDING ACCESS AISLE SLOPE, 2% IN | | | ALL DIRECTIONS. THIS IS IN CONFLICT WITH THE STATEMENT | | | ON THE PLAN THAT STATES THAT VARIOUS ELEMENTS ARE IN | | | COMPLIANCE WITH ADAAG. | | | | | | 6. ALL INFORMATION REQUIRED BY FAC61G15-23.002 IS | | | REQUIRED ON EACH SHEET (CERTIFICATE OF AUTHORIZATION | | | FOR T. Y. LIN INTERNATIONAL). | | | | | | 7. THE ADDRESS IN THE TITLE BLOCK FOR T. Y. LIN | | | INTERNATIONAL DOES NOT MATCH THE WEBSITE, | | | MYFLORIDALICENSE.COM. | | | | | | 8. PROVIDE FLORIDA STATE OR LOCAL PRODUCT APPROVALS FOR | | | THE 4'X5' DRIVE THRU WINDOW, FAC9B72 (+33.7/-36.7PSF DP | | | REQUIRED SHEET A0.0). | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-12-04 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-12-04 |
Time |
09:40 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-12-04 |
Time |
09:40 |
Sent To |
|
|
| Notes |
| 2008-12-04 09:54:16 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FS FLORIDA STATUTE | | | | | | 1. PLEASE SEE ZONING COMMENTS. CODE COMPLIANCE WITH FBC | | | TABLE 602 MUST BE SHOWN AS, WHEN PERMITTED, CODE | | | COMPLIANCE WAS DEMONSTRATED BASED ON AN ASSUMED | | | PROPERTY LINE BETWEEN TWO BUILDINGS RATHER THAN | | | DISTANCE TO THE PROPERTY LINE. IT APPEARS THAT THERE IS | | | NO ISSUE IN THIS CASE, BUT PLEASE SHOW CMOPLIANCE WITH | | | FBC TABLE 602, 704.8. | | | | | | 2. FBC EB 301.5, DECLARE LEVEL OF ALTERATION. | | | | | | 3. INFORMATIONAL ONLY - THE ADDRESS DOES NOT MATCH PAPA | | | RECORDS. THE CITY IS WORKING WITH THE COUNTY TO GET | | | PAPA RECORDS CHANGED TO REFLECT THE CORRECT ADDRESS. | | | | | | 4. SHEET SP1, A03, DOCUMENTS PREPARED BY AN ARCHITECT | | | AND SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, | | | SEALED, DATED ORIGINALS FS481. IT IS LIKELY THAT THIS | | | WAS SUBMITTED FOR INFORMATIONAL PURPOSES ONLY, BUT DUE | | | TO COMMENT #1 THIS IS REQUIRED TO SHOW CODE COMPLIANCE. | | | PLEASE ALSO BE ADVISED THAT, EVEN IF SUBMITTED AS | | | INFORMATIONAL ONLY, THE FLORIDA STATUTE STILL APPLIES | | | (NO EXEMPTION TO BEING SIGNED AND SEALED). | | | | | | 5. THE SITE PLAN SUBMITTED SHOWS A RAMP IN THE ACCESS | | | AISLE. FBC11-4.6.3 REGARDING ACCESS AISLE SLOPE, 2% IN | | | ALL DIRECTIONS. THIS IS IN CONFLICT WITH THE STATEMENT | | | ON THE PLAN THAT STATES THAT VARIOUS ELEMENTS ARE IN | | | COMPLIANCE WITH ADAAG. | | | | | | 6. ALL INFORMATION REQUIRED BY FAC61G1-15.003, 004, IS | | | REQUIRED ON EACH SHEET (CERTIFICATE OF AUTHORIZATION | | | FOR T. Y. LIN INTERNATIONAL). | | | | | | 7. THE ADDRESS IN THE TITLE BLOCK FOR T. Y. LIN | | | INTERNATIONAL DOES NOT MATCH THE WEBSITE, | | | MYFLORIDALICENSE.COM. | | | | | | 8. PROVIDE FLORIDA STATE OR LOCAL PRODUCT APPROVALS FOR | | | THE 4'X5' DRIVE THRU WINDOW, FAC9B72 (+33.7/-36.7PSF DP | | | REQUIRED SHEET A0.0). | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2009-05-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-05-08 |
Time |
16:58 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-05-08 |
Time |
16:58 |
Sent To |
|
|
| Notes |
| 2009-05-08 16:59:03 | PERMIT APPLICATION NOT IN PCKAGE. CALLED CONTRACTOR AS | | | THIS WAS MISSING FROM THE FIRST REVIEW BY THE PLUMBING | | | REVIEWER. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2009-04-16 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-04-16 |
Time |
10:04 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-04-16 |
Time |
10:04 |
Sent To |
|
|
| Notes |
| 2009-04-16 10:05:06 | ** DENIED 2ND REVIEW** | | | | | | | | | | | | 1) NOTE: TITLE BLOCKS ARE STILL MISSING THE REQUIRED | | | CERTIFICATE OF AUTHORIZATION NUMBER AS REQUIRED UNDER | | | FS 471.023. THIS IS REQUIRED ON ALL SHEETS WHETHER OR | | | NOT COMMENT IS MADE BY OTHER TRADES. | | | THE PRINTED LICENSE NUMBER OF THE ENGINEER WAS ADDED | | | HOWEVER THIS IS NOT THE C OF A REQUIRED TO BE ON TITLE | | | BLOCKS. | | | FAC 61G15-23.002 | | | | | | 2) NOTE: CODES NOT STATED ON ELECTRICAL PLANS. THE | | | PLANS SIMPLY STATE THE LATEST ADOPTED CODES WHICH IS | | | NOT ACCEPTABLE. IF THE LATEST ADOPTED CODES WERE USED | | | THIS WOULD PLACE THE ENTIRE PROJECT UNDER THE 2007 FBC | | | WITH 2009 GLITCH AMENDMENTS. | | | PLEASE STATE THE FOLLOWING AT A MINIMUM FOR THIS REVIEW | | | TRADE ON ELECTRICAL PLANS. | | | 2004 FBC W/2007 REVISIONS. | | | 2005 NFPA-70 | | | 2003 NFPA-101 | | | | | | 3) NOTE: AS NOTED ALSO ON PREVIOUS REVIEW THE PLANS | | | CONTAIN CODE REFERENCES FROM THE 1996 NEC. THE 1996 NEC | | | HAS NOT BEEN AN ADOPTED CODE FOR MANY CODE CYCLES. THIS | | | HAS BEEN MORE THAN 10YEARS. | | | PLEASE ADJUST. (SEE NOTES ON E-SHEET). | | | 250.122, NEC 2005 | | | | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2008-12-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-12-15 |
Time |
16:46 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-12-15 |
Time |
16:46 |
Sent To |
|
|
| Notes |
| 2008-12-15 16:46:38 | ** DENIED REVIEW ** | | | | | | 1) NOTE: PLEASE SEE FLORIDA ADMINISTRATIVE CODE | | | 61G15-23.002, FLORIDA STATUTES 471.023 AS THE TITLE | | | BLOCKS ARE MISSING REQUIRED LICENSING. THE CERTIFICATE | | | OF AUTHORIZATION NUMBER IS MISSING AND REQUIRED. | | | THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES | | | WHETHER OR NOT COMMENT IS MADE BY ANY OTHER TRADE. | | | | | | 2) NOTE: THE FOLLOWING CODES SHALL BE STATED ON | | | ELECTRICAL PLANS FOR THIS REVIEWER AT A MINIMUM. PLEASE | | | BE SURE ALL CODES ON PLANS ARE UPDATED. FOR EXAMPLE | | | THERE IS A CODE SECTION REFERENCE FROM THE 1996 | | | NATIONAL ELECTRICAL CODE. THIS CODE HAS NOT BEEN | | | ADOPTED IN MANY CODE CYCLES. | | | | | | 3) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS ON | | | EXISTING MAIN PANEL PP IN WHICH THE NEW PANEL CBB IS | | | BEING ADDED WITH NEW LOADS AS WELL AS EXISTING. | | | PLEASE BE SURE ALL CONTINUOUS LOADS ARE SHOWN AT 125%. | | | 220,230.42,215.3 ETC | | | | | | FBC 106.1.1, 106.3.5.1.2 FOR ADDITIONAL INFORMATION AND | | | CLARITY OF PLANS. | | | | | | 4) NOTE: PLEASE SUBMIT A RISER DIAGRAM FOR NEW FEEDERS | | | ETC. | | | 215.5, 310.16,240.4 ETC | | | | | | | | | | | | **IMPORTANT** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED | | | INTO TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2009-05-12 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-05-12 |
Time |
11:08 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-05-12 |
Time |
11:01 |
Sent To |
B1 |
|
| Notes |
| 2009-05-12 11:08:33 | *****APPROVED***** | | | | | | PLAN SHEET A0.0 STAMPED, INITIALED, AND INITIALED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2009-04-22 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-04-22 |
Time |
13:42 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-04-22 |
Time |
13:28 |
Sent To |
|
|
| Notes |
| 2009-04-22 13:42:44 | *****PENDING***** | | | | | | THE APPROPIATE PLAN SHEET(S) TO BE FIRE-STAMPED WHEN | | | THE OTHER PLAN EXAMINERS' COMMENTS HAVE BEEN ADDRESSED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2008-12-15 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-12-15 |
Time |
14:55 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-12-15 |
Time |
14:55 |
Sent To |
|
|
| Notes |
| 2008-12-15 15:16:29 | ***DENIED*** | | | | | | PLEASE SEE ZONING COMMENT #2. FIRE PLAN REVIEW WILL | | | REMAIN IN FAILED STATUS UNTIL PROPERTY ZONING ISSUES | | | HAVE BEEN CORRECTED. | | | | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2009-04-30 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-04-30 |
Time |
16:50 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-04-30 |
Time |
16:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2009-04-07 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2009-04-07 |
Time |
10:50 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2009-04-07 |
Time |
10:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-12-18 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-12-18 |
Time |
11:44 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-11-18 |
Time |
13:30 |
Sent To |
|
|
| Notes |
| 2008-11-18 13:32:30 | TO "COMM" BD#42 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2009-05-06 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-05-06 |
Time |
12:02 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-05-06 |
Time |
12:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2009-04-22 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-04-22 |
Time |
14:11 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-04-22 |
Time |
14:11 |
Sent To |
|
|
| Notes |
| 2009-04-22 14:18:50 | DENIED | | | REFERENCE: | | | FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | ****FROM PREVIOUS REVIEW: | | | | | | 1. ALL SHEETS A TITLE BLOCK SHALL BE USED ON EACH SHEET | | | CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE | | | NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND | | | LICENSE NUMBER OF THE ENGINEER, AND IF PRACTICING | | | THROUGH A DULY AUTHORIZED ENGINEERING BUSINESS, THE | | | NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER | | | OF THE ENGINEERING BUSINESS. FAC 61G15-23.002(2) & FS | | | 471.025. | | | ****RESPONSE NOTED, BUT THE CERTIFICATE OF | | | AUTHORIZATION, (9536), IS NOT IN THE TITLE BLOCK ON | | | EACH SHEET AS REQUIRED. | | | | | | 2. OK | | | | | | 3. SHT A1.0 HOT & COLD WATER RISER DIAGRAM. AIR | | | CHAMBERS ARE NOT APPROVED. PLEASE DELETE FROM RISER. | | | SECTION 604.9. WATER HAMMER ARRESTORS ARE REQUIRED FOR | | | QUICK CLOSING VALVES ONLY. IF INSTALLED THEY SHALL BE | | | INSTALLED NEAR THE FIXTURES IN AN "EFFECTIVE RANGE" NOT | | | IN THE CEILING. PDI-WH 201. | | | ****RESPONSE NOTED, BUT WATER HAMMER ARRESTORS ARE | | | SHOWN IN THE CEILING, NOT NEAR THE FIXTURE AS REQUIRED. | | | | | | 4. SHTS K1, K2 & K3 THE PERSON DESINGING THE PLANS | | | SHALL PRINT THEIR NAME ANS AFFIX THEIR SIGNATURE AS THE | | | PERSON RESPONSIBLE FOR THE PLANS. SECTION 106.1.3. | | | ****RESPONSE NOTED, BUT PLANS WERE NOT MARKED, "FOR | | | REFERENCE ONLY" AS INDICATED IN RESPONSE. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2008-12-18 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-12-18 |
Time |
11:21 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-12-18 |
Time |
11:21 |
Sent To |
|
|
| Notes |
| 2008-12-18 11:35:00 | DENIED | | | REFERENCE: | | | FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1. ALL SHEETS A TITLE BLOCK SHALL BE USED ON EACH SHEET | | | CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE | | | NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND | | | LICENSE NUMBER OF THE ENGINEER, AND IF PRACTICING | | | THROUGH A DULY AUTHORIZED ENGINEERING BUSINESS, THE | | | NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER | | | OF THE ENGINEERING BUSINESS. FAC 61G15-23.002(2) & FS | | | 471.025. | | | | | | 2. SHT CV 1 OF 1 PLEASE INDICATE THE 2007 REVISIONS TO | | | THE FBC-2004 IN THE BUILDING CODE SUMMARY. SECTION | | | 1-6.1.1. | | | | | | 3. SHT A1.0 HOT & COLD WATER RISER DIAGRAM. AIR | | | CHAMBERS ARE NOT APPROVED. PLEASE DELETE FROM RISER. | | | SECTION 604.9. WATER HAMMER ARRESTORS ARE REQUIRED FOR | | | QUICK CLOSING VALVES ONLY. IF INSTALLED THEY SHALL BE | | | INSTALLED NEAR THE FIXTURES IN AN "EFFECTIVE RANGE" NOT | | | IN THE CEILING. PDI-WH 201. | | | | | | 4. SHTS K1, K2 & K3 THE PERSON DESINGING THE PLANS | | | SHALL PRINT THEIR NAME ANS AFFIX THEIR SIGNATURE AS THE | | | PERSON RESPONSIBLE FOR THE PLANS. SECTION 106.1.3. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
N |
Date |
2009-04-14 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2009-04-14 |
Time |
15:55 |
Rev Time |
0.00 |
| Received By |
lfranco |
Date |
2009-04-14 |
Time |
15:55 |
Sent To |
|
|
| Notes |
| 2009-04-14 15:58:47 | PLANNING AND ZONING: **** PASSED **** | | | | | | NOTATION: ILLEGAL SUBDIVISION COMMENT PASSED/OK PER | | | ANGELLA JONES VANN, PLANNING AND ZONING ADMINISTRATOR. | | | | | | LMF | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2008-11-25 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2008-11-25 |
Time |
20:30 |
Rev Time |
0.00 |
| Received By |
lfranco |
Date |
2008-11-25 |
Time |
20:30 |
Sent To |
|
|
| Notes |
| 2008-11-25 20:38:40 | PLANNING AND ZONING: **** FAILED **** | | | | | | 1. RESPOND TO COMMENTS IN WRITING. | | | | | | 2. THIS PARCEL IS PART OF THE NORTHTRAIL PLAZA CPD, | | | PURSUANT TO ORDINANCE NOS. 1853-85, 22245-88, SNF | | | 2442-91, THIS PROPERTY AND PERTINENT PROPERTIES WITHIN | | | THE PARCEL HAVE BEEN ILLEGALLY SUBDIVIDED AND SOLD OFF | | | AS SEPARATE PARCELS. AS A RESULT, ANY DEVELOPMENTS | | | ORDERS, TO INCLUDE BUILDING PERMITS WITH THE EXCEPTION | | | OF LIFE SAFETY SYSTEMS (I.E. FIRE EXTINGUISHERS, FIRE | | | SPRINKLES, FIRE DETECTION AND ALARM SYSTEMS. ETCETERA), | | | FOR THE IS NOT ALLOWED UNTIL ALL PROPERTIES FILE AND | | | RECEIVE APPROVAL OF A REPLAT OF THE OF THE NORTH TRAIL | | | PLAZA PARCEL(S) THROUGH THE CITY?S SUBDIVISION PROCESS; | | | AND A MAJOR AMENDMENT TO THE NORTH TRAIL CPD TO ADDRESS | | | ORDINANCES REQUIREMENTS. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL ME AT THE NUMBER | | | BELOW. | | | | | | LINDA MIA FRANCO | | | SENIOR PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: (561) 822-1443 | | | EMAIL: [email protected] | | | | | | |
|
|