Plan Review Details - Permit 08110316
Plan Review Stops For Permit 08110316
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-02-05 Cont ID  
Sent By mjacobs Date 2009-02-05 Time 09:31 Rev Time 0.00
Received By mjacobs Date 2009-02-05 Time 09:31 Sent To PC
Notes
2009-02-03 13:18:452-3-09 WAITING FOR ADDITIONAL INFORMATION FROM THE
 OWNER. MJ

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-12-24 Cont ID  
Sent By mjacobs Date 2008-12-24 Time 13:36 Rev Time 0.00
Received By mjacobs Date 2008-12-24 Time 13:36 Sent To PC
Notes
2008-12-24 13:36:20BUILDING PLAN REVIEW
 PERMIT: 08110316
 ADD: 501 27TH STREET
 CONT: CHILD KAREN
 TEL: (561)310-8207
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 12-24-08
 REVIEW: 2ND
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 **NO RESPONSE NOT ADDRESSED**
 2) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 RESIDENTIAL WITH THE 2007 SUPPLEMENTS. INDICATE THIS
 INFORMATION ON THE PLANS.
  
 **NO RESPONSE NOT ADDRESSED**
 3) 2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE. INDICATE THE LEVEL OF ALTERATION ON THE
 DRAWINGS.
  
 **SHEET SK-2 IS MISSING THE ENGINEER SEAL FOR BOTH SETS
 OF PLANS. 61G15-23.002(2): EACH SHEET OF PLANS AND
 PRINTS SHALL BE SEALED SIGNED AND DATED BY THE
 PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE. A TITLE
 BLOCK SHALL BE USED ON EACH SHEET CONTAINING THE
 PRINTED NAME, ADDRESS, AND LICENSE NUMBER OF THE
 ENGINEER.**
 4) 106.1.3* BUILDING PLANS SHALL BE DRAWN TO A MINIMUM
 1/8 INCH SCALE UPON SUBSTANTIAL PAPER. CONSTRUCTION
 DOCUMENTS SHALL ALSO BE DIMENSIONED. THE DRAWINGS
 SUBMITTED DO NOT CLEARLY INDICATE WHAT WORK TO BE
 CONSTRUCTED THE PROPOSED LOCATION. SUBMIT DETAILED
 ARCHITECTURAL DRAWINGS TO CLEARLY INDICATE THE PROPOSED
 WORK. IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR
 ENGINEER LEGALLY REGISTERED UNDER THE LAWS OF THIS
 STATE REGULATING PRACTICE OF ARCHITECTURE AS PROVIDED
 IN CHAPTER 481 AND 471 FLORIDA STATUTES PART 1, THEN HE
 OR SHE SHALL AFFIX HIS OR HER OFFICIAL SEAL, SIGNATURE
 AND DATE TO THE DRAWINGS. FBC 106.1.
  
 ** THE DRAWINGS FAIL TO INDICATE HOW THE NEW 2X6 AND
 4X4 WOOD STUDS ARE ATTACHED TO THE BOTTOM
 PLATE/FLOOR**.
 5) R601.2 PROVIDE INFORMATION TO SHOW THE CONTINUOUS
 LOAD PATH BETWEEN THE FOUNDATIONS WALLS, AND ROOFS.
 PLEASE INDICATE THE TYPE OF FASTENING DEVICES USED FOR
 THE RAFTERS. THE ROOF TIE-DOWN SHALL BE IN COMPLIANCE
 WITH R802.2.9. INDICATE ALL HURRICANE STRAPS AND TIES
 USED, AND SHOW WHERE THEY ARE INSTALLED.
  
 6) OK
 7) OK.
  
 **NO RESPONSE NOT ADDRESSED**
 8) THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD) MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 108.3*
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 PHONE (561)805-6726
 FAX (561)805-6676
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-11-18 Cont ID  
Sent By mjacobs Date 2008-11-18 Time 15:18 Rev Time 0.00
Received By mjacobs Date 2008-11-18 Time 13:47 Sent To E
Notes
2008-11-18 15:18:03BUILDING PLAN REVIEW
 PERMIT: 08110316
 ADD: 501 27TH STREET
 CONT: CHILD KAREN
 TEL: (561)310-8207
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 11-18-08
 REVIEW: 1ST
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS. INDICATE THIS
 INFORMATION ON THE PLANS.
  
 3) 2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE. INDICATE THE LEVEL OF ALTERATION ON THE
 DRAWINGS.
  
 4) 106.1.3* BUILDING PLANS SHALL BE DRAWN TO A MINIMUM
 1/8 INCH SCALE UPON SUBSTANTIAL PAPER. CONSTRUCTION
 DOCUMENTS SHALL ALSO BE DIMENSIONED. THE DRAWINGS
 SUBMITTED DO NOT CLEARLY INDICATE WHAT WORK TO BE
 CONSTRUCTED THE PROPOSED LOCATION. SUBMIT DETAILED
 ARCHITECTURAL DRAWINGS TO CLEARLY INDICATE THE PROPOSED
 WORK. IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR
 ENGINEER LEGALLY REGISTERED UNDER THE LAWS OF THIS
 STATE REGULATING PRACTICE OF ARCHITECTURE AS PROVIDED
 IN CHAPTER 481 AND 471 FLORIDA STATUTES PART 1, THEN HE
 OR SHE SHALL AFFIX HIS OR HER OFFICIAL SEAL, SIGNATURE
 AND DATE TO THE DRAWINGS. FBC 106.1.
  
 5) R601.2 PROVIDE INFORMATION TO SHOW THE CONTINUOUS
 LOAD PATH BETWEEN THE FOUNDATIONS WALLS, AND ROOFS.
 PLEASE INDICATE THE TYPE OF FASTENING DEVICES USED FOR
 THE RAFTERS. THE ROOF TIE-DOWN SHALL BE IN COMPLIANCE
 WITH R802.2.9. INDICATE ALL HURRICANE STRAPS AND TIES
 USED, AND SHOW WHERE THEY ARE INSTALLED.
  
 6) THE PLANS FAIL TO INDICATE THE ROOF SLOPE, MEAN ROOF
 HEIGHT, THE LENGTH AND WIDTH OF THE STRUCTURE. PLEASE
 INDICATE THE USE OF THE STRUCTURE.
  
 7) (2004 FBC) 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE &
 EXTENT OF THE WORK PROPOSED & SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, AND RULES AND REGULATIONS AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 8) THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD) MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 108.3*
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 PHONE (561)805-6726
 FAX (561)805-6676
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-02-02 Cont ID  
Sent By dpalmer Date 2009-02-02 Time 14:39 Rev Time 0.00
Received By dpalmer Date 2009-02-02 Time 14:39 Sent To B
Notes
2009-02-02 14:40:59PERMIT IS FOR REMOVAL OF ALL ELECTRICAL INSTALLED
 WITHOUT PERMIT. THIS IS A DETACHED GARAGE WHICH FALLS
 UNDER THE EXCEPTIONS IN 210.70,210.52G FOR DETACHED
 BUILDINGS WITH NO ELECTRICAL.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-12-23 Cont ID  
Sent By dpalmer Date 2008-12-23 Time 09:34 Rev Time 0.00
Received By dpalmer Date 2008-12-23 Time 09:34 Sent To B
Notes
2008-12-23 09:35:29** DENIED**
  
 1) NOTE: PLEASE SUBMIT ELECTRICAL PLANS FOR ELECTRICAL
 SCOPE OF WORK ALREADY INSTALLED. PLEASE SEE NEC
 225.31-225.39, 250.32, 250.50, 210.52G, 210.8A.
  
 *** PLEASE SEE 210.52G AND 210.70. IF THE GARAGE IS
 COMPLETELY DETACHED AND DOES NOT CONTAIN *ANY*
 ELECTRICAL AT THIS BUILDING THEN ALL ELECTRICAL MAY BE
 REMOVED. PLEASE APPLY FOR AN ELECTRICAL PERMIT TO DEMO
 EXISTING ELECTRICAL SYSTEMS ONLY IF THERE WILL BE NO
 ELECTRICAL AT THIS BUILDING INCLUDING ANY ELECTRICAL
 SERVICE EQUIPMENT INSIDE OR OUTSIDE, LIGHTING ETC.
  
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-11-19 Cont ID  
Sent By dpalmer Date 2008-11-19 Time 10:05 Rev Time 0.00
Received By dpalmer Date 2008-11-19 Time 10:05 Sent To PC
Notes
2008-11-19 10:06:04** FAILED REVIEW **
  
  
  
 1) NOTE: PLEASE SUBMIT COMPLETE ELECTRICAL PLANS AND
 RISER FOR NEW ELECTRICAL SCOPE OF WORK INCLUDING THE
 ADDITION OF NEW ELECTRICAL PANEL INSTALLED AT THE
 GARAGE.
 SUBMIT ELECTRICAL PANEL SCHEDULE FOR NEW CIRCUITS
 SHOWING THE CONDUCTOR SIZES ALONG WITH THE OVER CURRENT
 PROTECTION ON EACH CIRCUIT.
 215.5,230.70,230.71,230.72,310.16,250.50,240.4 ETC
 FLORIDA BUILDING CODE 105.1, 106.3.5.4
  
 THERE ARE NO RECORDS OF ELECTRICAL PERMITS FOR THIS
 SCOPE OF WORK. PLEASE SUBMIT ELECTRICAL DRAWING/PLANS
 FOR THE NEW LIGHTING, SWITCHES ETC ON HOW CONTROLS.
  
 THE PERMIT APPLICATION SUBMITTED WILL NEED TO HAVE A
 SIGN ON FOR THE ELECTRICAL PERMIT REQUIRED. THIS WOULD
 BE REQUIRED TO BE DONE IN PERSON BEFORE PLANS CAN BE
 RESUBMITTED.
  
 2) NOTE: PLEASE SEE 210.52G, 210.8A FOR GARAGE
 RECEPTACLE REQUIRED.
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2008-11-17 Cont ID  
Sent By swurafti Date 2008-11-17 Time 09:05 Rev Time 0.00
Received By swurafti Date 2008-11-17 Time 09:05 Sent To  
Notes
2008-11-17 09:05:31HISTORIC APPROVED BY FMITTNER

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-01-28 Cont ID  
Sent By adarroug Date 2009-01-28 Time 16:19 Rev Time 0.00
Received By adarroug Date 2009-01-28 Time 16:19 Sent To E
Notes
2009-01-28 16:19:23TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-12-22 Cont ID  
Sent By adarroug Date 2008-12-22 Time 11:13 Rev Time 0.00
Received By adarroug Date 2008-12-22 Time 11:13 Sent To E
Notes
2008-12-22 11:13:39TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2008-11-19 Time   Rev Time 0.00
Received By mjacobs Date 2008-11-18 Time 13:47 Sent To  
Notes
***NONE***