Plan Review Details - Permit 08110310
Plan Review Stops For Permit 08110310
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-01-13 Cont ID  
Sent By mcarsill Date 2009-01-13 Time 07:12 Rev Time 0.00
Received By mcarsill Date 2009-01-13 Time 07:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-12-03 Cont ID  
Sent By mcarsill Date 2008-12-03 Time 15:02 Rev Time 0.00
Received By mcarsill Date 2008-12-03 Time 14:51 Sent To  
Notes
2008-12-03 15:02:01ROSARIAN ACADEMY
 807 NORTH FLAGLER DRIVE
 INSTALL FIRE ALARM SYSTEM
  
 1. PLEASE DECLARE ON THE PLANS WHAT THE VOICE
 EVACUATION MESSAGE WILL ADVISE OCCUPANTS TO DO IN THE
 EVENT OF AN EMERGENCY. PLEASE INDICATE THE LOCATIONS OF
 ANY ALERT TONES IN THE VOICE EVACUATION MESSAGE
 PORTION.
  
 2. THE ENTIRE FIRE ALARM SYSTEM SHALL BE INSTALLED IN
 ACCORDANCE WITH NFPA 72, THE NATIONAL FIRE ALARM CODE
 AND NFPA 60, THE NATIONAL ELECTRICAL CODE AND OTHER
 APPROPRIATE STANDARDS.
  
 3. ON PAGE 8 IT INDICATES THAT DUCT SMOKE DETECTORS
 WHEN ACTIVATED WILL CAUSE A SUPERVISORY SIGNAL. DUCT
 DETECTORS WHEN ACTIVATED SHALL CAUSE A FIRE GENERAL
 ALARM CONDITION.
  
 4. ENTIRE INSTALLATION IS SUBJECT TO FIELD INSPECTION
 AND APPROVAL. WHEN COMPLETED THE ENTIRE SHALL BE
 INSPECTED, TESTED, AND APPROVED.
  
 5. THE FIRE ALARM SHALL IDENTIFY AND TRANSMIT THE
 FOLLOWING SIGNALS TO THE MONITORING COMPANY; GENERAL
 ALARM, WATERFLOW, SUPERVISORY, AND TROUBLE.
  
 6. THE FIRE ALARM SYSTEM SHALL BE MONITORED BY A UL
 LISTED CENTRAL STATION APPROVED FOR CENTRAL STATION
 SERVICE.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-12-30 Cont ID  
Sent By adarroug Date 2008-12-30 Time 09:06 Rev Time 0.00
Received By adarroug Date 2008-12-30 Time 09:06 Sent To FIRE
Notes
2008-12-30 09:07:08TO "F" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-12-04 Cont ID  
Sent By mawillia Date 2008-12-04 Time 10:47 Rev Time 0.00
Received By mawillia Date 2008-11-18 Time 09:06 Sent To  
Notes
2008-11-18 09:06:47TO "F" BOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved