Plan Review Details - Permit 08110304
Plan Review Stops For Permit 08110304
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2009-10-19 Cont ID  
Sent By jwitmer Date 2009-10-19 Time 11:06 Rev Time 0.77
Received By jwitmer Date 2009-10-19 Time 11:06 Sent To  
Notes
2009-10-19 11:07:19REVISION: DRIVING RANGE NETTING CALCULATIONS

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2009-08-07 Cont ID  
Sent By jwitmer Date 2009-08-07 Time 16:21 Rev Time 1.33
Received By jwitmer Date 2009-08-07 Time 16:21 Sent To  
Notes
2009-08-07 16:30:00BUILDING PLAN REVIEW
 PERMIT: 08110304
 ADD: 7001 PARKER AVE.
 CONT:THE WEITZ CO.
 TEL: (407)461-0392 KRIS LENGIEZA
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISION REVIEW SUBMITTED AUGUST 07/2009
 ACTION: DENIED
  
 1) THE RANGE NETTING DESIGN CALCULATIONS INDICATE AN
 EXPOSURE "B" CALCULATION PLEASE SEE ATTACHED DIAGRAM OF
 OVER 3,000 FEET OF EXPOSURE "C" TERRAIN. PLEASE
 RECALCULATE WITH THE CORRECTED FACTOR.
  
 2) THE 2ND ISSUE SHEET 1OF 6 INDICATES 6.5.15 OTHER
 STRUCTURES 60' POLE, BURIED 8'-0". WHERE AS SHEET 4 THE
 FOUNDATION CALCULATIONS INDICATES A BURIAL DEPTH OF
 10'-0". PLEASE CORRECT DEPTH OF FOUNDATION WHICH MAY
 CHANGE WITH NEW EXPOSURE "C" CALCULATIONS.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-04-24 Cont ID  
Sent By jwitmer Date 2009-04-24 Time 14:29 Rev Time 2.22
Received By jwitmer Date 2009-04-24 Time 08:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-04-13 Cont ID  
Sent By jwitmer Date 2009-04-13 Time 11:54 Rev Time 1.33
Received By jwitmer Date 2009-04-13 Time 11:54 Sent To  
Notes
2009-04-13 12:10:19BUILDING PLAN REVIEW
 PERMIT: 08110304
 ADD: 7001 PARKER AVE.
 CONT: WEITZ GOLF INTERNATIONAL LLC
 TEL: (561)799-7800
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW AS PERMIT APPLICATION
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) PLANS SUBMITTED FOR PERMIT APPLICATION (FIRST TIME
 REVIEW) AFTER MARCH 1ST, 2009 SHALL BE REVIEWED TO THE
 2007 FBC BUILDING WITH THE 2009 SUPPLEMENTS.
  
 1C) PLANS SUBMITTED TO THE CITY FOR REVIEW ARE NOT
 SIGNED NOR SEALED ,
 2) SHEETS PS1 & PS2 INDICATE THE INSTALLATION OF A
 FIBERGLASS COMPOSITE PUMP STATION:
  
 2A) MISSING INFORMATION,110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR RECORD KEEPING &
 FOR CERTIFICATE OF OCCUPANCY:
 2A)(1) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT
 IS DESIGNED.
 2A)(2)) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 2A)(3)) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER
 6, TABLE 601.
  
 2B) SHEET PS2, NOTE 5.2.1.A SHELTERS NEEDING TO BE
 RATED FOR 140MPH, 3 SECOND GUST NEED PLANS TO BE SIGNED
 AND SEALED BY A FLORIDA P.E.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
 FL ADMIN CODE 61G16.003 ARCHITECTS
  
 2C) DESCREPANCY IN PLANS PS1 IT APPEARS THERE IS A
 I-BEAM FLOOR SYSTEM WHERE AS PS 2 DETAIL INDICATES
 FLOOR SLAB SYSTEM, NOR IS THERE STRUCTURAL INFORMATION
 ON THE PIT OR WELL WALL AND FLOOR SYSTEMS. PS2 OPTIONS
 INDICATE FLOOR SYSTEM FIBERGLASS, WOOD, ALUMINUM OR
 STEEL.
 106.1.2 ADDITIONAL INFORMATION REQUIRED/ 1609.6.2.1.
  
 2D) WIND DESIGN INFORMATION MISSING:
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE FOR THE
 SELECTION OF EXTERIOR COMPONENTS AND CLADDING MATERIALS
 NOT SPECIFICALLY DESIGNED BY THE REGISTERED
 DESIGN PROFESSIONAL.
  
 3) COMPLIED.
  
 4) SHEET 37, RAIN SHELTERS:
  
 4A) COMPLIED.
  
 4B) COMPLIED.
  
 4C)COMPLIED.
  
 4D) COMPLIED.
  
 4E) SECOND REQUEST, THE RAIN SHELTER ROOF PURLINS ARE
 INDICATED TO 1X4 AT 2'-0" O.C., PLEASE IDENTIFY THE
 TYPE OF METAL ROOFING TO BE USED. PLANS INDICATE A
 METAL STANDING SEAM SYSTEM, IS THIS A STRUCTURAL
 ROOFING SYSTEM NOT REQUIRING SHEATHIN BUT STRUCTURAL
 2X4 PURLINS 2308.10.5 OR WILL IT BE A ARCHITECURAL
 SYSTEM REQUIRING A SOLID OR CLOSELY FITTED DECK
 (1507.4.1).
  
 4F) SECOND REQUEST THE WATER FOUNTAIN SHELTER USES 1X4
 PURLINS AT 1'-0" O.C., PLEASE IDENTIFY THE TYPE OF
 METAL ROOFING TO BE USED. PLANS INDICATE A METAL
 STANDING SEAM SYSTEM, IS THIS A STRUCTURAL ROOFING
 SYSTEM NOT REQUIRING SHEATHIN BUT STRUCTURAL 2X4
 PURLINS 2308.10.5 OR WILL IT BE A ARCHITECURAL SYSTEM
 REQUIRING A SOLID OR CLOSELY FITTED DECK (1507.4.1).
  
 4G) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
  
 4G)(1) TRUSS ANCHORS, CLIPS
  
 4G)(2) ROOF COVERINGS: STANDING METAL SEAM
  
 4H) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4I) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-11-21 Cont ID  
Sent By jwitmer Date 2008-11-21 Time 08:49 Rev Time 1.33
Received By jwitmer Date 2008-11-21 Time 08:49 Sent To  
Notes
2008-11-24 09:52:45BUILDING PLAN REVIEW
 PERMIT: 08110304
 ADD: 7001 PARKER AVE.
 CONT: MAJOR WORKING DRAWING/ VINCENT NOEL
 TEL: (561)622-7288
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 1C) PLANS SUBMITTED TO THE CITY FOR REVIEW ARE NOT
 SIGNED NOR SEALED ,
 2) SHEETS PS1 & PS2 INDICATE THE INSTALLATION OF A
 FIBERGLASS COMPOSITE PUMP STATION:
  
 2A) MISSING INFORMATION,110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR RECORD KEEPING &
 FOR CERTIFICATE OF OCCUPANCY:
 2A)(1) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT
 IS DESIGNED.
 2A)(2)) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 2A)(3)) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER
 6, TABLE 601.
  
 2B) SHEET PS2, NOTE 5.2.1.A SHELTERS NEEDING TO BE
 RATED FOR 140MPH, 3 SECOND GUST NEED PLANS TO BE SIGNED
 AND SEALED BY A FLORIDA P.E.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
 FL ADMIN CODE 61G16.003 ARCHITECTS
  
 2C) DESCREPANCY IN PLANS PS1 IT APPEARS THERE IS A
 I-BEAM FLOOR SYSTEM WHERE AS PS 2 DETAIL INDICATES
 FLOOR SLAB SYSTEM, NOR IS THERE STRUCTURAL INFORMATION
 ON THE PIT OR WELL WALL AND FLOOR SYSTEMS.
 106.1.2 ADDITIONAL INFORMATION REQUIRED/ 1609.6.2.1.
  
 2D) WIND DESIGN INFORMATION MISSING:
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE FOR THE
 SELECTION OF EXTERIOR COMPONENTS AND CLADDING MATERIALS
 NOT SPECIFICALLY DESIGNED BY THE REGISTERED
 DESIGN PROFESSIONAL.
  
 3) SHEET OV & L2 INDICATE THE PUMP STATION OPERATES IN
 A HIGHLY CORROSIVE ENVIROMENT, WHAT CAUSES THE HIGHLY
 CORROSIVE ENVIROMENT, IS THERE CORROSIVE CHEMICALS TO
 BE STORED THERE OR INTRODUCED INTO THE IRRIGATION
 SYSTEM WITHIN THIS STRUCTURE? 106.1.2 ADDITIONAL
 INFORMATION REQUIRED, PLEASE SEE SECTION 307.6 FOR H-4
 TYPE OCCUPANCY AND TABLE 307.7(1).
  
 4) SHEET 37, RAIN SHELTERS:
  
 4A) MISSING INFORMATION,110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR RECORD KEEPING &
 FOR CERTIFICATE OF OCCUPANCY:
 4A)(1) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT
 IS DESIGNED.
 4A)(2)) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 4A)(3)) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER
 6, TABLE 601.
  
 4B) 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR
 THE SELECTION OF EXTERIOR COMPONENTS AND CLADDING
 MATERIALS NOT SPECIFICALLY DESIGNED BY THE REGISTERED
 DESIGN PROFESSIONAL.
  
 4C) PLANS CALL FOR 2X8 RAFTERS, PLEASE SUPPLY THE
 SPECIES OF WOOD, GRADE, DEFLECTION AND SPANS 2308.10.3.
  
 4D) PLANS ALSO CALL FOR A 2X8 RIDGE, PLEASE SEE
 2308.10.4 THE RIDGE SHALL BE NOT LESS IN DEPTH THAN THE
 CUT END OF THE RAFTER, NORMALLY ONE SIZE LARGER (2X10).
  
 4E) THE RAIN SHELTER ROOF PURLINS ARE INDICATED TO 1X4
 AT 2'-0" O.C., PLEASE IDENTIFY THE TYPE OF METAL
 ROOFING TO BE USED. PLANS INDICATE A METAL STANDING
 SEAM SYSTEM, IS THIS A STRUCTURAL ROOFING SYSTEM NOT
 REQUIRING SHEATHIN BUT STRUCTURAL 2X4 PURLINS 2308.10.5
 OR WILL IT BE A ARCHITECURAL SYSTEM REQUIRING A SOLID
 OR CLOSELY FITTED DECK (1507.4.1).
  
 4F) THE WATER FOUNTAIN SHELTER USES 1X4 PURLINS AT
 1'-0" O.C., PLEASE IDENTIFY THE TYPE OF METAL ROOFING
 TO BE USED. PLANS INDICATE A METAL STANDING SEAM
 SYSTEM, IS THIS A STRUCTURAL ROOFING SYSTEM NOT
 REQUIRING SHEATHIN BUT STRUCTURAL 2X4 PURLINS 2308.10.5
 OR WILL IT BE A ARCHITECURAL SYSTEM REQUIRING A SOLID
 OR CLOSELY FITTED DECK (1507.4.1).
  
 4G) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
  
 4G)(1) TRUSS ANCHORS, CLIPS
  
 4G)(2) ROOF COVERINGS
  
 4H) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4I) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2009-04-16 Cont ID  
Sent By dpalmer Date 2009-04-16 Time 08:17 Rev Time 0.00
Received By dpalmer Date 2009-04-16 Time 08:17 Sent To  
Notes
2009-04-16 08:17:41** NOTED**
  
  
  
 1) NOTE: SEPARATE PERMIT AND PLANS REQUIRED FOR
 ELECTRICAL SYSTEM CONTROLS, SEPARATE FEEDS AND
 CONNECTIONS TO IRRIGATION PUMPS ETC
 NO ELECTRICAL PER NEC 2005, NO PERMIT APPLIED FOR.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-11-20 Cont ID  
Sent By dpalmer Date 2008-11-20 Time 10:54 Rev Time 0.00
Received By dpalmer Date 2008-11-20 Time 10:54 Sent To  
Notes
2008-11-20 10:54:17 
  
  
 ** FAILED REVIEW **
  
  
  
 1) NOTE: PLANS ONLY SUBMITTED FOR * PLAN REVIEW * ONLY.
 PLEASE KNOW ONCE PLANS ARE FOUND TO BE CODE COMPLIANCE
 FOR ISSUANCE THE REVIEW WILL STILL REMAIN IN A FAILED
 STATUS UNTIL PERMIT APPLICATION BY A LICENSED
 CONTRACTOR HAS BEEN SUBMITTED. REVIEW OF CURRENT
 LICENSING OF CONTRACTOR(S), DESIGNER(S) AND FIRM WILL
 BE DONE AT THIS TIME.
 PLEASE ALSO KNOW THAT IN ORDER TO LOCK IN REVIEW AND
 DESIGN UNDER CURRENT ADOPTED CODE(S) PERMIT APPLICATION
 MUST BE MADE. THERE IS NO SCHEDULE OF CODE CHANGE UNTIL
 MARCH 1ST, 2009.
 ** IF THERE ARE ANY QUESTIONS ON THIS PROCESS PLEASE
 CONTACT THIS OFFICE/REVIEWER/.
  
 2) NOTE: ALL PLANS ARE REQUIRED UNDER FLORIDA
 ADMINISTRATIVE CODE TO CONTAIN THE TITLE BLOCKS FOR
 ARCHITECT, ARCHITECTURAL FIRMS, AND ENGINEERING FIRMS
 ETC. THESE TITLE BLOCKS ARE REQUIRED TO INCLUDE
 INFORMATION AND ADDRESS OF PROJECT.
 THEY ARE REQUIRED TO CONTAIN ALL LICENSING INFORMATION
 FOR THE FIRMS, PRINTED LICENSE NUMBER, ADDRESS, AND
 PHONE NUMBER ETC.
 PLEASE SEE FAC 61G1-16.004 FOR ARCHITECT, ARCHITECTURAL
 FIRMS.
 PLEASE SEE FAC 61G15-23.002 FOR ENGINEERS AND
 ENGINEERING FIRMS.
  
  
 ** PLEASE KNOW THAT A CERTIFICATE OF AUTHORIZATION
 LICENSE NUMBER IS REQUIRED FOR ALL ARCHITECTURAL FIRMS
 INCLUDING LANDSCAPING ARCHITECTURAL FIRMS PER FLORIDA
 STATUTES 481.219.
  
 ** PLEASE KNOW THAT A CERTIFICATE OF AUTHORIZATION
 LICENSE NUMBER IS REQUIRED FOR ALL ENGINEERING FIRMS
 PER FS 471.023
  
 ** THESE COMMENTS ARE FOR ALL TRADES AND ALL SHEETS
 WHETHER OR NOT COMMENTS ARE MADE BY OTHER TRADE
 REVIEWS. THESE ARE NOT NEW REQUIREMENTS IN FACT THEY
 HAVE BEEN AROUND SINCE LATE NINETEEN SEVENTIES.
 IF THERE ARE ANY QUESTIONS ON REQUIREMENTS PLEASE
 CONTACT THIS OFFICE/REVIEW OR DEPARTMENT OF BUSINESS
 AND PROFESSIONAL REGULATION FOR THE STATE OF FLORIDA.
  
 3) NOTE: SOME SHEETS IN SETS ARE NOT SIGNED, DATED OR
 SEALED BY ANY DESIGN PROFESSIONAL. PLEASE KNOW ALL
 PLANS SHALL CONTAIN PERSON RESPONSIBLE FOR DESIGN EVEN
 WHEN MEETING EXCEPTIONS TO FS 481.229 AND 471.003.
 THIS PROJECT DOES NOT MEET EXCEPTIONS AND THEREFORE
 MUST BE COMPLETED BY THE LICENSE DESIGNER OF RECORD.
 481.221,471.025.
  
 4) NOTE: PLEASE SUBMIT ELECTRICAL PLANS AND DETAILS FOR
 ELECTRICAL SCOPE OF WORK FOR SHELTERS ETC.
 PLEASE SHOW CONDUCTORS, OVER CURRENT PROTECTION,
 CIRCUITING ETC.
 PLEASE BE SURE TO SEE 2005 NEC, 2004 FBC FOR MINIMUM
 DESIGN FOR COMPLIANCE.
 IF THERE ARE ANY QUESTIONS ON THIS PLEASE CALL.
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2009-04-24 Cont ID  
Sent By dlauderm Date 2009-04-24 Time 09:47 Rev Time 0.00
Received By dlauderm Date 2009-04-24 Time 09:47 Sent To  
Notes
2009-04-24 09:46:19WENT OVER CHANGES WITH ARCHITECT AT MEETING ON 04/23/09
 AND REVIEWED THE CHANGES.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2009-04-14 Cont ID  
Sent By dlauderm Date 2009-04-14 Time 15:09 Rev Time 0.00
Received By dlauderm Date 2009-04-14 Time 15:06 Sent To  
Notes
2009-04-14 15:09:24ANY QUESTIONS CONTACT:
 DEAN S. LAUDERMILK, PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 [email protected]
 561-494-1083 (ENG. SERVICES)
 561-805-6716 (CONSTRUCTION SERVICES)
 SHEET 7 OF 40:
 1. KEY COLORING ON THIS SHEET DOES NOT MATCH 6 OF 40.
 CHANGE COLORING TO REDUCE CONFUSION.
 2. RAIN SHELTER IS NOT LOCATED AS SHOWN. IT IS
 APPROXIMATELY 87' NORTH AND 157' WEST OF CART PATH.
 SHEET 9 OF 40:
 1. SINCE YOU HAVE SHOWN THE PROPERTY LINE ON THIS SET
 OF DRAWINGS THE WORK SEEMS TO BE EXTENDING OFF THE
 PROPERTY. CHECK WITH THE PROJECT MANAGER V. NOEL
 (561-494-1096) FOR THE PROPER PROPERTY LINE. IF IT IS
 AS SHOWN THEN REDUCE THE "PERIMETER ZONE" WORK TO A
 POINT IT IS INSIDE CITY PROPERTY.
 SHEET 12, 14, 16, AND 18 OF 40:
 1. SEE NOTE ON 21 OF 40, THE OUTCOME OF HOW THE PUMP
 STATION IS DESIGNED WILL CHANGE THIS NOTE.
 2. THE NOTE STATES: "TO BE DISCONNECTED, OWNER TO
 DISPOSE OF PUMPS." THE DEMOLITION SHEET (5 OF 40) DOES
 NOT STATE THAT THE PUMP HOUSE, CONTROL PANEL, ELECTRIC
 LINES, OR CONCRETE PAD FOR THE EXISTING PUMPS ARE TO BE
 REMOVED. ARE THEY TO BE REMOVED, CAPPED OFF?
 SHEET 21 OF 40:
 1. I DO NOT HAVE THE PREVIOUS PLAN TO COMPARE TO THIS
 PLAN, BUT THIS PLAN SHOWS THE FINISHED FLOOR ELEVATION
 AS 15'-9". THE PLAN THEN GOES ON TO STATE THAT THE PUMP
 SET EXTENDS DOWN FROM THIS ELEVATION 11', WHICH PLACES
 IT AT ELEVATION 4'-9". THE ELEVATION ON THE INVERT OF
 THE INTAKE PIPE IS 1'-0". WHICH MEANS THAT THE BOTTOM
 OF THE WET WELL IS 2'-9" HIGHER THAN THE INTAKE PIPE.
 IT APPEARS THAT THE BOTTOM OF THE WETWELL SHOULD BE
 AROUND MINUS 2'-0" AND THAT THE PUMP SET SHOULD BOTTOM
 OUT AT AROUND MINUS 1'-0" OR 17' LONG. THIS WOULD MAKE
 THE WETWELL APPROXIMATELY 18' DEEP, WHICH WOULD AFFECT
 THE NOTES ON SHEETS 12,14, 16, AND 18 OF 40.
 2. INFORMATIONAL NOTE: SHEETS 12, 14, 16, AND 18 OF 40
 ALL HAVE A NOTE THAT STATE THE WETWELL SHALL BE "60"
 CONCRETE". HUGGER BANDS WILL NOT WORK WITH PVC PIPE,
 WHICH IS THE MATERIAL THAT HAS BEEN SUBMITTED WITH THIS
 SET OF PLANS (J-M PIPE, 24" CLASS 235 PSI, DR18, OR
 CLASS 165 PSI DR26), NEITHER CLASS WAS CHOSEN, BUT BOTH
 ARE PVC AND REQUIRE A DIFFERENT TYPE OF ADAPTER THAN
 THE "HUGGER BAND" THAT IS SHOWN ON THE PLAN. THE
 PREVIOUS REVIEWER WAS INTERESTED TO SEE WHAT MATERIAL
 WAS TO BE USED (IT DOES NOT STATE ON THIS SHEET, WHICH
 IT SHOULD). IT DOES GIVE A LIST OF PIPE MATERIALS THAT
 CAN BE USED ON SHEETS 12, 14, 16, AND 18 OF 40. THE
 MATERIALS DO NOT NEED TO BE SUBMITTED AT THIS TIME, TO
 CONSTRUCTION SERVICES, BUT LATER TO THE PROJECT MANAGER
 AT ENGINEERING SERVICES. TOWARDS THAT END ONE OF THE
 FOLLOWING ADAPTERS WILL BE REQUIRED TO ADAPT TO THE
 WETWELL FOR PVC;
 PVC MANHOLE TO PIPE ADAPTERS:
 USED TO SEAL THE PIPE TO THE MANHOLE. ALL ADAPTERS WILL
 BE MADE TO FIT PVC, SDR-26 PIPE. ADAPTERS FOR USE WITH
 ALL NEW CONSTRUCTION. PVC ADAPTERS SHALL HAVE DOUBLE
 GASKETED BELL, WITH SANDCOATING CAST INTO THE OUTSIDE
 TO ALLOW FOR ADHERENCE TO THE CONCRETE SEAL.
  HARCO - THE HARRINGTON CORP., P.O. BOX 10335,
 LYNCHBURG, VA 24306
 FLOW CONTROL
 OTHER MANHOLE TO PIPE ADAPTERS:
 USED TO SEAL THE PIPE TO THE MANHOLE. ALL ADAPTERS WILL
 BE MADE TO FIT PVC, SDR-26 PIPE. ADAPTERS FOR USE WITH
 ALL NEW CONSTRUCTION. ADAPTERS SHALL HAVE STAINLESS
 STEEL RING SEALS TO SEAL THE ADAPTER TO THE PIPE AND TO
 THE MANHOLE IF THEY ARE NOT POURED IN PLACE.
  PRESS SEAL GASKET CORPORATION
 PRESS-BOOT
 U.S. PRECAST MANHOLE W/HDPE LINER CAST-IN BOOT TO
 SLEEVE CONNECTION
 U.S. PRECAST HDPE LINER SYSTEM "TURN BACK" JOINT
 INSTALLED AFTER CAST
 3. I AM NOT A STRUCTURAL ENGINEER, BUT I WOULD THINK
 THAT THERE NEEDS TO BE SOME STEEL IN THE CONCRETE SLAB,
 AND THE SLAB NEEDS TO BE ON TOP OF THE WETWELL.
 4. SHEET 12 OF 40 HAS A NOTE THAT STATES: "WATER LEVEL
 NOVEMBER 18TH 1974 ELEV. 8.60', LOWEST ANTICIPATED
 WATER ELEV. 2.85'. SO WHY IS THERE A COMMENT THAT THE
 ELEVATION OF THE WATER (8.60') IS UNCONFIRMED ON THIS
 SHEET?
 5. SINCE THE WATER TABLE IS APPROXIMATELY 8.60' AND THE
 WETWELL IS AS DEEP AS IT MAY END UP, A NOTE NEEDS TO BE
 ADDED STATING THAT THE WETWELL NEEDS TO BE DESIGNED BY
 A PE AND CERTIFIED THAT IT WILL NOT FLOAT.
 34 OF 40:
 1. ADD TO ALL DETAILS THE USE OF FILTER FABRIC AROUND
 THE TOPS, SIDES AND BOTTOMS OF ALL OF THE GRAVEL.
 2. CHANGE THE NOTES "1/4 TO 3/4" WASHED GRAVEL TO 3/4"
 WASHED ROCK.
 35 OF 40:
 1. ADD TO DETAIL THE USE OF FILTER FABRIC AROUND THE
 TOPS, SIDES AND BOTTOMS OF ALL OF THE GRAVEL.
 2. CHANGE THE NOTES "1/4 TO 3/4" WASHED GRAVEL TO 3/4"
 WASHED ROCK.
 3. WHERE ARE THE CHANNEL DRAINS GOING TO BE PLACED THAT
 ARE SHOWN IN THIS DETAIL? STATE THERE SPECIFIC
 LOCATION.
 4. WATER FOUNTAIN SHELTER UTILITY PLAN IS CONFUSING.
 ADD TO THE END OF THE TITLE "(SEE SHEET F2, 28 OF 40)".
 5. I DO NOT KNOW HOW BUT CHANGE THE NOTE CONCERNING
 ABANDONING THE ELECTRIC AND WATER LINES, IT APPEARS YOU
 WANT TO CUT THEM OFF FROM THE BATHROOM. I WOULD THINK
 THAT YOU WOULD NEED THE WATER LINE FOR THE WATER
 FOUNTAIN.
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2008-12-09 Cont ID  
Sent By mgonzale Date 2008-12-09 Time   Rev Time 1.00
Received By   Date 2008-12-05 Time   Sent To ENG
Notes
2008-12-09 10:11:58ENGINEERING REVIEW - FAILED - 12-09-08
  
 #1 PLAN D2 (PAGE 18 OF 37) SHOWN INCONSISTENCIES WITH
 THE PS1 (SHEET 21 OF 37)
 SIZE OF INTAKE SCREENS, SCREEN PATTERNS,
 #2 INTAKE PIPE MATERIAL NEEDS TO BE SPECIFIC.
 #3 INCONSISTENCIES IN THE FFE AND GRADE.
 #4 SHOW ALL ELEVATIONS. PS1
 #5 PLEASE USE CONSISTENCY WHEN LABELING DIMENSIONS
 (EITHER DECIMAL OR FT. IN. PICK ONE)
 #6 PLAN VIEW OF THE INTAKE AREA IS NEEDED.
 STABILIZATION OF THE BANK IS REQUIRED. IT MUST PROVIDE
 ENOUGH COVERAGE TO INCLUDE RESTABILIZATION OF THE BANK
 BASED ON THE ANGLE OF REPOSE DISTURBED
 WHEN LAYING THE PIPE.
 #7 ELEVATIONS ARE NOT CONSISTENT FROM D2 TO PS1, VERIFY
 #8 PROVIDE SURVEY AND OR PROPERTY LINE SO AS TO
 IDENTIFY WHERE PUMP STATION WILL BE LOCATED.
 #9 PERMIT FROM SFWMD MAY APPLY. WATER USE CALCULATIONS
 WILL BE INCREASED? VERIFY
 #10 WHERE WILL 12"X8" REDUCER OFFSET PIPE SEGMENT ON
 SHEET PS1 WILL BE USED? CALL MATERIAL
 #11 SEE PLAN FOR NOTES AND REDLINES FOR OTHER MISC
 ITEMS.
 #12 SUBMIT A SWPPP (STORMWATER POLLUTION PREVENTION
 PLAN MUST BE USED. SPECIFICALLY WORKING AROUND THE NEW
 PUMP STATION AREA.
 ALSO IDENTIFY WHAT WORK WILL OCCUR AT THE PREVIOUS
 PUMPING LOCATION. CONTRACTOR WILL NEED THIS TO MAINTAIN
 HIS SWPPP
 HTTP://CFPUB.EPA.GOV/NPDES/STORMWATER/SWPPP.CFM
 #13 SHOW PROJECT INTERACTION WITH FDOT ROW (ANY
 DRAINAGE CONCERNS?)
  
 MANUEL J GONZALEZ, PROJECT COORDINATOR
 LOCATION ADDRESS:
 CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT
 1000 - 45TH STREET, SUITE 15
 WEST PALM BEACH FL 33407
 MAILING ADDRESS:
 CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT
 P.O. BOX 3506
 WEST PALM BEACH FL 33401
 TELEPHONE:
 45TH STREET OFFICE : 561-494-1040
 45TH DIRECT: 561-494-1085
 FAX: 561-494-1117
 CITY HALL OFFICE: (561) 805-6723
 CITY HALL DIRECT: (561) 805-6327
 CITY HALL FAX: (561) 805-6731 OR 805-6676
 NEXTEL: 561-644-7301
 NEXTEL DIRECT CONNECT: 159*28165*38
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2009-04-24 Cont ID  
Sent By mawillia Date 2009-04-24 Time 10:21 Rev Time 0.00
Received By mawillia Date 2009-04-24 Time 09:54 Sent To  
Notes
2009-04-24 10:15:34*****APPROVED W/PROVISO*****
  
 PLAN SHEET G-2 STAMPED, INITIALED, AND DATED WITH
 FOLLOWING PROVISO.
  
  
 PROVISO:
  
 ROADS WHICH MAY BE USED FOR FIRE DEPARTMENT ACCESS
 SHALL BE DESIGNED AND MAINTAINED TO SUPPORT THE IMPOSED
 LOADS OF FIRE APPARATUS AND SHALL BE PROVIDED WITH AN
 ALL-WEATHER DRIVING SURFACE. THESE ROADS SHALL HAVE
 ADEQUATE VERTICAL CLEARANCES AND WIDTH TO ACCOMMODATE
 FIRE APPARATUS.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2009-10-07 Time   Rev Time 0.00
Received By   Date 2009-10-07 Time   Sent To  
Notes
2009-10-07 17:12:52TO JW DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-08-05 Cont ID  
Sent By kstevens Date 2009-08-05 Time 09:17 Rev Time 0.00
Received By kstevens Date 2009-08-05 Time 09:17 Sent To B
Notes
2009-08-05 09:17:56TO JW'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-04-09 Cont ID  
Sent By adarroug Date 2009-04-09 Time 09:55 Rev Time 0.00
Received By adarroug Date 2009-04-09 Time 09:55 Sent To  
Notes
2009-04-09 09:55:54TO "C32"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2008-12-09 Time   Rev Time 0.00
Received By adarroug Date 2008-11-18 Time 08:50 Sent To  
Notes
2008-11-18 08:50:46TO "COMM" BD#43--EXPEDITED--

Review Stop L LANDSCAPING
Rev No 2 Status P Date 2009-04-24 Cont ID  
Sent By rkussner Date 2009-04-24 Time 15:02 Rev Time 0.00
Received By rkussner Date 2009-04-24 Time 15:02 Sent To  
Notes
2009-04-24 15:05:43***LANDSCAPE REVIEW PASSED WITH 'PROVISO'***
  
 1. ALL LANDSCAPE COMMENTS MADE ON 4/23/09 SHALL BE
 ADDRESSED WITH THE PLANS REVISED AND APPROVED PRIOR TO
 FINAL INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2009-04-24 Cont ID  
Sent By rkussner Date 2009-04-23 Time 13:05 Rev Time  
Received By jwitmer Date 2009-04-23 Time 12:11 Sent To  
Notes
2009-04-23 13:41:05***LANDSCAPE REVIEW FAILED***
  
 1 PURSUANT TO SECTION 94-445 (4)(G)(3), AUTOMATIC
 IRRIGATION SYSTEMS SHALL BE USED FOR THE CULTIVATED
 LANDSCAPED AREAS FOR ALL PROPERTIES.
  
 2. PURSUANT TO SECTION 94-448 (F)(11), TREES WHICH ARE
 INCLUDED AS PROHIBITED TREES PURSUANT TO SUBSECTION
 94-445(4)(I), SHALL BE REMOVED AND DISPOSED OF FROM THE
 ENTIRE SITE BEFORE A CERTIFICATE OF OCCUPANCY CAN BE
 OBTAINED. THIS WOULD INCLUDE ALL REAS MENTIONED IN ITEM
 #1.
  
 3 SUBMIT A TREE ALTERATION PERMIT APPLICATION WITH TWO
 (2) SETS OF PLANS TO THE PLANNING AND ZONING
 DEPARTMENT. ALL TREES TO REMAIN IN PLACE OR BE
 RELOCATED SHALL BE CLEARLY IDENTIFIED ON THE LANDSCAPE
 PLAN AND DISPLAYED IN TABULAR FORM. THE QUANTITIES
 SHALL BE SHOWN. THE NEW LOCATION OF TREES BEING
 RELOCATED SHALL BE SHOWN AND ALL TREES DESIGNATED TO BE
 RELOCATED ---SHALL BE RELOCATED. A NOTE MAKING THIS
 PROCESS OPTIONAL SHALL BE REMOVED FROM THE PLAN.
  
 4. PURSUANT TO SECTION 94-443 (D)(2)(E)(1), AT LEAST 30
 PERCENT OF THE LINEAR FEET AROUND THE EXTERIOR OF ALL
 COMMERCIAL STRUCTURES SHALL BE PLANTED WITH TREES,
 SHRUBS OR HEDGES. THIS APPLIES TO ALL PROPOSED
 STRUCTURES.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462,

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-04-24 Cont ID  
Sent By jwitmer Date 2009-04-24 Time 14:26 Rev Time 0.00
Received By jwitmer Date 2009-04-24 Time 14:26 Sent To  
Notes
2009-04-24 14:27:47PASSED BY THTE BUILDING OFFICIAL DOUG WISE WITH
 SIGNATURE ON COVERSHEET.

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-11-20 Cont ID  
Sent By kstevens Date 2008-11-20 Time 15:17 Rev Time 0.00
Received By kstevens Date 2008-11-20 Time 15:16 Sent To  
Notes
2008-11-21 07:16:13DENIED
 REFERENCE: FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 FBC-2004 CHAPTER 1
  
 1. ALL SHEETS DESIGNED BY THE LANDSCAPE ARCHITECT SHALL
 HAVE A TITLE BLOCK AND SHOW THE INFORMATION REQUIRED BY
 FAC 61G1-16.004(1)(2)(3)(4)(5)(6). FS 481.219,
 481.2055. ALSO THE DATE THE SIGNATURE AND SEAL ARE
 AFFIXED TO THE PLANS SHALL BE INDICATED ON THE PLANS ON
 OR NEAR THE SEAL.
  
 2. IRRIGATION SHEETS 12, 14, 16 OR 18 SHALL INDICATE
 THE LOCATION OF THE RAIN SENSOR/WEATHER STATION
 W/TELEPHONE LINK. SECTION 106.1.1
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 2009-04-24 Cont ID  
Sent By jroach Date 2009-04-24 Time 14:15 Rev Time 0.00
Received By jroach Date 2009-04-24 Time 14:15 Sent To  
Notes
2009-04-24 14:16:37ZONING PLAN REVIEW
  
 PERMIT NO.: 08110304
 ADDRESS: 7001 PARKER AVENUE
 CONTRACTOR/CONTACT: WEITZ GOLF INTERNATIONAL LLC -
 BRYAN BERNARDO
 TELEPHONE NO.: 561.799.7800
 SCOPE OF REVIEW: REGRADING/REGRASSING, NEW IRRIGATION,
 PUMP STATION, NEW SHELTERS, NEW LANDSCAPING.
  
 REVIEW STATUS: PASSED WITH PROVISOS
  
 PRIOR TO FINAL INSPECTION DETAILS SHALL BE PROVIDED
 REGARDING THE INSTALLATION OF THE ADDITIONAL NETTING.
 ARE THE POLES EXISTING? PLEASE INDICATE THE OVERALL
 HEIGHT, ETC. AND HOW THIS WILL BE INSTALLED.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 PHONE: (561) 822-1435
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 2009-04-23 Cont ID  
Sent By jroach Date 2009-04-23 Time 11:41 Rev Time 0.00
Received By jroach Date 2009-04-23 Time 11:41 Sent To  
Notes
2009-04-23 11:46:21ZONING PLAN REVIEW
  
 PERMIT NO.: 08110304
 ADDRESS: 7001 PARKER AVENUE
 CONTRACTOR/CONTACT: WEITZ GOLF INTERNATIONAL LLC -
 BRYAN BERNARDO
 TELEPHONE NO.: 561.799.7800
 SCOPE OF REVIEW: REGRADING/REGRASSING, NEW IRRIGATION,
 PUMP STATION, NEW SHELTERS, NEW LANDSCAPING.
  
 REVIEW STATUS: FAILED
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1) PLEASE PROVIDE DETAILS REGARDING THE INSTALLATION OF
 THE ADDITIONAL NETTING. ARE THE POLES EXISTING? PLEASE
 INDICATE THE OVERALL HEIGHT, ETC. AND HOW THIS WILL BE
 INSTALLED.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 PHONE: (561) 822-1435
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2008-11-26 Cont ID  
Sent By jroach Date 2008-11-26 Time 12:01 Rev Time 0.00
Received By jroach Date 2008-11-26 Time 11:28 Sent To  
Notes
2008-11-26 12:12:06ZONING PLAN REVIEW
 PERMIT: 08110304
 ADD: 7001 PARKER AVE.
 CONT: MAJOR WORKING DRAWING/ VINCENT NOEL
 TEL: (561) 622-7288
  
 REVIEW STATUS: FAILED
  
 1) A CLASS B SPECIAL USE PERMIT SHALL BE APPROVED BY
 THE ZONING BOARD OF APPEALS PRIOR TO THE ISSUANCE OF
 ANY PERMITS. PLEASE CONTACT ME REGARDING APPLICATION
 MATERIALS, PROCESS, ETC.
  
 2) THE PROPERTY SHALL BE REPLATTED.
  
 3) PLEASE CLARIFY WHY A PORTION OF THE PROPERTY IS
 UNDER PRIVATE OWNERSHIP. PLEASE REFER TO PCN:
 74-43-44-09-06-000-0790, WHICH IS OWNED BY TIM EDWARDS
 SERVICES, INC.
  
 4) THE SMALL SINGLE PARCEL ON THE SOUTH SIDE OF MADDOCK
 STREET, WEST OF GEORGIA AVENUE SHOULD BE REZONED TO
 RECREATION OPEN SPACE (ROS) SO AS TO CREATE A
 CONSISTENT ZONING/LAND USE ACROSS ALL OF THE GOLF
 COURSE/PARK PROPERTY.
  
 5) PLEASE PROVIDE DETAILS REGARDING THE INSTALLATION OF
 THE ADDITIONAL NETTING. ARE THE POLES EXISTING? PLEASE
 INDICATE THE OVERALL HEIGHT, ETC. AND HOW THIS WILL BE
 INSTALLED.
  
 6) PLEASE INDICATE THE PROPERTY LINES ON ALL PLANS AND
 PROVIDE THE DIMENSIONS FROM THE PROPERTY LINES TO ALL
 OF THE PROPOSED STRUCTURES/SHELTERS.
  
 7) PLEASE PROVIDE THE OVERALL HEIGHT DIMENSIONS ON ALL
 STRUCTURE DETAILS.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 PHONE: (561) 822-1435
 EMAIL: [email protected]