Plan Review Details - Permit 08110283
Plan Review Stops For Permit 08110283
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-12-08 Cont ID  
Sent By jwitmer Date 2008-12-08 Time 16:54 Rev Time 24.00
Received By jwitmer Date 2008-12-03 Time 08:06 Sent To  
Notes
2008-12-08 16:55:32BUILDING PLAN REVIEW
 PERMIT: 08110283
 ADD: 326 FERN STREET
 CONT: ?PLAN REVIEW?
 TEL: (312)375-0828 JOHN QUINN
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 ARCHITECT: GERALD REMBOWSKI
 STRUCTURAL ENGINEER: STEPHEN F. EBERSOLE
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1D) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS.
  
  
  
 2) G. M. REMBOWSKI ARCHITECT, INC IS MISSING THEIR
 CERTIFICATE OF AUTHORIZATION.
 481.219 F.S. CERTIFICATE OF AUTHORIZATION. THE TITLE
 BLOCK FOR ANY SHEET BEARING THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, A CORPORATION, OR A
 PARTNERSHIP, OFFERING ARCHITECTURAL SERVICES, SHALL
 INCLUDE THE CERTIFICATE OF AUTHORIZATION NUMBER. ADD
 THE NUMBER TO EACH SHEET. THIS MAY BE ADDED BY HAND.
  
 3) STEPHEN F. EBERSOLE P.E. MISSING THE PRINTED NAME
 AND LICENSE NUMBER.
 61G15-23.002(2) FL. ADMIN.CODE. PLANS SIGNED & SEALED
 BY A PROFESSIONAL ENGINEER SHALL INCLUDE EITHER THE:
 NAME, ADDRESS AND LICENSE NUMBER OF THE ENGINEER OR,
 THE NAME AND LICENSE NUMBER OF THE ENGINEER.
  
 4) SOILS REPORT, NO COPIES. 1802.2.1 QUESTIONABLE SOIL.
 WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN
 DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT
 SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION
 BE MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE
 PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 .
  
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
  
 5) SHEET TS, THRESHOLD BUILDING REQUIREMENTS:
  
 5A) INDICATES THE THRESHOLD INSPECTION PLAN IS LOCATED
 ON SHEET S-1. THIS SHEET ONLY PROVIDES GENERAL NOTES.
 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 5B)THRESHOLD INSPECTOR:
 WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE.
 CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION
 BEFORE THE PERMIT MAY BE ISSUED.
  
 5C) INFORMATIONAL:
 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR
 THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER HAS
 REQUIRED ON THE PLANS OR SPECIFICATIONS ONE MATERIAL,
 APPROVED FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND
 CEILINGS.
  
 6) INFORMATIONAL; 109.3.10* IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL BE
 PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS
 PERMITTED TO AFFECT SAID PROPERTY PURSUANT TO A CONSENT
 BY THE APPLICABLE PROPERTY OWNER, UNDER TERMS &
 CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY OWNER.
 THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 7) INFORMATIONAL: 109.3.10.1 HURRICANE PROTECTION. IT
 SHALL BE UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION
 RELATED MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE
 OR OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24
 HRS. AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION TO
 THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
 8) THE PLANS THAT ARE CURRENTLY UNDER REVIEW WERE
 BROUGHT IN AS A MAJOR WORKING DRAWING REVIEW BEFORE
 PLANS ARE TO BE BROUGHT IN AS A PERMIT APPLICATION
 PLEASE HAVE THEM STAMPED BY HISTORIC PRESERVATION
 DIVISION INDICATING THERE APPROVAL.
  
 9) 2004 EXISTING BUILDING CODE CHAPTER 10, 1005.1
 STRICT COMPLIANCE, 1005.2 COMPLIANCE OPTIONS AND
 1005.3. PLEASE REVIEW THESE CODE SECTIONS AND INDICATE
 WHICH OF THE LIFE SAFETY AND PROPERTY CONSERVATION
 OPTIONS SHALL BE PROVIDED IN ACCORDANCE WITH ONE OF THE
 FOLLOWING OPTIONS 1-3. PLEASE PROVIDE DOCUMENTATION FOR
 CODE COMPLIANCE FOR THE LISTED CODE SECTIONS ABOVE.
  
 10) 2004 EXISTING BUILDING CODE CHAPTER 10, 1006.1
 INVESTIGATION AND EVALUATION REPORT.
 AN HISTORIC BUILDING UNDERGOING ALTERATION OR CHANGE OF
 OCCUPANCY SHALL BE INVESTIGATED AND EVALUATED. IF IT IS
 INTENDED THAT THE BUILDING MEET THE REQUIREMENTS OF
 THIS CHAPTER, A WRITTEN REPORT SHALL BE PREPARED AND
 FILED WITH THE BUILDING OFFICIAL BY A
 FLORIDA-REGISTERED ARCHITECT OR ENGINEER. SUCH REPORT
 SHALL BE IN ACCORDANCE WITH THE PROVISIONS OF SECTIONS
 4.3.1.2 THROUGH 4.3.2 OF NFPA 914, CODE FOR FIRE
 PROTECTION OF HISTORIC STRUCTURES AND SHALL IDENTIFY
 EACH REQUIRED SAFETY FEATURE THAT IS IN COMPLIANCE WITH
 THIS CHAPTER AND WHERE COMPLIANCE WITH THIS OR OTHER
 CHAPTERS WOULD BE DAMAGING TO THE CONTRIBUTING HISTORIC
 FEATURES. IN ADDITION, THE REPORT SHALL DESCRIBE EACH
 FEATURE THAT IS NOT IN COMPLIANCE AND DEMONSTRATE HOW
 THE INTENT OF THE PROVISIONS OF THIS OR OTHER CHAPTERS
 ARE COMPLIED WITH IN PROVIDING AN EQUIVALENT LEVEL OF
 SAFETY. PLEASE PROVIDE COMPLIANCE WITH THIS SECTION.
  
 NOTE: SINCE WE HAVE NOT RECEIVED ANY INFORMATION
 CONCERNING COMMENT 9 NOR 10 THIS REVIEW WILL BE
 COMPLETED AS 2004 EXISTING BUILDING CODE CHAPTER 8
 CHANGE IN OCCUPANCY AND CHAPTER 9 ADDITIONS. TABLE
 812.4.1 HAZARD CATEGORIES & CLASSIFICATION LIFE SAFETY
 & EXITS PLACES THIS BUILDING INTO A HIGHER HAZARD GROUP
 FROM A BUSINESS (4) TO A R-1 (3) OR HIGHER HAZARD
 CATEGORY (LOWER NUMBER) WHICH ENACTS CHAPTER 10 OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 10A) THE INDEX SHEET DOES NOT INDICATE WITHIN THE
 SUBMITTED PLANS A LIFE SAFETY SHEETS INDICATING
 OCCUPANT LOADS AND EGRESS CAPACITIES. 106.3.5.1.1(6).
  
 10B) THE INDEX SHEET DOES NOT INDICATE WITHIN THE
 SUBMITTED PLANS FOR FIRE SPRINKLER SCHEMATIC
 106.3.5.1.1(5), 403.2 & 903.6.1.
  
 11) SHEET A00A :
  
 11A) TYPO: FBC CHAPTER 6 TYPE OF CONSTRUCTION
 REFERENCES THE IBC NOT THE FBC TABLE 601. PLEASE UPDATE
 PLANS.
  
 11B) DEFINITION FOR WIND-BORN DEBRIS REGION EITHER IS
 SHORTED OR NOT THE 2004FBC WITH 2007 SUPPLEMENT
 DEFINITION. PLEASE UPDATE PLANS.
  
 12) SHEET A00B:
  
 12A) PLANS INDICATE A WALL TYPE ?A? UL DESIGN U419
 INDICATES THE ?? RESILIENT CHANNEL @ 24? O.C.
 VERTICALLY. WHEN REVIEWING THE U419 ASSEMBLY IT
 INDICATES THE USE OF (6A)(A) FURRING CHANNEL TO BE A 2
 3/8? WIDE BY 7/8? DEEP, SPACED 24 ? O.C. PERPENDICULAR
 TO STUDS.
 IF THE CHANNEL IS VERTICAL IT IS PARALLEL TO THE STEEL
 STUD NOT PERPENDICULAR. PLEASE REVIEW AND CORRECT.
  
 12B) PLANS INDICATE A WALL TYPE ?G? SHAFT WALL DESIGN
 WITH A STC RATING OF 34, PLEASE REVIEW SECTION 1207.2
 AIR-BORNE SOUND TRANSMISSION REQUIRING A STC OF NOT
 LESS THAN 50.
  
 12C) PLANS FAIL TO PROVIDE THE FLOOR ASSEMBLY OF THE
 EXISTING STRUCTURE, PLEASE INDICATE COMPLIANCE WITH
 1207.3 STRUCTURE-BORNE SOUND.
  
 12D) PLANS INDICATE A WALL TYPE J2 WHERE THE GYPSUM
 BOARD IS TO BE GLUED DIRECTLY TO THE BLOCK, PLEASE
 PROVIDE SPECIFICATIONS UNLESS OTHERWISE SPECIFIED BY
 THE GYPSUM BOARD MANUFACTURER THE TYPE OF ADHESIVE ,
 AMOUNT AND SPACING OF ADHESIVE TO BE USED.
 2508.1 TABLE 2508.1 GYPSUM BOARD GA-216, 11.
  
 13) SHEET A100:
  
 13A) PLANS INDICATE A RESTRICTED EASEMENT AREA THAT
 RUNS NORTH TO SOUTH THROUGH THE LOWER LEVEL WITH A WALL
 TAG ?L? EXTERIOR WALL, NO RATING, THIS IS NEITHER A
 EXTERIOR WALL, PLEASE SEE TABLE 302.3.2 FOR THE
 SEPARATION REQUIREMENTS FROM UTILITY AND MISC GROUP.
  
 13B) ROOM# 022 EXISTING GENERATOR ROOM DOES NOT PROVIDE
 ANY INFORMATION ON THE EXISTING WALLS NOR FIRE RATINGS,
 PLEASE SEE 403.10.1 & NFPA 110.7.2.1.1 &
 NFPA 110.7.2.3 FLOODING. NOTE PLANS DO NOT INDICATE ANY
 FUEL STORAGE FOR THE GENERATOR, PLEASE REVIEW
 ELECTRICAL COMMENTS FOR THE REQUIRED AMOUNT OF FUEL
 NECESSARY FOR ON SITE
 STORAGE.
  
 13C) ROOM# 004 THE FIRE PUMP ROOM PLANS INDICATE SOME
 WALLS AS WALL TYPE ?L? EXTERIOR WALL NO RATING AND WALL
 TYPE ?F? NOT RATED, PLEASE SEE NFPA
 20.5.12.1.1.1.REQUIRING 2 HOUR SEPARATION FOR HIGH RISE
 CONSTRUCTION.
  
 13D) STAIR A # 001 ALSO DOES NOT INDICATE WALL TYPE
 EXCEPT FOR A SECTION WALL TAG ?L? OR EXTERIOR WALL
 WHICH SEPARATES THE STAIRWELL FROM THE GYM. SEE 707.4 A
 2 HR FIRE RATING IS REQUIRED ALSO 1019.1..
  
 13E) STAIR A # 001 ALSO LEADS INTO THE SUMP PIT ROOM
 DOOR # 01, PLEASE REVIEW 1019.1 AN EXIT ENCLOSURE SHALL
 NOT BE USED FOR ANY PURPOSE OTHER THAN MEANS OF EGRESS.
  
 13F) STAIR A # 001 DOOR # 02 DOES NOT INDICATE ANY FIRE
 RATING SEE SHEET A700. SEE TABLE 715.3 OPENING
 PROTECTIVE?S.
  
 13G) STAIR B # 028 STAIRS ARE EXISTING BUT THE PLANS DO
 NOT INDICATE TYPE OF WALLS, REQUIRES A 2HR FIRE
 RESISTANCE RATING 707.4 & 1019.1.
  
 14) SHEET A101:
  
 14A) STAIR A100 FIRST FLOOR CONTINUES TO THE LOWER
 LEVEL BELOW GRADE PLEASE REVIEW SECTION
 1019.1.6.
  
 14B) FIRE COMMAND ROOM, ROOM# 114 INDICATES WALL TAG
 ?F? A NON-RATED WALL. PLEASE REVIEW 911.1. A 1-HR FIRE
 RESISTANCE RATED FIRE BARRIER.
  
 14C) FIRE COMMAND DOOR# 132 DOES NOT INDICATE ANY FIRE
 RATING SHEET A700.
  
 14D) FIRE COMMAND DOOR# SHEET A700 INDICATES HARDWARE
 TYPE# 19 ON THE HARDWARE SCHEDULE A701 HARDWARE SET# 19
 ONLY INDICATES 2 DOORS RECEIVING THIS HARDWARE NEITHER
 THE FIRE COMMAND ROOM, SHEET A700 INDICATES 6 DOORS
 RECEIVING THIS TYPE HARDWARE, PLEASE CORRELATE PLANS,
 OPENING PROTECTIVE?S SECTION 715.
  
 14E) PLANS ARE TO INDICATE COMPLIANCE WITH 911.1.
 CONTAIN THE FOLLOWING FEATURES.
 1. THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM UNIT.
 2. THE FIRE DEPARTMENT COMMUNICATIONS UNIT.
 3. FIRE DETECTION AND ALARM SYSTEM ANNUNCIATOR UNIT.
 4. ANNUNCIATOR UNIT VISUALLY INDICATING THE LOCATION OF
 THE ELEVATORS AND WHETHER THEY ARE OPERATIONAL.
 5. STATUS INDICATORS AND CONTROLS FOR AIR-HANDLING
 SYSTEMS.
 6. THE FIRE-FIGHTER?S CONTROL PANEL REQUIRED BY SECTION
 909.16 FOR SMOKE CONTROL SYSTEMS INSTALLED IN THE
 BUILDING.
 7. CONTROLS FOR UNLOCKING STAIRWAY DOORS
 SIMULTANEOUSLY.
 8. SPRINKLER VALVE AND WATER-FLOW DETECTOR DISPLAY
 PANELS.
 9. EMERGENCY AND STANDBY POWER STATUS INDICATORS.
 10. A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED
 ACCESS TO THE PUBLIC TELEPHONE SYSTEM.
 11. FIRE PUMP STATUS INDICATORS.
 12. SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL
 FLOOR PLAN AND DETAILING THE BUILDING CORE, MEANS OF
 EGRESS, FIRE PROTECTION SYSTEMS, FIRE-FIGHTING
 EQUIPMENT AND FIRE DEPARTMENT ACCESS.
 13. WORKTABLE.
 14. GENERATOR SUPERVISION DEVICES, MANUAL START AND
 TRANSFER FEATURES.
 15. PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED
 BY OTHER SECTIONS OF THIS CODE.
  
  
 14F) JUST TO THE RIGHT OF THE FIRE COMMAND ROOM IN THE
 CORRIDOR THERE IS A PAIR OF DOUBLE DOORS WITH OPPOSITE
 LEAF ACTION, THIS SET OF DOORS ARE NOT IDENTIFIED, THE
 CORRIDOR IS INDICATED AS A 5?-10? MINIMUM, THE DOORS
 SCALE OUT TO BE APPROXIMATELY (2) 2?-6? WIDE, PLEASE
 REVIEW 1008.1.1 MINIMUM32?CLEAR OPENING, AND 11-4.3.(9)
 & 11-4.3.10.
  
 14G) THE COMMENT DIRECTLY ABOVE ALSO RELATES TO DOOR#
 119.
  
 14H) LINEN STORAGE ROOM DOOR# 119 WHICH ALSO ACTS AS A
 LAUNDRY CHUTE ACCESS ROOM, THE WALL MARKERS INDICATES
 MARKER ?F? NON-RATED WALLS, IF THIS ROOM HAD ONLY LINEN
 STORAGE THIS WOULD BE CORRECT. 707.13.3 LAUNDRY CHUTE
 ACCESS ROOM REQUIRE 1 HR FIRE RATED WALLS AND OPENING
 PROTECTIVES ? HR WITH SELF CLOSING OR AUTOMATIC CLOSING
 UPON ACTIVATION OF THE DETECTION OF SMOKE.
  
 14I) JUST TO THE RIGHT OF ELEVATOR# 3 THERE APPEARS TO
 BE A DOOR# 18A OR 18D NEITHER DOOR IS LOCATED ON THE
 DOOR SCHEDULE LOCATED ON SHEET A700.
  
  
 14J) HALL# 127 THERE SEAMS TO BE A DISCREPANCY IN THE
 SOUTH WALL LOCATION THAT BACKS UP TO THE STAIRS THAT
 DESCEND TO THE LOWER BASEMENT EASEMENT.
  
 14K) STAIR TOWER B VERSES KING ROOM 122, THE WALL TAG
 INDICATES A WALL TYPE ?A? A 1 HOUR RATED WALL. STAIR
 TOWER B (VERTICAL EXIT) DOES NOT END AT DOOR 126, IT
 BECOMES A EXIT PASSAGEWAY OR CONTINUATION OF THE 2 HR
 ENCLOSURE UNTIL DOOR# 127 THE EXIT . PLEASE VISIT
 1019.1.
  
 14L) STAIR TOWER B AT DOOR 124) SWINGS THE WRONG WAY IT
 SWINGS INTO THE EGRESS PATH BLOCKING THE EXIT, THE DOOR
 SHOULD REVERSE THE SWING OF THE DOOR AGAINST THE COMMON
 WALL WITH ROOM# 122. 1008.1.8.8.
  
 14M) DOOR# 126 FROM THE VERTICAL EXIT OPENS DIRECTLY
 INTO THE STAIR LANDING THE LOCATION OF THIS DOOR BLOCKS
 THE EGRESS PATH OF BOTH THOSE EXITING FROM THE LOWER
 LEVEL AS WELL AS FROM THIS LEVEL . 1008.1.5.
  
 14N) THE SOUTH WALL OR PROPERTY LINE WALL HAS NUMEROUS
 DOOR OPENINGS THAT CROSS OVER THE PROPERTY LINE INTO
 THE PUBLIC ALLEY WAY, PLEASE REVIEW 3202.2 DOORS AND
 WINDOWS SHALL NOT OPEN OR PROJECT INTO THE PUBLIC RIGHT
 ?OF-WAY.
  
 14O) THIS SHEET INDICATES THAT THERE IS AN EXISTING FPL
 EASEMENT, CURRENTLY THERE IS NO DOCUMENTS RELINQUISHING
 THE EASEMENT OR GRANTING USE OF THE EASEMENT WITH
 EXCEPTIONS TAKEN. 3201.03 .
  
 14P) FPL VAULT NOTE ON PLAN FOR WALL TAG IS K3 BUT THE
 NORTH AND SOUTH WALL FACING THE RIGHT-OF-WAY DO NOT
 INDICATE WALL TYPES, NOR DOES THE PLAN INDICATE THE
 FLOOR/ CEILING ASSEMBLY RATING FOR THIS ROOM FOR THREE
 HRS. NOTE NO REDUCTION FOR FIRE SPRINKLERS SINCE THE
 VAULT IS NOT FIRE SPRINKLERED. NEC 450.42/ FPL
 REQUIREMENTS MAY BE HIGHER. ALSO NOTE VAULT DOORS ALSO
 REQUIRE A 3HR RATING. CONTACT FPL FOR FURTHER VAULT
 REQUIREMENTS.
  
 14P) PLANS INDICATE NUMEROUS OPENINGS WITHIN THE FIRST
 STORY (ALLEYWAY) OF THE BUILDING, TABLE 704.8 ALLOWS
 25% OPENINGS FOR FIRE SPRINKLERED BUILDINGS, PLEASE
 PROVIDE CALCULATIONS FOR THE FIRST FLOOR.
  
 14R) THIS SHEET SCALES OUT TO HAVE THE ALLEYWAY AS A
 16?-0? RIGHT-OF-WAY WHERE THE SURVEY INDICATES A 15?-0?
 RIGHT OF WAY, PLEASE CORRECT. DISCREPANCY.
  
 15) SHEET A102:
  
 15A) THIS COMMENT WILL BE FOR THE 2ND FLOOR THROUGH THE
 6TH FLOOR STAIR ?A? INDICATES ONLY A ONE HOUR RATING
 (WALL TAG ?L?) BETWEEN THE STAIRWAY AND THE GUEST ROOMS
 DIRECTLY TO THE WEST 1019.1.
  
 15B) ELEVATOR LOBBY 201, COMMON COMMENT 2ND FLOOR
 THROUGH THE 6TH FLOOR, WILL REQUIRE A 1 HOUR RATING.
 SEE 707.14.1 AND CODE COMMENTARY. WILL REQUIRE ONE HOUR
 FIRE RESISTANCE WITH OPENING 715.3. ELEVATOR # 3 IS
 MISSING THE ELEVATOR LOBBY TOTALLY. COMMON TO ALL
 FLOORS.
  
 15C) SUITE 207 THE WALL COMMON WITH THE ELEVATOR LOBBY
 AND DATA ROOM 201DOES NOT HAVE A WALL TAG, WILL REQUIRE
 1 HOUR RATING 708.1(2) AND SOUND RATING STC OF NOT LESS
 THAN 50 1207.2. COMMON TO ALL FLOORS.
  
 15D) UNITS 207, 208 & 209 REMOVED THE EAST WALL LINE TO
 CREATE NEW BALCONIES. THE DISTANCE BACK TO THE NEW WALL
 LINE IS 5?-0? PLEASE REVIEW TABLE 704.8 FOR ALLOWABLE
 OPENINGS BETWEEN 3?-TO 5?-0? IS 15%, PLEASE PROVIDE THE
 PERCENTAGE OF WALL OPENINGS.
 3RD-6TH FLOORS WALL REMOVED SET BACK IS 5?-1? ALLOWABLE
 OPENINGS IS 25% PLEASE PROVIDE CALCULATIONS.
  
 15E) UNITS 207, 208 & 209 INDICATE THE WALL LINE 5?-0?
 FROM THE PROPERTY LINE. PLEASE SEE WALL TAG ?H?
 INDICATES UL DESIGN U-418, NOTE THIS ASSEMBLY IS RATED
 FROM THE INTERIOR SIDE ONLY. 704.5 INDICATES WHEN FIRE
 RESISTANCE RATINGS OF EXTERIOR WALLS WITH A FIRE
 SEPARATION DISTANCE OF 5 FEET OR LESS SHALL BE RATED
 FOR EXPOSURE TO FIRE FROM BOTH SIDES. PLEASE PROVIDE
 THE CORRECT ASSEMBLY.
  
 15F) SHEET A00B WALL TAG ?H? IS INDICATED AS A 2 HOUR
 FIRE RATING, UL U-418, AS DEPICTED IN THE PLAN ONLY ONE
 LAYER OF 5/8? GYPSUM IS INDICATED, IN THE UL LISTING
 UNDER HEADING NUMBER FOUR FOR A 2 HR RATING THREE
 LAYERS OF ?? GYPSUM BOARD, PLEASE REVIEW THE SOUTH WALL
 OF ANNEX.
  
 15G) SHEET A00B WALL TAG ?H? IS INDICATED AS A 2-HR
 EXTERIOR RATED WALL. WITHIN THE WALL ASSEMBLY THE PLAN
 CALLS FOR THE USE OF 5/8? EXTERIOR SHEATHING. PLEASE
 REVIEW SECTION 603.1.1(1.2) NONBEARING EXTERIOR WALLS
 WHERE NO FIRE RATING IS REQUIRED. TABLE 602
 REQUIRES A FIRE RATING FOR A TYPE IB UP TO 30?-0? FROM
 THE PROPERTY LINE.
  
 15H) THIS COMMENT WILL BE COMMON 2ND FLOOR THROUGH THE
 6TH FLOOR. ROOM GUEST ROOM 226 LIGHT WELL AND GUEST
 ROOM 227. TO DO AN ACCURATE REVIEW ON THIS AREA
 ADDITIONAL INFORMATION WILL BE REQUIRED. PLANS DO NOT
 PROVIDE ANY DETAIL ON THE GARDEN, PLANS DO NOT INDICATE
 WALLS THAT WILL RETAIN SOILS, WATER RESISTANT, OR WATER
 PROOFING, DEPTH OF SOIL AND TYPE OF PLANTS WILL THERE
 BE ANY WATER FEATURES? FIRE LOADS ARE NOT KNOWN?
 THE PLANS DO CALL OUT FOR A 2 HOUR RATED WALL BUT THE
 WINDOW TYPE M AND M1 ARE SINGLE HUNG WINDOWS KEYED FOR
 MAINTENANCE USE ONLY. THERE IS NO MENTION OF 1 ? HOUR
 OPENING PROTECTION ON THE WINDOWS.
  
 UNTIL THE FIRE LOADS ARE KNOWN WE CAN NOT ACCURATELY
 REVIEW THIS AREA IT MAY BE CLASSIFIED ONLY AS A SHAFT
 OR IT MAY BE CLASSIFIED AS A ATRIUM AND MEET THE
 REQUIREMENTS OF 404.
  
 15I) SUITE# 213 HAS A SHAFT LOCATED ON THE EAST SIDE OF
 THE ROOM, NO WALL TAG IS PROVIDED.
 SEE 707.4 SHAFT ENCLOSURES/ RATINGS.
  
 15J) SOUTH WALL OF ANNEX WALL TAG ?H?(SHEET A00B) IS
 INDICATED AS THREE WALL TYPE FINISHES, THE FIRST IS
 INDICATED AS A BRICK VENEER WITH WALL TIES. THERE IS NO
 DETAIL INDICATING HOW THE BRICK ARE SUPPORTED. THIS
 SAME DETAIL ALSO INDICATES A MINIMUM 1 INCH AIR SPACE
 WITH THE WALL TIES MEANING A FULL BRICK VENEER NOT JUST
 A FACING OF BRICK. THE CUT SECTION THROUGH THIS SAME
 WALL DETAIL C OF A501 FORWARDS YOU TO ANOTHER DETAIL
 1.1 OF A504 WHICH IS A THIN SET APPLICATION WITH JUST A
 FACING TREATMENT. PLEASE COORDINATE DETAILS SO A REVIEW
 OF THIS SECTION CAN BE COMPLETED. DISCREPANCY IN PLANS,
 INSUFFICIENT INFORMATION PLEASE COORDINATE PLANS. NOTE
 THERE IS NO STRUCTURAL DETAILS INDICATING A BRICK
 VENEER WITH WALL TIES.
  
 15K) SAME DETAIL AS LISTED ABOVE WALL TAG ?H? (SHEET
 A00B) LIST A METAL PANEL SYSTEM AS
  
  
 15I) ANNEX ADDITION PLAN SOUTH WALL TAG INDICATES WALL
 TAG ?H?, DETAIL ?C? SHEET 501 , AND DETAIL 1.2 A504
 INDICATE THE USE OF 5/8? EXTERIOR GRADE PLYWOOD, PLEASE
 REVIEW USE OF COMBUSTIBLES IN TYPE I / II BUILDINGS.
 603.1(1.2) ONLY ALLOWS THE EXTERIOR NONBEARING WALLS
 WHERE NO FIRE RATING IS REQUIRED. THIS WALL WILL
 REQUIRE A 2 HR RATING SEE TABLE 602.
  
 15J) BOTH THE NORTH AND WEST WALL OF THE ANNEX WILL
 HAVE A SEPARATION DISTANCE GREATER THAN 30? SO FIRE
 RETARDANT TREATED 5/8 INCH PLYWOOD WOULD BE ALLOWED,
 PLEASE SEE TABLE 602 AND ADD NOTE TO PLAN.
  
 15K) ANNEX PLANS NOTE EXTERIOR WALL TYPE ?E? BUT
 INDICATE THE USE OF METAL PANEL, IS THIS TO BE A MCM
 PANEL SYSTEM, PLEASE PROVIDE ADDITIONAL INFORMATION,
 MUST MEET ALL THE REQUIREMENTS OF SECTION 1407 FOR
 METAL COMPOSITE MATERIALS.
  
 15L) THIS SAME WALL TYPE ?E? INDICATES THE USE OF
 CURTAIN WALL GLAZING PLEASE PROVIDE ADDITIONAL
 INFORMATION FOR THIS SYSTEM. 1609.6.2.2 & 704.13.1
 VOIDS.
  
 15M) ROOMS 229& 230 AS WELL AS 231 & 232 BOTH INDICATE
 WALL TYPE ?J? WHICH ONLY HAS A STC RATING OF 45
  
 16) SHEET A103 3RD -6TH FLOOR HAVE SIMILAR PROBLEMS AS
 THE 2ND FLOOR LIST DIRECTLY ABOVE.
  
 17) SHEET A104 :
  
 17A) STAIR ?A? ROOM 702 HAS A STORAGE AND ELEVATOR
 EQUIPMENT ROOM ,MECHANICAL ROOM 703 ENTER DIRECTLY INTO
 IT.
 1019.1 THE MECHANICAL AND STORAGE ROOM SHOULD HAVE THE
 DOORWAY ON THE POOL DECK NOT INTO THE VERTICAL STAIR
 TOWER, 1019.1.
  
 17B) PLANS CALL OUT FOR A VERTICAL LIFT, PLEASE PROVIDE
 DOCUMENTATION WITH 11-4.11.2.
  
 17C) THE ROOF PLAN DOES NOT PROVIDE ENOUGH INFORMATION
 AS TO WHERE GUARDS AND HANDRAILS ARE LOCATED ON THE
 ELEVATED POOL DECK SECTION AND STAIRS AS TO LOCATION,
 MATERIAL CONSTRUCTED FROM AND HEIGHT. 1009.11, 1012.1,
 1012.2 & 1012.3.
  
 17D) THE PLAN INDICATES THE USE OF A 30?-0? SECTION OF
 GLAZED GUARD RAIL PLEASE PROVIDE INFORMATION FOR
 1607.7, 2407.1, 2407.1.1, & 2407.1.2.
  
 17E) PLANS INDICATE A ADA LIFT INTO THE POOL, PLEASE
 PROVIDE MANUFACTURES? SPECS. 106.1.2 ADDITIONAL
 INFORMATION REQUIRED & 424.1.2.5.6.
  
 17F) THE ROOF OVER THE STAIR A, RESTROOMS AND
 MECHANICAL ROOM INDICATE A ROOF DRAIN BUT NO SECONDARY
 OVER FLOW OR SCUPPER. 1503.4.3.
  
 17G) THE POOL DECK AND LOWER ROOF DECK ALSO ARE MISSING
 THE OVER FLOW ROOF DRAINS AND OR SCUPPERS 1503.4.3.
  
 17H) PLEASE PROVIDE A LARGER SECTION OF THE MEN?S AND
 WOMEN?S RESTROOMS,
  
 17H)1) BOTH DOORS 707 AND 708 APPEAR TO SWING INTO THE
 CLEAR FLOOR SPACE REQUIRED FOR ACCESSIBLE PLUMBING
 FIXTURES 11-4.22.3.
  
 17H)2) DOOR 207 AND 208 PLEASE REVIEW SECTION 11-4.13.7
 DOORS IN SERIES.
  
 17H)3) DOOR 703 IT APPEARS IS MISSING THE REQUIRED 18?
 AT THE LATCH SIDE OF THE DOOR.
 11-4.13.6.
  
 17I) IT APPEARS IN BOTH VERTICAL EXITS THERE IS A STEP
 DIRECTLY INSIDE THE BUILDING WITHOUT A LEVEL FLOOR WITH
 THE EXTERIOR OF THE BUILDING, 1008.1.4.
  
 17J) ROOM 703 THE ELEVATOR EQUIPMENT ROOM DOES NOT
 INDICATE ANY VENTILATION, WILL NEED TO COMPLY WITH
 3004.1 & 3004.2.
  
 17K) JUST TO THE RIGHT OF THE VERTICAL EXIT ?B? THERE
 IS A ROOM WITH NO IDENTIFICATION JUST DOOR NUMBER 710,
 PLEASE PROVIDE USAGE? 106.1.2. ADDITIONAL INFORMATION
 REQUIRED.
  
 17L) NOTE: POOL GATES AND FENCING REQUIREMENTS
 DEPARTMENT OF HEALTH RULE 64E-9 FLORIDA ADMINISTRATIVE
 CODE AND CHAPTER 514 FLORIDA STATUTES.
  
 18) SMOKE CONTROL SYSTEMS: UNDER THE EXISTING BUILDING
 CODE FOR THE BASE BUILDING THE CODE DOES NOT ADDRESS
 THIS, THE FLORIDA BUILDING CODE IS BASED OFF OF THE IBC
 WHERE SMOKE CONTROL IN HIGH RISES IS NOT A REQUIREMENT,
 SO IT HAS NEVER BEEN INTRODUCED INTO THE EXISTING
 BUILDING CODE.
 ADDITIONS UNDER THE EXISTING BUILDING CODE DOES REQUIRE
 SMOKE CONTROL PLEASE SEE 902.3 OF THE EXISTING BUILDING
 CODE. EXISTING ALLOWABLE AREAS INCREASED BY ADDITIONS
 SHALL COMPLY WITH CHAPTER 9 OF THE FLORIDA BUILDING
 CODE, BUILDING. PLEASE REVIEW 909.16 FIRE-FIGHTER?S
 SMOKE CONTROL PANEL. 909.16. 1-3.
  
 19) SHEET A105:
  
 19A) PLANS INDICATE A 3? ROLL DECK, PLEASE PROVIDE
 ADDITIONAL INFORMATION AS TO THIS PRODUCT. 106.1.2.
 ADDITIONAL INFORMATION REQUIRED.
  
 19B) DETAIL B INDICATES THE USE OF MCM PANELS
 (ALUMINUM) PLEASE PROVIDE INFORMATION ON THIS PRODUCT
 AS FAR AS FIRE RESISTANCE RATINGS AND WIND PRESSURES.
 1407 & 1609.6.
  
 19C) PLANS APPEAR WITH A HATCH LINE BUT IT IS NOT CLEAR
 WHAT THIS IS FOR, MECHANICAL PLANS INDICATE ROOF TOP
 MECHANICAL EQUIPMENT, IS THIS A SCREEN FOR THE
 MECHANICAL EQUIPMENT?
 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 19D) ROOF TOP EQUIPMENT; SHALL BE COVERED UNDER THIS
 REVIEW AS WELL AS MECHANICAL FOR THE RESISTANCE OF THE
 EQUIPMENT AND CASING TO RESIST WIND. PLEASE SHOW
 COMPLIANCE WITH
 MECHANICAL- 301.13 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES ON THE EQUIPMENT AND THE SUPPORTS AS
 DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, BUILDING. THIS MAY BE ACCOMPLISHED BY DESIGN OR
 BY APPLICATION OF SECTION 301.13.1. ROOF-MOUNTED
 MECHANICAL UNITS AND SUPPORTS SHALL BE SECURED TO THE
 STRUCTURE. THE USE OF WOOD ?SLEEPERS? SHALL NOT BE
 PERMITTED. PLEASE SHOW COMPLIANCE.
  
 19E) ROOF HATCH PLEASE REVIEW REQUIREMENTS FOR STAIRS
 TO THE ROOF WHEN BUILDINGS ARE 4 OR MORE STORIES.1009.
 12.
  
 20) SHEET A106 DETAIL# 4 NOTE: ROOF DRAINS ARE NOT IN
 THE MIDDLE OF THE ROOF CREATING LONGER RUNS IN SLOPED
 INSULATION. WHERE EVER THE ROOF DRAIN IS LOCATED THIS
 IS THE MINIMUM THICKNESS OF INSULATION, FOR INSTANCE IF
 YOUR ENERGY REPORT INDICATES A R-19 THIS IS THE MINIMUM
 THICKNESS OF INSULATION AND FROM THERE THE THICKNESS IS
 INCREASED. 13-404.1.ABCD.1 AND FBC INFORMAL
 INTERPRETATION REPORT#3731 & 3746.
  
 21) SHEET A200 LOWER CEILING LEVEL THE LAUNDRY DRYERS
 ARE GANGED TOGETHER NO ARCHITECTURAL PLANS OR
 MECHANICAL PLANS INDICATE A TERMINATION POINT? 106.1.2
 ADDITIONAL INFORMATION REQUIRED. DIRECTLY TO THE WEST
 IS THE EASEMENT ALONG THE WEST WALL!
  
 22) SHEET A201 DETAIL 02 SOFFIT DETAIL INDICATES THE
 USE OF UNISTRAT AND THREADED RODS, ON INFORMATION IS
 PROVIDED AS TO ANCHORAGE OF THE UNISTRUCT TO THE
 STRUCTURE ABOVE, CENTER TO CENTER OF THE UNISTRUCT,
 THICKNESS OF THE THREADED RODS AND SPACING, NOR THE
 HORIZONTAL MEMBER BETWEEN THE BOTTOM UNISTRUCT AND WOOD
 VENEER CEILING PANEL OR HOW WOOD CEILING PANELS WILL BE
 FASTENED. 106.1.2. ADDITIONAL INFORMATION REQUIRED AND
 803.4.2 SET OUT CONSTRUCTION AND REQUIREMENTS FOR FIRE
 TREATED RESISTANT FURRING OR BACKING.
  
 23) SHEET A202 DETAIL 02 INDICATES STRUCTURAL MEMBERS
 ARE TO HAVE A 2HR RATING TABLE 601 BUT NO UL ASSEMBLY
 WAS PROVIDED. PLANS ALSO INDICATE OR SPRAY ASSEMBLY.
 PLEASE IDENTIFY
 WHICH SYSTEM WILL BE INSTALLED WITHIN THE STRUCTURE AND
 PROVIDE ASSEMBLY OR PRODUCT INFORMATION. INFORMATIONAL
 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR
 IN PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED
 AS A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION
 DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 24) SHEET A303 DETAIL 03 IS MISSING COMPLIANCE WITH
 FIGURE 11-19?(D) AND 11-4.4.
  
 25) SHEET A303 DETAIL 3 THE HANDRAIL CAN NOT HAVE A
 PERIMETER GREATER THAN 6.25 INCHES,
 PLANS INDICATE A 6.5 INCHES. 1009.11.3.
  
 26) SHEET A305 INDICATES WOOD PANELING ON ?? PLYWOOD
 BACKER. PLEASE REVIEW 803.4.2 SET OUT CONSTRUCTION AND
 REQUIREMENTS FOR FIRE TREATED RESISTANT FURRING OR
 BACKING.
  
 27) SHEET A309 DETAIL F BREAK ROOM SINK THE CABINET HAS
 DOORS MAKING IT IMPOSSIBLE FOR A FRONT APPROACH. SINKS:
 11-4.24.2 SINKS, HEIGHT. SINKS SHALL BE MOUNTED WITH
 THE COUNTER NO HIGHER THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH 30"
 WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH SINKS.
 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT
 LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR
 FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE
 SINK.
  
 28) 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE
 DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M)
 ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
 29) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES,
 3 IF THRESHOLD OR RESIDENT INSPECTOR OF PRODUCT TESTING
 REPORTS, MISSING REPORTS ARE AS FOLLOWS:
  
 A) FIXED GLAZING
 B) STOREFRONT
 C) CURTAIN WALL
 D) MULLIONS
 E) EXTERIOR STOREFRONT
 F) EXTERIOR METAL DOORS ? INSULATED
 G) ROLLING OVERHEAD DOOR
 H) PANEL WALL SYSTEMS- SOFFITS, SIDING PRODEMA WOOD
 PANEL SYSTEMS,
 ALPOLIC METAL PANEL SYSTEMS, & MCM SYSTEM
 I) WALL LOUVERS
 J) SKYLIGHTS
 K) ROOFING ASSEMBLIES
 M) PRE-ENGINEERED A/C STANDS
 30) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 31) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 32) A702 DETAIL H SMOKE DRAFT CURTAIN PLEASE PROVIDE
 WHERE THIS DETAIL IS BEING INSTALLED?
  
 33) S-1 DESIGN NOTES MINIMUM LIVE LOADS PLEASE REVIEW
 THE FOLLOWING:
 33A) FLOORS INDICATES 40 PSF PLEASE PROVIDE WHAT
 OCCUPANCY TYPE
 33B) CORRIDORS ARE INDICATED AT 40 PSF THIS IS WITHIN
 HABITABLE AREAS
 33C) BALCONIES ARE INDICATED AT 60 PSF, EXTERIOR
 BALCONIES FOR 1 AND 2 FAMILIES CORRECT TO
 100 PSF
 33D) CORRIDORS 100 PSF
 33E) NOT MENTION IN PLANS DINING ROOMS AND RESTRAINT
 100PSF
 TABLE 1607.1
  
 34) S-1 DOES NOT PROVIDE THE CORRECT WIND SPEED, PLEASE
 SEE FIGURE 1609, WEST PALM BEACH IS LOCATED WITHIN A
 140 MPH 3 SECOND GUST. WIND PRESSURES WILL CHANGE WITH
 THE
 GREATER WIND SPEED.
  
 35) INPUT DATA REPORT:
 35A) EXTERIOR DOORS ARE MISSING FROM THE INPUT DATA
 REPORT.
 35B) SKYLIGHT IS MISSING INFORMATION FROM THE INPUT
 DATA REPORT
 35C) FLOORS IS LEFT BLANK FROM THE INPUT DATA REPORT
  
 36) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-12-12 Cont ID  
Sent By dpalmer Date 2008-12-12 Time 14:13 Rev Time 0.00
Received By dpalmer Date 2008-12-12 Time 14:13 Sent To  
Notes
2008-12-12 14:14:08 
 ** DENIED REVIEW **
  
 ** NOT SUBMITTED AS HISTORIC FOR EXISTING. NO
 SUPPORTING DOCUMENTS, PLANS ETC.
 PLEASE SEE NEW PORTION OF BUILDING AND MANY AREAS ARE
 CONSIDERED REVIEW UNDER FBC AND FBC EXISTING BUILDINGS
 AND ALL STATUTORY ADOPTED CODES, LAWS ETC.
  
  
  
  
 1) NOTE: PLANS ONLY SUBMITTED FOR *PLAN REVIEW * AND
 HAVE NOT BEEN SUBMITTED FOR PERMIT APPLICATION. AS PER
 FLORIDA STATUTES 553.73 ONLY PERMIT APPLICATION BY
 LICENSED CONTRACTOR WILL *LOCK-IN* PROJECTS UNDER
 ADOPTED CODES.
 FOR EXAMPLE: IF THIS PROJECT WHICH HAS ONLY BEEN
 SUBMITTED AS PLAN REVIEW AND DOES APPLY FOR PERMIT
 UNTIL MARCH 1ST, 2009 THE NEW CODES COMING IN AFFECT
 WILL BE REQUIRED TO BE THE MINIMUM CODES FOR DESIGN.
 OTHER ITEMS SUCH AS LICENSING OF CONTRACTORS AND
 DESIGNERS WILL ALSO BE REVIEWED ONCE PERMIT APPLICATION
 IS MADE.
 EVEN ONCE PLANS ARE FOUND TO BE CODE COMPLIANT FOR
 ISSUANCE THEY WILL REMAIN IN A FAILED STATUS UNTIL
 PERMIT APPLICATION IS MADE.
  
 2) NOTE: IT IS IMPORTANT TO UNDERSTAND THAT THE PLANS
 SUBMITTED FOR REVIEW ARE NOT COMPLETE AT THIS TIME FOR
 MINIMUM CODE COMPLIANCE. IN FACT MOST OF THE SHEETS FOR
 ELECTRICAL AND OTHER TRADES EVEN STATE ON THE SHEETS *
 PERMIT REVIEW/NOT FOR CONSTRUCTION* ALTHOUGH THEY ARE
 SIGNED, DATED AND SEALED BY THE RESPECTIVE DESIGN
 PROFESSIONAL.
 AS THERE ARE MANY ITEMS NOT COMPLETED IN THE SETS AND
 SUPPORTING DOCUMENTS A FULL AND COMPLETE REVIEW OF
 DOZENS OF ITEMS COULD NOT BE DONE. PLANS MAY VERY WELL
 HAVE NEW COMMENTS WHEN RE-SUBMITTED.
 PLEASE SEE MANY OF THE NOTES BELOW WHICH WILL NOTE MANY
 OF THESE ITEMS.
  
 3) NOTE: PLEASE SEE THE SUBMITTED LANDSCAPE
 ARCHITECTURAL PLANS. THE ONLY SHEET IN THE SET IS SHEET
 5 OF 6. THIS SHEET WHICH CONTAINS THE PRINTED NAME AND
 LICENSE NUMBER OF A LANDSCAPE ARCHITECT IS IN FACT
 SIGNED, DATED AND SEALED BY THE ARCHITECT OF THE
 PROJECT AS LISTED ON ARCHITECTURAL SHEETS.
 THIS IS NOT PERMITTED UNDER FLORIDA STATUTES 481.221,
 FAC 61G1-16. NO DESIGN PROFESSIONAL SHALL AFFIX HIS/HER
 SEAL TO ANY PLANS, DOCUMENTS ETC WHICH ARE NOT UNDER
 THEIR DESIGN.
 PLEASE SUBMIT COMPLETE LANDSCAPE PLANS FOR SETS SHOWING
 ANY LANDSCAPE LIGHTING AND BE SURE TO COORDINATE WITH
 THE SUBMITTED ELECTRICAL PLANS.
 NEC 2005
 FBC 106.1.1 FOR COORDINATION, COMPLETION AND CLARITY OF
 PLANS.
  
 4) NOTE: PLEASE KNOW AT THIS TIME BASED ON THE CURRENT
 ADOPTED CODES THE FOLLOWING SHALL BE LISTED ON THE
 SUBMITTED PLANS. SOME OF THESE MAY ALREADY BE PRESENT
 HOWEVER MANY ARE NOT.
 THE SUBMITTAL OF PERMIT APPLICATION UNDER LICENSED
 CONTRACTOR AS NOTED ABOVE IN NOTE #1 WILL AFFECT
 ADOPTED CODES AND APPLICABILITY.
  
 2004 FBC W/2007 REVISIONS.
 2004 FBC W /2007 REVISIONS: CHAPTER 13 ENERGY
 EFFICIENCY CODE
 2005 NFPA-70 ( NEC).
 2003 NFPA-101
 2002 NFPA-72
 2003 NFPA-20
 2002 NFPA-110
  
 5) NOTE: PLEASE BE SURE TO SUBMIT COMPLETED ENERGY
 CALCULATIONS. PLEASE BE SURE ALL INFORMATION O THE
 INPUT DATA REPORT AND SUMMARY SHEETS COORDINATE WITH
 THE SUBMITTED PLANS. THERE ARE NUMEROUS ITEMS NOT
 COMPLETED ON THE SUBMITTED CALCULATIONS. THE INPUT DATA
 REPORT WILL BE NOTED AS IDR FOR THE REMAINDER OF THIS
 COMMENT.
 THE FOLLOWING ITEMS ARE EXAMPLES OF INCOMPLETE AND
 NON-CODE COMPLIANT MINIMUMS.
  
  
 A) PLEASE SEE THE SQUARE FOOTAGE ON THE SUBMITTED
 CALCULATIONS IS DIFFERENT FROM THE SUBMITTED PLANS. IN
 FACT THERE ARE TOTALS ON SHEETS AND SUBMITTED DOCUMENTS
 WHICH DIFFER GREATLY. TOTAL SQUARE FOOTAGE IS SHOWN AS
 116,250,117,490,101,648. NONE OF THESE COORDINATE.
 FBC 13-101, 13-400.3.A ETC
 FBC 106.1.1
  
 B) PLEASE SEE THE IDR, THE DOOR SECTION IS BLANK. THIS
 IS NOT POSSIBLE ARE THERE ARE CLEARLY DOORS FROM
 CONDITIONED SPACES TO UNCONDITIONED SPACES AND EXTERIOR
 OF BUILDING.
 FBC 13-403
  
 C) PLEASE SEE THE IDR, THE FLOORS SECTION IS BLANK.
 THIS IS NOT POSSIBLE. SAME AS ABOVE.
 FBC 13-404
  
 D) PLEASE SEE THE IDR, THE SKY-LIGHT SECTION IS BLANK.
 THIS IS NOT POSSIBLE. SAME AS ABOVE.
 FBC 13-401
  
 E) PLEASE SEE THE IDR, THE EXTERIOR LIGHTING SECTION IS
 BLANK. THERE IS IN FACT NO EXTERIOR FIXTURES ENTERED
 HOWEVER BASED ON THE SUBMITTED PLANS THIS IS ONCE AGAIN
 NOT POSSIBLE. THE PLANS CONTAIN DOZENS OF FIXTURES AND
 NONE HAVE BEEN FIGURED.
 FBC 13-415, 13-415.2.ABC.1.3.
  
 F) PLEASE SEE THE IDR FOR INTERIOR LIGHTING. THIS
 INDICATES SOME INTERIOR LIGHTING HOWEVER THERE ARE
 LITERALLY HUNDREDS OF MISSING INTERIOR LIGHTS. PLEASE
 SEE SECTIONS 13-415.2, 13-415.2.ABC.1.1,.1.2 AND .1.3.
  
 G) PLEASE SUBMIT A COMPLETED FIXTURE LEGEND FOR ALL
 FIXTURES ON PLANS. REVIEW FOR CODE COMPLIANCE OF ENERGY
 CALCULATIONS CAN NOT BE DETERMINED AT THIS TIME.
 13-415.2, FBC 106.1.1, ADDITIONAL INFORMATION FOR
 COORDINATION, CLARITY AND MINIMUMS.
  
 THESE ARE SOME EXAMPLES ONLY OF NON-CODE COMPLIANCE.
 THIS IS GIVEN AS A BENEFIT TO DESIGN TEAM AND IT IS NOT
 A COMPLETE LIST OF ALL ITEMS ON THE SUBMITTED DOCUMENTS
 WHICH DO NOT MEET MINIMUMS UNDER SECTIONS GIVEN.
 ** THERE ARE MANY OTHER ITEMS.
  
 6) NOTE: PLEASE SUBMIT AND SHOW COMPLETE DESIGN FOR
 LIGHTING CONTROLS MEETING MINIMUMS FOR FBC 13-415.1,
 13-415.1.ABC.1.1,1.2, .1.3 AND .1.4.
 THE PLANS DO INDICATE SOME ITEMS FOR CODE COMPLIANCE
 HOWEVER THERE ARE NUMEROUS ITEMS MISSING.
  
 7) NOTE: PLEASE SUBMIT PLANS WITH COMPLETED CIRCUITING.
 PLEASE BE SURE ALL ITEMS ON PLANS COORDINATE WITH THE
 SUBMITTED PANEL SCHEDULES. PLEASE ALSO SEE 700.12E FOR
 CIRCUITING OF BATTERY BACK UP EMERGENCY AND EXIT
 LIGHTING. (SEE COMMENTS BELOW WITH RESPECT
 EMERGENCY/EXIT LIGHTING).
 PLANS ARE MISSING CIRCUITING IN MANY LOCATIONS AND
 ITEMS SUCH AS CONDUCTOR SIZES, LOADS ETC CAN NOT BE
 VERIFIED FOR MINIMUM COMPLIANCE AT THIS TIME.
 240.4,310.16,408.4.
 FBC106.1.1, 106.3.5.1.2 FOR CLARITY, COORDINATION ETC.
  
 8) NOTE: PLEASE SEE FPL AND NEC FOR MINIMUM STANDARDS
 AND WALL RATINGS OF VAULTS. THESE ARE NOT SPRINKLED AND
 SHALL MEET NEC MINIMUM STANDARDS OF 3 HOUR RATINGS OF
 ALL WALLS, FLOORS AND CEILINGS.
 450.41,450.42,450.43 ETC
  
 9) NOTE: PLEASE SEE PLANS AS THERE ARE ROOMS AND AREAS
 IN WHICH DO NOT CONTAIN DESIGNATIONS AND IDENTIFICATION
 OF EQUIPMENT. AN EXAMPLE OF THIS WOULD BE THE ROOM/AREA
 OUTSIDE OF DOUBLE QUEEN 128 WHICH APPEARS TO INDICATE A
 TRANSFORMER BY A STANDARD KNOWN SYMBOL HOWEVER NO OTHER
 INFORMATION IS NOTED OR SHOWN.
 NEC 450 IS GIVEN IN GENERAL AS NO INFORMATION IS SHOWN.
 PLEASE SEE POWER PLANS.
  
 10) NOTE: THE ELECTRICAL PLANS ALONG WITH ARCHITECTURAL
 MAKE NOTE OF LIGHTING IN THE RESTRICTED EASEMENT AREAS.
 HOW ARE THESE LIGHTS FED AND FROM WHERE?
 PLEASE ALSO OBTAIN AND SUBMIT INFORMATION ON WHAT
 EQUIPMENT IS LOCATED IN THESE AREAS. THIS WILL
 CERTAINLY AFFECT REVIEW OF WALL RATINGS ETC.
 SOME AREAS LIKE THE NORTHEAST STAIRS NOTES THIS AS A
 RESTRICTED EASEMENT AREA YET THE STAIR IS THE EGRESS
 FOR THE UPPER FLOORS. THERE ARE SEVERAL QUESTIONS YET
 TO BE ANSWERED.
 FBC 106.1.1, NEC 2005 CHAPTERS2,3,4 ETC
  
 11) NOTE: STAIRS ON LOWER LEVELS ARE SHOWING GENERAL
 PURPOSE RECEPTACLES WHICH IS NOT PERMITTED. PLEASE SEE
 FBC CHAPTER 10 FOR ITEMS REQUIRED AND ITEMS PERMITTED
 IN EXIT STAIRS.
 1019.1.2
  
 12) NOTE: PLEASE COMPLETE PLANS WITH ALL EGRESS
 LIGHTING FOR MINIMUM LEVELS IN NFPA-101 7.8, 7.8.1.3
 AND 7.9, 7.9.1.1,7.9.1.2 ETC WITH BATTERY BACK UP. THE
 STAIRS WILL REQUIRE BATTERY BACK UP ALONG WITH MAIN
 ELECTRICAL ROOMS, GENERATOR ROOMS, ELEVATOR EQUIPMENT
 ROOMS, FIRE PUMP ROOM (IN LATER COMMENT).
 PLEASE BE SURE TO SEE 700.12E, 700.16.
 PLEASE SUBMIT PHOTO-METRIC PLANS FOR ALL EGRESS. STAIRS
 REQUIRE 10FT CANDLES MINIMUM UNDER NORMAL AND IS
 PERMITTED TO GO DOWN TO 1FT CANDLE UNDER EMERGENCY
 CONDITIONS. THIS IS BASE ON AN AVERAGE.
 FBC 1006.2.3
 IF THE BUILDING WILL NOT BE OCCUPIED UNDER GENERATOR
 POWER A LETTER FROM OWNER STATING THE BUILDING WILL BE
 COMPLETELY EVACUATED WHEN UNDER GENERATOR BACK UP SHALL
 BE SUBMITTED. THIS INCLUDES ALL EMPLOYEES AND ANY OTHER
 PERSONNEL. IF THE BUILDING IS OCCUPIED UNDER GENERATOR
 AT ANYTIME NORMAL POWER IS LOST, BATTERY BACK UP
 FIXTURES FOR ALL MINIMUM LEVELS SHALL BE INSTALLED.
 ** PLEASE CALL TO GO OVER.
  
 13) NOTE: PLEASE KNOW THE OCCUPANCY OF THE BUILDING
 WOULD BE REQUIRED TO REMAIN AS A HOTEL. IF THE INTENT
 IS TO CHANGE THE OCCUPANCY TO RESIDENTIAL FOR PART OR
 ALL OF THE BUILDING AT A LATER DATE IT WOULD OF
 INTEREST TO LOOK UP FLORIDA STATE HOUSE BILL 7121 WHICH
 WOULD GREATLY AFFECT THIS PROJECT. THIS HOUSE BILL
 GREATLY AFFECTED NUMEROUS FLORIDA STATUTES FOR NOT ONLY
 HIGH-RISES BUT MANY OTHER BUILDINGS.
 ITEMS SUCH AS ON-SITE FUEL REQUIREMENT FOR HIGH-RISE
 BUILDING WOULD BE AFFECTED. IF THIS BUILDING WILL
 REMAIN A HOTEL THEN THIS COMMENT IS FOR INFORMATION
 ONLY.
 ALL BUILDINGS UNDER THE LIFE SAFETY CODE ARE TO BE
 EVACUATED WHEN UNDER LOSS OF POWER FROM THE NORMAL
 UTILITY SOURCE.
  
 14) NOTE: PLEASE SEE FLORIDA STATUTE 553.885. THIS
 BUILDING CONTAINS GAS APPLIANCES AND SHALL CONTAIN
 CARBON MONOXIDE DETECTORS/ALARMS. PLEASE SEE THE
 FOLLOWING WHICH WAS EXTRACTED FROM THE FLORIDA STATUTES
 ON LINE FOR EASE OF REVIEW OF REQUIREMENT.
  
 553.885 CARBON MONOXIDE ALARM REQUIRED.--
 (1) EVERY BUILDING, OTHER THAN A HOSPITAL, AN INPATIENT
 HOSPICE FACILITY, OR A NURSING HOME FACILITY LICENSED
 BY THE AGENCY FOR HEALTH CARE ADMINISTRATION, FOR WHICH
 A BUILDING PERMIT IS ISSUED FOR NEW CONSTRUCTION ON OR
 AFTER JULY 1, 2008, AND HAVING A FOSSIL-FUEL-BURNING
 HEATER OR APPLIANCE, A FIREPLACE, OR AN ATTACHED GARAGE
 SHALL HAVE AN APPROVED OPERATIONAL CARBON MONOXIDE
 ALARM INSTALLED WITHIN 10 FEET OF EACH ROOM USED FOR
 SLEEPING PURPOSES. FOR A NEW HOSPITAL, AN INPATIENT
 HOSPICE FACILITY, OR A NURSING HOME FACILITY LICENSED
 BY THE AGENCY FOR HEALTH CARE ADMINISTRATION, AN
 APPROVED OPERATIONAL CARBON MONOXIDE DETECTOR SHALL BE
 INSTALLED INSIDE OR DIRECTLY OUTSIDE OF EACH ROOM OR
 AREA WITHIN THE HOSPITAL OR FACILITY 1WHERE A
 FOSSIL-FUEL-BURNING HEATER, ENGINE, OR APPLIANCE IS
 LOCATED. THIS DETECTOR SHALL BE CONNECTED TO THE FIRE
 ALARM SYSTEM OF THE HOSPITAL OR FACILITY AS A
 SUPERVISORY SIGNAL.
  
  
 15) NOTE: THERE IS NOT ENOUGH INFORMATION SUBMITTED FOR
 FIRE PUMP AND FIRE PUMP CONTROLLER. THE RISER AND PLANS
 INDICATE A NEW FEED FROM FPL YET THE ROUTING IS SHOWN
 FROM ONE SIDE OF THE BUILDING TO THE OTHER UNDERGROUND.
 PLEASE CONFIRM THIS AS THIS IS AN EXISTING BUILDING.
 WILL ALL NEW SERVICE ENTRANCE CONDUCTORS BE ROUTED
 UNDERGROUND?
 PLEASE SEE NFPA-20 2003 FOR MANY OF THE FOLLOWING SUB
 COMMENTS.
 CHAPTERS 5,9 AND 10.
 THIS IS A CHANGE OF OCCUPANCY TO A HIGHER HAZARD, THE
 FIRE PUMP AND ALL ASSOCIATED EQUIPMENT SHALL MEET
 CURRENT CODES.
  
 A) PLEASE SEE 9.6.2.2 FOR REQUIRED ON-SITE FUEL FOR
 8HRS OF OPERATION ALONG WITH LOADS FOR LIFE SAFETY.
 PLEASE ALSO SEE SECTIONS FOR ADDITIONAL 5% FOR
 EXPANSION AND 5% FOR SUMP.
  
 B) PLEASE SEE 5.12.6 FOR REQUIRED DRAINAGE. NO
 INFORMATION WAS PROVIDED.
  
 C) PLEASE SEE 9.3.1 FOR FEEDERS OR SERVICE ENTRANCE
 CONDUCTORS. PLEASE ALSO SEE NFPA-70 695.6 A, B, AND C.
  
  
 D) PLEASE SEE LOCATION SHALL CONTAIN ACCESS DIRECTLY
 FROM OUTSIDE. THE ENTRANCE TO THIS ROOM AT THIS TIME IS
 NOT ACCEPTABLE. THIS ROUTE TAKES ANYONE THROUGH
 NUMEROUS LOCKED DOORS, EQUIPMENT ROOMS ETC.
 PLEASE SEE SECTION 9.2 AND COMMENTARY.
  
 E) PLANS SUBMITTED DO NOT CONTAIN ANY FIRE SPRINKLER
 PLANS AS REQUIRED. FS 633.
 PLEASE SEE COMMENTS FROM OTHER TRADES WITH RESPECT TO
 HOW THE EXISTING FIRE PUMP IS ADEQUATE FOR NEW
 SPRINKLER LOAD OF ADDITION.
 NO INFORMATION ON JOCKEY PUMP, OR PRESSURE MAINTENANCE
 PUMP WHICH IS A LEGALLY REQUIRED SYSTEM.
  
 F) PLANS/RISER INDICATES WHAT WOULD BE TWO METHODS OF
 OVER CURRENT PROTECTION FOR FIRE PUMP. THIS IS NOT
 NORMAL. PLEASE PROVIDE INFORMATION ON WHETHER OR NOT
 THE EXISTING FIRE PUMP CONTROLLER WITH ATS IS SERVICE
 ENTRANCE RATED WITH THE FACTORY LOCKED ROTOR SETTINGS.
 PLEASE ALSO SEE COMMENTS BELOW WITH RESPECT TO
 GROUNDING OF SERVICE WHICH IS NOT SHOWN. 695
 FBC 106.1.1
  
 G) PLEASE SEE 9.6.4 WITH RESPECT TO TRANSFER OF POWER.
  
 H) PLEASE SEE 5.12.4 AS BATTERY BACK UP LIGHTING IS
 REQUIRED. PLEASE BE SURE TO SEE 700.12E AND 700.16 FOR
 UNIT EQUIPMENT.
  
 ** THERE ARE NUMEROUS CODE SECTIONS AND UNANSWERED
 QUESTIONS OR INFORMATION NOT YET SHOWN OR SUBMITTED.
 PLEASE GO OVER NFPA-70 695, 701, ETC AND NFPA-20 (ALL).
  
 16) NOTE: PLEASE SEE NEC 250.20, 250.50, 250.24, 250.6
 ETC. A GROUNDED CONDUCTOR (NEUTRAL) IS ALWAYS REQUIRED
 TO THE FIRST MEANS OF SERVICE DISCONNECT EVEN WHEN ONLY
 FEEDING MOTOR LOADS. AS SHOWN THIS SERVICE FOR THE FIRE
 PUMP WOULD NOT BE GROUNDED AND DOES NOT FALL UNDER
 ELECTRICAL SYSTEMS WHICH ARE NOT TO BE GROUNDED.
 PLEASE REVISE RISER TO INCLUDED GROUNDED/NEUTRAL
 CONDUCTOR TO THE FIRST MEANS OF SERVICE DISCONNECT.
 PLEASE SEE PREVIOUS COMMENTS WITH RESPECT TO THE TWO
 MEANS OF OVER CURRENT PROTECTION.
  
 17) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE FOLLOWING. ONCE AGAIN THIS IS A CHANGE
 IN OCCUPANCY TO A HIGHER HAZARD AND MUST MEET CURRENT
 CODES.
 GENERATOR, ATS DEVICES, FIRE PUMP, FIRE PUMP
 CONTROLLER, FUEL TANKS (REVIEWED BY
 OTHERS).110.3,695,90.7.
  
 18) NOTE: PLEASE SEE 230.95, 240.13 ETC AS THE MAIN
 SWITCHBOARD BEING DOES NOT INDICATE THE REQUIRED GROUND
 FAULT PROTECTION.
 ** IT IS IMPORTANT TO KNOW AS THE OVER CURRENT
 PROTECTION AND OTHER INFORMATION WAS NOT SUBMITTED FOR
 GENERATOR AND OTHER SYSTEMS THERE MAY BE A NEED TO
 INSTALL 4-POLE TRANSFER SWITCHES FOR SOME OF THE BACK
 UP SYSTEMS OR ALL. PLEASE SEE NEC 700.7D, 700.26 AND
 NFPA-110 6.2.15. GROUND FAULT PROTECTION IS REQUIRED ON
 MAIN DISTRIBUTION SYSTEM AND NOT ON BACK UP OF
 EMERGENCY/LIFE SAFETY SYSTEMS. HOWEVER GROUND FAULT
 SENSING IS A REQUIREMENT. PLEASE SEE WHITE PAPERS FROM
 LEADING MANUFACTURES SUCH AS ASCO, CATERPILLAR ETC.
 WHEN A SYSTEM HAS GROUND FAULT PROTECTION ON THE
 PRIMARY AND GROUND FAULT SENSING ON THE SECONDARY WHEN
 A FAULT OCCURS THERE IS A COORDINATION LOSS WHEN A
 SEPARATION OF THE NEUTRAL CONDUCTORS AND USE OF A
 4-POLE TRANSFER SWITCH IS NOT INSTALLED. THIS IS NOT ON
 ALL BACK UP SYSTEMS HOWEVER AS MUCH INFORMATION ON THE
 BACK UP IS NOT PROVIDED THIS IS NOTED AS IT MAY BE
 REQUIRED TO USE 4-POLE TRANSFER SWITCHES AND CREATE A
 SEPARATELY DERIVED GENERATOR GROUND.
  
 19) NOTE: PLEASE SEE 110.14, 240.21, 240.4, AND 310.16.
 ALL TAPPED CONDUCTORS ON THE SECONDARY SIDE OF ANY
 TRANSFORMER SHALL TERMINATE IN OVER CURRENT PROTECTION
 WHICH LIMITS THE LOAD ON THE TAPPED CONDUCTORS. THE
 500MCM INSTALLED FROM THE SECONDARY SIDE OF THE
 TRANSFORMERS AS SHOWN ON RISER ARE RATED AT 380AMPS
 WITH OVER CURRENT PROTECTION SET AT 400AMPS. THIS IS
 NOT PERMITTED. TYPICALLY WHEN EQUIPMENT IS BELOW
 800AMPS (240.4B) AND THE OVER CURRENT PROTECTION DOES
 COORDINATE WITH THE STANDARD OVER CURRENT PROTECTION IN
 240.6 YOU ARE PERMITTED TO GO TO THE NEXT STANDARD SIZE
 OF OVER CURRENT PROTECTION. HOWEVER THIS IS NOT
 PERMITTED ON THE SECONDARY SIDE OF TRANSFORMERS. THIS
 HAS BEEN GONE OVER WITH CODE PANELIST IN SEVERAL
 INTERNATIONAL ASSOCIATION OF ELECTRICAL INSPECTORS
 (IAEI) MEETINGS ON STATE, AND NATIONAL LEVELS.
 PLEASE ADJUST.
  
 20) NOTE: PLEASE PLACE NOTE ON PLANS FOR REQUIRED ARC
 FLASH SIGNAGE AND PROTECTION. 110.16
  
 21) NOTE: PLEASE PROVIDE MORE INFORMATION ON THE RATING
 OF EQUIPMENT AND ROOM IN WHICH THE GENERATOR IS
 LOCATED. PLEASE SEE CHAPTER 7 OF NFPA-110.
 AS MOST OF THE NEEDED INFORMATION IS NOT SHOWN PLEASE
 SEE SOME OF THE ITEMS NEEDED ON PLANS LISTED BELOW.
 MANY OF THE SECTIONS BELOW WHICH ARE BEING GIVEN MAY
 ALSO RELATE TO OTHER TRADE REVIEWS HOWEVER THEY ALSO
 RELATE CLOSELY TO ELECTRICAL SYSTEMS, EQUIPMENT,
 DESIGNS ETC WHICH WILL BE AFFECTED BY MANY OF THESE
 ITEMS. THIS GENERATOR IS A LIFE SAFETY, AND LEGALLY
 REQUIRED EPSS. SEE CHAPTER 4,4.1 FOR CLASSIFICATIONS.
  
 A) THE LOCATION SHALL BE PER SECTION 7.2.
 7.2.1 THE EPS SHALL BE INSTALLED IN A SEPARATE ROOM FOR
 LEVEL 1 INSTALLATIONS. EPSS EQUIPMENT SHALL BE
 PERMITTED TO BE INSTALLED IN THIS ROOM.
 7.2.1.1 THE ROOM SHALL HAVE A MINIMUM 2-HOUR FIRE
 RATING OR BE LOCATED IN AN ADEQUATE ENCLOSURE LOCATED
 OUTSIDE THE BUILDING CAPABLE OF RESISTING THE ENTRANCE
 OF SNOW OR RAIN AT A MAXIMUM WIND VELOCITY REQUIRED BY
 LOCAL BUILDING CODES.
 7.2.1.2 NO OTHER EQUIPMENT, INCLUDING ARCHITECTURAL
 APPURTENANCES, EXCEPT THOSE THAT SERVE THIS SPACE,
 SHALL BE PERMITTED IN THIS ROOM.
 7.2.2 EPSS EQUIPMENT SHALL NOT BE INSTALLED IN THE SAME
 ROOM WHERE THE NORMAL ELECTRICAL SERVICE EQUIPMENT IS
 INSTALLED.
 7.2.2.1 TRANSFER SWITCHES SHALL BE PERMITTED TO BE
 INSTALLED IN THE NORMAL ELECTRICAL SERVICE ROOM WHERE
 TWICE THE CLEARANCE REQUIRED BY ARTICLE 110.26(A) OF
 NFPA 70, NATIONAL ELECTRICAL CODE, EXISTS BETWEEN
 EQUIPMENT ENCLOSURES.
 7.2.3* THE ROOMS, SHELTERS, OR SEPARATE BUILDINGS
 HOUSING LEVEL 1 OR LEVEL 2 EPSS EQUIPMENT SHALL BE
 DESIGNED AND LOCATED TO MINIMIZE THE DAMAGE FROM
 FLOODING, INCLUDING THAT CAUSED BY THE FOLLOWING:
 (1) FLOODING RESULTING FROM FIRE FIGHTING
 (2) SEWER WATER BACKUP
 (3) SIMILAR DISASTERS OR OCCURRENCES
 7.2.4* MINIMIZING THE POSSIBILITY OF DAMAGE RESULTING
 FROM INTERRUPTIONS OF THE EMERGENCY SOURCE SHALL BE A
 DESIGN CONSIDERATION FOR LEVEL 1 AND LEVEL 2 EPSS
 EQUIPMENT.
  
 ** PLEASE SEE COMMENTARY FOR ONE OF TWO ACCEPTABLE
 LEVELS. THE * 100YEAR STORM* LEVEL OR THE LEVEL SET BY
 THE *SLOSH* CHARTS BASED ON A CATEGORY 4 HURRICANE.
 (SEA, LAKE, OVERLAND SURGES BY HURRICANES).
  
 B) PLEASE BE SURE TO SEE 7.3.1 THE LEVEL 1 OR LEVEL 2
 EPS EQUIPMENT LOCATION(S) SHALL BE PROVIDED WITH
 BATTERY-POWERED EMERGENCY LIGHTING.
  
 C) PLEASE SEE 7.3.3 AS THE MINIMUM FOOT CANDLES SHALL
 BE 30 FT CANDLES. PLEASE PROVIDE PHOTO-METRICS SHOWING
 LEVELS.
  
 D) PLEASE BE SURE TO SEE 7.5 FOR VIBRATION ISOLATORS
 FROM STRUCTURE ETC.
  
 E) PLEASE SEE 7.7 FOR REQUIRED VENTILATION DIRECTLY
 FROM OUTSIDE. PLEASE ALSO SEE 7.10 FOR EXHAUST SYSTEMS.
 THIS COULD GREATLY AFFECT THE DESIGN. SEE COMMENTS FROM
 OTHER TRADES SUCH AS MECHANICAL REVIEWER.
  
 F) PLEASE SEE 7.8 FOR COOLING WHICH DOES NOT PERMIT
 RELYING ON UTILITY.
  
 G) PLEASE SEE 7.9 FOR FUEL PIPING. (INFORMATION YET
 THIS WILL AFFECT ELECTRICAL PLANS.). ANY REMOTE FILLING
 WITH ELECTRICAL SHUT OFF, FILL ALARMS ETC IS NOT KNOWN
 AT THIS TIME. NOT ENOUGH INFORMATION SHOWN.
  
 22) NOTE: PLEASE SUPPLY LIGHTING PHOTO-METRICS LEVELS
 FOR ELEVATOR PITS. PLEASE SEE NEC 620.23 COMMENTARY,
 ASME A17.1-2004, SAFETY CODE FOR ELEVATORS AND
 ESCALATORS, REQUIRES A MINIMUM OF 5 FT-CANDLES (54 LUX)
 AT THE PIT FLOOR AND REQUIRES LUMINAIRES TO BE
 EXTERNALLY GUARDED TO PREVENT ACCIDENTAL BREAKAGE.
  
  
 23) NOTE: PLEASE BE SURE TO SHOW ALL HORN AND STROBE
 DEVICES IN COMPLIANCE FOR MINIMUMS PER FBC 11-4.28.1,
 .2 AND .3.
 PLEASE BE SURE ALL LOCATIONS, HEIGHTS AND LEVELS ARE
 INDICATED.
 KEEP IN MIND THERE ARE MANY CIRCUMSTANCES IN WHICH THE
 FLORIDA BUILDING CODE IS MORE RESTRICTIVE THAN NFPA-72.
  
 24) NOTE: PLEASE SEE FBC 3006.2 FOR VENTILATION
 REQUIREMENTS OF ELEVATOR EQUIPMENT/MACHINE ROOMS. THE
 ELECTRICAL AND MECHANICAL PLANS ARE NOT REAL CLEAR ON
 ANY NEW OR EXISTING SYSTEMS FOR NEW AND EXISTING
 EQUIPMENT ROOMS.
  
 25) NOTE: PLEASE KNOW THAT ANY LIGHTING OUTSIDE THE
 PROPERTY LINE SHALL BE UNDER SEPARATE PERMITS. THESE
 WOULD BE CONSIDERED RIGHT OF WAY AREAS AND ARE NOT
 PERMITTED TO BE FED FROM THIS BUILDING ELECTRICAL
 SYSTEM.
 ** NOTE FOR INFORMATION.
  
 26) NOTE: PLEASE KNOW THAT ANY LIGHTNING PROTECTION
 SYSTEM WHICH MAY BE PROPOSED SHALL BE UNDER SEPARATE
 PERMIT. ANY PROPOSED SYSTEM SHALL ALSO COMPLY WITH
 NFPA-780.
 PLEASE PLACE NOT ON PLANS ACCORDINGLY.
 THERE ARE NUMEROUS SYSTEMS WHICH ARE IN THE MARKET
 PLACE WHICH DO NOT CONFORM TO ANY ADOPTED STANDARD OR
 CODE.
  
 27) NOTE: PLEASE KNOW THE POOL WILL BE REQUIRED TO BE
 UNDER SEPARATE PERMIT. PLEASE PLACED NOTE ON PLANS.
 PLEASE ALSO KNOW THAT PLANS SHALL CLEARLY STATE NO DUSK
 TO DAWN SWIMMING OR PLEASE SUBMIT PHOTO-METRICS TO PALM
 BEACH COUNT HEALTH DEPARTMENT FOR REVIEW AND STAMPING.
 ** PHOTO-METRICS FOR EGRESS AREAS ARE ALREADY NEEDED
 AND MAY USE THE SAME LAYOUT. PLEASE VERIFY LIGHTING
 LEVELS WITH PBCHD.
  
 28) NOTE: THE LOW VOLTAGE SYSTEMS AS SUBMITTED WILL BE
 UNDER SEPARATE PERMITS. PLANS MAY COME IN WITH BASE
 BUILDING AND WILL BE REVIEWED. WHEN PERMIT APPLICATION
 IS MADE FOR THE LOW VOLTAGE PERMITS CONTRACTOR WILL
 REFERENCE BASE BUILDING PLANS AND PERMIT IS ISSUED AS A
 *TURNAROUND PERMIT*.
  
 29) NOTE: PLEASE BE SURE TO SHOW ALL CONDUCTORS ON
 COMPLETED PANELS SCHEDULES PER 310.16, 240.4, AND 408.4
  
 30) NOTE: PLEASE PROVIDE ALL LOADS ON ALL PANELS.
 PLEASE BE SURE TO COMPLETE LOAD CALCULATIONS.
 NEC 220
 FBC 106.1.1,106.3.5.1.2 ADDITIONAL INFORMATION,
 CLARITY, COORDINATION.
  
 31) NOTE: PLEASE SEE 210.8B2 FOR REQUIRED GFI
 PROTECTION FOR ALL 15/20AMP 120 CIRCUITS IN
 KITCHEN/SERVING AREAS.
 THIS IS REQUIRED FOR ALL WHETHER OR NOT FEEDING COUNTER
 SPACES.
  
 32) NOTE: PLEASE PROVIDE DETAIL FOR ALL VERTICAL
 SUPPORT OF CONDUCTORS PER 300.19
  
 33) NOTE: PLEASE PROVIDE BUS-DUCT CURBING DETAIL.
 PLEASE SEE 368.10C1 AND 2
  
 34) NOTE: PLEASE SEE NEC 680.22 FOR TYPES OF FIXTURES
 AND LOCATIONS OF FIXTURES AROUND POOL. PLEASE BE SURE
 TO ALSO SEE 411.4B FOR LV TYPE FIXTURES. AS THE
 LIGHTING FOR POOL AREA IS NOT COMPLETE ALONE WITH A
 FIXTURE LEGEND CODE COMPLIANCE FOR MANY ITEMS CAN NOT
 BE DETERMINED.
  
 35) NOTE: PLEASE BE SURE TO SUBMIT WIND LOAD
 INFORMATION FOR ROOF TOP AND OTHER LIGHT POLES.
 FBC 1609
 FBC 106.1.14
 PLEASE BE SURE TO INCLUDE THE EFFECTIVE PROJECTED AREAS
 OF FIXTURES.
  
 36) NOTE: PLEASE SEE 250.50, 250.66, THE GROUNDING
 ELECTRODE SIZE TO FOOTER STEEL SHALL BE BASED ON
 250.66. THIS IS NOT THE SOLE CONNECTION.
  
 37) NOTE: PLEASE PROVIDE A GROUNDING ELECTRODE RISER
 FOR ATTACHMENT OF ALL SYSTEMS. 250.58. THIS CAN BE
 SHOWN ON RISER SHEET.
 250.20.250.30, 250.50 ETC
  
 38) NOTE: PLEASE PROVIDE NOTE FOR COLOR CODING OF
 277/480V SYSTEMS AS FOLLOWS. BROWN, PURPLE, YELLOW. ALL
 EXISTING SYSTEMS IN THE CITY OF WEST PALM BEACH ARE
 BASED ON THIS COLOR CODING DUE TO PREVIOUS LOCAL
 AMENDMENTS. THE NEC DOES NOT CONTAIN COLOR CODING FOR
 SUCH SYSTEMS AND ORANGE IS FOR OPEN DELTA HIGH LEG
 SYSTEMS. IN THE INTEREST OF CONSISTENCY AND SAFETY OF
 ELECTRICAL SYSTEMS PLEASE ADJUST SPECS AND PLEASE ADD
 NOTES TO RISER AND/OR ELECTRICAL NOTES.
 90.4.
  
 39) NOTE: PLEASE PROVIDE BACK UP INFORMATION ON FIRE
 ALARM PANELS. I COULD NOT LOCATE BACK UP BATTERY BACK
 UP NOTES ON PLANS. THE USE OF THE GENERATOR AS THE
 PRIMARY BACK UP IS NOT PERMITTED AS NOTED ABOVE WITH
 RESPECT TO OCCUPANCY OF THE BUILDING. NFPA-72 4.4.1.3
  
 40) NOTE: PLEASE SEE BUILDING REVIEW NOTES WITH RESPECT
 TO REQUIRED NOTES ON PLANS WITH RESPECT TO FS 633 FOR
 FIRE AND LIFE SAFETY DESIGN.
 FBC 109.3.6.4.4.
  
 41) NOTE: PLEASE CLARIFY WHY THE MAIN SWITCH BOARD
 EQUIPMENT LOCATED ON E104 IS SHOWN AS THREE YET RISER
 IS INCOMPLETE WITH THE SAME. THE PLANS ACTUALLY STATE
 TWO SECTIONS?
 110.3, 230.70 ETC
 FBC 106.1.1 FOR ADDITIONAL INFORMATION AND CLARITY.
  
 42) NOTE: PLEASE 210.63, 210.8B3, 4 AND 5. PLEASE BE
 SURE TO COMPLETE ALL REQUIRED RECEPTACLES.
  
 43) NOTE: PLEASE BE SURE TO SEE 13-415.1,
 13-415.1.ABC.1.3 FOR AUTOMATED LIGHTING CONTROLS
 REQUIRED IN HOTEL ROOMS.
  
 44) NOTE: PLEASE COORDINATE RISER AND PANELS. PANEL 1KP
 SHOWN AS 150AMP ON RISER YET 200AMP ON PANEL SCHEDULE.
 230,220,408
 FBC 106.1.1 FOR COORDINATION AND CLARITY.
  
 45) NOTE: PLEASE COORDINATE RISER AND PANELS. PANEL
 SCHEDULE FOR RB YET NOT ON RISER.
 230, 215, 220, 408 ETC
 FBC 106.1.1 FOR CLARITY AND COORDINATION.
  
 46) NOTE: PLEASE COORDINATE RISER AND PANELS. SAME AS
 NOTED ABOVE PANEL 2H SHOWN AS 200AMP AND 150AMP. IF 2H
 IS TYPICAL AS NOTED FOR OTHER FLOORS COORDINATION IS
 NEEDED AS THE OTHER FLOORS ARE SHOWN AS 150AMP ON
 RISER.
 230,220,408 ETC
 FBC 106.1.1
  
 47) NOTE: PLEASE COORDINATE ALL EQUIPMENT AS NOTED IN
 NOTES 44,45 AND 46 ABOVE. THERE ARE OTHER PANELS AND
 EQUIPMENT WHICH ARE NOT THE SAME.
 THERE ARE SEVERAL OTHERS.
  
 **** AS NOTED IN THE BEGINNING OF THE REVIEW COMMENTS.
 IT IS IMPORTANT TO SUBMIT 100% PLANS AND DOCUMENTS FOR
 A COMPLETE REVIEW FOR CODE COMPLIANCE. WHEN SUBMITTING
 FOR PERMIT THIS WILL GREATLY AFFECT THE REVIEWS,
 ISSUANCE, DELAYS AND POSSIBLE FEES ASSOCIATED WITH
 PROJECT. THE NAME AND CONTACT INFORMATION WILL BE GIVEN
 BELOW. IF CONTACTING REVIEWER BY PHONE AND VOICEMAIL IS
 ENCOUNTERED PLEASE LEAVE A MESSAGE ALONG WITH CONTACT
 PHONE NUMBER. THE CALL WILL BE RETURNED AS SOON AS
 POSSIBLE.
 COMMUNICATION IS THE KEY TO THE SUCCESS OF THIS PROJECT
 AS WITH ANY OTHERS.
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2008-11-19 Cont ID  
Sent By mgonzale Date 2008-11-19 Time 10:33 Rev Time 1.00
Received By mgonzale Date 2008-11-19 Time 10:33 Sent To ENG
Notes
2008-11-19 10:33:11-FAILED-
  
 ENGINEERING ITEMS:
 RESOLVE AN ABANDONED BELL SOUTH VAULT AT THE SIDEWALK
 ON FERN
 THE SIZE OF A SWIMMING POOL, WHICH HAS BEEN USED AS A
 CISTERN.
 SOLID WASTE LOCATION HAS NOT NOT BEEN RESOLVED YET.
 FEES FOR ENGINEERING REVIEW HAVE NOT BEEN PAID, FEES
 MUST BE CLCULATED AS PER CWPB CERTIFIED ENGINEER'S
 ESTIMATE FOR THE CIVIL WORK.
 YOU MAY REFER TO THE CITY'S WEB SITE. WWW.CITYOFWPB.ORG
 ENGINEERING.
  
 MANUEL J GONZALEZ, PROJECT COORDINATOR
 LOCATION ADDRESS:
 CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT
 1000 - 45TH STREET, SUITE 15
 WEST PALM BEACH FL 33407
 MAILING ADDRESS:
 CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT
 P.O. BOX 3506
 WEST PALM BEACH FL 33401
 TELEPHONE:
 45TH STREET OFFICE : 561-494-1040
 45TH DIRECT: 561-494-1085
 FAX: 561-494-1117
 CITY HALL OFFICE: (561) 805-6723
 CITY HALL DIRECT: (561) 805-6327
 CITY HALL FAX: (561) 805-6731 OR 805-6676
 NEXTEL: 561-644-7301
 NEXTEL DIRECT CONNECT: 159*28165*38
 EMERGENCIES:
 CENTRAL OPERATIONS CENTER (DISPATCH) 561-822-2210
 E-MAIL:
 [email protected]
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-12-18 Cont ID  
Sent By mwennerg Date 2008-12-18 Time 12:48 Rev Time 0.00
Received By mwennerg Date 2008-12-18 Time 12:48 Sent To  
Notes
2008-12-18 13:18:51PLANS HAVE BEEN SUBMITTED FOR PLAN REVIEW ONLY AND NOT
 FOR PERMIT.
  
 1) PROVIDE LIFE SAFETY PLAN ILLUSTRATING MAXIMUM TRAVEL
 DISTANCES.
  
 2) LIFE SAFETY TO COMPY WITH FLORIDA FIRE PRVENTION
 CODE, 2004 AND NFPA 101, 2003 EDITION.
  
 3) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241. ADD TO BUILDING CODES ON SHEET A00A.
  
 4) VERIFY IF PROJECT MEETS THE DEFINITION OF HIGHRISE
 BUILDING IN ACCORDANCE WITH NFPA 101, SEC. 3.3.2.7.7.
  
 5) FIRE ALARM SYSTEM SHALL BE UL CERTIFICATED BEFORE OR
 AT THE TIME OF THE FINAL INSPECTION.
  
 6) IF THIS BUILDING IS DETERMINED TO BE A HIGHRISE BY
 DEFINITION, A MINIMUM OF TWO (2) FIRE DEPARTMENT
 CONNECTIONS ARE REQUIRED. OK ON SHEET C5.1
  
 7) NEW FDC'C SHALL BE PROVIDED WITH KNOX LOCKING CAPS.
  
 8) TEMPORARY STANDPIPE IS REQUIRED WHEN BUILDING
 REACHES THREE (3) STORIES OR THIRT (30)' IN HEIGHT.
  
 9) PROVIDE ADDITIONAL INFORMATION REGARDING AREA OF
 RESTRICTED EASEMENT AND HOW IF ANY THIS WILL IMPACT
 EMERGENCY RESPONDERS.
  
 10) MINIMUM 2A-10B,C RATED FIRE EXTINGUISHERS TO BE
 PROVIDED AT LOCATIONS NOT TO EXCEED (75)' TRAVEL
 DISTANCE REQUIREMENT. A SHEETS GENERAL NOTES
  
 11) ALL WALKING SURFACES SHALL BE SLIP RESISTANT.
 ILLUSTRATE COMPLIANCE ON SHEET A104 ROOF PLAN.
  
 12) PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS FOR
 HANDRAILS AND GUARDRAILS.
  
 13) NEW GUARDRAILS SHALL BE MINIMUM (42)" IN HEIGHT.
 SHEET A104 ROOF PLAN
  
 14) COMBUSTIBLE FURNITURE ON ROOF THAT IS LOCATED
 BENEATH OVERHANGS EXCEEDING (48)" IN WIDTH SHALL BE
 PROTECTED BY AN AUTOMATIC FIRE SPRINKLER SYSTEM. THIS
 REQUIREMENT APPLIES TO ANY ENCLOSURES, AREAS OR ROOMS
 ON THE ROOF.
  
 15) PROVIDE A SPRINKLER LAYOUT FOR REVIEW AT TIME OF
 PERMIT APPLICATION. IN ADDITION, SEPARATE SHOP DRAWINGS
 AND PERMIT IS REQUIRED FOR FIRE SPRINKLER SYSTEM PRIOR
 TO EQUIPMENT INSTALLATION.
  
 16) KNOX BOX ACCESS SYSTEM IS REQUIRED NEAR FRONT DOOR
 ENTRANCE. CONTACT BUREAU OF FIRE PREVENTION AT (561)
 804-4756 FOR ASSISTANCE AT APPROPRIATE TIME.
  
 17) PROVIDE MINIMUM INTERIOR FINISH CLASSIFICATION FOR
 WALLS AND CEILINGS.
  
 18) ELEVATOR WARNING SIGNS ARE REQUIRED IN ELEVATOR
 LOBBIES.
  
 19) PROVIDE ADDITIONAL INFORMATION REGARDING USE OF
 RE-FUEL AREA 104.
  
 20) ILLUSTRATE OCCUPANT LOAD CALCULATIONS FOR WHOM
 MEANS OF EGRESS AND OTHER PROVISIONS ARE REQUIRED. NFPA
 101, SEC. 28.1.7
  
 21) ELEVATORS SHALL COMPLY WITH THE REQUIREMENTS OF
 ASME A117.1 AND SHALL BE OF SUFFICIENT SIZE TO
 ACCOMODATE A STRETCHER. OK SHEET A601, NOTE #1
  
 22) EMERGENCY INSTRUCTIONS FOR GUESTS SHALL BE PROVIDED
 ON OR IMMEDIATELY ADJACENT TO EVERY GUEST ROOM DOOR.
 NFPA 101, SEC. 28.7.4.1
  
 23) ADDRESS IS REQUIRED ON BUILDING THAT SHALL BE
 MINIMUM OF 6" IN HEIGHT, 1" WIDTH AND CONTRASTING WITH
 BACKGROUND. ADD TO APPROPRIATE ELEVATION SHEET
  
 24) SHEET A701 REFERENCES CARD READERS. SEPARATE SHOP
 DRAWINGS AND PERMIT REQUIRED FOR ACCESS-CONTROL
 EQUIPMENTINSTALLATION. WORK TO COMPLY WITH NFPA 101,
 SEC. 7.2.1.6.2 (ACCESS-CONTROLLED EGRESS DOORS.)
  
 25) PROPER CLEARANCES TO BE MAINTAINED NEAR FIRE
 PROTECTION EQUIPMENT. THE EXISTING FIRE DEPARTMENT
 CONNECTION APPEARS TO BE OBSTRUCTED BY THE PROPOSED
 MEMORIAL WALL.
  
 26) SHEET C4.3, NOTE #4 SHOULD READ CITY OF WEST PALM
 BEACH AS AUTHORITY HAVING JURISDICTION. IN ADDITION TO
 ELECTRONIC SUPERVISION, DOUBLE CHECK DETECTOR ASSEMBLY
 TO BE SECURED WITH CHAIN AND LOCK.
  
 27) PLEASE VERIFY THE LOCATION OF THE DOUBLE CHECK
 DETECTOR ASSEMBLY.
  
 28) FIRE DAMPERS TO BE TESTED FOR CLOSURE PER THE
 REQUIREMENTS OF UL 555 PRIOR TO FINAL INSPECTION.
  
 29) FIRE ALARM SYSTEM SHALL MEET THE TWO HOUR
 SURVIVABILITY REQUIREMENTS FOR HIGHRISE BUILDINGS IF
 APPLICABLE. NFPA 72, 2002 EDITION
  
 30) COOLING TOWERS TO COMPLY WITH NFPA 214.
  
 31) DUCT SMOKE DETECTORS IN ADDITION TO FAN SHUT DOWN
 SHALL BE CONNECTED TO THE FIRE ALARM SYSTEM AND
 INITIATE A GENERAL FIRE ALARM IN ACCORDANCE WITH LOCAL
 REQUIREMENTS. SHEET E300 NOTE #5D
  
 32) PROJECT PHYSICAL ADDRESS IS REQUIRED ON EACH SHEET
 OF PLANS AND SUPPORTING DOCUMENTS.
  
 33) EMERGENCY LIGHTING FACILITIES ARE NOT SHOWN INSIDE
 STAIRWELLS WITH THE EXCEPTION OF STAIR #3.
  
 34) FIRE COMMEND ROOM IS NOT CLEARLY SHOWN ON SHEET
 E103. EMERGENCY LIGHTING IS REQUIRED AND THE DOOR SHALL
 BE PROVIDED WITH APPROPRIATE SIGNAGE.
  
 35) IT APPEARS THAT ADDITIONAL EXIT SIGNS ARE NEEDED ON
 ROOF. SHEET E107
  
 36) SOME OF THE ENCLOSED AREAS/ROOMS ON THE ROOF ARE
 MISSING EMERGENCY LIGHTS.
  
 37) SOME OF THE ELECTRICAL SHEETS (TYPICAL ROOM PLANS)
 REFERENCE SMOKE DETECTORS INSIDE GUEST ROOMS. DEVICES
 PROVIDED IN EVERY GUEST ROOM SHALL BE APPROVED SINGLE
 STATION SMOKE ALARMS, NFPA 101 SEC. 28.3.4.5 AND SHALL
 NOT INITIATE A GENERAL FIRE ALARM. ELECTRICAL SHEETS
 SEEM TO ILLUSTRATE BOTH TYPES OF DEVICES IN ROOMS.
  
 38) SMOKE ALARMS SHALL BE LOCATED MINIMUM OF THREE (3)'
 FROM AC DIFFUSERS.
  
 39) CUTTING AND WELDING OPERATIONS ARE PROHIBITED
 WITHOUT BUREAU OF FIRE PREVENTION APPROVAL AND STRICT
 COMPLIANCE WITH NFPA 51B.
  
 40) PROVIDE VOICE MESSAGE LANGUAGE FOR FIRE ALARM
 EVACUATION SIGNAL.
  
 41) A MANUAL PULL STATION SHALL BE LOCATED AT THE HOTEL
 DESK OR OTHER CONVENIENT CENTRAL CONTROL POINT UNDER
 CONTINUOUS SUPERVISION. NFPA 101, SEC. 28.3.4.2 (2).
  
 42) FIRE COMMAND ROOM SHALL COMPLY WITH THE
 REQUIREMENTS OF NFPA 101, SEC. 11.8.5.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-01-26 Cont ID  
Sent By rregueir Date 2009-01-26 Time 07:59 Rev Time 0.00
Received By rregueir Date 2008-11-17 Time 15:56 Sent To PC
Notes
2008-11-17 15:56:42TO "COMM" BD#52/PLANS ON RACK/4 ROLLS, 1 BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-01-26 Cont ID  
Sent By rregueir Date 2009-01-26 Time 07:59 Rev Time 0.00
Received By rregueir Date 2009-01-26 Time 00:16 Sent To PC
Notes
2009-01-26 00:22:16REVIEW #:1ST **PLAN CHECK ONLY**
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THESE PLANS HAVE BEEN REVIEWED FOR CODE COMPLIANCE AND
 THE FOLLOWING DEFICIENCIES HAVE BEEN IDENTIFIED:
  
 1. PG A101: GENERAL NOTE #8 CALLS FOR CO DETECTORS IN
 ALL AREAS WITH GAS POWERED EQUIPMENT. EVERY BUILDING
 FOR WHICH A BUILDING PERMIT IS ISSUED FOR NEW
 CONSTRUCTION ON OR AFTER JULY 1, 2008, AND HAVING A
 FOSSIL-FUEL-BURNING HEATER OR APPLIANCE, A FIREPLACE,
 OR AN ATTACHED GARAGE SHALL HAVE AN APPROVED
 OPERATIONAL CARBON MONOXIDE ALARM INSTALLED WITHIN 10
 FEET OF EACH ROOM USED FOR SLEEPING PURPOSES IN
 ACCORDANCE WITH FS 553.885(1).
  
 2. PG M101: THE VENTILATION SCHEDULE REFERENCES ASHRAE
 62.1-2007. THE CORRECT REFERENCE STANDARD FOR THE
 FLORIDA BUILDING CODE IS ASHRAE 62.1-2004. PROVIDE THE
 CORRECT REFERENCE ON PLANS AND ENSURE CALCULATIONS ARE
 BASED ON THE CORRECT EDITION OF THIS STANDARD.
  
 3. PG M101: VENTILATION SCHEDULE CALLS FOR A
 VENTILATION RATE OF 5 CFM/PERSON IN THE FITNESS ROOM.
 THE MINIMUM VENTILATION RATE REQUIRED IS 20 CFM/PERSON
 IN ACCORDANCE WITH ASHRAE 62.1-2004 TABLE 6-1.
 RECALCULATE THE REQUIRED VENTILATION FOR THIS SPACE
 BASED ON THE CORRECT PEOPLE OUTDOOR AIR RATE.
  
 4. PG M102: THE 32 INCH ROUND DRYER EXHAUST DUCT IS
 SHOWN PENETRATING FIRE RATED WALL ASSEMBLIES. HOW WILL
 THESE PENETRATIONS BE PROTECTED? SHOW HOW THESE DUCT
 PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH FBCM
 607.5 AND FBCM 504.2.
  
 5. PG M102: THE FLOOR PLAN SHOWS THE DRYER EXHAUST
 DUCTS BEING MANIFOLDED PRIOR TO CONNECTION TO THE LINT
 COLLECTOR. THE MANUFACTURER???S INSTRUCTIONS FOR THE
 LINT COLLECTOR CALL FOR EACH DRYER TO BE DUCTED TO THE
 LINT COLLECTOR WITHOUT A COMMON DRYER DUCT MANIFOLD.
 SEE DRAWING 2008.20 OF MANUFACTURER???S INSTRUCTIONS.
 SHOW THESE DUCT INSTALLED PER MANUFACTURER???S
 INSTRUCTIONS IN ACCORDANCE WITH FBCM 304.1.
  
 6. PG M102: EACH DRYER EXHAUST DUCT SHALL BE PROVIDED
 WITH BACKDRAFT DAMPER IN ACCORDANCE WITH FBCM 504.4.
  
 7. PG M102: COMPRESSED AIR AND WATER CONNECTIONS ARE
 REQUIRED FOR THE LINT COLLECTOR. PROVISIONS FOR THESE
 CONNECTIONS COULD NOT BE FOUND ON MECHANICAL OR
 PLUMBING PLANS. SHOW HOW THESE REQUIREMENTS ARE TO BE
 MET IN ACCORDANCE WITH FBCM 304.1.
  
 8. PG M102: ACCORDING TO DRYER SUBMITTAL, EACH OF THE
 FOUR DRYERS SHOWN ON PLANS WILL EXHAUST 1600 CFM. EACH
 DRYER IS REQUIRED TO HAVE 360 SQ.IN. OF FREE AREA TO
 THE OUTDOORS FOR MAKEUP AIR. NO SOURCE FOR MAKEUP AIR
 IS SHOWN ON PLANS. PROVIDE MAKEUP AIR PER INSTALLATION
 INSTRUCTIONS IN ACCORDANCE WITH FBCM 504.7.
  
 9. PG M102: ELEVATOR MACHINE ROOM 024 DOES NOT SHOW ANY
 MEANS OF VENTILATION OR AIR CONDITIONING. ELEVATOR
 MACHINE ROOMS THAT CONTAIN SOLID-STATE EQUIPMENT FOR
 ELEVATOR OPERATION SHALL BE PROVIDED WITH AN
 INDEPENDENT VENTILATION OR AIR-CONDITIONING SYSTEM TO
 PROTECT AGAINST THE OVERHEATING OF THE ELECTRICAL
 EQUIPMENT. THE SYSTEM SHALL BE CAPABLE OF MAINTAINING
 TEMPERATURES WITHIN THE RANGE ESTABLISHED FOR THE
 ELEVATOR EQUIPMENT IN ACCORDANCE WITH FBCB 3006.2.
  
 10. PG M102: FLOOR PLAN SHOWS HP-4 IN MECH ROOM 006
 PROVIDING 1650 CFM OF SUPPLY. ACCORDING TO THE HEAT
 PUMP SCHEDULE ON M301, HP-4 WILL PROVIDE 1200 CFM OF
 SUPPLY. HOW WILL HP-4 PROVIDE THE QUANTITIES OF SUPPLY
 CALLED FOR ON THE FLOOR PLAN? AN AIR DISTRIBUTION
 SYSTEM SHALL BE DESIGNED AND INSTALLED TO SUPPLY THE
 REQUIRED DISTRIBUTION OF AIR IN ACCORDANCE WITH FBCM
 603.1.
  
 11. PG M102: FLOOR PLAN SHOWS HP-4 IN BREAK ROOM 017
 PROVIDING 1000 CFM OF SUPPLY. ACCORDING TO THE HEAT
 PUMP SCHEDULE ON M301, HP-4 WILL PROVIDE 1200 CFM OF
 SUPPLY. HOW WILL HP-4 PROVIDE THE QUANTITIES OF SUPPLY
 CALLED FOR ON THE FLOOR PLAN? AN AIR DISTRIBUTION
 SYSTEM SHALL BE DESIGNED AND INSTALLED TO SUPPLY THE
 REQUIRED DISTRIBUTION OF AIR IN ACCORDANCE WITH FBCM
 603.1.
  
 12. PG M102: FLOOR PLAN SHOWS A 12X6 DUCT FROM HP-6 IN
 LAUNDRY ROOM PENETRATING A FIRE RESISTANCE RATED WALL
 ASSEMBLY WITH NO PROTECTION. SHOW HOW THIS DUCT
 PENETRATION IS TO BE PROTECTED IN ACCORDANCE WITH FBCM
 607.5.
 NOTE: IF CLAIMING AN EXCEPTION TO THE REQUIREMENT FOR A
 FIRE DAMPER, SHOW COMPLIANCE WITH FBCM 607.1.1.
  
 13. PG M102: FLOOR PLAN CALLS FOR THE OUTSIDE AIR DUCT
 SERVING HP-6 IN LAUNDRY ROOM TO BE BALANCED AT 125 CFM.
 THIS DOES NOT CORRESPOND WITH THE VENTILATION SCHEDULE
 ON M101 WHICH CALLS FOR THE LAUNDRY/LINEN AREAS TO BE
 PROVIDED WITH 140 CFM OF OUTSIDE AIR. ALSO TAKE INTO
 ACCOUNT THAT HP-6 SERVES AREAS OTHER THAN THE
 LAUNDRY/LINEN AREAS. AN AIR DISTRIBUTION SYSTEM SHALL
 BE DESIGNED AND INSTALLED TO SUPPLY THE REQUIRED
 DISTRIBUTION OF AIR IN ACCORDANCE WITH FBCM 603.1.
  
 14. PG M104: FLOOR PLAN SHOWS LUGGAGE ROOM 111 IN THE
 SAME LOCATION AS THE FIRE COMMAND ROOM SHOWN ON PG
 A101. PLEASE COORDINATE FLOOR PLANS. ALSO, A FIRE
 COMMEND ROOM IS REQUIRED TO BE PROTECTED BY A MINIMUM
 1-HOUR FIRE BARRIER IN ACCORDANCE WITH FBCB 911.1.
 THERE ARE MULTIPLE DUCT PENETRATIONS FROM HP-4 LOCATED
 ABOVE THIS ROOM WHICH WOULD BE PENETRATING THE FIRE
 BARRIER. SHOW THE FIRE BARRIER AS REQUIRED FOR THE FIRE
 COMMAND ROOM AND SHOW THE DUCT PENETRATIONS PROTECTED
 IN ACCORDANCE WITH FBCM 607.5.2.
  
 15. PG M104: THE 12X10 OA DUCT PENETRATING THE RATED
 WALL AT STORAGE ROOM 128 IS UNPROTECTED. SHOW HOW THIS
 PENETRATION OF A RATED WALL ASSEMBLY IS TO BE PROTECTED
 IN ACCORDANCE WITH FBCM 607.5.
  
 16. PG M104: THE 20X12 OA INTAKE DUCT PENETRATING THE
 RATED WALL AT STORAGE ROOM 128 IS UNPROTECTED. SHOW HOW
 THIS PENETRATION OF A RATED WALL ASSEMBLY IS TO BE
 PROTECTED IN ACCORDANCE WITH FBCM 607.5.
  
 17. PG M104: THE TWO EXTENDED ROOMS (DOUBLE QUEEN 119
 AND 121) ON THE FLOOR PLAN SHOW 30 CFM OF OA EACH WHILE
 THE VENTILATION SCHEDULE ON M101 CALLS FOR THESE ROOMS
 TO BE PROVIDED WITH 50 CFM EACH. COORDINATE FLOOR PLAN
 DUCT DESIGN WITH VENTILATION SCHEDULE, SHOWING THE
 PROPER DISTRIBUTION OF AIR IN ACCORDANCE WITH FBCM
 603.1.
  
 18. PG M104 AND M106: HP-OA1 IS SHOWN ON FLOOR PLAN TO
 BE WITHIN A FIRE RATED WALL ASSEMBLY BETWEEN STORAGE
 128 AND HALL 127. IT IS NOT POSSIBLE TO MAINTAIN THE
 FIRE RESISTANCE RATING OF THIS ASSEMBLY WITH A HEAT
 PUMP IN IT. ALSO, CLEARANCES AROUND APPLIANCES TO
 ELEMENTS OF PERMANENT CONSTRUCTION SHALL BE SUFFICIENT
 TO ALLOW INSPECTIONS, SERVICE, REPAIR OR REPLACEMENT
 WITHOUT REMOVING SUCH ELEMENTS OF PERMANENT
 CONSTRUCTION OR DISABLING THE FUNCTION OF A REQUIRED
 FIRE RESISTANCE-RATED ASSEMBLY IN ACCORDANCE WITH FBCM
 306.1.
  
 19.PG M104 AND M106: THIS PAGE CONTAINS A GENERAL NOTE
 WHICH CLAIMS ALL DUCT PENETRATIONS INTO GUEST ROOMS DO
 NOT REQUIRE FIRE DAMPERS IN ACCORDANCE WITH EXCEPTION
 #2 UNDER FBCM 607.5.3. WHILE IT APPEARS THAT THE
 EXHAUST DUCTS TO THE GUEST ROOMS QUALIFY FOR THIS
 EXCEPTION, THE OUTSIDE AIR DUCT PENETRATIONS DO NOT
 QUALIFY. THE DUCT MUST MEET ALL SIX PARTS OF EXCEPTION
 #2. PART 2.3 OF THE EXCEPTION REQUIRES THAT THE DUCT
 MUST NOT HAVE ANY OPENINGS WHICH COMMUNICATE WITH THE
 CORRIDOR. THE OA DUCT HAS OPENINGS INTO THE CORRIDOR
 AND THEREFORE DOES NOT QUALIFY FOR THIS EXCEPTION. SHOW
 THE OA DUCT PENETRATIONS OF THE GUEST ROOMS FROM THE
 CORRIDOR PROTECTED WITH FIRE DAMPERS IN ACCORDANCE WITH
 FBCM 607.5.3.
  
 NOTE: EVEN THOUGH THE EXHAUST DUCTS MAY QUALIFY FOR THE
 FIRE DAMPER EXCEPTION, THEY SHALL BE PROTECTED AS A
 THROUGH-PENETRATION WITH A THROUGH-PENETRATION FIRESTOP
 SYSTEM IN ACCORDANCE WITH FBCM 607.1.1.
  
 20. PG M104 AND M106: IN ADDITION TO THE FIRE DAMPER
 REQUIREMENTS ABOVE FOR THE GUEST ROOM OA DUCTS, THESE
 AND ALL OA DUCT PENETRATIONS OF THE CORRIDOR WALLS
 SHALL BE PROTECTED WITH SMOKE DAMPERS IN ACCORDANCE
 WITH FBCM 607.5.4. SHOW HOW THESE DAMPERS ARE TO BE
 ACTUATED IN ACCORDANCE WITH FBCM 607.5.4.1.
  
 21. PG M104 AND M106: FLOOR PLAN SHOWS RELIEF AIR VENT
 LOUVERS FOR 3 STAIR SHAFT ENCLOSURES. STAIR AND
 ELEVATOR SHAFT VENTS SHALL BE EQUIPPED WITH MOTORIZED
 DAMPERS THAT ARE CAPABLE OF BEING AUTOMATICALLY CLOSED
 DURING NORMAL BUILDING OPERATION AND ARE INTERLOCKED TO
 OPEN AS REQUIRED BY FIRE AND SMOKE DETECTION SYSTEMS IN
 ACCORDANCE WITH FBCB 13-409.1.ABC.3.1
  
 22. PG M104 AND M106: EXIT ENCLOSURE VENTILATION
 OPENINGS INTO THE FIRE-RESISTANCE-RATED CONSTRUCTION
 SHALL BE LIMITED TO THOSE NEEDED FOR MAINTENANCE AND
 OPERATION AND SHALL BE PROTECTED BY SELF-CLOSING
 FIRE-RESISTANCE-RATED DEVICES IN ACCORDANCE WITH
 CHAPTER 7 FOR ENCLOSURE WALL OPENING PROTECTIVES PER
 FBCB 1019.1.3.
  
 23. PG M106: THE OA INTAKE DUCT FOR HP-OA1 IS
 PENETRATING A RATED WALL BETWEEN THE CORRIDOR AND ROOM
 313. SHOW THIS DUCT PENETRATION PROTECTED WITH FIRE AND
 SMOKE DAMPER IN ACCORDANCE WITH FBCM 607.5.3 AND
 607.5.4.
  
 24. PG M106: SEVERAL OF THE EXHAUST BRANCH DUCTS FOR
 EF1 IN GUEST ROOMS ARE MISSING SIZES ON THE PLANS.
 PROVIDE THE MISSING INFORMATION ON PLANS. FBCB 106.1.1.
  
 25. PG M106: THE RELIEF AIR DUCT FOR STAIR C IS
 CROSSING THE CORRIDOR. EXIT ENCLOSURE VENTILATION SHALL
 BE DIRECTLY CONNECTED TO THE EXIT ENCLOSURE BY DUCTWORK
 ENCLOSED IN CONSTRUCTION AS REQUIRED BY THE FLORIDA
 BUILDING CODE, BUILDING FOR SHAFTS IN ACCORDANCE WITH
 FBCM 401.4(1) AND FBCB 1019.1.3(1).
  
 26. PG M106: THE 6 INCH ROUND DUCT PENETRATING THE WALL
 BETWEEN LINEN STORAGE 306 AND THE CORRIDOR SHALL BE
 PROTECTED WITH FIRE AND SMOKE DAMPER IN ACCORDANCE WITH
 FBCM 607.5.3 AND 607.5.4.
  
 27. PG M108: STAIR PRESSURIZATION FANS SF1, SF2 AND SF3
 SHALL BE PROVIDED WITH PERMANENT ACCESS FOR SERVICE AND
 MAINTENANCE. SUCH ACCESS SHALL BE PROVIDED BY A
 PERMANENT APPROVED MEANS OF ACCESS, THE EXTENT OF WHICH
 SHALL BE FROM GRADE OR FLOOR LEVEL TO THE EQUIPMENT AND
 APPLIANCES??? LEVEL SERVICE SPACE IN ACCORDANCE WITH
 FBCM 306.5.
  
 28. PG M108: STAIR PRESSURIZATION FANS SF1, SF2 AND SF3
 ARE SUPPLY FANS AND SHALL PROVIDED WITH SMOKE DETECTORS
 IN ACCORDANCE WITH FBCM 606.2.1. THE SMOKE DETECTORS
 SHALL SHUT DOWN THE FANS UPON ACTIVATION AND SHALL BE
 CONNECTED TO THE FIRE ALARM SYSTEM IN ACCORDANCE WITH
 FBCM 606.4.
  
 29. PG M108: HOISTWAYS OF ELEVATORS PENETRATING MORE
 THAN THREE STORIES SHALL BE PROVIDED WITH A MEANS FOR
 VENTING SMOKE AND HOT GASES TO THE OUTER AIR IN CASE OF
 FIRE IN ACCORDANCE WITH FBCB 3004.1. HOISTWAY VENTS
 SHALL BE LOCATED IN ACCORDANCE WITH 3004.2 AND SIZED IN
 ACCORDANCE WITH 3004.3. ELEVATOR SHAFT VENTS SHALL BE
 EQUIPPED WITH MOTORIZED DAMPERS THAT ARE CAPABLE OF
 BEING AUTOMATICALLY CLOSED DURING NORMAL BUILDING
 OPERATION AND ARE INTERLOCKED TO OPEN AS REQUIRED BY
 FIRE AND SMOKE DETECTION SYSTEMS IN ACCORDANCE WITH
 FBCB 13-409.1.ABC.3.1.
  
 30. PG M108: SF1, SF2, SF3 AND CT1 SHALL BE DESIGNED
 AND INSTALLED TO RESIST WIND PRESSURES IN ACCORDANCE
 WITH FBCM 301.13.
  
 31. PG M201: SEE COMMENT ABOVE FOR REQUIREMENTS FOR
 PROTECTION OF DUCT PENETRATIONS INTO GUEST ROOMS.
  
 32. PG M201: ENLARGED ROOM PLANS SHOW ALL ROOMS WITH 50
 CFM OF OA SUPPLY WHILE FLOOR PLANS ON M104 AND M106 AS
 WELL AS VENTILATION SCHEDULE ON M101 CALL FOR MOST
 ROOMS TO BE PROVIDED WITH 30 CFM OF OA. COORDINATE
 ENLARGED FLOOR PLANS WITH OTHER FLOOR PLANS AND
 VENTILATION SCHEDULE. THE VENTILATION RATES AS SHOWN ON
 THIS PAGE MAY EXCEED THE CAPACITY OF THE HP OA1 UNITS.
  
 33. PG M401: HEAT PUMP PIPING DIAGRAM, EACH WATER
 SOURCE HEAT PUMP SHALL HAVE A TWO-POSITION AUTOMATIC
 VALVE INTERLOCKED TO SHUT OFF WATER FLOW WHEN THE
 COMPRESSOR IS OFF IN ACCORDANCE WITH FBCB
 13-411.1.ABC.1.4.
  
 34. PG M401: SHOW HOW EACH HEAT PUMP WILL BE PROVIDED
 WITH AUXILIARY DRAIN PROTECTION IN ACCORDANCE WITH FBCM
 307.2.3.
  
 35. PG M402: FLEX DUCT RUNOUT DETAIL, FLEX DUCT
 SUPPORTS SHALL ME MIN. 1 1/2 INCHES WIDE AND SPACED NO
 MORE THAN 5 FEET APART IN ACCORDANCE WITH FBCM
 603.5.6.6.
  
 36. PG M402: FIRE DAMPER INSTALLATION DETAIL, THE FIRE
 DAMPER MANUFACTURER???S INSTALLATION INSTRUCTIONS SHALL
 GOVERN AND SHALL BE AVAILABLE ON THE JOBSITE AT TIME OF
 INSPECTION IN ACCORDANCE WITH FBCM 607.2 AND FBCM
 304.1.
  
 37. ATRIUM: ARCHITECTURAL PLAN SHOWS AN ATRIUM
 CONNECTING FLOORS 2 THROUGH 6 ON PAGE A500. A SMOKE
 CONTROL SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH
 FBCB 404.4 AND FBCB SECTION 909. THE EXHAUST METHOD MAY
 BE USED IN THIS AREA IN ACCORDANCE WITH FBCB 909.8.
  
 38. THE ANNEX PORTION OF THIS BUILDING IS AN ADDITION
 TO AN EXISTING BUILDING. AN ADDITION TO A BUILDING OR
 STRUCTURE SHALL COMPLY WITH THE BUILDING, PLUMBING,
 ELECTRICAL, AND MECHANICAL CODES IN ACCORDANCE WITH
 FBCEB 901.1. AS THIS ADDITION HAS OCCUPIED FLOORS
 LOCATED MORE THAN 75 FEET ABOVE THE LOWEST LEVEL OF
 FIRE DEPARTMENT VEHICLE ACCESS, IT IS CLASSIFIED AS A
 HIGH-RISE BUILDING IN ACCORDANCE WITH FBCB 403.1. ALSO,
 SMOKE CONTROL SHALL BE PROVIDED IN ACCORDANCE WITH FBCB
 403.15 AND FBCB SECTION 909. PROVIDE GENERAL DESIGN
 REQUIREMENTS FOR SMOKE CONTROL SYSTEMS AS WELL AS A
 RATIONAL ANALYSIS WITH SEQUENCE OF OPERATIONS IN
 ACCORDANCE WITH FBCB 909.2 AND 909.4
  
 39. ENERGY CODE: ENERGY CODE COMPLIANCE FORM WAS
 PROVIDED, HOWEVER, THE COMPLIANCE FORM WAS NOT
 CERTIFIED BY THE DESIGNER OF RECORD AS REQUIRED IN
 ACCORDANCE WITH FBCB 13-103.1.
  
 40. ENERGY CODE: THIS REVIEW IS FOR THE MECHANICAL
 PORTIONS OF THE ENERGY CALCULATIONS ONLY. PLEASE SEE
 OTHER TRADE REVIEWS FOR REQUIREMENTS RELATED TO THOSE
 TRADES.
  
 41. ENERGY CODE: COOLING LOAD CALCULATIONS SHALL BE
 PROVIDED AND APPENDED TO THE ENERGY CALCULATIONS IN
 ACCORDANCE WITH FBCB 13-407.1.ABC.1. A THOROUGH REVIEW
 OF THE ENERGY CALCULATIONS CANNOT BE PERFORMED WITHOUT
 THIS INFORMATION.
  
 42. ENERGY CODE: THE COOLING SYSTEMS LISTED IN THE
 INPUT REPORT DO NOT CORRESPOND WITH THE SYSTEMS SHOWN
 ON THE PLANS. EXAMPLE: ALL HEAT PUMPS ON EACH FLOOR
 APPEAR TO BE COMBINED INTO ONE SYSTEM WITH AN
 EFFICIENCY OF 12.00 LISTED. THERE ARE MULTIPLE,
 DIFFERENT SIZED HEAT PUMPS ON EACH FLOOR AND THEY HAVE
 DIFFERENT EFFICIENCIES. USE MULTIPLIERS TO LIST EACH
 TYPE OF SYSTEM ON EACH FLOOR WITH THE CORRECT
 CORRESPONDING EFFICIENCY RATING. ALSO, UNDER PLANT THE
 SYSTEM IS LISTED AS A CHILLER PLANT. THERE IS NO
 CHILLER PLANT SHOWN ON THE PLANS. THIS IS A WATER
 COOLED SYSTEM WITH COOLING TOWERS. THE PLANS AND
 SPECIFICATIONS, INCLUDING THE ENERGY CODE CALCULATIONS,
 SHALL SHOW, IN SUFFICIENT DETAIL, ALL PERTINENT DATA
 AND FEATURES OF THE BUILDING AND THE EQUIPMENT AND
 SYSTEMS AS HEREIN GOVERNED IN ACCORDANCE WITH FBCB
 13-103.2.
  
 NOTE: THESE PLANS HAVE BEEN SUBMITTED FOR PLAN REVIEW
 ONLY. A PERMIT APPLICATION HAS NOT BEEN SUBMITTED. IF A
 PERMIT APPLICATION IS SUBMITTED AFTER MARCH 1ST, 2009,
 THE PLANS WILL NEED TO BE REVIEWED FOR COMPLIANCE WITH
 THE NEW 2007 EDITION OF THE FLORIDA BUILDING CODE.
 SUBMISSION OF A PERMIT APPLICATION BEFORE THAT DATE
 WILL ENSURE THE PLANS WILL REMAIN UNDER THE CODES WHICH
 ARE CURRENTLY IN EFFECT.
  
 WHEN RESUBMITTING PLANS, PLEASE RESPOND TO EACH COMMENT
 IN WRITING WITH A DESCRIPTION OF HOW THE COMMENT WAS
 ADDRESSED AND WHERE THE RELEVANT INFORMATION CAN BE
 LOCATED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-01-20 Cont ID  
Sent By kstevens Date 2009-01-20 Time 08:24 Rev Time 0.00
Received By kstevens Date 2008-12-23 Time 12:14 Sent To  
Notes
2009-01-20 11:36:44DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1 (ADMIN)
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 CITY WPB MUNICIPAL CODE
  
 ****PLAN REVIEW ONLY****
  
 1. ALL SHEETS WITH G.M. REMBOWSKI ARCHITECT INC. THE
 BUSINESS LICENSE, (CERTIFICATE OF AUTHORIZATION), IS
 REQUIRED IN THE TITLE BLOCK OF EACH SHEET. FAC
 61G1-16.004(2) & FS 481.219, 481.2055.
  
 2. SHT A00A BUILDING CODES TO INCLUDE THE 2007
 REVISIONS. PLEASE BE ADVISED, SINCE THE PLANS HAVE BEEN
 SUBMITTED FOR PLAN REVIEW ONLY AT THIS TIME, IF THE
 PERMIT IS NOT APPLIED FOR PRIOR TO MARCH 1. 2009 THE
 PROJECT SHALL BE DESIGNED TO THE THE REQUIREMENTS OF
 THE FBC-2007 CODE.
  
 3. SHT A00A FBC CHAPTER 11 ACCESSIBILITY INDICATES 7
 GUESTROOMS WITH MOBILITY FEATURES. PER THE TABLE FOR
 SECTION 11-9.1.2, FIVE ARE REQUIRED WITH AN ADDITIONAL
 2 SLEEPING ROOMS WITH ROLL IN SHOWERS WHICH IS
 INDICATED ON THE PLANS. BUT PER THE FLORIDA SPECIFIC
 AREA OF SECTION 11-9.1.2, FIVE PERCENT OF THE
 GUESTROOMS, MINUS THE NUMBER OF ACCESSIBLE GUESTROOM
 REQUIRED BY THE TABLE, (5), SHALL PROVIDE ADDITIONAL
 SPECIAL ACCESSIBILITY FEATURES OF SECTION 11-9.2.3.
 THIS NUMBER COMES OUT TO 3 UNITS, (150 X .05 = 7.5
 MINUS 5 = 2.5 ROUNDED UP TO 3 UNITS). PLEASE INDICATE
 WHICH 3 ROOMS ARE COMPLIANT WITH THIS REQUIREMENT.
 SECTION 106.1.2.
  
 4. SHT A100 GUESTROOM SUMMARY SHOWS DOUBLE QUEEN,
 DOUBLE QUEEN SUITE, NARROW KING, KING & KING SUITE
 CLASSES OF ACCOMMODATIONS. THE ONLY ACCESSIBLE UNITS
 SHOWN ARE THE DOUBLE QUEEN AND THE KING UNITS. PER
 SECTION 11-9.1.4 IN ORDER TO PROVIDE PERSONS WITH
 DISABILITIES A RANGE OF OPTIONS EQUIVALENT TO THOSE
 AVAILABLE TO OTHER PERSONS SERVED BY THE FACILITY,
 SLEEPING ROOMS AND SUITES REQUIRED TO ACCESSIBLE BY
 SECTION 11-9.1.2 SHALL BE DISPERSED AMONG THE VARIOUS
 CLASSES OF SLEEPING ACCOMMODATIONS AVAILABLE TO PATRONS
 OF THE PLACE OF TRANSIENT LODGING. NO ACCESSIBLE UNITS
 ARE INDICATED FOR THE DOUBLE QUEEN SUITE, THE NARROW
 KING AND THE KING SUITES. PLEASE INDICATE HOW
 COMPLIANCE WITH SECTION 11-9.1.4 WILL BE ADDRESSED.
  
 5. SHT A100 SHOWS 10 ACCESSIBLE ROOMS BUT SHT A00A FBC
 CHAPTER 11 ACCESSIBILITY INDICATES GUESTROOMS WITH
 MOBILITY FEATURES TOTALS 7 (2 TO HAVE ROLL-IN SHOWERS),
 AS WELL AS 12 GUESTROOMS WITH COMMUNICATION FEATURES.
 PLEASE CLARIFY & CORRELATE. SECTIONS 11-9.1.2 &
 11-9.1.3..
  
 6. SHT A100 FOOD PREP AREA MAY REQUIRE A GREASE
 INTERCEPTOR. PLEASE CONTACT THE UTILITY DEPT.,
 INDUSTRIAL PRETREATMENT, ENVIRONMENTAL COMPLIANCE.
 PLEASE CONTACT HOLLY MCGRATH, LABORATORY SUPERVISOR AT
 HER OFFICE, (561) 822-2271, OR BY FAX (561) 822-2279.
 OR BY E-MAIL [email protected]. INTERCEPTOR SIZE WILL BE
 DETERMINED AND A WRITTEN DETERMINATION WILL BE
 SUBMITTED WITH RESPONSE COMMENTS. ARTICLE III SECTION
 90-124(7).
  
 7. SHTS A102 & A103 SHOWS ACCESSIBLE KING SUITE WHICH
 DOES NOT REFLECT THE GUESTROOM SUMMARY ON SHT A100
 WHICH INDICATES ACCESSIBLE KING UNIT. PLEASE CLARIFY &
 CORRELATE. SECTIONS 106.1.1 & 11-9.1.4.
  
 8. SHTS A102 & A103 ROOMS FOR PERSONS WITH HEARING
 IMPAIRMENTS SHALL BE IN ADDITION TO ROOMS THAT ARE
 ACCESSIBLE. SECTION 11-9-1.3. PLEASE INDICATE THE
 LOCATION OF THESE UNITS.
  
 9. SHTS A104 & L5/6 ROOF INFORMATION DOES NOT MATCH.
 PLEASE CORRELATE. SECTIONS 106.1.1 & 1101.1 AND TABLE
 1106.3.
  
 10. SHT A104 NO SECONDARY ROOF DRAINAGE IS SHOWN.
 SECTION 1107. PLEASE INDICATE LOCATION OF REQUIRED
 SECOND ROOF DRAINAGE.
  
 11. A104 SUBMIT CALCULATIONS FOR THE PRIMARY AND
 SECONDARY ROOF/DECK DRAINS. SHOW THE AREA BEING DRAIN
 FOR EACH DRAIN AND INDICATE 1/2 THE AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPETS ADDED TO EACH AREA TO
 VERIFY DRAIN & RWL SIZES. SECTIONS 106.1.2, 1106 & 1107
 & TABLES 1106.3 & 1106.7. -- PLEASE DESIGNATE EACH
 DRAIN AND RWL WITH A NUMBER OR LETTER TO VERIFY
 CALCULATIONS AND TRACK PIPE SIZING THROUGH THE BUILDING
 FROM ROOF TO UNDERGROUND.
  
 12. SHT A104 NO INFORMATION FOR THE ROOF DRAINAGE OVER
 THE STAIR B OR THE ELEVATOR HAS BEEN SUBMITTED.
 INDICATE THE PRIMARY AND SECONDARY ROOF DRAINS PER
 SECTIONS 1106 & 1107. INDICATE IF THERE ARE PARAPET
 WALLS AROUND THESE ROOFS.
  
 13. SHT A105 SUBMIT CALCULATIONS FOR THE PRIMARY AND
 SECONDARY ROOF/DECK DRAINS. SHOW THE AREA BEING DRAIN
 FOR EACH DRAIN AND INDICATE 1/2 THE AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPETS ADDED TO EACH AREA.
 SECTIONS 106.1.2, 1106 & 1107 & TABLES 1106.3 & 1106.7.
  
 14. SHT A106 SUBMIT A DETAIL FOR THE OVERFLOW SCUPPERS.
 INDICATE HEIGHT & WIDTH AS WELL AS THE DISTANCE OFF THE
 ROOF TO THE FLOW LINE OF THE OVERFLOW SCUPPER. SECTIONS
 106.1.2, 1503.4.3 & TABLE 1106.7.
  
 15. SHT A309 BREAKROOM SINK SHALL BE ACCESSIBLE. SHOW
 COMPLIANCE WITH THE FOLLOWING:
 A. 11-4.24-3 KNEE CLEARANCE
 B. 11-4.24.4 SINK DEPTH
 C. 11-4.24.5 CLEAR FLOOR SPACE
 D. 11-4.24.6 EXPOSED PIPES & SURFACES
 E. 11-4.24.7 FAUCETS
  
 16. SHTS A310 & A311 SHOW COMPLIANCE FOR THE FOLLOWING:
 ___W/C'S:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.3 HEIGHT
 C. 11-4.16.5 FLUSH CONTROLS
 ___STALL
 A. 11-4.17.3 SIZE & ARRANGEMENT - FIG 30(E)
 ___URINAL:
 A. 11-4.18.3 CLEAR FLOOR SPACE
 B. 11-4.18.4 FLUSH CONTROLS
 ___LAVS:
 A. 11-4.19.2 CLEARANCES (29")
 B. 11-4.19.3 CLEAR FLOOR SPACE
 C. 11-4.19.5 FAUCETS
 D. 11-4.19.6 MIRRORS
 ___TOILET ROOMS:
 A. 11-4.22.3 UNOBSTRUCTED TURNING AREA
  
 17. SHT A311 DETAIL E. THE CABINET IS NOT APPROVED FOR
 THE LAV. FORWARD APPROACH CLEAR FLOOR SPACE IS REQUIRED
 PER SECTION 11-4.19.3. THE LAV SHALL BE A MINIMUM 15"
 OFF THE WALL TO THE CENTERLINE OF THE FIXTURE TO BE
 CENTERED ON THE 30" DIMENSION OF THE CLEAR FLOOR SPACE.
 PLEASE INDICATE ON PLANS.
  
 18. SUBMIT A DETAIL FOR THE DRINKING FOUNTAINS SHOWING
 COMPLIANCE WITH SECTIONS 11-4.15 WITH ALL SUBSECTIONS
 AS WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE
 WHO HAVE DIFFICULTY BENDING OR STOOPING.
  
 19. SHTS A323 & A327 INDICATES 10 ACCESSIBLE UNITS, BUT
 SHT A00A FBC CHAPTER 11 ACCESSIBILITY INDICATES 7.
 PLEASE CORRELATE. SECTIONS 106.1.1 & 11-9.1.2.
  
 20. SHTS A347 & A349 SHOW COMPLIANCE WITH THE
 FOLLOWING:
 ___W/C'S:
 A. 11-4.16.3 HEIGHT
 B. 11-4.16.4 GRAB BARS (36" SHOWN FOR SIDEWALL - 42"
 REQD) - (NOT SHOWN ON DETAIL 2E SHT A349)
 C. 11-4.16.5 FLUSH CONTROLS
 ___LAVS:
 A. 11-4.19.2 HEIGHT & CLEARANCE
 B. 11-4.19.4 EXPOSED PIPES & CLEARANCE
 C. 11-4.19.5 FAUCETS
 ___SHOWER:
 A. 11-4.21.2 SIZE & CLEARANCE
 B. 11-4.21.3 SEAT (HEIGHT)
  
 21. SHT FS1-1 EQUIPMENT SCHEDULE ITEM #4 INDICATES
 QTY-2, BUT FLOOR PLAN ONLY SHOWS 1. PLEASE CORRELATE.
 SECTIONS 106.1.1 & 701.1. INDICATE THE LOCATION OF BOTH
 ITEMS.
  
 22. SHT D102 DEMO SHEET FOR THE 2ND AND 3RD FLOORS HAS
 NOT BEEN SUBMITTED. PER SECTION 106.1 TWO OR MORE SETS
 OF PLANS ARE REQUIRED. PLEASE SUBMIT COMPLETE SETS OF
 PLANS FOR REVIEW.
  
 23. SHTS P102, P103, P104 & P105. INDICATE THE RISER
 NUMBERS FOR EACH WATER RISER IN ORDER TO TRACK THE
 RISERS THROUGH THE BUILDING AND VERIFY CODE COMPLIANCE
 OF RISERS. SECTIONS 106.1.2, & 601.1.
  
 24. SHT P106 NOTE STATES POOL SHOWER BY POOL
 CONTRACTOR. THE SHOWER SHALL BE INSTALLED BY A LICENSED
 PLUMBING CONTRACTOR PER FS 489. PLEASE CORRECT NOTE.
  
 25. SHTS P202, P203, P204 & P205. SHOW THE LOCATION OF
 ALL SANITARY RISERS AND IDENTIFY RISERS WITH RISERS
 NUMBERS TO REFLECT THE RISERS ON SHTS P703, P704 &
 P705. THIS WILL ENABLE THE REVIEWER TO TRACK PIPING
 THROUGH THE BUILDING FROM BUILDING DRAIN TO VTR FOR
 EACH RISER AND VERIFY CODE REQUIREMENTS. SECTIONS
 106.1.2 & TABLES 710.1(1) & 710.1(2).
  
 26. SHT P205 DOES NOT RELFECT RISER DIAGRAMS ON SHTS
 P703, P704 & P705 WHICH SHOWS THE VENTS CONNECTING TO
 THE LAVS AND SHOWERS. PLEASE CORRELATE. SECTION 106.1.1
 & TABLE 916.1.
  
 27. SHT P307 MAIN BUILDING STORM RISER. TOP OF RISER
 SHOWING 2 AREA DRAINS 1,708 SF & ONE AREA DRAIN 745 SF
 ALSO SHOWS A 5" LINE ABOVE THE ROOF. MORE INFORMATION
 IS REQUIRED. PLEASE INDICATE WHERE THIS STORM LINE
 TERMINATES AND IF THERE ARE MORE AREAS DRAINING INTO
 THE RISER. SECTION 106.1.2 & TABLE 1106.3.
  
 28. SHT P308 A SEPARATE GAS PERMIT IS REQUIRED. THE
 FOLLOWING INFORMATION IS REQUIRED TO ISSUE PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. LENGHTS NOT SHOWN.
  
 B. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 C. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 D. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 INFORMATIONAL: - (WELD PIPE INDICATED. - WELD
 CERTIFICTIONS & WELDING PROCEDURE REQUIRED AT TIME OF
 APPLICATION FOR GAS PERMIT)
  
 29. SHT P402 DETAIL #2 INDICATE WHERE SUPPLY LINES FOR
 THE BAR CONNECT TO THE WATER MAINS. SECTIONS 106.1.2 &
 601.1.
  
 30. SHT P403 DETAIL #2 A RELIEF VENT IS REQUIRED FOR
 THE AIR ADMITTANCE VALVE. SECTION 917.3.2. PLEASE
 INDICATE ON FLOOR PLAN AND RISER DIAGRAM.
  
 31. SHT P405 DETAIL #1 SHOWS NO WATER SUPPLY TO THE
 URINAL. PLEASE SHOW ON PLANS. SECTIONS 106.1.2 & 601.1.
  
 32. SHT P405 DETAIL #3 SHOWS THE WATER HAMMER ARRESTORS
 IN THE CEILING. WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURES IN AN "EFFECTIVE RANGE" NOT IN THE
 CEILING. PDI-WH 201.
  
 33. SHT P501 WATER PIPING NOTES #2. NO COPPER JOINTS
 UNDER THE SLAB. SECTION 303.2. PLEASE INDICATE IN NOTE.
  
 34. SHT P501 WATER PIPING NOTES #3 BACKFLOW PREVENTOR
 TO BE INSTALLED BY A LICENSED PLUMBING CONTRACTOR PER
 FS 489. PLEASE INDICATE IN NOTE.
  
 35. SHT P501 WATER HEATER SCHEDULE NOTE #2 CODE
 REQUIREMENT IS THE FBC-2004 PLUMBING & MECHANICAL WITH
 2007 AMENDMENTS, NOT THE STANDARD CODE AS INDICATED.
 PLEASE CORRECT THE CODE REFERENCE. SECTION 106.1.1.
  
 36. SHT P601 DETAIL #1 DOES NOT RELFECT THE FLOOR PLAN
 AT THE EWC-A. PLEASE CORRELATE. SECTION 106.1.1.
  
 37. SHT P601 DETAIL #1 SUPPLY RISERS (LOWER LEVEL)
 SHOWS 3 COLD WATER SUPPLY LINES TO 3 WASH MACHINES AND
 2 COLD WATER SUPPLY LINES TO THE LAST WASH MACHINE.
 PLEASE CLAIFY. SUBMIT A DETAIL SHOWING THE PIPING TO
 THE WASH MACHINES. SECTIONS 106.1.2 & 601.1
  
 38. SHT P601 DETAIL #1 SUPPLY RISERS (LOWER LEVEL).
 WATER HAMMER ARRESTORS ARE REQUIRED ON THE SUPPLY LINES
 TO THE WASH MACHINES AND SHALL BE LOCATED NEAR THE
 FIXTURES IN AN "EFFECTIVE RANGE". SECTION 604.9 &
 PDI-WH 201.
  
 39. SHT P602 A WATER HAMMER ARRESTOR IS REQUIRE A THE
 ICE MAKER PER SECTION 604.9 AND SHALL BE LOCATED NEAR
 THE FIXTURES IN AN "EFFECTIVE RANGE". SECTION 604.9 &
 PDI-WH 201.
  
 40. SHT P602 RISER 3A NEAR ANNEX BUILDING DOES NOT
 REFLECT THE FLOOR PLAN. PLEASE CORRELATE. SECTION
 106.1.1 & 601.1.
  
 41. SHT P602 NO WATER SUPPLY CONNECTION TO THE WATER
 MAINS TO THE BAR AREA. PLEASE CLARIFY. SECTIONS
 106.1.1, 106.1.2 & 601.1.
  
 42. SHT P602 TWO RISERS DESIGNATED 7A ARE REVERSE FROM
 THE FLOOR PLAN. PLEASE INDICATE ON THE FLOOR PLAN, (7A
 REVERSE), OR SUBMIT A REVERSE RISER DIAGRAM THAT
 REFLECT THE FLOOR PLAN. SECTIONS 106.1.1, 106.1.2 &
 601.1.
  
 43. SHT P701 SANITARY RISERS (LOWER LEVEL). THE SUMP
 PUMP FROM THE ELEVATOR CONNECTION TO THE SANITARY
 SYSTEM IS PROHIBITED. SECTION 301.6. A LINE TO WHERE
 THE CONTENTS CAN BE PUMPED TO A CONTAINER AND DISPOSED
 IN AN APPROVED HAZARDOUS WASTE FACILITY IS REQUIRED.
  
 44. SHT P701 SANITARY RISERS (LOWER LEVEL) SHOWS A 4"
 VENT UP THAT IS NOT FOUND ON SHT P702. PLEASE CLARIFY.
 SECTION 106.1.1 & TABLE 916.1.
  
 45. SHT P702 SANITARY RISERS (1ST FLOOR) DOES NOT
 REFLECT THE FLOOR PLAN. RISER 9A IS NOT SHOWN ON THE
 FLOOR PLAN. PLEASE CORRELATE. SECTIONS 106.1.1 & 901.1.
  
 46. SHT P702 SANITARY RISERS (1ST FLOOR) DOES NOT
 REFLECT THE FLOOR PLAN. NOTE: "SEE SHT P701 FOR
 CONTINUATION" PIPING WAS NOT FOUND ON THE FLOOR PLAN.
 PLEASE CORRELATE. SECTIONS 106.1.1 & 901.1.
  
 47. SHT P702 SANITARY RISERS (1ST FLOOR) DOES NOT
 REFLECT THE FLOOR PLAN. A BRANCH LINE TO 4" SS UP
 UPSTREAM OF THE ELEVATOR BRANCH LINE IS SHOWN ON THE
 FLOOR PLAN BUT NOT ON THE RISER DIAGRAM. PLEASE
 CORRELATE. SECTIONS 106.1.1 & 901.1.
  
 48. SHT P702 SANITARY RISERS (1ST FLOOR). SHOW PIPE
 SIZES FOR THE FLOOR DRAIN AND THE FLOOR SINK BY THE
 PREP HAND SINK. TABLES 710.1.(1) & 710.1(2).
  
 49. SHTS P703, P704 & P705 ALL VENT STACKS SHALL
 CONNECT AT THE BASE OF THE WASTE/SOIL STACKS. SECTION
 903.4. PLEASE SHOW ON RISERS.
  
 50. SHT P706 DETAIL #1 RISER DOES NOT REFLECT THE FLOOR
 PLAN ON SHT P205 AT 4" VENT UP NEAR RISER 15B. PLEASE
 CORRELATE. SECTIONS 106.1.1 & 901.1.
  
 51. SHT P801 ELEVATOR SUMP CONNECTION DETAIL NOT
 APPROVED. SECTION 301.6. A LINE TO WHERE THE CONTENTS
 CAN BE PUMPED TO A CONTAINER AND DISPOSED IN AN
 APPROVED HAZARDOUS WASTE FACILITY IS REQUIRED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2008-12-04 Cont ID  
Sent By aaponte Date 2008-12-04 Time 11:53 Rev Time 0.00
Received By aaponte Date 2008-12-04 Time 11:40 Sent To  
Notes
2008-12-04 11:52:551. PLEASE CLARIFY IF THE SUBMITTED BUILDING PERMIT
 INCLUDES THE HOTEL AND THE PARK OR IT IS ONLY FOR THE
 HOTEL. PLEASE INLCUDE DATA TO CONFIRM THE AREA OF THE
 PROPOSED PARK IS MINIMUM OF 12,500 SQUARE FEET.
 2. THE TOTAL GROSS SQUARE FOOTAGE ON PAGE A002 DOES NOT
 MATCH THE TOTAL SQUARE FOOTAGE ON PAGE A00A
 3. LANDSCAPE DRAWINGS DO NOT MATCH ROOF PLAN ON SHEET
 A104 AND A104C.
 4. LANDSCAPE DRAWINGS FOR PARK SHOULD REFLECT THE
 LATEST FOOTPRINT CHANGES FOR THE ANNEX. LANDSCAPE
 DRAWINGS SHOULD NOT INCLUDE ANYTHING RELATED TO THE
 CENTRAL PARK PLAZA BUILDING (NORTH OF FERN)
 5. INFORMATION SHOULD BE PROVIDED REGARDING THE
 PROPOSED LOCATION FOR THE PARKING SPACES REQUIRED FOR
 THE NEW HOTEL ROOMS ON THE ANNEX BUILDING. 35 SPACES
 ARE REQUIRED BY CODE.
 6. IF PARK IS INCLUDED AS PART OF THIS PERMIT DRAWINGS
 SHALL INCLUDE DETAILS FOR PROPOSED PAVERS, BENCHES,
 DRINKING FOUNTAIN, FOUNTAIN DETAILS, LIGHTING, TREE
 GRATES, AND ANY OTHER ELEMENTS NECESSARY TO ACCURATELY
 DEPICT THE PROPOSED DESIGN FOR CONSTRUCTION.
 7. A TREE RELOCATION PERMIT IS REQUIRED FOR THE REMOVAL
 OF THE TREES CURRENTLY LOCATED AT THE PARKING LOT.
 8. PAVERS PROPOSED FOR PARK AREA MAY EXTEND OVER THE
 PUBLIC SIDEWALK TO CONTINUE THE MAIN PATTERN. SIDEWALK
 IN FRONT OF HOTEL AND ANNEX BUILDING SHOULD MATCH THE
 DIXIE HWAY STREETSCAPE OR FERN STREET SIDEWALK
 MATERIAL.