| 2008-12-08 16:55:32 | BUILDING PLAN REVIEW |
| | PERMIT: 08110283 |
| | ADD: 326 FERN STREET |
| | CONT: ?PLAN REVIEW? |
| | TEL: (312)375-0828 JOHN QUINN |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | ARCHITECT: GERALD REMBOWSKI |
| | STRUCTURAL ENGINEER: STEPHEN F. EBERSOLE |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS, |
| | PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR |
| | SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL |
| | REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A |
| | THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN |
| | (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED |
| | FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS |
| | WEST PALM BEACH ADMINISTRATIVE CODE. |
| | |
| | 1C) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 1D) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST |
| | TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO |
| | THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS. |
| | |
| | |
| | |
| | 2) G. M. REMBOWSKI ARCHITECT, INC IS MISSING THEIR |
| | CERTIFICATE OF AUTHORIZATION. |
| | 481.219 F.S. CERTIFICATE OF AUTHORIZATION. THE TITLE |
| | BLOCK FOR ANY SHEET BEARING THE NAME OF AN ARCHITECT |
| | PRACTICING UNDER A FICTITIOUS NAME, A CORPORATION, OR A |
| | PARTNERSHIP, OFFERING ARCHITECTURAL SERVICES, SHALL |
| | INCLUDE THE CERTIFICATE OF AUTHORIZATION NUMBER. ADD |
| | THE NUMBER TO EACH SHEET. THIS MAY BE ADDED BY HAND. |
| | |
| | 3) STEPHEN F. EBERSOLE P.E. MISSING THE PRINTED NAME |
| | AND LICENSE NUMBER. |
| | 61G15-23.002(2) FL. ADMIN.CODE. PLANS SIGNED & SEALED |
| | BY A PROFESSIONAL ENGINEER SHALL INCLUDE EITHER THE: |
| | NAME, ADDRESS AND LICENSE NUMBER OF THE ENGINEER OR, |
| | THE NAME AND LICENSE NUMBER OF THE ENGINEER. |
| | |
| | 4) SOILS REPORT, NO COPIES. 1802.2.1 QUESTIONABLE SOIL. |
| | WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN |
| | DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT |
| | SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING |
| | OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION |
| | BE MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE |
| | PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 . |
| | |
| | PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| | PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR |
| | PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE |
| | DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. |
| | FL ADMIN CODE 61G15-23.002 ENGINEERS |
| | |
| | 5) SHEET TS, THRESHOLD BUILDING REQUIREMENTS: |
| | |
| | 5A) INDICATES THE THRESHOLD INSPECTION PLAN IS LOCATED |
| | ON SHEET S-1. THIS SHEET ONLY PROVIDES GENERAL NOTES. |
| | 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL |
| | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A |
| | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION |
| | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL |
| | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING |
| | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR |
| | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE |
| | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE |
| | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT |
| | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| | WITH THE PERMITTED DOCUMENTS. |
| | |
| | 5B)THRESHOLD INSPECTOR: |
| | WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION SERVICES |
| | DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL |
| | INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA |
| | STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS |
| | CODE. |
| | CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR |
| | PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION |
| | BEFORE THE PERMIT MAY BE ISSUED. |
| | |
| | 5C) INFORMATIONAL: |
| | 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR |
| | THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER HAS |
| | REQUIRED ON THE PLANS OR SPECIFICATIONS ONE MATERIAL, |
| | APPROVED FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND |
| | CEILINGS. |
| | |
| | 6) INFORMATIONAL; 109.3.10* IMPACT OF CONSTRUCTION. ALL |
| | CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL BE |
| | PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT THE |
| | CONDITION OF ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS |
| | PERMITTED TO AFFECT SAID PROPERTY PURSUANT TO A CONSENT |
| | BY THE APPLICABLE PROPERTY OWNER, UNDER TERMS & |
| | CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY OWNER. |
| | THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF |
| | DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE |
| | STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION |
| | ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE |
| | WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY |
| | REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH |
| | ENGINEERING STANDARDS TO PRESERVE THE |
| | POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY, |
| | DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW |
| | RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS, |
| | PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING |
| | PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ |
| | FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A |
| | PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED |
| | DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS |
| | PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A |
| | CERTIFICATION FROM A LICENSED ENGINEER SHALL BE |
| | SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL |
| | OF THE FINAL INSPECTION. |
| | |
| | 7) INFORMATIONAL: 109.3.10.1 HURRICANE PROTECTION. IT |
| | SHALL BE UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION |
| | RELATED MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE |
| | OR OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 |
| | HRS. AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE |
| | HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH |
| | CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE |
| | EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN |
| | SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH |
| | CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING |
| | DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY |
| | PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE |
| | CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24 |
| | HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE |
| | SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION TO |
| | THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS |
| | SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO |
| | SECTION 113 OF THIS CHAPTER. |
| | |
| | 8) THE PLANS THAT ARE CURRENTLY UNDER REVIEW WERE |
| | BROUGHT IN AS A MAJOR WORKING DRAWING REVIEW BEFORE |
| | PLANS ARE TO BE BROUGHT IN AS A PERMIT APPLICATION |
| | PLEASE HAVE THEM STAMPED BY HISTORIC PRESERVATION |
| | DIVISION INDICATING THERE APPROVAL. |
| | |
| | 9) 2004 EXISTING BUILDING CODE CHAPTER 10, 1005.1 |
| | STRICT COMPLIANCE, 1005.2 COMPLIANCE OPTIONS AND |
| | 1005.3. PLEASE REVIEW THESE CODE SECTIONS AND INDICATE |
| | WHICH OF THE LIFE SAFETY AND PROPERTY CONSERVATION |
| | OPTIONS SHALL BE PROVIDED IN ACCORDANCE WITH ONE OF THE |
| | FOLLOWING OPTIONS 1-3. PLEASE PROVIDE DOCUMENTATION FOR |
| | CODE COMPLIANCE FOR THE LISTED CODE SECTIONS ABOVE. |
| | |
| | 10) 2004 EXISTING BUILDING CODE CHAPTER 10, 1006.1 |
| | INVESTIGATION AND EVALUATION REPORT. |
| | AN HISTORIC BUILDING UNDERGOING ALTERATION OR CHANGE OF |
| | OCCUPANCY SHALL BE INVESTIGATED AND EVALUATED. IF IT IS |
| | INTENDED THAT THE BUILDING MEET THE REQUIREMENTS OF |
| | THIS CHAPTER, A WRITTEN REPORT SHALL BE PREPARED AND |
| | FILED WITH THE BUILDING OFFICIAL BY A |
| | FLORIDA-REGISTERED ARCHITECT OR ENGINEER. SUCH REPORT |
| | SHALL BE IN ACCORDANCE WITH THE PROVISIONS OF SECTIONS |
| | 4.3.1.2 THROUGH 4.3.2 OF NFPA 914, CODE FOR FIRE |
| | PROTECTION OF HISTORIC STRUCTURES AND SHALL IDENTIFY |
| | EACH REQUIRED SAFETY FEATURE THAT IS IN COMPLIANCE WITH |
| | THIS CHAPTER AND WHERE COMPLIANCE WITH THIS OR OTHER |
| | CHAPTERS WOULD BE DAMAGING TO THE CONTRIBUTING HISTORIC |
| | FEATURES. IN ADDITION, THE REPORT SHALL DESCRIBE EACH |
| | FEATURE THAT IS NOT IN COMPLIANCE AND DEMONSTRATE HOW |
| | THE INTENT OF THE PROVISIONS OF THIS OR OTHER CHAPTERS |
| | ARE COMPLIED WITH IN PROVIDING AN EQUIVALENT LEVEL OF |
| | SAFETY. PLEASE PROVIDE COMPLIANCE WITH THIS SECTION. |
| | |
| | NOTE: SINCE WE HAVE NOT RECEIVED ANY INFORMATION |
| | CONCERNING COMMENT 9 NOR 10 THIS REVIEW WILL BE |
| | COMPLETED AS 2004 EXISTING BUILDING CODE CHAPTER 8 |
| | CHANGE IN OCCUPANCY AND CHAPTER 9 ADDITIONS. TABLE |
| | 812.4.1 HAZARD CATEGORIES & CLASSIFICATION LIFE SAFETY |
| | & EXITS PLACES THIS BUILDING INTO A HIGHER HAZARD GROUP |
| | FROM A BUSINESS (4) TO A R-1 (3) OR HIGHER HAZARD |
| | CATEGORY (LOWER NUMBER) WHICH ENACTS CHAPTER 10 OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 10A) THE INDEX SHEET DOES NOT INDICATE WITHIN THE |
| | SUBMITTED PLANS A LIFE SAFETY SHEETS INDICATING |
| | OCCUPANT LOADS AND EGRESS CAPACITIES. 106.3.5.1.1(6). |
| | |
| | 10B) THE INDEX SHEET DOES NOT INDICATE WITHIN THE |
| | SUBMITTED PLANS FOR FIRE SPRINKLER SCHEMATIC |
| | 106.3.5.1.1(5), 403.2 & 903.6.1. |
| | |
| | 11) SHEET A00A : |
| | |
| | 11A) TYPO: FBC CHAPTER 6 TYPE OF CONSTRUCTION |
| | REFERENCES THE IBC NOT THE FBC TABLE 601. PLEASE UPDATE |
| | PLANS. |
| | |
| | 11B) DEFINITION FOR WIND-BORN DEBRIS REGION EITHER IS |
| | SHORTED OR NOT THE 2004FBC WITH 2007 SUPPLEMENT |
| | DEFINITION. PLEASE UPDATE PLANS. |
| | |
| | 12) SHEET A00B: |
| | |
| | 12A) PLANS INDICATE A WALL TYPE ?A? UL DESIGN U419 |
| | INDICATES THE ?? RESILIENT CHANNEL @ 24? O.C. |
| | VERTICALLY. WHEN REVIEWING THE U419 ASSEMBLY IT |
| | INDICATES THE USE OF (6A)(A) FURRING CHANNEL TO BE A 2 |
| | 3/8? WIDE BY 7/8? DEEP, SPACED 24 ? O.C. PERPENDICULAR |
| | TO STUDS. |
| | IF THE CHANNEL IS VERTICAL IT IS PARALLEL TO THE STEEL |
| | STUD NOT PERPENDICULAR. PLEASE REVIEW AND CORRECT. |
| | |
| | 12B) PLANS INDICATE A WALL TYPE ?G? SHAFT WALL DESIGN |
| | WITH A STC RATING OF 34, PLEASE REVIEW SECTION 1207.2 |
| | AIR-BORNE SOUND TRANSMISSION REQUIRING A STC OF NOT |
| | LESS THAN 50. |
| | |
| | 12C) PLANS FAIL TO PROVIDE THE FLOOR ASSEMBLY OF THE |
| | EXISTING STRUCTURE, PLEASE INDICATE COMPLIANCE WITH |
| | 1207.3 STRUCTURE-BORNE SOUND. |
| | |
| | 12D) PLANS INDICATE A WALL TYPE J2 WHERE THE GYPSUM |
| | BOARD IS TO BE GLUED DIRECTLY TO THE BLOCK, PLEASE |
| | PROVIDE SPECIFICATIONS UNLESS OTHERWISE SPECIFIED BY |
| | THE GYPSUM BOARD MANUFACTURER THE TYPE OF ADHESIVE , |
| | AMOUNT AND SPACING OF ADHESIVE TO BE USED. |
| | 2508.1 TABLE 2508.1 GYPSUM BOARD GA-216, 11. |
| | |
| | 13) SHEET A100: |
| | |
| | 13A) PLANS INDICATE A RESTRICTED EASEMENT AREA THAT |
| | RUNS NORTH TO SOUTH THROUGH THE LOWER LEVEL WITH A WALL |
| | TAG ?L? EXTERIOR WALL, NO RATING, THIS IS NEITHER A |
| | EXTERIOR WALL, PLEASE SEE TABLE 302.3.2 FOR THE |
| | SEPARATION REQUIREMENTS FROM UTILITY AND MISC GROUP. |
| | |
| | 13B) ROOM# 022 EXISTING GENERATOR ROOM DOES NOT PROVIDE |
| | ANY INFORMATION ON THE EXISTING WALLS NOR FIRE RATINGS, |
| | PLEASE SEE 403.10.1 & NFPA 110.7.2.1.1 & |
| | NFPA 110.7.2.3 FLOODING. NOTE PLANS DO NOT INDICATE ANY |
| | FUEL STORAGE FOR THE GENERATOR, PLEASE REVIEW |
| | ELECTRICAL COMMENTS FOR THE REQUIRED AMOUNT OF FUEL |
| | NECESSARY FOR ON SITE |
| | STORAGE. |
| | |
| | 13C) ROOM# 004 THE FIRE PUMP ROOM PLANS INDICATE SOME |
| | WALLS AS WALL TYPE ?L? EXTERIOR WALL NO RATING AND WALL |
| | TYPE ?F? NOT RATED, PLEASE SEE NFPA |
| | 20.5.12.1.1.1.REQUIRING 2 HOUR SEPARATION FOR HIGH RISE |
| | CONSTRUCTION. |
| | |
| | 13D) STAIR A # 001 ALSO DOES NOT INDICATE WALL TYPE |
| | EXCEPT FOR A SECTION WALL TAG ?L? OR EXTERIOR WALL |
| | WHICH SEPARATES THE STAIRWELL FROM THE GYM. SEE 707.4 A |
| | 2 HR FIRE RATING IS REQUIRED ALSO 1019.1.. |
| | |
| | 13E) STAIR A # 001 ALSO LEADS INTO THE SUMP PIT ROOM |
| | DOOR # 01, PLEASE REVIEW 1019.1 AN EXIT ENCLOSURE SHALL |
| | NOT BE USED FOR ANY PURPOSE OTHER THAN MEANS OF EGRESS. |
| | |
| | 13F) STAIR A # 001 DOOR # 02 DOES NOT INDICATE ANY FIRE |
| | RATING SEE SHEET A700. SEE TABLE 715.3 OPENING |
| | PROTECTIVE?S. |
| | |
| | 13G) STAIR B # 028 STAIRS ARE EXISTING BUT THE PLANS DO |
| | NOT INDICATE TYPE OF WALLS, REQUIRES A 2HR FIRE |
| | RESISTANCE RATING 707.4 & 1019.1. |
| | |
| | 14) SHEET A101: |
| | |
| | 14A) STAIR A100 FIRST FLOOR CONTINUES TO THE LOWER |
| | LEVEL BELOW GRADE PLEASE REVIEW SECTION |
| | 1019.1.6. |
| | |
| | 14B) FIRE COMMAND ROOM, ROOM# 114 INDICATES WALL TAG |
| | ?F? A NON-RATED WALL. PLEASE REVIEW 911.1. A 1-HR FIRE |
| | RESISTANCE RATED FIRE BARRIER. |
| | |
| | 14C) FIRE COMMAND DOOR# 132 DOES NOT INDICATE ANY FIRE |
| | RATING SHEET A700. |
| | |
| | 14D) FIRE COMMAND DOOR# SHEET A700 INDICATES HARDWARE |
| | TYPE# 19 ON THE HARDWARE SCHEDULE A701 HARDWARE SET# 19 |
| | ONLY INDICATES 2 DOORS RECEIVING THIS HARDWARE NEITHER |
| | THE FIRE COMMAND ROOM, SHEET A700 INDICATES 6 DOORS |
| | RECEIVING THIS TYPE HARDWARE, PLEASE CORRELATE PLANS, |
| | OPENING PROTECTIVE?S SECTION 715. |
| | |
| | 14E) PLANS ARE TO INDICATE COMPLIANCE WITH 911.1. |
| | CONTAIN THE FOLLOWING FEATURES. |
| | 1. THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM UNIT. |
| | 2. THE FIRE DEPARTMENT COMMUNICATIONS UNIT. |
| | 3. FIRE DETECTION AND ALARM SYSTEM ANNUNCIATOR UNIT. |
| | 4. ANNUNCIATOR UNIT VISUALLY INDICATING THE LOCATION OF |
| | THE ELEVATORS AND WHETHER THEY ARE OPERATIONAL. |
| | 5. STATUS INDICATORS AND CONTROLS FOR AIR-HANDLING |
| | SYSTEMS. |
| | 6. THE FIRE-FIGHTER?S CONTROL PANEL REQUIRED BY SECTION |
| | 909.16 FOR SMOKE CONTROL SYSTEMS INSTALLED IN THE |
| | BUILDING. |
| | 7. CONTROLS FOR UNLOCKING STAIRWAY DOORS |
| | SIMULTANEOUSLY. |
| | 8. SPRINKLER VALVE AND WATER-FLOW DETECTOR DISPLAY |
| | PANELS. |
| | 9. EMERGENCY AND STANDBY POWER STATUS INDICATORS. |
| | 10. A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED |
| | ACCESS TO THE PUBLIC TELEPHONE SYSTEM. |
| | 11. FIRE PUMP STATUS INDICATORS. |
| | 12. SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL |
| | FLOOR PLAN AND DETAILING THE BUILDING CORE, MEANS OF |
| | EGRESS, FIRE PROTECTION SYSTEMS, FIRE-FIGHTING |
| | EQUIPMENT AND FIRE DEPARTMENT ACCESS. |
| | 13. WORKTABLE. |
| | 14. GENERATOR SUPERVISION DEVICES, MANUAL START AND |
| | TRANSFER FEATURES. |
| | 15. PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED |
| | BY OTHER SECTIONS OF THIS CODE. |
| | |
| | |
| | 14F) JUST TO THE RIGHT OF THE FIRE COMMAND ROOM IN THE |
| | CORRIDOR THERE IS A PAIR OF DOUBLE DOORS WITH OPPOSITE |
| | LEAF ACTION, THIS SET OF DOORS ARE NOT IDENTIFIED, THE |
| | CORRIDOR IS INDICATED AS A 5?-10? MINIMUM, THE DOORS |
| | SCALE OUT TO BE APPROXIMATELY (2) 2?-6? WIDE, PLEASE |
| | REVIEW 1008.1.1 MINIMUM32?CLEAR OPENING, AND 11-4.3.(9) |
| | & 11-4.3.10. |
| | |
| | 14G) THE COMMENT DIRECTLY ABOVE ALSO RELATES TO DOOR# |
| | 119. |
| | |
| | 14H) LINEN STORAGE ROOM DOOR# 119 WHICH ALSO ACTS AS A |
| | LAUNDRY CHUTE ACCESS ROOM, THE WALL MARKERS INDICATES |
| | MARKER ?F? NON-RATED WALLS, IF THIS ROOM HAD ONLY LINEN |
| | STORAGE THIS WOULD BE CORRECT. 707.13.3 LAUNDRY CHUTE |
| | ACCESS ROOM REQUIRE 1 HR FIRE RATED WALLS AND OPENING |
| | PROTECTIVES ? HR WITH SELF CLOSING OR AUTOMATIC CLOSING |
| | UPON ACTIVATION OF THE DETECTION OF SMOKE. |
| | |
| | 14I) JUST TO THE RIGHT OF ELEVATOR# 3 THERE APPEARS TO |
| | BE A DOOR# 18A OR 18D NEITHER DOOR IS LOCATED ON THE |
| | DOOR SCHEDULE LOCATED ON SHEET A700. |
| | |
| | |
| | 14J) HALL# 127 THERE SEAMS TO BE A DISCREPANCY IN THE |
| | SOUTH WALL LOCATION THAT BACKS UP TO THE STAIRS THAT |
| | DESCEND TO THE LOWER BASEMENT EASEMENT. |
| | |
| | 14K) STAIR TOWER B VERSES KING ROOM 122, THE WALL TAG |
| | INDICATES A WALL TYPE ?A? A 1 HOUR RATED WALL. STAIR |
| | TOWER B (VERTICAL EXIT) DOES NOT END AT DOOR 126, IT |
| | BECOMES A EXIT PASSAGEWAY OR CONTINUATION OF THE 2 HR |
| | ENCLOSURE UNTIL DOOR# 127 THE EXIT . PLEASE VISIT |
| | 1019.1. |
| | |
| | 14L) STAIR TOWER B AT DOOR 124) SWINGS THE WRONG WAY IT |
| | SWINGS INTO THE EGRESS PATH BLOCKING THE EXIT, THE DOOR |
| | SHOULD REVERSE THE SWING OF THE DOOR AGAINST THE COMMON |
| | WALL WITH ROOM# 122. 1008.1.8.8. |
| | |
| | 14M) DOOR# 126 FROM THE VERTICAL EXIT OPENS DIRECTLY |
| | INTO THE STAIR LANDING THE LOCATION OF THIS DOOR BLOCKS |
| | THE EGRESS PATH OF BOTH THOSE EXITING FROM THE LOWER |
| | LEVEL AS WELL AS FROM THIS LEVEL . 1008.1.5. |
| | |
| | 14N) THE SOUTH WALL OR PROPERTY LINE WALL HAS NUMEROUS |
| | DOOR OPENINGS THAT CROSS OVER THE PROPERTY LINE INTO |
| | THE PUBLIC ALLEY WAY, PLEASE REVIEW 3202.2 DOORS AND |
| | WINDOWS SHALL NOT OPEN OR PROJECT INTO THE PUBLIC RIGHT |
| | ?OF-WAY. |
| | |
| | 14O) THIS SHEET INDICATES THAT THERE IS AN EXISTING FPL |
| | EASEMENT, CURRENTLY THERE IS NO DOCUMENTS RELINQUISHING |
| | THE EASEMENT OR GRANTING USE OF THE EASEMENT WITH |
| | EXCEPTIONS TAKEN. 3201.03 . |
| | |
| | 14P) FPL VAULT NOTE ON PLAN FOR WALL TAG IS K3 BUT THE |
| | NORTH AND SOUTH WALL FACING THE RIGHT-OF-WAY DO NOT |
| | INDICATE WALL TYPES, NOR DOES THE PLAN INDICATE THE |
| | FLOOR/ CEILING ASSEMBLY RATING FOR THIS ROOM FOR THREE |
| | HRS. NOTE NO REDUCTION FOR FIRE SPRINKLERS SINCE THE |
| | VAULT IS NOT FIRE SPRINKLERED. NEC 450.42/ FPL |
| | REQUIREMENTS MAY BE HIGHER. ALSO NOTE VAULT DOORS ALSO |
| | REQUIRE A 3HR RATING. CONTACT FPL FOR FURTHER VAULT |
| | REQUIREMENTS. |
| | |
| | 14P) PLANS INDICATE NUMEROUS OPENINGS WITHIN THE FIRST |
| | STORY (ALLEYWAY) OF THE BUILDING, TABLE 704.8 ALLOWS |
| | 25% OPENINGS FOR FIRE SPRINKLERED BUILDINGS, PLEASE |
| | PROVIDE CALCULATIONS FOR THE FIRST FLOOR. |
| | |
| | 14R) THIS SHEET SCALES OUT TO HAVE THE ALLEYWAY AS A |
| | 16?-0? RIGHT-OF-WAY WHERE THE SURVEY INDICATES A 15?-0? |
| | RIGHT OF WAY, PLEASE CORRECT. DISCREPANCY. |
| | |
| | 15) SHEET A102: |
| | |
| | 15A) THIS COMMENT WILL BE FOR THE 2ND FLOOR THROUGH THE |
| | 6TH FLOOR STAIR ?A? INDICATES ONLY A ONE HOUR RATING |
| | (WALL TAG ?L?) BETWEEN THE STAIRWAY AND THE GUEST ROOMS |
| | DIRECTLY TO THE WEST 1019.1. |
| | |
| | 15B) ELEVATOR LOBBY 201, COMMON COMMENT 2ND FLOOR |
| | THROUGH THE 6TH FLOOR, WILL REQUIRE A 1 HOUR RATING. |
| | SEE 707.14.1 AND CODE COMMENTARY. WILL REQUIRE ONE HOUR |
| | FIRE RESISTANCE WITH OPENING 715.3. ELEVATOR # 3 IS |
| | MISSING THE ELEVATOR LOBBY TOTALLY. COMMON TO ALL |
| | FLOORS. |
| | |
| | 15C) SUITE 207 THE WALL COMMON WITH THE ELEVATOR LOBBY |
| | AND DATA ROOM 201DOES NOT HAVE A WALL TAG, WILL REQUIRE |
| | 1 HOUR RATING 708.1(2) AND SOUND RATING STC OF NOT LESS |
| | THAN 50 1207.2. COMMON TO ALL FLOORS. |
| | |
| | 15D) UNITS 207, 208 & 209 REMOVED THE EAST WALL LINE TO |
| | CREATE NEW BALCONIES. THE DISTANCE BACK TO THE NEW WALL |
| | LINE IS 5?-0? PLEASE REVIEW TABLE 704.8 FOR ALLOWABLE |
| | OPENINGS BETWEEN 3?-TO 5?-0? IS 15%, PLEASE PROVIDE THE |
| | PERCENTAGE OF WALL OPENINGS. |
| | 3RD-6TH FLOORS WALL REMOVED SET BACK IS 5?-1? ALLOWABLE |
| | OPENINGS IS 25% PLEASE PROVIDE CALCULATIONS. |
| | |
| | 15E) UNITS 207, 208 & 209 INDICATE THE WALL LINE 5?-0? |
| | FROM THE PROPERTY LINE. PLEASE SEE WALL TAG ?H? |
| | INDICATES UL DESIGN U-418, NOTE THIS ASSEMBLY IS RATED |
| | FROM THE INTERIOR SIDE ONLY. 704.5 INDICATES WHEN FIRE |
| | RESISTANCE RATINGS OF EXTERIOR WALLS WITH A FIRE |
| | SEPARATION DISTANCE OF 5 FEET OR LESS SHALL BE RATED |
| | FOR EXPOSURE TO FIRE FROM BOTH SIDES. PLEASE PROVIDE |
| | THE CORRECT ASSEMBLY. |
| | |
| | 15F) SHEET A00B WALL TAG ?H? IS INDICATED AS A 2 HOUR |
| | FIRE RATING, UL U-418, AS DEPICTED IN THE PLAN ONLY ONE |
| | LAYER OF 5/8? GYPSUM IS INDICATED, IN THE UL LISTING |
| | UNDER HEADING NUMBER FOUR FOR A 2 HR RATING THREE |
| | LAYERS OF ?? GYPSUM BOARD, PLEASE REVIEW THE SOUTH WALL |
| | OF ANNEX. |
| | |
| | 15G) SHEET A00B WALL TAG ?H? IS INDICATED AS A 2-HR |
| | EXTERIOR RATED WALL. WITHIN THE WALL ASSEMBLY THE PLAN |
| | CALLS FOR THE USE OF 5/8? EXTERIOR SHEATHING. PLEASE |
| | REVIEW SECTION 603.1.1(1.2) NONBEARING EXTERIOR WALLS |
| | WHERE NO FIRE RATING IS REQUIRED. TABLE 602 |
| | REQUIRES A FIRE RATING FOR A TYPE IB UP TO 30?-0? FROM |
| | THE PROPERTY LINE. |
| | |
| | 15H) THIS COMMENT WILL BE COMMON 2ND FLOOR THROUGH THE |
| | 6TH FLOOR. ROOM GUEST ROOM 226 LIGHT WELL AND GUEST |
| | ROOM 227. TO DO AN ACCURATE REVIEW ON THIS AREA |
| | ADDITIONAL INFORMATION WILL BE REQUIRED. PLANS DO NOT |
| | PROVIDE ANY DETAIL ON THE GARDEN, PLANS DO NOT INDICATE |
| | WALLS THAT WILL RETAIN SOILS, WATER RESISTANT, OR WATER |
| | PROOFING, DEPTH OF SOIL AND TYPE OF PLANTS WILL THERE |
| | BE ANY WATER FEATURES? FIRE LOADS ARE NOT KNOWN? |
| | THE PLANS DO CALL OUT FOR A 2 HOUR RATED WALL BUT THE |
| | WINDOW TYPE M AND M1 ARE SINGLE HUNG WINDOWS KEYED FOR |
| | MAINTENANCE USE ONLY. THERE IS NO MENTION OF 1 ? HOUR |
| | OPENING PROTECTION ON THE WINDOWS. |
| | |
| | UNTIL THE FIRE LOADS ARE KNOWN WE CAN NOT ACCURATELY |
| | REVIEW THIS AREA IT MAY BE CLASSIFIED ONLY AS A SHAFT |
| | OR IT MAY BE CLASSIFIED AS A ATRIUM AND MEET THE |
| | REQUIREMENTS OF 404. |
| | |
| | 15I) SUITE# 213 HAS A SHAFT LOCATED ON THE EAST SIDE OF |
| | THE ROOM, NO WALL TAG IS PROVIDED. |
| | SEE 707.4 SHAFT ENCLOSURES/ RATINGS. |
| | |
| | 15J) SOUTH WALL OF ANNEX WALL TAG ?H?(SHEET A00B) IS |
| | INDICATED AS THREE WALL TYPE FINISHES, THE FIRST IS |
| | INDICATED AS A BRICK VENEER WITH WALL TIES. THERE IS NO |
| | DETAIL INDICATING HOW THE BRICK ARE SUPPORTED. THIS |
| | SAME DETAIL ALSO INDICATES A MINIMUM 1 INCH AIR SPACE |
| | WITH THE WALL TIES MEANING A FULL BRICK VENEER NOT JUST |
| | A FACING OF BRICK. THE CUT SECTION THROUGH THIS SAME |
| | WALL DETAIL C OF A501 FORWARDS YOU TO ANOTHER DETAIL |
| | 1.1 OF A504 WHICH IS A THIN SET APPLICATION WITH JUST A |
| | FACING TREATMENT. PLEASE COORDINATE DETAILS SO A REVIEW |
| | OF THIS SECTION CAN BE COMPLETED. DISCREPANCY IN PLANS, |
| | INSUFFICIENT INFORMATION PLEASE COORDINATE PLANS. NOTE |
| | THERE IS NO STRUCTURAL DETAILS INDICATING A BRICK |
| | VENEER WITH WALL TIES. |
| | |
| | 15K) SAME DETAIL AS LISTED ABOVE WALL TAG ?H? (SHEET |
| | A00B) LIST A METAL PANEL SYSTEM AS |
| | |
| | |
| | 15I) ANNEX ADDITION PLAN SOUTH WALL TAG INDICATES WALL |
| | TAG ?H?, DETAIL ?C? SHEET 501 , AND DETAIL 1.2 A504 |
| | INDICATE THE USE OF 5/8? EXTERIOR GRADE PLYWOOD, PLEASE |
| | REVIEW USE OF COMBUSTIBLES IN TYPE I / II BUILDINGS. |
| | 603.1(1.2) ONLY ALLOWS THE EXTERIOR NONBEARING WALLS |
| | WHERE NO FIRE RATING IS REQUIRED. THIS WALL WILL |
| | REQUIRE A 2 HR RATING SEE TABLE 602. |
| | |
| | 15J) BOTH THE NORTH AND WEST WALL OF THE ANNEX WILL |
| | HAVE A SEPARATION DISTANCE GREATER THAN 30? SO FIRE |
| | RETARDANT TREATED 5/8 INCH PLYWOOD WOULD BE ALLOWED, |
| | PLEASE SEE TABLE 602 AND ADD NOTE TO PLAN. |
| | |
| | 15K) ANNEX PLANS NOTE EXTERIOR WALL TYPE ?E? BUT |
| | INDICATE THE USE OF METAL PANEL, IS THIS TO BE A MCM |
| | PANEL SYSTEM, PLEASE PROVIDE ADDITIONAL INFORMATION, |
| | MUST MEET ALL THE REQUIREMENTS OF SECTION 1407 FOR |
| | METAL COMPOSITE MATERIALS. |
| | |
| | 15L) THIS SAME WALL TYPE ?E? INDICATES THE USE OF |
| | CURTAIN WALL GLAZING PLEASE PROVIDE ADDITIONAL |
| | INFORMATION FOR THIS SYSTEM. 1609.6.2.2 & 704.13.1 |
| | VOIDS. |
| | |
| | 15M) ROOMS 229& 230 AS WELL AS 231 & 232 BOTH INDICATE |
| | WALL TYPE ?J? WHICH ONLY HAS A STC RATING OF 45 |
| | |
| | 16) SHEET A103 3RD -6TH FLOOR HAVE SIMILAR PROBLEMS AS |
| | THE 2ND FLOOR LIST DIRECTLY ABOVE. |
| | |
| | 17) SHEET A104 : |
| | |
| | 17A) STAIR ?A? ROOM 702 HAS A STORAGE AND ELEVATOR |
| | EQUIPMENT ROOM ,MECHANICAL ROOM 703 ENTER DIRECTLY INTO |
| | IT. |
| | 1019.1 THE MECHANICAL AND STORAGE ROOM SHOULD HAVE THE |
| | DOORWAY ON THE POOL DECK NOT INTO THE VERTICAL STAIR |
| | TOWER, 1019.1. |
| | |
| | 17B) PLANS CALL OUT FOR A VERTICAL LIFT, PLEASE PROVIDE |
| | DOCUMENTATION WITH 11-4.11.2. |
| | |
| | 17C) THE ROOF PLAN DOES NOT PROVIDE ENOUGH INFORMATION |
| | AS TO WHERE GUARDS AND HANDRAILS ARE LOCATED ON THE |
| | ELEVATED POOL DECK SECTION AND STAIRS AS TO LOCATION, |
| | MATERIAL CONSTRUCTED FROM AND HEIGHT. 1009.11, 1012.1, |
| | 1012.2 & 1012.3. |
| | |
| | 17D) THE PLAN INDICATES THE USE OF A 30?-0? SECTION OF |
| | GLAZED GUARD RAIL PLEASE PROVIDE INFORMATION FOR |
| | 1607.7, 2407.1, 2407.1.1, & 2407.1.2. |
| | |
| | 17E) PLANS INDICATE A ADA LIFT INTO THE POOL, PLEASE |
| | PROVIDE MANUFACTURES? SPECS. 106.1.2 ADDITIONAL |
| | INFORMATION REQUIRED & 424.1.2.5.6. |
| | |
| | 17F) THE ROOF OVER THE STAIR A, RESTROOMS AND |
| | MECHANICAL ROOM INDICATE A ROOF DRAIN BUT NO SECONDARY |
| | OVER FLOW OR SCUPPER. 1503.4.3. |
| | |
| | 17G) THE POOL DECK AND LOWER ROOF DECK ALSO ARE MISSING |
| | THE OVER FLOW ROOF DRAINS AND OR SCUPPERS 1503.4.3. |
| | |
| | 17H) PLEASE PROVIDE A LARGER SECTION OF THE MEN?S AND |
| | WOMEN?S RESTROOMS, |
| | |
| | 17H)1) BOTH DOORS 707 AND 708 APPEAR TO SWING INTO THE |
| | CLEAR FLOOR SPACE REQUIRED FOR ACCESSIBLE PLUMBING |
| | FIXTURES 11-4.22.3. |
| | |
| | 17H)2) DOOR 207 AND 208 PLEASE REVIEW SECTION 11-4.13.7 |
| | DOORS IN SERIES. |
| | |
| | 17H)3) DOOR 703 IT APPEARS IS MISSING THE REQUIRED 18? |
| | AT THE LATCH SIDE OF THE DOOR. |
| | 11-4.13.6. |
| | |
| | 17I) IT APPEARS IN BOTH VERTICAL EXITS THERE IS A STEP |
| | DIRECTLY INSIDE THE BUILDING WITHOUT A LEVEL FLOOR WITH |
| | THE EXTERIOR OF THE BUILDING, 1008.1.4. |
| | |
| | 17J) ROOM 703 THE ELEVATOR EQUIPMENT ROOM DOES NOT |
| | INDICATE ANY VENTILATION, WILL NEED TO COMPLY WITH |
| | 3004.1 & 3004.2. |
| | |
| | 17K) JUST TO THE RIGHT OF THE VERTICAL EXIT ?B? THERE |
| | IS A ROOM WITH NO IDENTIFICATION JUST DOOR NUMBER 710, |
| | PLEASE PROVIDE USAGE? 106.1.2. ADDITIONAL INFORMATION |
| | REQUIRED. |
| | |
| | 17L) NOTE: POOL GATES AND FENCING REQUIREMENTS |
| | DEPARTMENT OF HEALTH RULE 64E-9 FLORIDA ADMINISTRATIVE |
| | CODE AND CHAPTER 514 FLORIDA STATUTES. |
| | |
| | 18) SMOKE CONTROL SYSTEMS: UNDER THE EXISTING BUILDING |
| | CODE FOR THE BASE BUILDING THE CODE DOES NOT ADDRESS |
| | THIS, THE FLORIDA BUILDING CODE IS BASED OFF OF THE IBC |
| | WHERE SMOKE CONTROL IN HIGH RISES IS NOT A REQUIREMENT, |
| | SO IT HAS NEVER BEEN INTRODUCED INTO THE EXISTING |
| | BUILDING CODE. |
| | ADDITIONS UNDER THE EXISTING BUILDING CODE DOES REQUIRE |
| | SMOKE CONTROL PLEASE SEE 902.3 OF THE EXISTING BUILDING |
| | CODE. EXISTING ALLOWABLE AREAS INCREASED BY ADDITIONS |
| | SHALL COMPLY WITH CHAPTER 9 OF THE FLORIDA BUILDING |
| | CODE, BUILDING. PLEASE REVIEW 909.16 FIRE-FIGHTER?S |
| | SMOKE CONTROL PANEL. 909.16. 1-3. |
| | |
| | 19) SHEET A105: |
| | |
| | 19A) PLANS INDICATE A 3? ROLL DECK, PLEASE PROVIDE |
| | ADDITIONAL INFORMATION AS TO THIS PRODUCT. 106.1.2. |
| | ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 19B) DETAIL B INDICATES THE USE OF MCM PANELS |
| | (ALUMINUM) PLEASE PROVIDE INFORMATION ON THIS PRODUCT |
| | AS FAR AS FIRE RESISTANCE RATINGS AND WIND PRESSURES. |
| | 1407 & 1609.6. |
| | |
| | 19C) PLANS APPEAR WITH A HATCH LINE BUT IT IS NOT CLEAR |
| | WHAT THIS IS FOR, MECHANICAL PLANS INDICATE ROOF TOP |
| | MECHANICAL EQUIPMENT, IS THIS A SCREEN FOR THE |
| | MECHANICAL EQUIPMENT? |
| | 106.1.2 ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 19D) ROOF TOP EQUIPMENT; SHALL BE COVERED UNDER THIS |
| | REVIEW AS WELL AS MECHANICAL FOR THE RESISTANCE OF THE |
| | EQUIPMENT AND CASING TO RESIST WIND. PLEASE SHOW |
| | COMPLIANCE WITH |
| | MECHANICAL- 301.13 WIND RESISTANCE. MECHANICAL |
| | EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO |
| | WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND |
| | PRESSURES ON THE EQUIPMENT AND THE SUPPORTS AS |
| | DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING |
| | CODE, BUILDING. THIS MAY BE ACCOMPLISHED BY DESIGN OR |
| | BY APPLICATION OF SECTION 301.13.1. ROOF-MOUNTED |
| | MECHANICAL UNITS AND SUPPORTS SHALL BE SECURED TO THE |
| | STRUCTURE. THE USE OF WOOD ?SLEEPERS? SHALL NOT BE |
| | PERMITTED. PLEASE SHOW COMPLIANCE. |
| | |
| | 19E) ROOF HATCH PLEASE REVIEW REQUIREMENTS FOR STAIRS |
| | TO THE ROOF WHEN BUILDINGS ARE 4 OR MORE STORIES.1009. |
| | 12. |
| | |
| | 20) SHEET A106 DETAIL# 4 NOTE: ROOF DRAINS ARE NOT IN |
| | THE MIDDLE OF THE ROOF CREATING LONGER RUNS IN SLOPED |
| | INSULATION. WHERE EVER THE ROOF DRAIN IS LOCATED THIS |
| | IS THE MINIMUM THICKNESS OF INSULATION, FOR INSTANCE IF |
| | YOUR ENERGY REPORT INDICATES A R-19 THIS IS THE MINIMUM |
| | THICKNESS OF INSULATION AND FROM THERE THE THICKNESS IS |
| | INCREASED. 13-404.1.ABCD.1 AND FBC INFORMAL |
| | INTERPRETATION REPORT#3731 & 3746. |
| | |
| | 21) SHEET A200 LOWER CEILING LEVEL THE LAUNDRY DRYERS |
| | ARE GANGED TOGETHER NO ARCHITECTURAL PLANS OR |
| | MECHANICAL PLANS INDICATE A TERMINATION POINT? 106.1.2 |
| | ADDITIONAL INFORMATION REQUIRED. DIRECTLY TO THE WEST |
| | IS THE EASEMENT ALONG THE WEST WALL! |
| | |
| | 22) SHEET A201 DETAIL 02 SOFFIT DETAIL INDICATES THE |
| | USE OF UNISTRAT AND THREADED RODS, ON INFORMATION IS |
| | PROVIDED AS TO ANCHORAGE OF THE UNISTRUCT TO THE |
| | STRUCTURE ABOVE, CENTER TO CENTER OF THE UNISTRUCT, |
| | THICKNESS OF THE THREADED RODS AND SPACING, NOR THE |
| | HORIZONTAL MEMBER BETWEEN THE BOTTOM UNISTRUCT AND WOOD |
| | VENEER CEILING PANEL OR HOW WOOD CEILING PANELS WILL BE |
| | FASTENED. 106.1.2. ADDITIONAL INFORMATION REQUIRED AND |
| | 803.4.2 SET OUT CONSTRUCTION AND REQUIREMENTS FOR FIRE |
| | TREATED RESISTANT FURRING OR BACKING. |
| | |
| | 23) SHEET A202 DETAIL 02 INDICATES STRUCTURAL MEMBERS |
| | ARE TO HAVE A 2HR RATING TABLE 601 BUT NO UL ASSEMBLY |
| | WAS PROVIDED. PLANS ALSO INDICATE OR SPRAY ASSEMBLY. |
| | PLEASE IDENTIFY |
| | WHICH SYSTEM WILL BE INSTALLED WITHIN THE STRUCTURE AND |
| | PROVIDE ASSEMBLY OR PRODUCT INFORMATION. INFORMATIONAL |
| | 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 DRAWINGS & |
| | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO |
| | THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR |
| | IN PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED |
| | AS A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION |
| | DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE |
| | LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND |
| | SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS |
| | OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND |
| | REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 24) SHEET A303 DETAIL 03 IS MISSING COMPLIANCE WITH |
| | FIGURE 11-19?(D) AND 11-4.4. |
| | |
| | 25) SHEET A303 DETAIL 3 THE HANDRAIL CAN NOT HAVE A |
| | PERIMETER GREATER THAN 6.25 INCHES, |
| | PLANS INDICATE A 6.5 INCHES. 1009.11.3. |
| | |
| | 26) SHEET A305 INDICATES WOOD PANELING ON ?? PLYWOOD |
| | BACKER. PLEASE REVIEW 803.4.2 SET OUT CONSTRUCTION AND |
| | REQUIREMENTS FOR FIRE TREATED RESISTANT FURRING OR |
| | BACKING. |
| | |
| | 27) SHEET A309 DETAIL F BREAK ROOM SINK THE CABINET HAS |
| | DOORS MAKING IT IMPOSSIBLE FOR A FRONT APPROACH. SINKS: |
| | 11-4.24.2 SINKS, HEIGHT. SINKS SHALL BE MOUNTED WITH |
| | THE COUNTER NO HIGHER THAN 34" ABOVE THE FINISH FLOOR. |
| | 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH 30" |
| | WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH SINKS. |
| | 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT |
| | LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM) |
| | COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN |
| | FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR |
| | FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL |
| | EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE |
| | SINK. |
| | |
| | 28) 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE |
| | DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE |
| | PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS |
| | SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF |
| | GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE |
| | ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES |
| | POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH |
| | AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS |
| | OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE |
| | TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1. |
| | GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE |
| | SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST. |
| | 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M) |
| | ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL |
| | MISSILE TEST. |
| | |
| | 29) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, |
| | PROVIDE 2 COPIES, |
| | 3 IF THRESHOLD OR RESIDENT INSPECTOR OF PRODUCT TESTING |
| | REPORTS, MISSING REPORTS ARE AS FOLLOWS: |
| | |
| | A) FIXED GLAZING |
| | B) STOREFRONT |
| | C) CURTAIN WALL |
| | D) MULLIONS |
| | E) EXTERIOR STOREFRONT |
| | F) EXTERIOR METAL DOORS ? INSULATED |
| | G) ROLLING OVERHEAD DOOR |
| | H) PANEL WALL SYSTEMS- SOFFITS, SIDING PRODEMA WOOD |
| | PANEL SYSTEMS, |
| | ALPOLIC METAL PANEL SYSTEMS, & MCM SYSTEM |
| | I) WALL LOUVERS |
| | J) SKYLIGHTS |
| | K) ROOFING ASSEMBLIES |
| | M) PRE-ENGINEERED A/C STANDS |
| | 30) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE |
| | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT |
| | IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT |
| | HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR |
| | LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE |
| | 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 31) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 32) A702 DETAIL H SMOKE DRAFT CURTAIN PLEASE PROVIDE |
| | WHERE THIS DETAIL IS BEING INSTALLED? |
| | |
| | 33) S-1 DESIGN NOTES MINIMUM LIVE LOADS PLEASE REVIEW |
| | THE FOLLOWING: |
| | 33A) FLOORS INDICATES 40 PSF PLEASE PROVIDE WHAT |
| | OCCUPANCY TYPE |
| | 33B) CORRIDORS ARE INDICATED AT 40 PSF THIS IS WITHIN |
| | HABITABLE AREAS |
| | 33C) BALCONIES ARE INDICATED AT 60 PSF, EXTERIOR |
| | BALCONIES FOR 1 AND 2 FAMILIES CORRECT TO |
| | 100 PSF |
| | 33D) CORRIDORS 100 PSF |
| | 33E) NOT MENTION IN PLANS DINING ROOMS AND RESTRAINT |
| | 100PSF |
| | TABLE 1607.1 |
| | |
| | 34) S-1 DOES NOT PROVIDE THE CORRECT WIND SPEED, PLEASE |
| | SEE FIGURE 1609, WEST PALM BEACH IS LOCATED WITHIN A |
| | 140 MPH 3 SECOND GUST. WIND PRESSURES WILL CHANGE WITH |
| | THE |
| | GREATER WIND SPEED. |
| | |
| | 35) INPUT DATA REPORT: |
| | 35A) EXTERIOR DOORS ARE MISSING FROM THE INPUT DATA |
| | REPORT. |
| | 35B) SKYLIGHT IS MISSING INFORMATION FROM THE INPUT |
| | DATA REPORT |
| | 35C) FLOORS IS LEFT BLANK FROM THE INPUT DATA REPORT |
| | |
| | 36) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |