| 2008-11-18 09:47:00 | ** FAILED REVIEW ** |
| | |
| | |
| | 1) NOTE: PLAN SUBMITTED NEEDS TO CONTAIN A MINIMUM 1/8 |
| | INCH SCALE AND MORE DETAIL FOR SCOPE OF WORK. PLEASE BE |
| | SURE TO ADD A TITLE BLOCK FOR ADDRESS AND LOCATION OF |
| | WORK. |
| | PLEASE PROVIDE THE PRINTED NAME AND SIGNATURE OF PERSON |
| | RESPONSIBLE FOR PLANS WHEN MEETING EXCEPTIONS OF FS |
| | 471.003. |
| | FBC 105.1, 106.1.1, 106.1.2 |
| | NO SYMBOL LIST. |
| | NO WIRING DETAIL FOR ANY WALL PENETRATIONS. 300.21 |
| | NEC 2005 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |