 |
Plan Review Details - Permit 08110248
| Plan Review Stops For Permit 08110248 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2009-04-07 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2009-04-07 |
Time |
10:27 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2009-04-07 |
Time |
10:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2009-01-30 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2009-01-30 |
Time |
16:07 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2009-01-30 |
Time |
16:07 |
Sent To |
|
|
| Notes |
| 2009-01-30 13:43:52 | BUILDING PLAN REVIEW | | | PERMIT: 08110248 | | | ADD: 801 S. OLIVE AVE #110 &111 | | | CONT: T.M. MOTTLEY CONST. | | | TEL: (561)502-1986 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1-30-09 | | | REVIEW: 2ND | | | ACTION: DENIED | | | | | | 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2) **2ND REVIEW SECOND FLOOR LAYOUT WAS NOT SHOWN** | | | SUBMIT AN EXISTING AND A PROPOSED FLOOR AND ELEVATION | | | PLAN OF BOTH UNITS INDICATING THE PROPOSED WORK. THE | | | DRAWINGS NEED TO SHOW THE ENTIRE LAYOUT OF BOTH UNITS. | | | SHOW IN DETAIL HOW THE STRUCTURAL INTEGRITY OF THE | | | CONCRETE WALL WILL BE MAINTAINED ONCE THE PASS THROUGH | | | IS CREATED. PROVIDE ELEVATION DRAWINGS. ADDITIONAL | | | INFORMATION IS REQUIRED 106.1.2* | | | | | | 3) **2ND REVIEW** A 'UNITY OF TITLE' SHALL BE RECORDED | | | AT THE COUNTY COURTHOUSE. SUBMIT A COPY OF THE RECORDED | | | 'UNITY OF TITLE' DOCUMENT SO THAT FBC TABLE 601 | | | BOUNDARY LINE REQUIREMENTS MAY BE DEEMED NOT | | | APPLICABLE. | | | | | | 4) **2ND REVIEW** THE DRAWINGS INDICATE REMOVING THE | | | KITCHEN IN BOTH DWELLING UNITS WHICH MEANS THERE WILL | | | BE A CHANGE OF OCCUPANCY OF EACH SPACE. THE DRAWINGS | | | SHOW TWO SETS OF SPIRAL STAIRWAYS, DO THESE STAIRWAYS | | | LEAD TO ADDITIONAL OFFICE SPACE ABOVE? IS THE SPACE | | | ABOVE THE FIRST LEVEL A MEZZANINE OR A SECOND FLOOR, | | | AND WILL THERE BE AN OPENING IN THE PARTITION WALL TO | | | SIMILAR TO THE ONE ON THE FIRST FLOOR CREATING ONE | | | UNIT? PROVIDE PLANS SHOWING THE LAYOUT OF THE SECOND | | | FLOOR IN RELATION THE NEW SPACE BEING CREATED. | | | ADDITIONAL INFORMATION IS REQUIRED. 106.1.2* | | | | | | 5) OK | | | | | | 6) **2ND REVIEW** 106.1.1 INFORMATION ON CONSTRUCTION | | | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF | | | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE & | | | EXTENT OF THE WORK PROPOSED & SHOW IN DETAIL THAT IT | | | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | | RELEVANT LAWS, ORDINANCES, AND RULES AND REGULATIONS AS | | | DETERMINED BY THE BUILDING OFFICIAL. PROVIDE THE FLOOR | | | PLAN FOR THE SECOND FLOOR, INDICATING THE USE OF EACH | | | ROOM. | | | | | | 7) **2ND REVIEW**. THE CLAIMED VALUATION ON THE PERMIT | | | APPLICATION IS LOW. FOR PERMITTING PURPOSES, VALUATION | | | OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT | | | VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, | | | MECHANICAL, INTERIOR FINISH, ARCHITECTURAL AND DESIGN | | | FEES, MARKETING COSTS, OVERHEAD AND PROFIT EXCLUDING | | | LAND VALUE. OUR VALUATION REFERENCE IS ICC (BVD) | | | MARSHALL- SWIFT AND MEANS COST ANALYSIS SERVICES PER | | | 108.3* | | | | | | 8) OK | | | | | | 9) DOES THE EXISTING ELEVATOR PROVIDE VERTICAL | | | ACCESSIBILITY TO THE SECOND FLOOR? IF SO, PLEASE SHOW | | | COMPLIANCE. VERTICAL ACCESSIBILITY SHALL BE PROVIDED TO | | | ALL LEVELS ABOVE AND BELOW THE OCCUPIABLE GRADE LEVEL, | | | REGARDLESS OF WHETHER THE CODE REQUIRES AND ELEVATOR TO | | | BE INSTALLED IN SUCH BUILDINGS. 11-4.1.3(5) | | | | | | 10) FBC (EXISTING) 806.1 ACCESSIBILITY IN PORTIONS OF | | | BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY | | | CLASSIFICATION SHALL COMPLY WITH CHAPTER 11 OF THE | | | FLORIDA BUILDING CODE. | | | BOTH BATHROOMS FAIL TO SHOW THE CLEAR FLOOR SPACE/ GRAB | | | BARS/ FLUSH CONTROLS ETC. SEE 11-4.16 AND 11-4.19. SHOW | | | COMPLIANCE. | | | | | | 11) THE PLANS SUBMITTED ARE MISSING THE SEAL/ | | | SIGNATURE/DATE. ALL FINAL CONSTRUCTION DOCUMENTS | | | INCLUDING DRAWINGS, PLANS, SPECIFICATIONS, OR REPORTS | | | PREPARED OR ISSUED BY THE REGISTERED ARCHITECT AND | | | BEING FILED FOR PUBLIC RECORD SHALL BEAR THE SIGNATURE | | | AND SEAL OF THE REGISTERED ARCHITECT WHO PREPARED OR | | | APPROVED THE DOCUMENT AND THE DATE ON WHICH THEY WERE | | | SEALED. THE SIGNATURE, DATE AND SEAL SHALL BE EVIDENCE | | | OF THE AUTHENTICITY OF THAT TO WHICH THEY ARE AFFIXED | | | FLORIDA STATUTES 481.221 | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | PHONE (561)805-6726 | | | FAX (561) 805-6676 | | | [email protected] | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-11-25 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-11-25 |
Time |
07:59 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-11-25 |
Time |
07:59 |
Sent To |
|
|
| Notes |
| 2008-11-25 07:59:06 | | | | BUILDING PLAN REVIEW | | | PERMIT: 08110248 | | | ADD: 801 S. OLIVE AVE #110 &111 | | | CONT: T.M. MOTTLEY CONST. | | | TEL: (561)502-1986 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 11-25-08 | | | REVIEW: 1ST | | | ACTION: DENIED | | | | | | 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2) SUBMIT AN EXISTING AND A PROPOSED FLOOR AND | | | ELEVATION PLAN OF BOTH UNITS INDICATING THE PROPOSED | | | WORK. THE DRAWINGS NEED TO SHOW THE ENTIRE LAYOUT OF | | | BOTH UNITS. SHOW IN DETAIL HOW THE STRUCTURAL INTEGRITY | | | OF THE CONCRETE WALL WILL BE MAINTAINED ONCE THE PASS | | | THROUGH IS CREATED. PROVIDE ELEVATION DRAWINGS. | | | ADDITIONAL INFORMATION IS REQUIRED 106.1.2* | | | | | | 3) A 'UNITY OF TITLE' SHALL BE RECORDED AT THE COUNTY | | | COURTHOUSE. SUBMIT A COPY OF THE RECORDED 'UNITY OF | | | TITLE' DOCUMENT SO THAT FBC TABLE 601 BOUNDARY LINE | | | REQUIREMENTS MAY BE DEEMED NOT APPLICABLE. | | | | | | 4) THE DRAWINGS INDICATE REMOVING THE KITCHEN IN BOTH | | | DWELLING UNITS WHICH MEANS THERE WILL BE A CHANGE OF | | | OCCUPANCY OF EACH SPACE. | | | | | | 5) STATE CLEARLY ON THE PLANS IF THERE WILL BE A CHANGE | | | OF OCCUPANCY TO THE SPACE, IF THERE WILL BE A CHANGE OF | | | OCCUPANCY, INDICATE THE TYPE OF OCCUPANCY PER FBC | | | CHAPTER 3 ON THE PLANS. | | | | | | 6) (2004 FBC) 106.1.1 INFORMATION ON CONSTRUCTION | | | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF | | | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE & | | | EXTENT OF THE WORK PROPOSED & SHOW IN DETAIL THAT IT | | | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | | RELEVANT LAWS, ORDINANCES, AND RULES AND REGULATIONS AS | | | DETERMINED BY THE BUILDING OFFICIAL. | | | | | | 7) THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS | | | LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS | | | AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE | | | STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, INTERIOR | | | FINISH, ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, | | | OVERHEAD AND PROFIT EXCLUDING LAND VALUE. OUR VALUATION | | | REFERENCE IS ICC (BVD) MARSHALL- SWIFT AND MEANS COST | | | ANALYSIS SERVICES PER 108.3* | | | | | | 8) 2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN | | | OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF | | | ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF | | | THIS CODE. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected] | | | | | 2008-11-14 13:19:40 | TO "BOB"#16 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2009-04-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-04-10 |
Time |
12:12 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-04-10 |
Time |
12:12 |
Sent To |
PC |
|
| Notes |
| 2009-04-10 12:21:10 | NO GROSS ERRORS ON LPD. | | | PANEL SCHEDULES VIF, |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2009-02-02 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-02-02 |
Time |
15:22 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-02-02 |
Time |
15:22 |
Sent To |
|
|
| Notes |
| 2009-02-02 15:22:54 | ** DENIED 2ND REVIEW ** | | | | | | 1) NOTE: *** SAME EXACT NOTES FROM PREVIOUS REVIEW. NO | | | CHANGES WERE MADE OR CORRECTIONS MADE TO PLANS. THIS IS | | | A CHANGE IN OCCUPANCY TO LOCATION. PLEASE SEE FBC | | | CHAPTER 3, 13 FOR CHANGES IN OCCUPANCY. PLEASE SEE FBC | | | EXISTING BUILDING CODE CHAPTER 8 FOR CHANGES IN | | | OCCUPANCY. | | | PLEASE SEE NFPA-72, 70, 101 ALSO FOR MINIMUM | | | REQUIREMENTS. | | | PLEASE SUBMIT COMPLETE ELECTRICAL PLANS FOR ALL NEW AS | | | THIS IS NOW A COMMERCIAL OCCUPANCY AND ALL PLANS NEED | | | TO SHOW MINIMUM COMPLIANCE WITH THIS TYPE OF OCCUPANCY. | | | LOAD CALCULATIONS, NEC 220 | | | CIRCUITING, NEC 240.4,310.16,408.4 ETC | | | ENERGY EFFICIENCY, CHAPTER 13, LIGHTING CONTROLS | | | 13-415.1.ABC.1 | | | PANELS, 408.4, | | | PERFORMANCE CALCULATIONS, 13-415.2 | | | NOTES ARE BROAD AS NO INFORMATION WAS SHOWN. | | | ** MAY NOT QUOTE CODES FOR MINIMUM DESIGN IN LIEU OF | | | SPECIFIC CODE COMPLIANCE DETAILS. | | | | | | | | | ** IT IS NOTED ONCE AGAIN THAT AS THERE ARE SEVERAL | | | UNKNOWN FACTORS AND MISSING INFORMATION, THERE MAY VERY | | | WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH CAN | | | NOT BE MADE AT THIS TIME. | | | | | | 2) NOTE: PLANS WHICH WERE BROUGHT BACK IN AND SUBMITTED | | | ARE NOT SIGNED, DATED OR SEALED BY THE DESIGN | | | PROFESSIONAL OF RECORD. | | | SEE FS 481.221 | | | | | | 3) NOTE: VALUE FOR SCOPE OF WORK INCREASED HOWEVER WORK | | | AS NOTED IS STILL LOW AND UNKNOWN WORK IS NOT INCLUDED. | | | FBC 108.3 | | | | | | | | | ** IMPORTANT ** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED | | | INTO TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2008-11-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-11-19 |
Time |
09:35 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-11-19 |
Time |
09:35 |
Sent To |
|
|
| Notes |
| 2008-11-19 09:36:00 | ** FAILED REVIEW ** | | | | | | ** | | | | | | | | | 1) NOTE: PLANS SHOW REMOVAL OF KITCHENS FROM BOTH UNITS | | | WHICH ARE DWELLING UNITS. WHAT WILL THE NEW OCCUPANCY | | | BE? FBC 303.1 | | | THE WALLS AND OTHER LOCATIONS ARE BEING FINISHED TO AND | | | END USE HOWEVER PLEASE SEE SECTION ABOVE AS THE | | | OCCUPANCY WHICH WILL BE CHANGING FROM DWELLING TO | | | OTHER. | | | PLEASE SEE FBC CHAPTER 13 FOR ANY NEW BEING INSTALLED. | | | PLEASE SEE FBC EXISTING BUILDING CODE CHAPTER 8 FOR USE | | | AND CLASSIFICATION TO POSSIBLE HIGHER HAZARD. | | | | | | 2) NOTE: PLANS WILL BE REQUIRED TO SHOW THE FOLLOWING | | | CODES: | | | 2002 NFPA_72 | | | 2003 NFPA-101 | | | 2005 NFPA-70 | | | | | | 3) NOTE: PLEASE SEE CHAPTER 9 OF THE FBC FOR FIRE ALARM | | | DEVICES ALONG WITH CHAPTER 11, SPECIFICALLY | | | 11-4.28.1,.2 AND .3. | | | | | | 4) NOTE: THE APPLIED VALUATION SHALL INCLUDE ALL LABOR, | | | MATERIALS, EQUIPMENT, DESIGN COST ETC EVEN IF ANY OF | | | THESE ITEMS ARE OWNER SUPPLIED. | | | THE APPLIED VALUE OF $2,300.00 IS LOW. | | | FBC 108.3 | | | | | | 5) NOTE: IT IS IMPORTANT TO KNOW AS THERE ARE SEVERAL | | | UNKNOWN FACTORS AT THIS TIME THERE MAY VERY WELL BE NEW | | | COMMENTS ON THE FOLLOWING REVIEW WHICH COULD NOT BE | | | MADE AT THIS TIME. | | | PLEASE CALL TO GO OVER ANY ITEMS OR QUESTIONS WHICH MAY | | | HELP ALLEVIATE ANY DELAY OF THE PROJECT. | | | | | | | | | | | | **IMPORTANT** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED | | | INTO TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2009-05-27 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-05-27 |
Time |
15:21 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-05-27 |
Time |
14:56 |
Sent To |
|
|
| Notes |
| 2009-05-27 15:20:51 | *****REVISION, DATED MAY 2009, APPROVED | | | | | | | | | THE REVISED/NEWLY ADDED SHEET F-1 WAS STAMPED, | | | INITIALED, AND DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2009-04-08 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-04-08 |
Time |
15:27 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-04-08 |
Time |
15:01 |
Sent To |
|
|
| Notes |
| 2009-04-08 15:27:05 | *****APPROVED***** | | | | | | | | | THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE | | | BEEN ADDRESSED; PLAN SHEETS A-1, E-1, AND LIFE SAFETY | | | (1ST FLOOR) & LIFE SAFETY (MEZZANINE) WERE STAMPED, | | | INITIALED, AND DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2009-02-05 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2009-02-05 |
Time |
11:12 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2009-02-05 |
Time |
11:12 |
Sent To |
|
|
| Notes |
| 2009-02-05 11:14:55 | ***DENIED*** | | | | | | 1) OK | | | | | | 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY | | | WITH NFPA 241. | | | | | | 3) WILL WORK IMPACT EXISTING FIRE SPRINKLER AND FIRE | | | ALARM SYSTEMS? | | | | | | 4) SEPARATE SHOP DARWINGS AND PERMITS REQUIRED FOR FIRE | | | SPRINKLER AND FIRE ALARM REMODEL. | | | | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2008-11-25 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-11-25 |
Time |
15:45 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-11-25 |
Time |
15:45 |
Sent To |
|
|
| Notes |
| 2008-11-25 15:57:23 | ***DENIED*** | | | | | | 1) IN ADDITION TO APPLICABLE BUILDING CODES, LIFE | | | SAFETY SHALL COMPLY WITH NFPA 101, 2003. | | | | | | 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY | | | WITH NFPA 241. | | | | | | 3) WILL WORK IMPACT EXISTING FIRE SPRINKLER AND FIRE | | | ALARM SYSTEMS? | | | | | | 4) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE | | | SPRINKLER AND FIRE ALARM REMODEL. | | | | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2009-03-30 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2009-03-30 |
Time |
09:55 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2009-03-30 |
Time |
09:55 |
Sent To |
|
|
| Notes |
| 2009-03-30 10:27:55 | TO IN-BOX "B11" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2009-01-26 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2009-01-26 |
Time |
15:56 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2009-01-26 |
Time |
15:56 |
Sent To |
|
|
| Notes |
| 2009-01-26 15:58:58 | TO "BOB"#1 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-12-01 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-12-01 |
Time |
15:28 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-11-14 |
Time |
13:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2009-02-04 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2009-02-04 |
Time |
13:12 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2009-02-04 |
Time |
13:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2009-04-06 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-04-06 |
Time |
10:07 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-04-06 |
Time |
10:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2009-02-05 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-02-05 |
Time |
08:53 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-02-05 |
Time |
08:53 |
Sent To |
|
|
| Notes |
| 2009-02-05 09:35:19 | DENIED | | | REFERENCE: | | | FBC-2004 PLUMBING | | | FBC-2004 EXISTING BUILDING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | MUNICIPAL CODE CITY WPB | | | | | | 2ND REVIEW: | | | | | | ****FROM PREVIOUS REVIEW: | | | | | | 1. OK | | | | | | 2, APPLICATION INDICATES NO CHANGE OF OCCUPANCY, | | | THEREFORE THE OCCUPANCY IS R-2 AND AS SUCH THE | | | OCCUPANCY REQUIRES A KITCHEN SINK PER TABLE 403.1. ALSO | | | REQUIRED IS PROVISIONS FOR COOKING, SANITATION AND | | | EATING PER CITY WPB MUNICIPAL CODE. PLEASE INDICATE | | | COMPLIANCE. | | | ****PLANS NOW INDICATE A CHANGE OF OCCUPANCY FROM | | | RESIDENTIAL TO BUSINESS. PER SECTION 806.1 OF THE | | | EXISTING BUILDING CODE, "ACCESSIBILITY IN PORTIONS OF | | | BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY | | | CLASSIFICATION SHALL COMPLY WITH CHAPTER 11 OF THE | | | FLORIDA BUILDING CODE, BUILDING". PLEASE SHOW | | | COMPLIANCE WITH SECTIONS 11-4.15, 11-4.16, 11-4.19 & | | | 11-4.22 WITH ALL SUBSECTIONS. -- APPLICATION FOR PERMIT | | | STILL INDICATES NO CHANGE OF OCCUPANCY. PLEASE CORRECT | | | APPLICATION TO REFLECT THE WORK BEING DONE. | | | | | | 3. OK | | | | | | 4. SUBMIT A SANITARY RISER DIAGRAM SHOWING COMPLIANCE | | | WITH SECTION 704.5. DEAD ENDS ARE PROHIBITED. SHOW THE | | | LOCATION OF THE STACKS FOR EACH KITCHEN SINK BEING | | | DEMO'D. SECTION 106.3.5.1.3. | | | ****NO RESPONSE, COMMENT NOT ADDRESSED. SHOW THE | | | SANITARY PIPING TO THE REQUIRED DRINKING FOUNTAIN ON | | | THE SANITARY ISOMETRIC RISER DIAGRAM. (TABLE 403.1). | | | SECTION 106.3.5.1.3(1)(4)(6)(13). | | | | | | 5. THE VALUATION OF THE JOB APPEARS TO BE LOW. PLEASE | | | CHECK THE LABOR, MATERIALS, EQUIPMENT & DESIGN COST AND | | | MAKE SURE ALL IS INCLUDED. SECTION 108.3. | | | ****NO RESPONSE, COMMENT NOT ADDRESSED. | | | | | | **********NEW COMMENT********** | | | | | | 1B. PER TABLE 403.1 A DRINKING FOUNTAIN IS REQUIRED. | | | PLEASE INDICATE THE LOCATION AND SUBMIT A DETAIL | | | SHOWING COMPLIANCE WITH SECTION 11-4.15 WITH ALL | | | SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A) | | | PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR | | | STOOPING. | | | | | | 2B. SUBMIT A WATER ISOMETRIC RISER DIAGRAM SHOWING THE | | | CONNECTION, PIPING AND VALVE, ETC. FOR THE REQUIRED | | | DRINKING FOUNTAIN. SECTION 106.3.5.1.3(1)(3)(10)(13). | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | ****NO RESPONSE TO TRANSMITTAL LETTER. LETTER NOT | | | SUBMITTED. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2008-11-25 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-11-25 |
Time |
14:50 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-11-25 |
Time |
14:50 |
Sent To |
|
|
| Notes |
| 2008-11-25 15:06:17 | DENIED | | | REFERENCE: | | | FBC-2004 PLUMBING | | | FBC-2004 EXISTING BUILDING | | | FBC-2004 CHAPTER 1 | | | MUNICIPAL CODE CITY WPB | | | | | | 1. PLEASE INDICATE THE LEVEL OF ALTERATION AS REQUIRED | | | IN CHAPTER 3 OF THE EXISTING BUILDING CODE. | | | | | | 2, APPLICATION INDICATES NO CHANGE OF OCCUPANCY, | | | THEREFORE THE OCCUPANCY IS R-2 AND AS SUCH THE | | | OCCUPANCY REQUIRES A KITCHEN SINK PER TABLE 403.1. ALSO | | | REQUIRED IS PROVISIONS FOR COOKING, SANITATION AND | | | EATING PER CITY WPB MUNICIPAL CODE. PLEASE INDICATE | | | COMPLIANCE. | | | | | | 3. PLEASE SUBMIT A DEMO PLAN AND A COMPLETE BUILD-OUT | | | PLAN SHOWING THE COMPLETE FINISHED UNIT. MORE | | | INFORMATION REQUIRED. SECTION 106.1.2. | | | | | | 4. SUBMIT A SANITARY RISER DIAGRAM SHOWING COMPLIANCE | | | WITH SECTION 704.5. DEAD ENDS ARE PROHIBITED. SHOW THE | | | LOCATION OF THE STACKS FOR EACH KITCHEN SINK BEING | | | DEMO'D. SECTION 106.3.5.1.3. | | | | | | 5. THE VALUATION OF THE JOB APPEARS TO BE LOW. PLEASE | | | CHECK THE LABOR, MATERIALS, EQUIPMENT & DESIGN COST AND | | | MAKE SURE ALL IS INCLUDED. SECTION 108.3. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2008-12-01 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2008-12-01 |
Time |
08:17 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2008-12-01 |
Time |
08:17 |
Sent To |
|
|
| Notes |
| 2008-12-01 08:17:56 | ALL INTERIOR WORK. ZONING REVIEW NOT REQUIRED. |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |