Plan Review Details - Permit 08110243
Plan Review Stops For Permit 08110243
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-03-10 Cont ID  
Sent By mjacobs Date 2009-03-10 Time 07:46 Rev Time 0.00
Received By mjacobs Date 2009-03-10 Time 07:46 Sent To  
Notes
2009-03-10 07:46:09BUILDING PLAN REVIEW
 PERMIT: 08110243
 ADD: 464 FERN ST.
 CONT: NETCO TEK, INC.
 TEL: (561)307-8766
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 3/10/09
 REVIEW: 2ND
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS. THIS INFORMATION
 SHALL BE INDICATED ON THE PLANS.
  
 3) *NO RESOIBSE NOT ADDRESSED* 2004 FBC EXISTING 301.5
 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE OR A
 COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE. INDICATE THE
 LEVEL OF ALTERATION ON THE DRAWINGS.
  
 4) *NOT ADDRESSED* FBC 11-4.17.3 THE GRAB BARS SHALL BE
 CONSTRUCTED IN ACCORDANCE WITH FIGURE 30(A) AND FIGURE
 30 (E).
  
 5) *NOT ADDRESSED* FBC 11-4.16.5 FLUSH CONTROLS SHALL
 BE HAND OPERATED OR AUTOMATIC AND SHALL COMPLY WITH
 SECTION 11-4.27.4. CONTROLS FOR FLUSH VALVES SHALL BE
 MOUNTED ON THE WIDE SIDE OF TOILET AREAS NO MORE THAN
 44 INCHES ABOVE THE FLOOR. THE FLUSH CONTROL FOR THE
 TOILET IS SHOWN ON THE NARROW SIDE OF THE WALL.
  
 6) *NOT ADDRESSED* PLEASE INDICATE WHAT MATERIALS WILL
 BE USED TO CONSTRUCT THE NEW WALLS, AND SHOW HOW THE
 WALLS WILL BE FASTENED TO THE FLOOR AND STRUCTURE
 ABOVE. 106.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 7) 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE & EXTENT OF THE WORK
 PROPOSED & SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 AND RULES AND REGULATIONS AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 PHONE (561)805-6726
 FAX (561) 805-6676
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-11-24 Cont ID  
Sent By mjacobs Date 2008-11-24 Time 13:51 Rev Time 0.00
Received By mjacobs Date 2008-11-24 Time 13:51 Sent To  
Notes
2008-11-24 13:51:13BUILDING PLAN REVIEW
 PERMIT: 08110243
 ADD: 464 FERN ST.
 CONT: NETCO TEK, INC.
 TEL: (561)307-8766
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 11-24-08
 REVIEW: 1ST
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS. THIS INFORMATION
 SHALL BE INDICATED ON THE PLANS.
  
 3) 2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE. INDICATE THE LEVEL OF ALTERATION ON THE
 DRAWINGS.
  
 4) FBC 11-4.17.3 THE GRAB BARS SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH FIGURE 30(A) AND FIGURE 30 (E).
  
 5) FBC 11-4.16.5 FLUSH CONTROLS SHALL BE HAND OPERATED
 OR AUTOMATIC AND SHALL COMPLY WITH SECTION 11-4.27.4.
 CONTROLS FOR FLUSH VALVES SHALL BE MOUNTED ON THE WIDE
 SIDE OF TOILET AREAS NO MORE THAN 44 INCHES ABOVE THE
 FLOOR. THE FLUSH CONTROL FOR THE TOILET IS SHOWN ON THE
 NARROW SIDE OF THE WALL.
  
 6) PLEASE INDICATE WHAT MATERIALS WILL BE USED TO
 CONSTRUCT THE NEW WALLS, AND SHOW HOW THE WALLS WILL BE
 FASTENED TO THE FLOOR AND STRUCTURE ABOVE. 106.1.2
 ADDITIONAL INFORMATION IS REQUIRED.
 7) 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE & EXTENT OF THE WORK
 PROPOSED & SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 AND RULES AND REGULATIONS AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 PHONE (561)805-6726
 FAX (561) 805-6676
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-03-09 Cont ID  
Sent By dpalmer Date 2009-03-09 Time 10:45 Rev Time 0.00
Received By dpalmer Date 2009-03-09 Time 10:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-11-24 Cont ID  
Sent By dpalmer Date 2008-11-24 Time 08:51 Rev Time 0.00
Received By dpalmer Date 2008-11-24 Time 08:51 Sent To  
Notes
2008-11-24 08:51:27** FAILED RESUBMITTED PLANS **
  
  
  
 1) NOTE: PER MECHANICAL COMMENTS, THERE WILL BE A NEED
 TO REVISE ELECTRICAL PLANS/PLANS SUBMITTED. WILL NEED
 TO SHOW CONTROLS FOR NEW VENTILATION REQUIRED.
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-11-19 Cont ID  
Sent By dpalmer Date 2008-11-19 Time 11:44 Rev Time 0.00
Received By dpalmer Date 2008-11-19 Time 11:44 Sent To  
Notes
2008-11-19 11:45:08 
  
  
 ** FAILED REVIEW **
  
  
  
 1) NOTE: PLEASE SEE THE PLANS SUBMITTED DO NOT CONTAIN
 ANY TITLE BLOCKS AS REQUIRED PER FAC 61G15-23.002
  
 2) NOTE: PLEASE SEE THE SEAL IN USE ON THE SIGNED,
 DATED AND SEALED PLANS HAS NOT BEEN A VALID SEAL IN THE
 STATE OF FLORIDA SINCE THE RULING FROM THE FLORIDA
 BOARD OF ENGINEERS IN FEBRUARY 2004. THE STATE GAVE AN
 EXTENSION TO DECEMBER 31ST 2005 HOWEVER NO USE OF THE
 SEAL AS SUBMITTED MAY BE USED AFTER THAT DATE ANYWHERE
 IN THE STATE OF FLORIDA.
 THIS IS NOT PERMITTED PER THE FLORIDA ADMINISTRATIVE
 CODE 61G15-23.001 AND FLORIDA STATUTES 471.025. THE
 LICENSE IS STILL CURRENT AND ACTIVE WITH THE STATE,
 PLEASE RENEW SEAL.
  
 2) NOTE: PERMIT APPLICATION SUBMITTED CLEARLY STATES TO
 REMODEL BATHROOM, REMOVING WALL ETC HOWEVER NO DETAIL
 WAS SHOWN FOR ANY ELECTRICAL SCOPE OF WORK BEING
 REMOVED OR NEW BEING INSTALLED.
 PLANS SHOW THE DEMOLITION WORK HOWEVER NOT THE NEW
 DETAILS FOR NEW WORK.
 PLEASE BE SURE TO SEE FBC 13-415.1.ABC.1.1,.1.2 FOR ANY
 NEW LIGHTING CONTROL TO MEET PRESCRIPTIVE REQUIREMENTS.
 PLEASE SEE NFPA-101 7.8 FOR REQUIRED LIGHTING FOR
 EGRESS EVEN UNDER NORMAL OCCUPANCY.
 PLEASE SUBMIT PLANS FOR COMPLETION OF WORK.
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-03-10 Cont ID  
Sent By mwennerg Date 2009-03-10 Time 10:43 Rev Time 0.00
Received By mwennerg Date 2009-03-10 Time 10:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-11-25 Cont ID  
Sent By mwennerg Date 2008-11-25 Time 13:38 Rev Time 0.00
Received By mwennerg Date 2008-11-25 Time 13:38 Sent To  
Notes
2008-11-25 13:40:35***DENIED***
  
 1) PLEASE SEE ELECTRICAL COMMENT #2 REGARDING FS AND
 FAC REQUIREMENTS FOR PLANS.
  
 2) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003.
  
 3) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-03-02 Cont ID  
Sent By adarroug Date 2009-03-02 Time 10:05 Rev Time 0.00
Received By adarroug Date 2009-03-02 Time 10:05 Sent To  
Notes
2009-03-02 10:07:38TO "BOB"#18

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-12-03 Cont ID  
Sent By adarroug Date 2008-12-03 Time 10:34 Rev Time 0.00
Received By adarroug Date 2008-11-14 Time 11:39 Sent To  
Notes
2008-11-14 11:42:16TO "BOB"#6

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-03-16 Cont ID  
Sent By hmoser Date 2009-03-16 Time 09:30 Rev Time 0.00
Received By hmoser Date 2009-03-16 Time 09:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-11-22 Cont ID  
Sent By rregueir Date 2008-11-22 Time 17:43 Rev Time 0.00
Received By rregueir Date 2008-11-22 Time 17:43 Sent To  
Notes
2008-11-22 17:45:11REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 SHOW MEANS OF VENTILATION FOR TOILET ROOM. RECONFIGURED
 SPACES SHALL BE PROVIDED WITH VENTILATION IN ACCORDANCE
 WITH FBCEB 609.2.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2009-03-12 Cont ID  
Sent By kstevens Date 2009-03-12 Time 14:58 Rev Time 0.00
Received By kstevens Date 2009-03-12 Time 14:58 Sent To  
Notes
2009-03-12 15:01:05DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 EXISTING BLDG CODE
 FBC-2004 CHAPTER 1
  
 ****FROM PREVIOUS REVIEW:
  
 1. PLEASE INDICATE CODE IN EFFECT WHEN DESIGNING THE
 PLANS. SHOULD READ FBC-2004 WITH 2007 REVISIONS.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 2. PLEASE INDICATE THE LEVEL OF ALTERATION. SECTION
 301.5.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 3. PLEASE SUBMIT A SANITARY RISER DIAGRAM SHOWING ALL
 PIPE SIZES, TRAPS & VENTS AS WELL AS THE CONNECTION
 POINT TO EXISTING DRAIN LINES AND VENTS. SECTION
 106.3.5.1.3.
 ****SANITARY RISER DIAGRAM SUBMITTED, THE PRINTED NAME
 & SIGNATURE OF PERSON RESPONSIBLE FOR THE RISER DESIGN
 SHALL BE ON EACH COPY OF THE RISER DIAGRAM. SECTION
 106.3.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-11-25 Cont ID  
Sent By kstevens Date 2008-11-25 Time 11:29 Rev Time 0.00
Received By kstevens Date 2008-11-25 Time 11:29 Sent To  
Notes
2008-11-25 11:34:32DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 EXISTING BLDG CODE
 FBC-2004 CHAPTER 1
  
 1. PLEASE INDICATE CODE IN EFFECT WHEN DESIGNING THE
 PLANS. SHOULD READ FBC-2004 WITH SUPPLEMENTS 2005, 2006
 & 2007.
  
 2. PLEASE INDICATE THE LEVEL OF ALTERATION. SECTION
 301.5.
  
 3. PLEASE SUBMIT A SANITARY RISER DIAGRAM SHOWING ALL
 PIPE SIZES, TRAPS & VENTS AS WELL AS THE CONNECTION
 POINT TO EXISTING DRAIN LINES AND VENTS. SECTION
 106.3.5.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status N Date 2008-12-02 Cont ID  
Sent By mflis Date 2008-12-02 Time 11:13 Rev Time 0.00
Received By mflis Date 2008-12-02 Time 11:13 Sent To  
Notes
2008-12-02 11:13:31ZONING REVIEW: NOT REQUIRED
  
 ** INTERIOR WORK ONLY
  
 MATT FLIS - 822-1445


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved