Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-03-06 Cont ID  
Sent By mjacobs Date 2009-03-06 Time 09:07 Rev Time 0.00
Received By mjacobs Date 2009-03-06 Time 09:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2009-02-10 Cont ID  
Sent By mjacobs Date 2009-02-10 Time 11:37 Rev Time 0.00
Received By mjacobs Date 2009-02-10 Time 11:37 Sent To  
Notes
2009-02-10 11:37:19BUILDING PLAN REVIEW
 PERMIT: 08110217
 ADD: 6907 OKEECHOBEE BLVD
 CONT: PLAN REVIEW
 TEL: (727)815-3336
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2/10/09
 REVIEW; 3RD
 ACTION: DENIED
  
 1) OK
 2) NOTED
 2) OK
 3) OK
  
 **THIRD REQUEST**
 4) UNTIL A LICENSE CONTRACTOR IS SIGNED ON THE
 APPLICATION AND A PERMIT IS APPLIED FOR THE PLANS WILL
 HAVE A FAIL STATUS. EVEN IF THE PLANS ARE FOUND TO BE
 CODE COMPLIANT, THE FAIL STATUS WILL REMAIN UNTIL A
 LICENSE CONTRACTOR IS SIGNED ON AND A PERMIT IS APPLIED
 FOR. NOTE: THE 2007 FBC WILL GO INTO EFFECT MARCH 1ST.
 IF A PERMIT IS APPLIED FOR AFTER THAT DATE THE PLANS
 WILL BE REVIEWED TO THOSE CODES.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 PHONE (561)805-6726
 FAX (561) 805-6676
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-01-05 Cont ID  
Sent By mjacobs Date 2009-01-05 Time 13:38 Rev Time 0.00
Received By mjacobs Date 2009-01-05 Time 13:38 Sent To  
Notes
2009-01-05 12:18:42BUILDING PLAN REVIEW
 PERMIT: 08110217
 ADD: 6907 OKEECHOBEE BLVD
 CONT: PLAN REVIEW
 TEL: (727)815-3336
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1-05-09
 REVIEW; 2ND
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 2) OK
 3) OK
  
 **SECOND REQUEST**
 4) UNTIL A LICENSE CONTRACTOR IS SIGNED ON THE
 APPLICATION AND A PERMIT IS APPLIED FOR THE PLANS WILL
 HAVE A FAIL STATUS. EVEN IF THE PLANS ARE FOUND TO BE
 CODE COMPLIANT, THE FAIL STATUS WILL REMAIN UNTIL A
 LICENSE CONTRACTOR IS SIGNED ON AND A PERMIT IS APPLIED
 FOR.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-11-20 Cont ID  
Sent By mjacobs Date 2008-11-20 Time 08:33 Rev Time 0.00
Received By mjacobs Date 2008-11-20 Time 08:33 Sent To  
Notes
2008-11-20 08:32:47BUILDING PLAN REVIEW
 PERMIT: 08110217
 ADD: 6907 OKEECHOBEE BLVD
 CONT: PLAN REVIEW
 TEL: (727)815-3336
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 11-20-08
 REVIEW; 1ST
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 2) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS. THIS INFORMATION IS
 REQUIRED ON THE PLANS.
  
 3) 2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE.
  
 4) UNTIL A LICENSE CONTRACTOR IS SIGNED ON THE
 APPLICATION THE PLANS WILL HAVE A FAIL STATUS. EVEN IF
 THE PLANS ARE FOUND TO BE CODE COMPLIANT, THE FAIL
 STATUS WILL REMAIN UNTIL A LICENSE CONTRACTOR IS SIGNED
 ON THE APPLICATION.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 PHONE (561)805-6726
 FAX (561) 805-6676
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2009-03-06 Cont ID  
Sent By dpalmer Date 2009-03-06 Time 08:27 Rev Time 0.00
Received By dpalmer Date 2009-03-06 Time 08:27 Sent To  
Notes
2009-03-06 08:27:24REDLINED 2006 NFPA-101/ LS CODE

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2009-02-09 Cont ID  
Sent By dpalmer Date 2009-02-09 Time 14:29 Rev Time 0.00
Received By dpalmer Date 2009-02-09 Time 14:29 Sent To  
Notes
2009-02-09 14:29:41** DENIED **
  
 1) NOTE: REVIEW TO REMAIN IN FAILED STATUS AS PERMIT
 HAS NOT BEEN APPLIED FOR WITH A LICENSED CONTRACTOR FOR
 SCOPE OF WORK WITH REQUIRED FEES. REVIEW OF ALL
 LICENSING, CODES, AND PERMIT APPLIED FEE WILL BE DONE
 WHEN PERMIT HAS BEEN APPLIED FOR.
 PLEASE KEEP IN MIND ALL PERMIT APPLICATIONS MUST BE IN
 BY MARCH 1ST OR COMPLETE DESIGN WILL BE REQUIRED TO BE
 DONE UNDER THE NEW CODES.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-12-29 Cont ID  
Sent By dpalmer Date 2008-12-29 Time 16:03 Rev Time 0.00
Received By dpalmer Date 2008-12-29 Time 16:03 Sent To  
Notes
2008-12-29 16:03:57** DENIED REVIEW **
  
 SOME NOTES FORM PREVIOUS REVIEW ARE STILL IN NEED OF
 ADDRESSING.
  
 1) NOTE: PLEASE SEE NOTE FROM PREVIOUS REVIEW IN WHICH
 THERE WAS A NOTE ** IMPORTANT**. THIS WAS NOTED SO THAT
 ALL OLD/VOIDED SHEETS WERE TO BE REMOVED FROM SETS AND
 FOR ALL NEW REVISED SHEETS TO BE INSERTED INTO COMPLETE
 SETS FOR REVIEW AND STAMPING. THIS WAS NOT DONE IN FACT
 THE NEW SHEET WERE JUST PLACED ON TOP OF THE OLD SETS.
 PLEASE BE SURE THIS ID DONE IN A NEAT AND ORDERLY
 FASHION WITH REVISED PLANS.
  
 2) NOTE: PERMIT APPLICATION HAS NOT BEEN MADE AT THIS
 TIME. PLEASE KNOW THE FLORIDA BUILDING CODE WILL BE
 CHANGING ON MATCH 1ST, 2009.
 ONLY ONCE PERMIT APPLICATION IS MADE BY LICENSED
 CONTRACTOR AND ALL CODE COMPLIANCE COMMENTS ARE
 ADDRESSED WILL THE REVIEW GO INTO A PASSED STATUS.
 THERE ARE MANY ASPECTS OF THE REVIEW WHICH ENTAIL
 REVIEW OF ALL LICENSING INCLUDING THAT OF DESIGNERS AT
 THE TIME OF APPLICATION, REVIEW AND PERMITTING.
  
 3) NOTE: PLEASE PROVIDE LIGHTING CONTROLS PER FBC
 13-415.1.ABC.1.1, .1.2, .1.3.
 THE RESPONSE LETTER MENTIONS THE STORE CONTAINS AN
 ENERGY MANAGEMENT SYSTEM HOWEVER THE PLANS STILL
 INDICATE ONLY STANDARD SINGLE POLE SWITCHES. THESE DO
 NOT MEET THE CODE SECTIONS FOR SEPARATE SPACES.
 PLEASE REVISE PLANS ACCORDINGLY.
 SEPARATE SPACES WITH FLOOR TO CEILING PARTITIONS MAY BE
 CONTROLLED FROM SYSTEM HOWEVER AUTOMATIC OVER RIDES
 WOULD BE REQUIRED OR MEET AUTOMATED CONTROLS FOR THESE
 AREAS SEPARATELY FROM THE SYSTEM.
  
 4) NOTE: PLEASE SPECIFY WHICH METHOD OF CALCULATION IS
 BEING USED. PLEASE SEE TABLES B AND C. BUILDING AREA
 METHOD IN TABLE *C* DOES NOT CONTAIN THE SAME
 ALLOWANCES AS SPACE BY SPACE.
 13-415.2,13-415.2.ABC.1.1,.1.2, 13-415.2.B, 13-415.2.C.
  
 5) NOTE: PLEASE COMPLETE TITLE BLOCK FOR ELECTRICAL
 ENGINEERING FIRM AS LISTED ON COVER SHEET. PLEASE SEE
 FAC 61G15-23.002 FOR MISSING INFORMATION SUCH AS THE
 CERTIFICATE OF AUTHORIZATION NUMBER. THIS IS ALSO
 REQUIRED PER FS 471.023.
  
  
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-11-19 Cont ID  
Sent By dpalmer Date 2008-11-19 Time 08:41 Rev Time 0.00
Received By dpalmer Date 2008-11-19 Time 08:41 Sent To  
Notes
2008-11-19 08:42:07 
 ** FAILED REVIEW **
  
 **
  
  
 1) NOTE: PLANS SUBMITTED FOR * PLAN REVIEW * ONLY. ONCE
 PLANS ARE FOUND TO BE CODE COMPLIANT AND REVIEW WILL
 STILL REMAIN IN FAILED STATUS UNTIL PERMIT APPLICATION
 HAS BEEN MADE BY A LICENSED CONTRACTOR. VERIFICATION OF
 LICENSING, CODES ETC AT THE TIME OF PERMIT APPLICATION
 WILL BE VERIFIED AT THAT TIME.
  
 2) NOTE: CODES SHOULD REFERENCE LATEST ADOPTED
 STANDARDS WHICH ARE 2004 FBC W/ 2007 REVISIONS. PLANS
 INDICATE 2007, HOWEVER THE 2007 REVISIONS TO THE 2004
 FBC WERE ADOPTED MORE THAN A YEAR AGO. PLEASE ADJUST
 NOTES/CODES.
  
 3) NOTE: LIGHTING CONTROLS FOR NEW BEING INSTALLED ARE
 REQUIRED TO MEET 13-415.1.ABC.1.1, .1.2.
 THIS IS ONLY FOR NEW BEING INSTALLED WHICH DOES REQUIRE
 AUTOMATED LIGHTING CONTROLS OF SOME TYPE.
  
 4) NOTE: PLEASE SUBMIT AND SHOW LIGHTING PERFORMANCE
 CALCULATIONS PER 13-415.2,13-415.2.B,
 13-415.2.ABC.1.1,.1.2.
  
 5) NOTE: PLEASE SUBMIT AND SHOW THE UPDATE PANEL
 SCHEDULE FOR NEW LP1 PANEL. AS RECORD SETS OF PLANS
 NEED TO SHOW ALL PERMITTED WORK AND BE UPDATED FOR NEW
 CIRCUITS ETC THESE NEED TO BE SUBMITTED AND SHOWN.
 PLEASE BE SURE TO UPDATE LOADS ON ALL PANELS EVEN AS
 MINOR AS THE LOAD MAY BE. THE RECORD DOCUMENTS ARE
 REQUIRED TO COORDINATE WITH THE SCOPE OF WORK.
 408.4, 310.16, 240.4, 220 ETC
 FBC 106.1.1, 106.5
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2009-03-06 Cont ID  
Sent By mawillia Date 2009-03-06 Time 12:31 Rev Time 0.00
Received By mawillia Date 2009-03-06 Time 12:19 Sent To  
Notes
2009-03-06 12:31:37*****APPROVED*****
  
  
 PLAN SHEETS A1.1, A1.2, FP1.1, AND E1.1 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2009-02-12 Cont ID  
Sent By mwennerg Date 2009-02-12 Time 15:29 Rev Time 0.00
Received By mwennerg Date 2009-02-12 Time 15:29 Sent To  
Notes
2009-02-12 15:32:01***DENIED***
  
 PLANS SUBMITTED FOR PLAN REVIEW ONLY. PLANS APPEAR TO
 BE CODE COMPLIANT BUT WILL REMAIN IN FAILED STATUS
 UNTIL SUBMITTED AND REVIEWED FOR PERMIT APPLICATION.
  
 PLEASE NOTE THE FOLLOWING:
  
 LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2006. THIS
 CURRENT CODE WAS ADOPTED ON DECEMBER 31, 2008 AND WILL
 APPLY TO THIS PROJECT AT THE TIME OF FIRE PLAN REVIEW
 FOR PERMIT.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2009-01-07 Cont ID  
Sent By mwennerg Date 2009-01-07 Time 10:59 Rev Time 0.00
Received By mwennerg Date 2009-01-07 Time 10:59 Sent To  
Notes
2009-01-07 11:00:19***DENIED***
  
 PLANS SUBMITTED FOR PLAN REVIEW ONLY. PLANS APPEAR TO
 BE CODE COMPLIANT BUT WILL REMAIN IN FAILED STATUS
 UNTIL SUBMITTED AND REVIEWED FOR PERMIT APPLICATION.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-11-24 Cont ID  
Sent By mwennerg Date 2008-11-24 Time 11:19 Rev Time 0.00
Received By mwennerg Date 2008-11-24 Time 11:19 Sent To  
Notes
2008-11-24 11:19:55***DENIED***
  
 PLANS SUBMITTED FOR PLAN REVIEW ONLY. PLANS APPEAR TO
 BE CODE COMPLIANT BUT WILL REMAIN IN FAILED STATUS
 UNTIL SUBMITTED AND REVIEWED FOR PERMIT APPLICATION.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-03-03 Cont ID  
Sent By adarroug Date 2009-03-03 Time 09:15 Rev Time 0.00
Received By adarroug Date 2009-03-03 Time 09:15 Sent To  
Notes
2009-03-04 13:14:28TO "BOB"#2
2009-03-03 09:15:55WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-02-03 Cont ID  
Sent By adarroug Date 2009-02-03 Time 15:37 Rev Time 0.00
Received By adarroug Date 2009-02-03 Time 15:37 Sent To  
Notes
2009-02-03 15:40:07TO "BOB"#2

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-12-26 Cont ID  
Sent By adarroug Date 2008-12-26 Time 09:38 Rev Time 0.00
Received By adarroug Date 2008-12-26 Time 09:38 Sent To  
Notes
2008-12-26 09:40:14TO "BOB"#12

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-11-25 Cont ID  
Sent By kstevens Date 2008-11-25 Time 10:21 Rev Time 0.00
Received By kstevens Date 2008-11-13 Time 11:11 Sent To  
Notes
2008-11-13 11:11:14TO "BOB"#7

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2009-03-06 Cont ID  
Sent By rregueir Date 2009-03-06 Time 08:49 Rev Time 0.00
Received By rregueir Date 2009-03-06 Time 08:49 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2009-02-15 Cont ID  
Sent By rregueir Date 2009-02-15 Time 09:49 Rev Time 0.00
Received By rregueir Date 2009-02-15 Time 09:48 Sent To PC
Notes
2009-02-15 09:49:05**PLAN CHECK ONLY**
  
 PLANS HAVE BEEN REVIEWED FOR CODE COMPLIANCE AND
 PASSED. HWEVER, THE REVIEW WILL REMIAN IN FAIL STATUS
 PENDING ACTUAL APPLICATION FOR PERMIT.
 NOTE: THE NEW 2007 FBC IS IN EFFECT ON MARCH 1, 2009.
 ANY APPLICATION FOR PERMIT SUBMITTED ON OR AFTER THAT
 DATE WILL REQUIRE PLANS TO BE REVIEWED FOR COMPLIANCE
 WITH THE NEW CODE.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2009-01-10 Cont ID  
Sent By rregueir Date 2009-01-10 Time 17:04 Rev Time 0.00
Received By rregueir Date 2009-01-10 Time 17:03 Sent To PC
Notes
2009-01-10 17:06:17REVIEW WILL REMAIN IN FAIL STATUS PENDING SUBMISSION OF
 A PERMIT APPLICATION.
 NOTE: THE 2007 FBC WILL BE IN EFFECT MARCH 1, 2009. A
 PERMIT APPLICATION SUBMITTED ON OR AFTER THAT DATE WILL
 REQUIRE REVIEW FOR COMPLIANCE WITH THE NEW CODE.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-11-22 Cont ID  
Sent By rregueir Date 2008-11-22 Time 17:19 Rev Time 0.00
Received By rregueir Date 2008-11-22 Time 17:19 Sent To  
Notes
2008-11-22 17:19:15**PLAN CHECK ONLY**
  
 PLANS HAVE BEEN REVIEWED FOR CODE COMPLIANCE AND
 PASSED. HWEVER, THE REVIEW WILL REMIAN IN FAIL STATUS
 PENDING ACTUAL APPLICATION FOR PERMIT.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-03-06 Cont ID  
Sent By dpalmer Date 2009-03-06 Time 13:39 Rev Time 0.00
Received By dpalmer Date 2009-03-06 Time 13:38 Sent To  
Notes
2009-03-06 13:39:10OK PER KEN STEVENS. REVIEW WAS FAILED AS PERMIT HAD NOT
 BEEN APPLIED FOR BY A LICENSED CONTRACTOR. SPOKE TO KEN
 STEVENS AND HE WAS OK WITH REVIEW BEING CHANGED INTO A
 PASSED STATUS.
 PLANS WERE ALREADY STAMPED.

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-01-09 Cont ID  
Sent By kstevens Date 2009-01-09 Time 13:43 Rev Time 0.00
Received By kstevens Date 2009-01-09 Time 13:43 Sent To  
Notes
2009-01-09 13:43:58DENIED
 REFERENCE:
 FBC-2004 PLUMBING
  
 1. UNTIL A LICENSED CONTRACTOR IS SIGNED ON AN
 APPLICATION FOR PERMIT THE STATUS WILL BE FAILED. PLANS
 ARE CODE COMPLIANT AT THIS TIME.
  
 I M P O R T A N T - I N F O R M A T I O N
  
 B E L O W
  
 (NEW SHEETS SHALL BE INSERTED AND OLD SHEETS REMOVED.
 PLANS SHALL BE SUBMITTED MINIMUM 2 SETS OF BOUND
 PLANS).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-11-25 Cont ID  
Sent By kstevens Date 2008-11-25 Time 10:18 Rev Time 0.00
Received By kstevens Date 2008-11-25 Time 10:18 Sent To  
Notes
2008-11-25 10:20:58DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 *****PLAN REVIEW ONLY*****
  
 1. SHT A0.1 CODE REFERENCE SHALL ALSO INDICATE 2007
 AMENDMENTS/REVISIONS/SUPLIMENTS TO THE 2004 FBC.
  
 2. PLEASE INDICATE THE LEVEL OF ALTERATION PER SECTION
 301.5 OF THE EXISTING BUILDING CODE.
  
 3. SHT A1.0 DEMO KEYED NOTES #3. PLEASE IDENTIFY THE
 FIXTURES. IF THERE ARE PLUMBING FIXTURES, THEN DEAD
 ENDS ARE PROHIBITED PER SECTION 704.5. SECTION 106.1.2
 MORE INFORMATION REQUIRED.
  
 4. SHT P1.1 THE SIGNATURE OF THE ENGINEER IS REQUIRED
 WHEN SEALING THE PLANS. IT APPEARS THAT INITIALS WERE
 USED IN PLACE OF THE SIGNATURE. IF INDEED THIS IS THE
 LEGAL SIGNATURE OF THE ENGINEER, THEN A SIGNED, SEALED,
 NOTORIZED LETTER INDICATING THE LEGAL SIGNATURE OF THE
 ENGINEER SHALL BE SUBMITTED TO THIS OFFICE FOR OUR
 FILE. FAC 61G15-23.002(1)(2) & FS 471.025.
  
 5. SHT P1.1 ELECTRIC WATER HEATER DETAIL. THE RELIEF
 VALVE (T & P) SHALL HAVE A VISIBLE AIR GAP OR AIR GAP
 FITTING LOCATED IN THE SAME ROOM AS THE WATER HEATER.
 SECTION 504.6.1. PLEASE SHOW ON THE DETAIL.
  
 6. SHT P1.1 PLUMBING DRAWING NOTES #2.3 AIR CHAMBERS
 ARE NOT APPROVED. PLEASE DELETE FROM NOTES. SECTION
 604.9 & PDI-WH 201. WATER HAMMER ARRESTORS ARE REQUIRED
 FOR QUICK CLOSING VALVES ONLY. (ICE MACHINES, DISH
 WASHERS & AUTOMATIC CLOTHES WASHERS).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  