| 2008-11-14 15:09:21 | RESIDENTIAL (R3) SHUTTERS BUILDING REVIEW CHECKLIST. |
| | REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007 |
| | REVISIONS. |
| | |
| | 1- ACCORDION SHUTTERS PRODUCT APPROVAL FL5133: |
| | SHEETS SUBMITTED ARE 1 THRU 8 OF 16 OF DRAWING 05-208. |
| | THEY ARE FOR MID-RISE BERTHA ACCORDION SHUTTERS. THIS |
| | HOUSE IS A ONE STORY BUILDING, NOT A MID-RISE BUILDING. |
| | NEED TO PROVIDE PROPER DRAWINGS (9 THRU 16 OF 16) WHICH |
| | ARE THE DRAWINGS THAT APPLY TO THIS PROJECT. |
| | |
| | 2- INSTALLATION SCHEDULE SUBMITTED FOR ACCORDION |
| | SHUTTERS: CLEARLY IDENTIFY SUBSTRATE WHERE SHUTTERS ARE |
| | GOING TO BE ATTACHED. EG: CONCRETE, CONCRETE BLOCK OR |
| | WOOD. COLUMN WAS LEFT BLANK. NEED THIS INFORMATION TO |
| | VERIFY COMPLIANCE WITH PRODUCT APPROVAL AND DESIGN |
| | PRESSURES AS REQUIRED BY SEC. R301 OF 2004 FLORIDA |
| | RESIDENTIAL CODE. |
| | NOTE: TOP AND BOTTOM SUBSTRATE MUST BE POURED CONCRETE. |
| | FILLED CELLS DON'T COUNT AS CONCRETE. NEED TO USE |
| | MASONRY ANCHOR SCHEDULE OR PROVIDE PROOF/TESTING THAT |
| | FILLED CELLS HAVE THE SAME OR MORE STRENGTH THAN |
| | CONCRETE. |
| | |
| | 3- STORM PANELS: |
| | A) FOR A 122" PANEL SPAN NEED TO USE CORRECT ANCHOR |
| | SCHEDULE. SEE ANCHOR SCHEDULE ON SHEET 11 OF 17 AND |
| | REVISE INSTALLATION SCHEDULE AS REQUIRED. |
| | B) CLEARLY MARK SPECIFIC CONNECTION AT TOP AND BOTTOM. |
| | EG: 3A (TOP) AND 2(BOTTOM). |
| | C) CLEARLY IDENTIFY SUBSTRATE TO RECEIVE SHUTTERS AT |
| | TOP AND BOTTOM. EG: CONCRETE OR MASONRY. |
| | NOTE: FILLED CELLS NEED TO USE MASONRY ANCHOR SPACING |
| | OR PROVIDE PROOF THAT FILLED CELLS ARE EQUIVALENT OR |
| | STRONGER THAN POURED CONCRETE. |
| | D) REVISE PANEL SPAN ON INSTALLATION SCHEDULE |
| | SUBMITTED. IF THE EDGE DISTANCE IS 3.5", THEN THE PANEL |
| | SPAN NEEDS TO BE COORDINATED WITH THE OPENING SIZE AND |
| | THE EDGE DISTANCE. EDGE DISTANCE DOESN'T INCLUDE STUCCO |
| | THICKNESS. ALSO, THE EDGE DISTANCE IS TO THE CENTER OF |
| | THE ANCHOR. PANEL SPAN NEEDS TO BE INCREASED AS |
| | REQUIRED. |
| | E) IF BOTTOM CONNECTION IS ON MASONRY, THEN THE MASONRY |
| | ANCHOR SPACING NEEDS TO BE USED. REVISE INSTALLATION |
| | SCHEDULE AS REQUIRED. |
| | F) CLARIFY HOW ARE SHUTTERS GOING TO BE INSTALLED |
| | VERTICALLY OR HORIZONTALLY. INSTALLATION SCHEDULE |
| | SUBMITTED SAYS VERTICAL BUT SHUTTER SPAN IS 122" WHICH |
| | IS ON THE HORIZONTAL INSTALLATION. |
| | NOTE: THIS ALSO AFFECTS THE CONNECTIONS TOP AND BOTTOM |
| | SINCE HEADERS CAN'T BE INSTALLED ON HORIZONTAL |
| | APPLICATIONS. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |