Plan Review Details - Permit 08110178
| Plan Review Stops For Permit 08110178 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
P |
Date |
2008-12-02 |
|
|
Cont ID |
|
| Sent By |
jnguyen |
Date |
2008-12-02 |
Time |
11:49 |
Rev Time |
0.00 |
| Received By |
jnguyen |
Date |
2008-12-02 |
Time |
08:08 |
Sent To |
|
|
| Notes |
| 2008-12-02 11:31:54 | UPON EXAMINATION OF THE SITE PLANS, I HAVE DETERMINED | | | THAT THIS PERMIT HAS BEEN ATTACHED TO THE WRONG PCN# | | | 74424322080010020 WHEN IT SHOULD ACTUALLY BE APPLIED TO | | | PCN# 74424322080010010 INSTEAD. THE PERMIT IS TO | | | RENOVATE THE EXISTING SPACE OF THE TENANT'S (FRESENIUS | | | MEDICAL CARE) AT 6901 OKEEECHOBEE BLVD SUITE # D19, AS | | | WELL AS MERGE WITH THE AREAS OF SUITES # D23 & # E1 | | | (THEY ARE SPACES TO THE SOUTHEAST OF THE WAL-MART | | | NEIGHBORHOOD MARKET.). THE ADDRESSES OF THESE SUITE | | | NUMBERS CURRENTLY EXIST IN COMMUNITYPLUS UNDER PCN# | | | 74424322080010010 AS UNIT 0023 - # D19, UNIT 0024 - # | | | D23 & UNIT 0025 - # E1. IN COMMUNITYPLUS, THIS PERMIT | | | SHOULD BE ATTACHED TO PCN# 74424322080010010, | | | SPECIFICALLY UNIT 0023 - 6901 OKEECHOBEE BLVD # D19 | | | (SINCE # D23 & # E1 ARE GOING TO BE EXPANDED AS A PART | | | # D19). I HAVE ALREADY MADE THE CORRECTION OF PCN# | | | 74424322080010010 ON THE ORIGINAL PERMIT APPLICATION, | | | BUT I DO NOT HAVE AUTHORIZATION TO CORRECT IT IN THE | | | COMMUNITYPLUS SYSTEM. | | | | | | *PLEASE NOTE THAT JAMES HAS BROUGHT TO MY ATTENTION | | | THAT THESE SUITE # ADDRESSES DO NOT CONFORM TO OUR | | | ADDRESSING POLICY, IN THAT EACH COMMERCIAL BUSINESS | | | MUST HAVE THEIR OWN UNIQUE NUMERICAL ADDRESS. POLICY | | | SECTION 1.4 ADDRESSING FOR COMMERCIAL STRUCTURES: STRIP | | | MALLS & OTHER COMMERCIAL BUSINESSES WILL EACH BE ISSUED | | | A RANGE OF UNIQUE ADDRESS NUMBERS FROM THE DRIVEWAY | | | ACCESS. MULTIPLE COMMERCIAL STRUCTURES ON CORNER LOTS | | | SHALL BE ASSIGNED AN ADDRESS NUMBER FROM THE ROAD | | | PARALLEL WITH THE PRIMARY ENTRANCE OF THE BUILDING. | | | JAMES HAS STRONGLY ADVISED THAT I TRY TO NEGOTIATE WITH | | | THE LANDLORD (LINPRO INVESTMENTS, INC.) TO RELAY TO THE | | | TENANTS TO CHANGE THEIR ADDRESSES TO CONFORM TO OUR | | | POLICY. HOWEVER, THAT BRIDGE WON'T BE CROSSED IN THE | | | MEANTIME UNTIL FURTHER RESEARCH & COMMUNICATION IS | | | INITIATED BY ME. UPDATE: AFTER GOING OUT ON SITE TO | | | CHECK OUT THE BUSINESSES OF LAKE POINT CENTRE PLAZA & | | | TALKING TO TRISH (A REPRESENTATIVE OF LINPRO | | | INVESTMENTS, INC.), JAMES & I HAVE DECIDED TO BACK DOWN | | | FROM ENFORCING THIS POLICY. THE ADDRESSES FOR THE | | | SURROUNDING BUSINESSES OF BP GAS STATION, WALGREEN'S & | | | BURGER KING WOULD NEED TO BE ADJUSTED TOO TO MAKE | | | CHRONOLOGICAL SENSE FOR THE PROSPECTIVE ADDRESSES FOR | | | THE TENANTS OF LAKE POINT CENTRE PLAZA. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2009-05-14 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-05-14 |
Time |
11:50 |
Rev Time |
1.30 |
| Received By |
jwitmer |
Date |
2009-05-14 |
Time |
11:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2009-03-31 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-03-31 |
Time |
15:04 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2009-03-31 |
Time |
15:04 |
Sent To |
|
|
| Notes |
| 2009-03-31 15:19:01 | BUILDING PLAN REVIEW | | | PERMIT: 08110178 | | | ADD:6901 OKEECHOBEE BLVD SUITE D19, D23 & E1. | | | CONT: "PLAN REVIEW" | | | TEL: (262)901-0505 EXT 110 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 2ND MAJOR WORKING DRAWING REVIEW/ PLAN REVIEW | | | ACTION: DENIED | | | MARCH 31/2009 | | | | | | 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE | | | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | 1B) COMPLIED. | | | | | | 1C) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT, | | | TO BE FILED WITH THE CLERK OF THE COURT. NOTE: | | | 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF | | | COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS | | | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & | | | VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF | | | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST | | | INSPECTION. | | | | | | 1D) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST | | | TIME REVIEW) AFTER MAARCH 1/2009 SHALL BE REVIEWED TO | | | THE 2007 FBC BUILDING WITH THE 2009 SUPPLEMENTS & 2007 | | | EXISTING BUILDING CODE WITH 2009 SUPPLEMENTS. PLEASE | | | PROVIDE AS TO WHAT LEVEL OF ALTERATIONS WILL BE | | | COMPLETED UNDER THIS PERMIT. 2007 EXIST FBC 101.5 | | | COMPLIANCE METHODS. THE REPAIRS, ALTERATIONS, CHANGE IN | | | OCCUPANCY, ADDITION OR RELOCATION OF ALL EXISTING | | | BUILDINGS SHALL COMPLY WITH ONE OF THE FOLLOWING | | | METHODS LISTED IN SECTION 101.5.1 THROUGH 101.5.3 AS | | | SELECTED BY THE APPLICANT. | | | | | | 2) COMPLIED. | | | | | | 3-4) COMPLIED. | | | | | | 5) SEMI-COMPLIED. MISSING WIND DESIGN INFORMATION FOR | | | ROOF TOP EQUIPMENT. | | | 1603.1.4 WIND DESIGN DATA. | | | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL | | | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE | | | DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE | | | BUILDING: | | | 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR | | | (KM/HR). THE CITY OF WEST PALM BEACH IS LOCATED IN A | | | 140 MPH WIND-BORNE DEBRIS REGION. | | | | | | 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING | | | CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7 | | | AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. | | | | | | 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS | | | UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND | | | DIRECTION SHALL BE INDICATED. | | | | | | 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF | | | DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT. | | | | | | 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES | | | IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR | | | THE SELECTION OF EXTERIOR COMPONENTS AND CLADDING | | | MATERIALS NOT SPECIFICALLY DESIGNED BY THE REGISTERED | | | DESIGN PROFESSIONAL. | | | | | | 6) COMPLIED. | | | | | | 7) 2ND REQUEST, PLEASE SEE MECHANICAL COMMENT# 3 ABOUT | | | THE ROOF TOP EQUIPMENT BEING REQUIRED TO MEET WIND | | | PRESSURES, FBCM 301.13. | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)805-6731 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2008-11-24 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-11-24 |
Time |
13:31 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2008-11-24 |
Time |
13:31 |
Sent To |
|
|
| Notes |
| 2008-11-24 14:38:56 | BUILDING PLAN REVIEW | | | PERMIT: 08110178 | | | ADD:6901 OKEECHOBEE BLVD SUITE D19, D23 & E1. | | | CONT: "PLAN REVIEW" | | | TEL: (262)901-0505 EXT 110 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW | | | ACTION: DENIED | | | | | | 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE | | | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS, | | | PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR | | | SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL | | | REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A | | | THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN | | | (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED | | | FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS | | | WEST PALM BEACH ADMINISTRATIVE CODE. | | | | | | 1C) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT, | | | TO BE FILED WITH THE CLERK OF THE COURT. NOTE: | | | 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF | | | COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS | | | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & | | | VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF | | | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST | | | INSPECTION. | | | | | | 1E) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST | | | TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO | | | THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS & 2004 | | | EXISTING BUILDING DODE WITH 2007 SUPPLEMENTS. PLEASE | | | PROVIDE AS TO WHAT LEVEL OF ALTERATIONS WILL BE | | | COMPLETED UNDER THIS PERMIT? 2004 EXIST FBC 301.5. | | | | | | 2) NOTE WHEN PLANS WILL COME IN AS A PERMIT | | | APPLICATION.PLANS, SPECIFICATIONS, REPORTS OR OTHER | | | DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING | | | FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND | | | SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE | | | DOCUMENT. THE SEAL SHALL CONTAIN THE NAME OF THE | | | ARCHITECT AND REGISTRATION NUMBER, THE SEAL SHALL BE | | | CIRCULAR AND APPRXIMATELY 2 INCHES IN DIAMETER. | | | FL ADMIN CODE 61G1-16.002 ARCHITECTS. | | | | | | 3) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, | | | PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING | | | REPORTS ARE AS FOLLOWS: | | | 3A) STOREFRONT WINDOWS- ONLY ONE SUBMITTED | | | | | | 4) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE | | | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | | | | 5) MISSING WIND DESIGN INFORMATION FOR STOREFRONT | | | WINDOW AS WELL AS ROOF TOP EQUIPMENT. | | | 1603.1.4 WIND DESIGN DATA. | | | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL | | | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE | | | DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE | | | BUILDING: | | | 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR | | | (KM/HR). | | | | | | 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING | | | CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7 | | | AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. | | | | | | 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS | | | UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND | | | DIRECTION SHALL BE INDICATED. | | | | | | 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF | | | DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT. | | | 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES | | | IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR | | | THE SELECTION OF EXTERIOR COMPONENTS AND CLADDING | | | MATERIALS NOT SPECIFICALLY DESIGNED BY THE REGISTERED | | | DESIGN PROFESSIONAL. | | | | | | 6) M215 INDICATES NEW ROOF TOP RTU UNITS BUT NO | | | INFORMATION WAS PROVIDED FOR BAR JOIST REINFORCEMENT, | | | CURB ATTACHMENTS NOR UNITS ATTACHED TO CURBS. 1609.1.3 | | | ANCHORAGE AGAINST OVER TURNING. | | | | | | 7) ) PLEASE SEE MECHANICAL COMMENT# 3 ABOUT THE ROOF | | | TOP EQUIPMENT BEING REQUIRED TO MEET WIND PRESSURES, | | | FBCM 301.13. | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)805-6731 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2009-05-14 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-05-14 |
Time |
11:50 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2009-05-14 |
Time |
11:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2009-05-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-05-18 |
Time |
15:20 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-05-18 |
Time |
15:20 |
Sent To |
|
|
| Notes |
| 2009-05-18 15:21:09 | STAMPED SECOND SET |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2009-05-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-05-14 |
Time |
12:24 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-05-14 |
Time |
12:24 |
Sent To |
|
|
| Notes |
| 2009-05-14 12:24:48 | **PROVISO/ REDLINED NOTES ** | | | | | | * TEMPORARY FAILED* | | | | | | | | | ** THE FOLLOWING ITEMS SHALL BE ADDRESSED AND REVISED | | | BEFORE ANY ROUGH ELECTRICAL INSPECTION. SEE NOTE #4 | | | WHICH NEEDS TO BE DONE AT THIS TIME. NOTE NUMBER FOUR | | | WAS GIVEN ON INITIAL REVIEW HOWEVER HAS NOT BEEN | | | ADDRESSED IN SECOND SET. | | | | | | 1) NOTE: PLEASE SEE FBC 13-415.AB.1, .1.3 NOTED IN ALL | | | PREVIOUS REVIEWS. THERE ARE LIGHTING FIXTURES WHICH DO | | | NOT MEET SECTIONS GIVEN. ALL ACCENT/TASK LIGHTING SHALL | | | CONTAIN SOME SORT OF CONTROL WHICH WILL TURN OFF | | | FIXTURES IN SOME SORT OF AUTOMATED WAY. THESE MAY BE | | | PART OF THE LIGHTING TIME CLOCK WITH OVER RIDES OR | | | OCCUPANCY SENSOR TYPE DEVICES. | | | THESE ARE LOCATED IN SEPARATION ROOM, PREP SINK, AND | | | MED PREP AREAS. | | | THE BASE SYSTEM AS SHOWN NEEDS TO BE MORE SPECIFIC ON | | | PLANS WITH ACTUAL SYSTEM CHOSEN AND INSTALLED. THE TYPE | | | OF SYSTEM WHICH MUST BE LISTED PER A NATIONAL | | | RECOGNIZED TESTING LABORATORY SHALL BE SHOWN. ( NRTL) | | | NEC 110.3, FBC 13-415.AB.1.1, .1.2 AND .1.3. SEE NEXT | | | NOTE: | | | | | | 2) NOTE: PLEASE SEE FBC 11-4.27.4 AS THE PLANS DO | | | CONTAIN A DEVICE WHICH IS NOTED AS BEING A *TWIST | | | TIMER* DEVICE. DEVICE WHICH MAY BE ACCESSIBLE AND IN | | | USE FOR ANYONE MEETING ADA GUIDELINES SHALL NOT BE OF | | | TWISTING TYPE. | | | | | | 3) NOTE: ** ALL LOW VOLTAGE SYSTEMS SHALL BE UNDER | | | SEPARATE PERMITS. ANY ACCESS CONTROLS WOULD ALSO BE | | | UNDER SEPARATE PERMIT WITH PLANS AND REVIEW BY THE FIRE | | | MARSHAL AS WELL AS ELECTRICAL REVIEWS IN ACCORDANCE | | | WITH NFPA-70 2005 AND NFPA-101 2006 CHAPTER 7. | | | | | | 4) NOTE: THE SECOND SET OF PLANS CONTAINS ALMOST ALL OF | | | THE ORIGINAL SHEETS SUBMITTED FROM SHEETS 230, 250, AND | | | 270 NEEDS TO BE RE-SEALED WITH CURRENT SEALS ACCEPTABLE | | | IN THE STATE OF FLORIDA. THE OTHER NEW REVISED SHEETS | | | IN SETS ARE OK AS THEY CONTAIN NEW SEAL. FAC61G1-16.002 | | | THIS WAS NOTED ON COMMENT #3 ON INITIAL REVIEW YET MANY | | | OF THE OLDER SHEETS STILL CONTAIN OLD SEAL. THIS IS | | | REQUIRED FOR ALL SHEETS WHETHER OR NOT COMMENT IS MADE | | | BY ANY OTHER TRADE. THE ARCHITECT OF RECORD MAY COME | | | INTO OFFICE, PRESENT IDENTIFICATION AND RE-SEAL PLANS | | | WITH NEW SEAL IN ORDER TO GET PROJECT ISSUED FOR | | | PERMIT. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2009-03-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-03-26 |
Time |
13:07 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-03-26 |
Time |
13:07 |
Sent To |
|
|
| Notes |
| 2009-03-26 13:07:19 | ** DENIED REVIEW ** | | | | | | 1) NOTE: AS NOTED ON THE PREVIOUS REVIEW ON THE FIRST | | | COMMENT. IT IS IMPORTANT TO KNOW THAT PLANS WERE ONLY | | | SUBMITTED FOR PLAN REVIEW ONLY. THIS DOES NOT *LOCK* A | | | PROJECT UNDER ANY SPECIFIC CODE EDITIONS UNLESS PERMIT | | | APPLICATION IS MADE. AS THE PROJECT WAS ONLY SUBMITTED | | | FOR PLAN REVIEW AND IS DESIGNED UNDER THE 2004 FBC THIS | | | DID NOT LOCK PROJECT UNDER THE 2004 FBC. AS OF MARCH 1, | | | 2009 THE STATE OF FLORIDA UNDER FS 553.73 HAS ADOPTED | | | THE 2007 FBC WITH 2009 REVISIONS. | | | PLEASE ALSO KNOW SOME OTHER CODES SUCH AS THE LIFE | | | SAFETY CODE AND STATE FIRE CODE WERE ALSO REVISED PER | | | FLORIDA ADMINISTRATIVE CODE 69A-60.003 AND .004 BY THE | | | STATE FIRE MARSHAL. | | | THE FOLLOWING CODES NEED TO BE ON PLANS. PLEASE BE SURE | | | THE FOLLOWING ARE ON ELECTRICAL AS WELL. SOME CODES | | | STATED ON PLANS ARE OK AND IN EFFECT. PLEASE BE SURE | | | THE FOLLOWING ARE UPDATED ON ALL RELEVANT SHEETS. | | | | | | 2007 FBC W/2009 REVISIONS. | | | 2006 NFPA-101 | | | 2006 NFPA-1 | | | OTHER CODES SUCH AS 2002 NFPA-72, 2005 NFPA-70 ARE | | | STILL ACCURATE. | | | | | | 2) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO FBC | | | AND CHAPTER 13 FOR LIGHTING PERFORMANCE CALCULATIONS. | | | THE SUBMITTED DOCUMENTS FROM COMCHECK ARE NOT ADOPTED | | | BY THE FLORIDA BUILDING CODE OR PERMITTED IN THE STATE | | | OF FLORIDA. THE PREVIOUS CODE SECTIONS GIVEN WERE | | | STATED BASED ON THE CODE IN EFFECT AT THE TIME OF THE | | | PLAN REVIEW SUBMISSION. SINCE THAT TIME AS STATED IN | | | NOTE #1, THE STATE HAS ADOPTED A NEW CODE. | | | PLEASE SEE FBC CHAPTER 13 2007 EDITION WITH 2009 GLITCH | | | AMENDMENTS. THIS CHAPTER WAS COMPLETELY REVISED FROM | | | THE FIRST PRINTING OF THE 2007 FBC. THERE ARE | | | SUBSTANTIAL CHANGES WHICH WILL AFFECT THIS PROJECT. | | | ** PLEASE SUBMIT LIGHTING PERFORMANCE CALCULATIONS PER | | | 13-415.2, 13-415.AB.5, 13-415.AB.5.1, 13-415.B | | | THESE SECTIONS FOR LIGHTING PERFORMANCE CALCULATIONS | | | HAVE BEEN COMPLETELY REVISED. | | | | | | ** ONCE AGAIN THE SUBMITTED COMCHECK CALCULATIONS ARE | | | NOT PERMITTED AND CAN NOT BE USED IN THE STATE OF | | | FLORIDA. ONE COPY HAS BEEN RETAINED BY THIS OFFICE. | | | | | | ** IT IS ALSO IMPORTANT TO KNOW THAT THE INPUT DATA | | | REPORT WHICH WILL ACCOMPANY THE SUBMITTED ENERGY | | | CALCULATIONS MUST COORDINATE WITH ALL COMPONENTS OF | | | CONSTRUCTION AS SHOWN ON PLANS. THIS INCLUDES ALL | | | LIGHTING FROM PLANS, FIXTURE LEGEND ETC. | | | | | | 3) NOTE: AS STATED IN PREVIOUS REVIEW PLEASE SUBMIT AND | | | SHOW LIGHTING CONTROLS MEETING MINIMUM CODE COMPLIANCE. | | | THE RESPONSE MENTIONS TO SEE 210 AND 220 HOWEVER THE | | | ONLY ITEM ON THOSE SHEETS ARE NOTES TO PROVIDE A SYSTEM | | | OF SOME SORT. PLACING A NOTE ON PLANS IN LIEU OF ACTUAL | | | DETAILS OR DESIGN OF A CODE COMPLIANT SYSTEM IS NOT | | | PERMITTED. MUST SHOW CODE COMPLIANCE. PLEASE KNOW THE | | | CODE SECTIONS UNDER THE 2007 FBC HAVE NOW BEEN REVISED. | | | PLEASE SEE THE FOLLOWING SECTIONS. 13-415.AB.1.1, .1.2 | | | AND .1.3 | | | | | | | | | 4) NOTE: THIS IS A NEW NOTE: BY DEFINITIONS IN THE FBC, | | | ARE THESE TWO SEPARATE BUILDINGS? IS THE WALL WITH NEW | | | OPENINGS A FIRE WALL? PLEASE SEE DEFINITIONS OF FIRE | | | WALL. | | | IF THESE ARE TWO SEPARATE BUILDINGS, ON TWO SEPARATE | | | SERVICES AND NOW BECOMING ONE BUILDING THEN SOME | | | CLARIFICATION AND CHANGES IN DOCUMENTS MAY BE NEEDED. | | | THERE CAN BE OPENINGS IN FIRE WALLS HOWEVER THERE ARE | | | REQUIREMENTS FOR OTHERS TRADES INCLUDING ELECTRICAL. | | | PLEASE PROVIDE THE COMPLETE RISER DIAGRAM FOR ALL | | | SERVICE EQUIPMENT ON THESE BUILDINGS. THE WALMART WHICH | | | IS LOCATED IN THIS SAME SHOPPING CENTER IS A SEPARATE | | | BUILDING WITH FIRE WALL SEPARATION AND IS NOT PART OF | | | THESE TWO BUILDINGS. THE WALMART SECTION IS NOT PART OF | | | THIS QUESTION. | | | BASED ON THE ARCHITECTURAL SHEETS THESE APPEAR TO BE | | | POSSIBLY BE TWO BUILDINGS WHICH EXIST BEING MADE INTO | | | ONE. | | | BASED ON RISER THERE SEEMS TO BE TWO SEPARATE | | | ELECTRICAL SERVICES WHICH WOULD NOW BE FED FROM ONE | | | GENERATOR. | | | BONDING OF SERVICES, ETC ARE NOT KNOWN. | | | THERE IS A 400 AMP BREAKER FEEDING NEW ATS TO PANEL D | | | HOWEVER THE CONDUCTORS AS SHOWN ARE ONLY RATED FOR | | | 200AMPS. 310.16, 240.4 RISER DOES NOT INDICATE PARALLEL | | | FEEDERS. | | | | | | *** PLEASE GO OVER DESIGNS FOR MINIMUM CODE COMPLIANCE. | | | | | | ** ONCE AGAIN THERE ARE SOME ITEMS NOT SUBMITTED OR | | | KNOW AT THIS TIME AND THERE MAY BE NEW COMMENTS ON THE | | | FOLLOWING REVIEW WHICH CAN NOT BE MADE AT THIS TIME. | | | ONE SET OF PLANS FOR ELECTRICAL WILL ALSO BE RETAINED | | | BY THIS OFFICE. | | | | | | | | | ** IMPORTANT ** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED | | | INTO TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2008-12-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-12-01 |
Time |
17:48 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-12-01 |
Time |
17:48 |
Sent To |
|
|
| Notes |
| 2008-12-01 17:48:27 | | | | ** DENIED ** | | | | | | | | | 1) NOTE: PLANS ONLY SUBMITTED FOR PLAN REVIEW. PLEASE | | | KNOW EVEN ONCE PLANS ARE FOUND TO BE CODE COMPLIANT AND | | | PERMIT APPLICATION HAS NOT BEEN MADE THE REVIEW WILL | | | STILL REMAIN IN A FAILED STATUS. VERIFICATION OF | | | LICENSING AND SEVERAL OTHER ITEMS WILL TAKE PLACE ONCE | | | PERMIT APPLICATION IS MADE. | | | | | | 2) NOTE: PLEASE SEE FLORIDA STATUTES 481.221 AS THE | | | ONLY SEAL PERMITTED IS REQUIRED TO BE A RAISED | | | IMPRESSION TYPE SEAL. SOME DOCUMENTS AND SHEETS | | | SUBMITTED CONTAIN A *RUBBER-STAMPED* SEAL WHICH IS NOT | | | PERMITTED. | | | ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY | | | ANY OTHER TRADE FOR ALL SHEETS. | | | | | | 3) NOTE: PLEASE SEE THE SEAL ON SHEETS WHICH IS AN | | | IMPRESSION TYPE SEAL IS NO LONGER ACCEPTABLE IN THE | | | STATE OF FLORIDA. PLEASE SEE FLORIDA ADMINISTRATIVE | | | CODE 61G1-16.002 FOR CORRECT TYPE OF SEAL. THE INITIAL | | | RULING OF A 2INCH SEAL WAS ADOPTED IN 1989. THIS HAS | | | SINCE BEEN UPDATE HOWEVER HAS BEEN A REQUIREMENT FOR | | | ALMOST 20YEARS. | | | ** THIS IS REQUIRED WHETHER OR NOT THE COMMENT IS MADE | | | BY ANY OTHER TRADES FOR ALL SHEETS. | | | | | | 4) NOTE: PLEASE SEE THE TITLE BLOCKS ARE MISSING THE | | | REQUIRED CERTIFICATE OF AUTHORIZATION NUMBER FOR THE | | | ARCHITECTURAL FIRM. THIS IS REQUIRED ON TITLE BLOCKS | | | PER FAC61G1-16.004 AND PER FLORIDA STATUTES 481.219 | | | | | | 5) NOTE: PLEASE SEE THE TITLE BLOCKS ARE MISSING THE | | | REQUIRED CERTIFICATE OF AUTHORIZATION NUMBER FOR | | | ENGINEERING BUSINESS/FIRM PER FLORIDA ADMINISTRATIVE | | | CODE (FAC 61G15-23.002) AND FS 471.023 | | | | | | 6) NOTE: PLEASE SEE THE TITLE BLOCKS ARE REQUIRED TO | | | CONTAIN THE PRINTED NAME AND PRINTED LICENSE NUMBER OF | | | THE DESIGNER. FAC 61G1-16.002, 61G15-23.002. | | | ** REQUIRED FOR ALL TRADES AND FOR ALL SHEETS WHETHER | | | OR NOT COMMENT IS MADE BY OTHER TRADES. | | | | | | 7) NOTE: PLEASE SEE THE RAISED SEAL WHICH DISPLAYS A | | | LICENSE NUMBER. THE NUMBER AS PRINTED IN SEAL IS: | | | AR90016025. THERE IS NO RECORD OF THIS LICENSE NUMBER | | | ON THE DEPARTMENT OF BUSINESS AND PROFESSIONAL | | | REGULATION WEBSITE. THE NUMBER AS LISTED ABOVE WITHOUT | | | THE *9* IS A RELEVANT NUMBER. | | | PLEASE ADJUST SEAL. | | | ** REQUIRED FOR ALL TRADES AND FOR ALL SHEETS WHETHER | | | OR NOT COMMENTS IS MADE BY OTHER TRADES REVIEWERS. | | | | | | 8) NOTE: PLEASE SEE THE PRINT OUT ATTACHED TO NOTES AS | | | THE ADDRESS ON PLANS DOES NOT CORRELATE WITH THE TITLE | | | BLOCKS. IN FACT THE STATE SITE LISTS AN ADDRESS OF | | | 15380 KATA DR. ELM GROVE, WISCONSIN 53122. | | | PLEASE CORRECT PLANS AND TITLE BLOCKS OR CONTACT THE | | | DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION TO | | | UPDATE INFORMATION. | | | ** REQUIRED FOR ALL TRADES AND FOR ALL SHEETS WHETHER | | | OR NOT COMMENT IS MADE BY OTHER TRADE REVIEWERS. | | | | | | 9) NOTE: THE CODES RELEVANT TO PROJECT ARE REQUIRED TO | | | MEET ADOPTED CODES UNDER FS 553.73. PLEASE SEE THAT THE | | | PLANS ARE CURRENTLY LISTING CODES WHICH ARE NO LONGER | | | ADOPTED IN THE STATE OF FLORIDA. SOME SUCH AS THE 2002 | | | NATIONAL ELECTRICAL CODE AS SHOWN AS NOT BEEN IN EFFECT | | | SINCE DECEMBER 2006. | | | THE CODES FOR THIS REVIEWER ALONE SHOULD BE STATED AS | | | FOLLOWS. | | | | | | 2004 FBC W/2007 REVISIONS. | | | 2005 NFPA-70. ( NEC) | | | 2003 NFPA-101 | | | 2002 NFPA-72 | | | * PLEASE NOTE, THE NFPA-72 MAY OR MAY NOT BE APPLICABLE | | | TO THIS PROJECT. | | | | | | 10) NOTE: PLEASE SEE FBC 13-106.1.1. THE SUBMIT ENERGY | | | CALCULATIONS ARE METHOD *A* WHICH IS FOR WHOLE BUILDING | | | COMPLIANCE. PLEASE SEE DEFINITIONS IN SECTION 202 AS | | | THIS IS NOT A WHOLE BUILDING OR NEW CONSTRUCTION. | | | PLEASE PROVIDE LIGHTING PERFORMANCE CALCULATIONS PER | | | 13-415.2,13-415.2.ABC.1.1, .1.2. | | | | | | 11) NOTE: PLEASE SEE 13-413.1.ABC.2.1 AND .2.2 AND | | | PLACE NOTES ON PLANS ACCORDINGLY. | | | | | | 12) NOTE: PLEASE SEE FBC 11-4.27.4 AS THE LIGHTING | | | CONTROLS NOTED AS *SPRING WOUND* TIMERS ARE NOT | | | PERMITTED. | | | MUST MEET ADA REQUIREMENTS. | | | | | | 13) NOTE: PLANS INDICATE ELECTRICAL PANELS IN WHAT | | | WOULD BE A CLOSET FOR STORAGE OF SUPPLIES. | | | PLEASE SEE 110.26,240.24D AND 408.17 AS ELECTRICAL | | | EQUIPMENT ALONG WITH OVER CURRENT PROTECTION IS NOTED | | | PERMITTED IN AREAS WHERE THERE IS STORAGE OF EASILY | | | IGNITABLE MATERIALS OR COMBUSTIBLES. | | | | | | 14) NOTE: PLEASE INCLUDE LIGHTING CONTROLS AS REQUIRED | | | PER 13-415.1.ABC.1.1,.1.2 AND .1.3. | | | | | | 15) NOTE: PLEASE SEE FBC 11-4.28.1, .2 AND .3 FOR ALL | | | MINIMUM LEVELS FOR DEVICES OF FIRE ALARM SYSTEM. | | | PLEASE BE SURE ALL DEVICE HEIGHTS AND LEVELS ARE SHOWN. | | | ** NOTE MINIMUM CANDELA LEVELS FOR STROBE DEVICES ARE | | | 75CD | | | | | | 16) NOTE: PLEASE OBTAIN THE LATEST ELECTRICAL RISER FOR | | | THIS SPACE. IT IS UNDERSTOOD THIS SAME TENANT HAS | | | OBTAINED PERMITS FOR NEW GENERATOR AND ELECTRICAL | | | EQUIPMENT WHICH IS NOT PART OF THE CURRENT SUBMITTED | | | ELECTRICAL PLANS. | | | 230,220,215,240 ETC | | | FBC 106.1.1 FOR CLARITY AND COORDINATION OF PLANS. | | | | | | 17) NOTE: PLEASE SHOW ALL CONTINUOUS LOADS SUCH AS | | | LIGHTING AT 125%. 215.3,230.42 ETC | | | | | | ** IT IS IMPORTANT TO KNOW AS THERE ARE SOME ITEMS NOT | | | YET SUBMITTED FOR REVIEW THERE MAY BE NEW COMMENTS ON | | | THE FOLLOWING REVIEW WHICH CAN NOT BE MADE AT THIS | | | TIME. | | | | | | 18) NOTE: DOCUMENTATION HAS BEEN ROUTED TO THE | | | ADDRESSING REVIEWER. THIS WILL BE ONE TENANT SPACE AND | | | ADDRESS SHOULD BE LISTED UNDER A PRIME SUITE OR UNIT | | | NUMBER. THE PLANS AND PLAN REVIEW APPLICATION IS | | | PRESENTLY SUBMITTED AS THREE SEPARATE UNITS/SPACES. | | | ONCE FINAL ADDRESS IS DETERMINED PLEASE ADJUST TITLE | | | BLOCKS. | | | FAC 61G1-16.004, 61G15-23.002 | | | FBC 106.5 | | | | | | 19) NOTE: PLEASE BE SURE ALL ELECTRICAL SERVICE | | | EQUIPMENT ONCE REVISED IS LABELED ACCORDINGLY. TENANT | | | DISCONNECTS AND MAINS NEED IDENTIFICATION IN ANY EVEN | | | THE POWER NEEDS TO BE SHUT DOWN. | | | 230.2E ECT. | | | | | | | | | **IMPORTANT** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED | | | INTO TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2008-12-26 |
Time |
|
Rev Time |
1.00 |
| Received By |
|
Date |
2008-12-26 |
Time |
|
Sent To |
ENG |
|
| Notes |
| 2008-12-26 13:47:39 | ********* PASSED ********** | | | | | | NO NEED FOR CITY OF WPB ENGINEERING TO SEE. | | | LOCATION SERVED THRU MASTER WATER METER TO SHOPPING. | | | FIRELINE PROPTECTION IS ALSO AVAILABLE ON-SITE. | | | IF ANY CONNECTION IS MADE TO FIRELINE AN ENGINEER OF | | | RECORD | | | WOULD HAVE TO CERTIFY TO THE CITY. PLUMBING AND FIRE | | | DEPARTMENT | | | WOULD BE LEAD ON THE REVIEW AND ACCEPTANCE. | | | | | | ANY QUESTIONS: | | | | | | MANUEL J GONZALEZ, PROJECT COORDINATOR | | | LOCATION ADDRESS: | | | CITY OF WEST PALM BEACH | | | ENGINEERING SERVICES DEPARTMENT | | | 1000 - 45TH STREET, SUITE 15 | | | WEST PALM BEACH FL 33407 | | | MAILING ADDRESS: | | | CITY OF WEST PALM BEACH | | | ENGINEERING SERVICES DEPARTMENT | | | P.O. BOX 3506 | | | WEST PALM BEACH FL 33401 | | | TELEPHONE: | | | 45TH STREET OFFICE : 561-494-1040 | | | 45TH DIRECT: 561-494-1085 | | | FAX: 561-494-1117 | | | CITY HALL OFFICE: (561) 805-6713 | | | CITY HALL DIRECT: (561) 805-6313 | | | CITY HALL FAX: (561) 805-6731 OR 805-6676 | | | | | | NEXTEL CELL: 561-644-7301 | | | | | | NEXTEL DIRECT CONNECT: 159*28165*38 | | | EMERGENCIES: | | | CENTRAL OPERATIONS CENTER (DISPATCH) 561-822-2210 | | | E-MAIL: | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2009-05-18 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-05-18 |
Time |
15:12 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-05-18 |
Time |
14:07 |
Sent To |
|
|
| Notes |
| 2009-05-18 15:08:48 | *****APPROVED***** | | | | | | | | | THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE | | | BEEN ADDRESSED; PLAN SHEETS A210, A211, A810, E210, AND | | | E230 WERE STAMPED, INITIALED, AND DATED. | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2009-04-03 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2009-04-03 |
Time |
14:26 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2009-04-03 |
Time |
14:26 |
Sent To |
|
|
| Notes |
| 2009-04-03 14:31:44 | ***DENIED*** | | | | | | 1) OK PLEASE NOTE THAT PLANS WERE SUBMITTED FOR REVIEW | | | ONLY PRIOR TO DEC. 31, 2008 HOWEVER DESIGNS FOR LIFE | | | SAFET THAT ARE SUBMITTED FOR PERMIT REVIEW AFTER THAT | | | DATE SHALL COMPLY WITH NFPA 101, 2006. | | | | | | 6) SHEET E210 ILLUSTRATES THE EXTERIOR DOOR IN ROOM 107 | | | AS AN EXIT BUT SHOWS THE DOOR AS BEING REMOVED ON SHEET | | | A210. | | | | | | | | | PLANS WILL REMAIN IN FAILED STATUS UNTIL SUBMITTED FOR | | | REVIEW UNDER PERMIT APPLICATION. | | | | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2008-12-11 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-12-11 |
Time |
12:11 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-12-11 |
Time |
12:11 |
Sent To |
|
|
| Notes |
| 2008-12-11 12:20:35 | ***DENIED*** | | | | | | 1) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003 | | | EDITION. ADD TO APPLICABLE CODES. | | | | | | 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY | | | WITH NFPA 241. ADD TO APPLICABLE CODES. | | | | | | 3) PLEASE INDICATE MINIMUM INTERIOR FINISH | | | CLASSIFICATION FOR WALSS AND CEILING IN TERMS OF CLASS | | | A,B OR C. | | | | | | 4) IN ADDITION TO SEPARATE PERMIT PROCESS, INDICATE THE | | | FIRE SPRINKLER HEAD LAYOUT THAT MAY BE SHOWN ON THE | | | RELECTED CEILING PLAN. | | | | | | 5) DUCT SMOKE DETECTORS SHALL BE PROVIDED IN SUPPLY | | | DUCT UNLESS UNITS ARE LARGE ENOUGH FOR BOTH SUPPLY AND | | | RETURN. DUCT SMOKE DETECTORS SHALL BE TIED INTO THE | | | FIRE ALARM SYSTEM IF APPLICABLE AND INITIATE A GENERAL | | | FIRE ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS. | | | | | | 6) PLANS SEEM TO SUGGEST EXITING THROUGH STORAGE/WORK | | | ROOMS. SPECIFIC AREAS WOULD PROVIDE AN AREA OF GREATER | | | HAZARD. PLEASE PROVIDE INFORMATION THAT WOULD ALLOW | | | THIS ARRANGEMENT. | | | | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2009-05-08 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-05-08 |
Time |
09:51 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-05-08 |
Time |
09:51 |
Sent To |
|
|
| Notes |
| 2009-05-08 09:51:58 | C27 PROJECT TO PERMIT |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2009-02-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2009-02-18 |
Time |
12:46 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2009-02-18 |
Time |
12:46 |
Sent To |
|
|
| Notes |
| 2009-02-18 12:46:34 | TO "COMM" BD#32 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2008-12-26 |
Time |
|
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-11-12 |
Time |
11:53 |
Sent To |
|
|
| Notes |
| 2008-11-12 11:56:54 | TO "COMM" BD#48 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2009-05-27 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-05-27 |
Time |
08:59 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-05-27 |
Time |
08:59 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2009-05-15 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-05-15 |
Time |
10:03 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-05-15 |
Time |
09:37 |
Sent To |
|
|
| Notes |
| 2009-05-15 10:03:43 | ALL PREVIOUS REVIEW COMMENTS HAVE BEEN ADDRESSED. | | | HOWEVER, ONE OF THE TWO SETS OF PLANS WHICH WERE | | | SUBMITTED CONTAINS A PREVIOUS VERSION OF SHEET M210. | | | PLEASE PROVIDE TWO COMPLETE UPDATED SETS OF PLANS WITH | | | APPLICATION FOR PERMIT ISSUANCE IN ACCORDANCE WITH | | | FBC-B 106.1. PLANS WILL BE STAMPED IF THE SECOND SET OF | | | PLANS ARE CORRECTED DURING THIS REVIEW CYCLE. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2009-03-27 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-03-27 |
Time |
11:23 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-03-27 |
Time |
08:10 |
Sent To |
|
|
| Notes |
| 2009-03-27 11:23:07 | REVIEW #: 2ND **PLAN CHECK ONLY** | | | ACTION: DENIED | | | | | | THIS PROJECT REVIEWED FOR COMPLIANCE WITH THE FOLLOWING | | | CODES: | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | NOTE: PLANS STILL SUBMITTED FOR PLAN REVIEW WITH NO | | | PERMIT APPLICATION. PLANS ARE NOW SUBJECT TO THE | | | REQUIREMENTS OF THE 2007 FLORIDA BUILDING CODE WHICH | | | WENT INTO EFFECT ON MARCH 1, 2009. PLANS WILL REMAIN IN | | | FAIL STATUS PENDING SUBMISSION OF AN ACTUAL PERMIT | | | APPLICATION. | | | | | | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH | | | PREVIOUS REVIEW COMMENTS. | | | | | | 1. OK | | | | | | 2. OK | | | | | | 3. **PREVIOUS COMMENT**PLANS CALL FOR NEW RTU AND | | | EXHAUST FAN TO BE INSTALLED ON ROOF. NO INFORMATION | | | COULD BE FOUND ON PLANS REGARDING WIND RESISTANCE. | | | MECHANICAL APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO | | | WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND | | | PRESSURES ON THE EQUIPMENT AND THE SUPPORTS AS | | | DETERMINED IN ACCORDANCE WITH FBCB SECTION 1609 PER | | | FBCM 301.13. PROVIDE ATTACHMENT DETAIL SHOWING ROOF | | | CURBS TO BUILDING STRUCTURE AND RTU/EF TO ROOF CURB | | | ATTACHMENTS. ALSO, PLEASE PROVIDE MANUFACTURER'S DATA | | | SHOWING THESE APPLIANCES ARE DESIGNED TO RESIST WIND | | | PRESSURES IN ACCORDANCE WITH THIS SECTION. | | | **NOT ADDRESSED**: THE WIND LOAD CALCULATIONS PROVIDED | | | ARE FOR THE ATTACHMENT OF THE RTU TO THE ROOF AND DO | | | NOT PROVIDE INFORMATION REGARDING THE WIND RESISTANCE | | | CAPABILITIES OF THE RTU ITSELF. PLEASE SHOW COMPLIANCE | | | WITH FBC-M 301.12. ALSO, THE MANUFACTURER'S DATA FOR | | | THE ROOTOP FAN INDICATE THE FAN IS DESIGNED FOR 130 MPH | | | WINDS. ACCORDING TO THE WIND MAPS FOUND INH FBC-B 1609, | | | THE CITY OF WEST PALM BEACH IS IN THE 140 MPH WIND | | | ZONE. FAN SHALL BE DESIGNED FOR THE PROPER WIND ZONE IN | | | ACCORDANCE WITH THESE SECTIONS. | | | NOTE: ALL WIND RESISTANCE DOCUMENTATION PROVIDED WILL | | | BE REVIEWED BY THE BUILDING (STRUCTURAL) PLANS | | | EXAMINER. | | | | | | 4. OK | | | | | | 5. OK | | | | | | 6. OK | | | | | | 7. OK | | | | | | NOTE: PLEASE RESPOND TO EACH COMMENT IN WRITING, WITH | | | INFORMATION ON HOW EACH COMMENT WAS ADDRESSED AND WHERE | | | THE RELEVANT INFOAMTION CAN BE FOUND. THIS WILL HELP TO | | | FACILITATE A TIMELY REVIEW UPON RESUBMISSION. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2008-11-22 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-11-22 |
Time |
16:06 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-11-22 |
Time |
15:30 |
Sent To |
|
|
| Notes |
| 2008-11-22 16:06:04 | REVIEW #: 1ST **PLAN CHECK ONLY** | | | ACTION: DENIED | | | | | | THIS PROJECT REVIEWED FOR COMPLIANCE WITH THE FOLLOWING | | | CODES: | | | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | THE FOLLWING COMMENTS SHALL BE ADDRESSED PRIOR TO | | | RESUBMISSION OF PLANS WITH PERMIT APPLICATION: | | | | | | 1. THE DESIGN PROFESSIONAL MUST ELECT ONE OR A | | | COMBINATION OF LEVELS OF ALTERATION PURSUANT TO | | | SECTIONS 303, 304 AND 305 OF THIS CODE IN ACCORDANCE | | | WITH FBCEB 301.5. PLEASE SHOW THIS ON PLANS WITH THE | | | PROJECT INFORMATION. | | | | | | 2. ALL RECONFIGURED SPACES INTENDED FOR OCCUPANCY AND | | | ALL SPACES CONVERTED TO HABITABLE OR OCCUPIABLE SPACE | | | IN ANY WORK AREA SHALL BE PROVIDED WITH NATURAL OR | | | MECHANICAL VENTILATION OR EXHAUST IN ACCORDANCE WITH | | | THE FLORIDA BUILDING CODE, MECHANICAL PER FBCEB 609.1. | | | PROVIDE VENTILATION CALCULATIONS FOR ALL RECONFIGURED | | | SPACES IN ACCORDANCE WITH FBCM SECTION 403. | | | | | | 3. PLANS CALL FOR NEW RTU AND EXHAUST FAN TO BE | | | INSTALLED ON ROOF. NO INFORMATION COULD BE FOUND ON | | | PLANS REGARDING WIND RESISTANCE. MECHANICAL APPLIANCES | | | AND SUPPORTS THAT ARE EXPOSED TO WIND SHALL BE DESIGNED | | | AND INSTALLED TO RESIST THE WIND PRESSURES ON THE | | | EQUIPMENT AND THE SUPPORTS AS DETERMINED IN ACCORDANCE | | | WITH FBCB SECTION 1609 PER FBCM 301.13. PROVIDE | | | ATTACHMENT DETAIL SHOWING ROOF CURBS TO BUILDING | | | STRUCTURE AND RTU/EF TO ROOF CURB ATTACHMENTS. ALSO, | | | PLEASE PROVIDE MANUFACTURER'S DATA SHOWING THESE | | | APPLIANCES ARE DESIGNED TO RESIST WIND PRESSURES IN | | | ACCORDANCE WITH THIS SECTION. | | | | | | 4. PLANS CALL FOR DUCT SMOKE DETECTOR TO BE INSTALLED | | | IN THE RETURN DUCT FOR RTU. SMOKE DETECTORS SHALL BE | | | INSTALLED IN SUPPLY AIR SYSTEMS WITH A DESIGN CAPACITY | | | GREATER THAN 2,000 CFM, IN THE SUPPLY AIR DUCT IN | | | ACCORDANCE WITH FBCM 606.2.1. | | | | | | 5. MECHANICAL FLOOR PLAN SHOWS FLEX DUCTS ATTACHED | | | DIRECTLY TO FIRE DAMPERS. PROVIDE FD MANUFACTURER'S | | | INSTALLATION INSTRUCTIONS SHOWING HOW FLEX DUCT IS TO | | | BE ATTACHED TO THE DAMPERS. FIRE DAMPERS AND | | | COMBINATION FIRE/SMOKE DAMPERS SHALL BE INSTALLED IN | | | ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION | | | INSTRUCTIONS AND LISTING PER FBCM 607.2. | | | | | | 6. SHOW HOW DUCT ACCESS DOORS ARE TO BE INSTALLED AT | | | THESE LOCATIONS. A SERVICE OPENING (DUCT ACCESS DOOR) | | | SHALL BE PROVIDED IN AIR DUCTS ADJACENT TO EACH FIRE | | | DAMPER, SMOKE DAMPER, AND DUCT SMOKE DETECTOR. THE | | | OPENING SHALL BE LARGE ENOUGH TO PERMIT MAINTENANCE AND | | | RESETTING OF THE DEVICE. SERVICE OPENINGS SHALL BE | | | IDENTIFIED WITH LETTERS HAVING A MINIMUM HEIGHT OF 1/2 | | | INCH TO INDICATE THE LOCATION OF THE FIRE PROTECTION | | | DEVICE(S) WITHIN THE DUCT IN ACCORDANCE WITH FBCM | | | 301.15 AND NFPA 90A-2002. | | | | | | 7. EXHAUST/RETURN DETAIL CALLS FOR LINED GRILL CANS AND | | | INSULATED FLEX. ALL EXHAUST DUCTS SHALL BE OF METAL | | | (NON-LINED) AND SUCH CONSTRUCTION SHALL COMPLY WITH | | | FBCM 501.4. | | | | | | NOTE: THE SUBMITTED METHOD A ENERGYCALCULATIONS WERE | | | NOT REVIEWED FOR COMPLIANCE WITH THE MECHANICAL | | | PROVISIONS OF THE FLORIDA ENERGY CODE (FBCB CHAPTER | | | 13). THIS PROJECT IS NOT NEW CONSTRUCTION, IS NOT A | | | WHOLE BUILDING AND DOES NOT MEET THE DEFINITION OF A | | | RENOVATION (SEE FBCB SECTION 13-202) AND THEREFORE ONLY | | | COMPLIANCE WITH FBCB 13-101.6 NEEDS TO BE DEMONSTRATED. | | | | | | NOTE: PLEASE RESPOND TO EACH COMMENT IN WRITING, WITH | | | INFORMATION ON HOW EACH COMMENT WAS ADDRESSED AND WHERE | | | THE RELEVANT INFOAMTION CAN BE FOUND. THIS WILL HELP TO | | | FACILITATE A TIMELY REVIEW UPON RESUBMISSION. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2009-05-11 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-05-11 |
Time |
14:51 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-05-11 |
Time |
14:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2009-03-25 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-03-25 |
Time |
12:19 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-03-25 |
Time |
12:19 |
Sent To |
|
|
| Notes |
| 2009-03-25 14:00:44 | DENIED | | | REFERENCE: | | | FBC-2007 | | | | | | **********NEW COMMENT********** | | | | | | 1B. SINCE THE APPLICATION FOR PERMIT WAS NOT SUBMITTED | | | PRIOR TO MARCH 1, 2009 THE DESIGN CRITERIA SHALL NOW BE | | | FBC-2007. PLEASE CHANGE THE CODE REFERENCE ON SHTS "T", | | | P210 OR ANY OTHER SHEET THAT REFERENCES THE FBC-2004 | | | CODE TO REFLECT THIS CHANGE. -- PLUMBING REVIEW WILL | | | REMAIN IN FAILED STATUS UNTIL THIS CHANGE IS MADE AND | | | THE APPLICATION IS SUBMITTED. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2008-12-05 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-12-05 |
Time |
15:02 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-12-05 |
Time |
15:02 |
Sent To |
|
|
| Notes |
| 2008-12-05 15:52:46 | PLAN REVIEW DENIED | | | REFERENCE: | | | FBC-2004 PLUMBING | | | FBC-2004 EXISTING BUILDING CODE | | | FBC-2004 CHAPTER 1 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | CITY WPB MUNICIPAL CODE | | | | | | 1. SHT "T" THE DESIGN CRITERIA SHALL INCLUDE THE 2005, | | | 2006 & 2007 REVISIONS TO THE 2004 FLORIDA BUILDING | | | CODE. SECTION 106.1.1. | | | | | | 2. SHT "T" INDICATE THE LEVEL OF ALTERATION AS REQUIRED | | | IN CHAPTER 3 OF THE FBC-2004 EXISTING BUILDING CODE. | | | | | | 3. SHT "T" AN IMPRESSION TYPE SEALING COMPLYING WITH | | | FAC 61G1-16.001, 61G1-16.002 & FS 481.2055 IS REQUIRED. | | | STAMP TYPE SEALS ARE NOT APPROVED. | | | | | | 4. ALL SHEETS REQUIRE THE CERTIFICATE OF AUTHORIZATION | | | NUMBER FOR THE ENGINEERING FIRM, (APPLIED FOR - SEE | | | ATTACHED SHEET), AND FOR THE ARCHITECT, (NOT FOUND), IN | | | THE TITLE BLOCK OF EACH SHEET. FAC 61G15-23.002, | | | 61G1-16.004(2) & FS 471.025, 481.219, 481.2055. | | | | | | 5. ALL SHEETS REQUIRE THE PRINTED NAME OF THE PERSON | | | SEALING THE DOCUMENTS. FAC 61G1-16.004(6), FAC | | | 61G15-23.002(2) & FS 471.025 & 481.2055. | | | | | | 6. THE SEAL AFFIXED TO THE SHEETS IS NOT APPROVED. SEAL | | | SHALL BE APPROXIMATELY 2 INCHES IN DIAMETER. ALSO THE | | | ARCHITECTURAL NUMBER ON THE SEAL, AR90016025 DOES NOT | | | REFLECT THE NUMBER INDICATED ON THE STATE OF FLORIDA | | | DBPR WEBSITE FOR LICENSURE. PLEASE CORRELATE. FAC | | | 61G1-16.001, 61G1-16.002 & FS 481.2055. | | | | | | 7. SHTS P210 & P215 IN THE INSTALLATION OR REMOVAL OF | | | OF ANY PART OF A DRAINAGE SYSTEM, DEAD ENDS SHALL BE | | | PROHIBITED. DISCONNECT ALL DRAINAGE A MAXIMUM OF 2 FEET | | | FROM ACTIVE BUILDING DRAIN LINES. ALL PIPING CAPPED FOR | | | DEMOLITION SHALL REMAIN UNCOVERED UNTIL INSPECTED AND | | | APPROVED BY THE FIELD INSPECTOR. SECTION 704.5. PLEASE | | | INDICATE ON THE DEMO SHEET THE LOCATION OF ALL | | | CAPPED/ABANDONED PIPING. | | | | | | 8. SHT P210 THE ABANDONED GREASE INTERCEPTOR SHALL BE | | | PUMPED OUT, AND REMOVED, OR IT SHALL BE PUMPED OUT, THE | | | BOTTOM SHALL BE SUITABLY OPENED OR RUPTURED SO AS TO | | | PREVENT THE INTERCEPTOR FROM RETAINING WATER AND FILLED | | | WITH CLEAN SAND OR OTHER SUITABLE MATERIAL, THE ACTIONS | | | BEING TAKEN IN THE ORDER LISTED. ARTICLE III SECTION | | | 90-123, (CODE 1979 & 31-60). | | | | | | 9. SHT P210 INDICATE WHAT DRAINS INTO FIXTURE P-16 & | | | P30 F.S. SECTION 106.1.2. | | | | | | 10. SHT P210 IDENTIFY THE FIXTURES CONNECTING TO DSP | | | AND SUBMIT A DETAIL SHOWING HOW THEY ARE CONNECTED. | | | SECTION, 106.1.2, | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2008-11-14 |
|
|
Cont ID |
|
| Sent By |
kdfreema |
Date |
2008-11-14 |
Time |
11:56 |
Rev Time |
0.00 |
| Received By |
kdfreema |
Date |
2008-11-14 |
Time |
11:56 |
Sent To |
|
|
| Notes |
| 2008-11-14 11:57:11 | INTERIOR RENOVATION ONLY. |
|
|
|