Plan Review Details - Permit 08110178
Plan Review Stops For Permit 08110178
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2008-12-02 Cont ID  
Sent By jnguyen Date 2008-12-02 Time 11:49 Rev Time 0.00
Received By jnguyen Date 2008-12-02 Time 08:08 Sent To  
Notes
2008-12-02 11:31:54UPON EXAMINATION OF THE SITE PLANS, I HAVE DETERMINED
 THAT THIS PERMIT HAS BEEN ATTACHED TO THE WRONG PCN#
 74424322080010020 WHEN IT SHOULD ACTUALLY BE APPLIED TO
 PCN# 74424322080010010 INSTEAD. THE PERMIT IS TO
 RENOVATE THE EXISTING SPACE OF THE TENANT'S (FRESENIUS
 MEDICAL CARE) AT 6901 OKEEECHOBEE BLVD SUITE # D19, AS
 WELL AS MERGE WITH THE AREAS OF SUITES # D23 & # E1
 (THEY ARE SPACES TO THE SOUTHEAST OF THE WAL-MART
 NEIGHBORHOOD MARKET.). THE ADDRESSES OF THESE SUITE
 NUMBERS CURRENTLY EXIST IN COMMUNITYPLUS UNDER PCN#
 74424322080010010 AS UNIT 0023 - # D19, UNIT 0024 - #
 D23 & UNIT 0025 - # E1. IN COMMUNITYPLUS, THIS PERMIT
 SHOULD BE ATTACHED TO PCN# 74424322080010010,
 SPECIFICALLY UNIT 0023 - 6901 OKEECHOBEE BLVD # D19
 (SINCE # D23 & # E1 ARE GOING TO BE EXPANDED AS A PART
 # D19). I HAVE ALREADY MADE THE CORRECTION OF PCN#
 74424322080010010 ON THE ORIGINAL PERMIT APPLICATION,
 BUT I DO NOT HAVE AUTHORIZATION TO CORRECT IT IN THE
 COMMUNITYPLUS SYSTEM.
  
 *PLEASE NOTE THAT JAMES HAS BROUGHT TO MY ATTENTION
 THAT THESE SUITE # ADDRESSES DO NOT CONFORM TO OUR
 ADDRESSING POLICY, IN THAT EACH COMMERCIAL BUSINESS
 MUST HAVE THEIR OWN UNIQUE NUMERICAL ADDRESS. POLICY
 SECTION 1.4 ADDRESSING FOR COMMERCIAL STRUCTURES: STRIP
 MALLS & OTHER COMMERCIAL BUSINESSES WILL EACH BE ISSUED
 A RANGE OF UNIQUE ADDRESS NUMBERS FROM THE DRIVEWAY
 ACCESS. MULTIPLE COMMERCIAL STRUCTURES ON CORNER LOTS
 SHALL BE ASSIGNED AN ADDRESS NUMBER FROM THE ROAD
 PARALLEL WITH THE PRIMARY ENTRANCE OF THE BUILDING.
 JAMES HAS STRONGLY ADVISED THAT I TRY TO NEGOTIATE WITH
 THE LANDLORD (LINPRO INVESTMENTS, INC.) TO RELAY TO THE
 TENANTS TO CHANGE THEIR ADDRESSES TO CONFORM TO OUR
 POLICY. HOWEVER, THAT BRIDGE WON'T BE CROSSED IN THE
 MEANTIME UNTIL FURTHER RESEARCH & COMMUNICATION IS
 INITIATED BY ME. UPDATE: AFTER GOING OUT ON SITE TO
 CHECK OUT THE BUSINESSES OF LAKE POINT CENTRE PLAZA &
 TALKING TO TRISH (A REPRESENTATIVE OF LINPRO
 INVESTMENTS, INC.), JAMES & I HAVE DECIDED TO BACK DOWN
 FROM ENFORCING THIS POLICY. THE ADDRESSES FOR THE
 SURROUNDING BUSINESSES OF BP GAS STATION, WALGREEN'S &
 BURGER KING WOULD NEED TO BE ADJUSTED TOO TO MAKE
 CHRONOLOGICAL SENSE FOR THE PROSPECTIVE ADDRESSES FOR
 THE TENANTS OF LAKE POINT CENTRE PLAZA.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-05-14 Cont ID  
Sent By jwitmer Date 2009-05-14 Time 11:50 Rev Time 1.30
Received By jwitmer Date 2009-05-14 Time 11:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2009-03-31 Cont ID  
Sent By jwitmer Date 2009-03-31 Time 15:04 Rev Time 2.22
Received By jwitmer Date 2009-03-31 Time 15:04 Sent To  
Notes
2009-03-31 15:19:01BUILDING PLAN REVIEW
 PERMIT: 08110178
 ADD:6901 OKEECHOBEE BLVD SUITE D19, D23 & E1.
 CONT: "PLAN REVIEW"
 TEL: (262)901-0505 EXT 110
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2ND MAJOR WORKING DRAWING REVIEW/ PLAN REVIEW
 ACTION: DENIED
 MARCH 31/2009
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) COMPLIED.
  
 1C) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1D) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER MAARCH 1/2009 SHALL BE REVIEWED TO
 THE 2007 FBC BUILDING WITH THE 2009 SUPPLEMENTS & 2007
 EXISTING BUILDING CODE WITH 2009 SUPPLEMENTS. PLEASE
 PROVIDE AS TO WHAT LEVEL OF ALTERATIONS WILL BE
 COMPLETED UNDER THIS PERMIT. 2007 EXIST FBC 101.5
 COMPLIANCE METHODS. THE REPAIRS, ALTERATIONS, CHANGE IN
 OCCUPANCY, ADDITION OR RELOCATION OF ALL EXISTING
 BUILDINGS SHALL COMPLY WITH ONE OF THE FOLLOWING
 METHODS LISTED IN SECTION 101.5.1 THROUGH 101.5.3 AS
 SELECTED BY THE APPLICANT.
  
 2) COMPLIED.
  
 3-4) COMPLIED.
  
 5) SEMI-COMPLIED. MISSING WIND DESIGN INFORMATION FOR
 ROOF TOP EQUIPMENT.
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR). THE CITY OF WEST PALM BEACH IS LOCATED IN A
 140 MPH WIND-BORNE DEBRIS REGION.
  
 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
  
 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR
 THE SELECTION OF EXTERIOR COMPONENTS AND CLADDING
 MATERIALS NOT SPECIFICALLY DESIGNED BY THE REGISTERED
 DESIGN PROFESSIONAL.
  
 6) COMPLIED.
  
 7) 2ND REQUEST, PLEASE SEE MECHANICAL COMMENT# 3 ABOUT
 THE ROOF TOP EQUIPMENT BEING REQUIRED TO MEET WIND
 PRESSURES, FBCM 301.13.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-11-24 Cont ID  
Sent By jwitmer Date 2008-11-24 Time 13:31 Rev Time 0.77
Received By jwitmer Date 2008-11-24 Time 13:31 Sent To  
Notes
2008-11-24 14:38:56BUILDING PLAN REVIEW
 PERMIT: 08110178
 ADD:6901 OKEECHOBEE BLVD SUITE D19, D23 & E1.
 CONT: "PLAN REVIEW"
 TEL: (262)901-0505 EXT 110
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS & 2004
 EXISTING BUILDING DODE WITH 2007 SUPPLEMENTS. PLEASE
 PROVIDE AS TO WHAT LEVEL OF ALTERATIONS WILL BE
 COMPLETED UNDER THIS PERMIT? 2004 EXIST FBC 301.5.
  
 2) NOTE WHEN PLANS WILL COME IN AS A PERMIT
 APPLICATION.PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING
 FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE
 DOCUMENT. THE SEAL SHALL CONTAIN THE NAME OF THE
 ARCHITECT AND REGISTRATION NUMBER, THE SEAL SHALL BE
 CIRCULAR AND APPRXIMATELY 2 INCHES IN DIAMETER.
 FL ADMIN CODE 61G1-16.002 ARCHITECTS.
  
 3) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 3A) STOREFRONT WINDOWS- ONLY ONE SUBMITTED
  
 4) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 5) MISSING WIND DESIGN INFORMATION FOR STOREFRONT
 WINDOW AS WELL AS ROOF TOP EQUIPMENT.
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR
 THE SELECTION OF EXTERIOR COMPONENTS AND CLADDING
 MATERIALS NOT SPECIFICALLY DESIGNED BY THE REGISTERED
 DESIGN PROFESSIONAL.
  
 6) M215 INDICATES NEW ROOF TOP RTU UNITS BUT NO
 INFORMATION WAS PROVIDED FOR BAR JOIST REINFORCEMENT,
 CURB ATTACHMENTS NOR UNITS ATTACHED TO CURBS. 1609.1.3
 ANCHORAGE AGAINST OVER TURNING.
  
 7) ) PLEASE SEE MECHANICAL COMMENT# 3 ABOUT THE ROOF
 TOP EQUIPMENT BEING REQUIRED TO MEET WIND PRESSURES,
 FBCM 301.13.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-05-14 Cont ID  
Sent By jwitmer Date 2009-05-14 Time 11:50 Rev Time 0.00
Received By jwitmer Date 2009-05-14 Time 11:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2009-05-18 Cont ID  
Sent By dpalmer Date 2009-05-18 Time 15:20 Rev Time 0.00
Received By dpalmer Date 2009-05-18 Time 15:20 Sent To  
Notes
2009-05-18 15:21:09STAMPED SECOND SET

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2009-05-14 Cont ID  
Sent By dpalmer Date 2009-05-14 Time 12:24 Rev Time 0.00
Received By dpalmer Date 2009-05-14 Time 12:24 Sent To  
Notes
2009-05-14 12:24:48**PROVISO/ REDLINED NOTES **
  
 * TEMPORARY FAILED*
  
  
 ** THE FOLLOWING ITEMS SHALL BE ADDRESSED AND REVISED
 BEFORE ANY ROUGH ELECTRICAL INSPECTION. SEE NOTE #4
 WHICH NEEDS TO BE DONE AT THIS TIME. NOTE NUMBER FOUR
 WAS GIVEN ON INITIAL REVIEW HOWEVER HAS NOT BEEN
 ADDRESSED IN SECOND SET.
  
 1) NOTE: PLEASE SEE FBC 13-415.AB.1, .1.3 NOTED IN ALL
 PREVIOUS REVIEWS. THERE ARE LIGHTING FIXTURES WHICH DO
 NOT MEET SECTIONS GIVEN. ALL ACCENT/TASK LIGHTING SHALL
 CONTAIN SOME SORT OF CONTROL WHICH WILL TURN OFF
 FIXTURES IN SOME SORT OF AUTOMATED WAY. THESE MAY BE
 PART OF THE LIGHTING TIME CLOCK WITH OVER RIDES OR
 OCCUPANCY SENSOR TYPE DEVICES.
 THESE ARE LOCATED IN SEPARATION ROOM, PREP SINK, AND
 MED PREP AREAS.
 THE BASE SYSTEM AS SHOWN NEEDS TO BE MORE SPECIFIC ON
 PLANS WITH ACTUAL SYSTEM CHOSEN AND INSTALLED. THE TYPE
 OF SYSTEM WHICH MUST BE LISTED PER A NATIONAL
 RECOGNIZED TESTING LABORATORY SHALL BE SHOWN. ( NRTL)
 NEC 110.3, FBC 13-415.AB.1.1, .1.2 AND .1.3. SEE NEXT
 NOTE:
  
 2) NOTE: PLEASE SEE FBC 11-4.27.4 AS THE PLANS DO
 CONTAIN A DEVICE WHICH IS NOTED AS BEING A *TWIST
 TIMER* DEVICE. DEVICE WHICH MAY BE ACCESSIBLE AND IN
 USE FOR ANYONE MEETING ADA GUIDELINES SHALL NOT BE OF
 TWISTING TYPE.
  
 3) NOTE: ** ALL LOW VOLTAGE SYSTEMS SHALL BE UNDER
 SEPARATE PERMITS. ANY ACCESS CONTROLS WOULD ALSO BE
 UNDER SEPARATE PERMIT WITH PLANS AND REVIEW BY THE FIRE
 MARSHAL AS WELL AS ELECTRICAL REVIEWS IN ACCORDANCE
 WITH NFPA-70 2005 AND NFPA-101 2006 CHAPTER 7.
  
 4) NOTE: THE SECOND SET OF PLANS CONTAINS ALMOST ALL OF
 THE ORIGINAL SHEETS SUBMITTED FROM SHEETS 230, 250, AND
 270 NEEDS TO BE RE-SEALED WITH CURRENT SEALS ACCEPTABLE
 IN THE STATE OF FLORIDA. THE OTHER NEW REVISED SHEETS
 IN SETS ARE OK AS THEY CONTAIN NEW SEAL. FAC61G1-16.002
 THIS WAS NOTED ON COMMENT #3 ON INITIAL REVIEW YET MANY
 OF THE OLDER SHEETS STILL CONTAIN OLD SEAL. THIS IS
 REQUIRED FOR ALL SHEETS WHETHER OR NOT COMMENT IS MADE
 BY ANY OTHER TRADE. THE ARCHITECT OF RECORD MAY COME
 INTO OFFICE, PRESENT IDENTIFICATION AND RE-SEAL PLANS
 WITH NEW SEAL IN ORDER TO GET PROJECT ISSUED FOR
 PERMIT.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-03-26 Cont ID  
Sent By dpalmer Date 2009-03-26 Time 13:07 Rev Time 0.00
Received By dpalmer Date 2009-03-26 Time 13:07 Sent To  
Notes
2009-03-26 13:07:19** DENIED REVIEW **
  
 1) NOTE: AS NOTED ON THE PREVIOUS REVIEW ON THE FIRST
 COMMENT. IT IS IMPORTANT TO KNOW THAT PLANS WERE ONLY
 SUBMITTED FOR PLAN REVIEW ONLY. THIS DOES NOT *LOCK* A
 PROJECT UNDER ANY SPECIFIC CODE EDITIONS UNLESS PERMIT
 APPLICATION IS MADE. AS THE PROJECT WAS ONLY SUBMITTED
 FOR PLAN REVIEW AND IS DESIGNED UNDER THE 2004 FBC THIS
 DID NOT LOCK PROJECT UNDER THE 2004 FBC. AS OF MARCH 1,
 2009 THE STATE OF FLORIDA UNDER FS 553.73 HAS ADOPTED
 THE 2007 FBC WITH 2009 REVISIONS.
 PLEASE ALSO KNOW SOME OTHER CODES SUCH AS THE LIFE
 SAFETY CODE AND STATE FIRE CODE WERE ALSO REVISED PER
 FLORIDA ADMINISTRATIVE CODE 69A-60.003 AND .004 BY THE
 STATE FIRE MARSHAL.
 THE FOLLOWING CODES NEED TO BE ON PLANS. PLEASE BE SURE
 THE FOLLOWING ARE ON ELECTRICAL AS WELL. SOME CODES
 STATED ON PLANS ARE OK AND IN EFFECT. PLEASE BE SURE
 THE FOLLOWING ARE UPDATED ON ALL RELEVANT SHEETS.
  
 2007 FBC W/2009 REVISIONS.
 2006 NFPA-101
 2006 NFPA-1
 OTHER CODES SUCH AS 2002 NFPA-72, 2005 NFPA-70 ARE
 STILL ACCURATE.
  
 2) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO FBC
 AND CHAPTER 13 FOR LIGHTING PERFORMANCE CALCULATIONS.
 THE SUBMITTED DOCUMENTS FROM COMCHECK ARE NOT ADOPTED
 BY THE FLORIDA BUILDING CODE OR PERMITTED IN THE STATE
 OF FLORIDA. THE PREVIOUS CODE SECTIONS GIVEN WERE
 STATED BASED ON THE CODE IN EFFECT AT THE TIME OF THE
 PLAN REVIEW SUBMISSION. SINCE THAT TIME AS STATED IN
 NOTE #1, THE STATE HAS ADOPTED A NEW CODE.
 PLEASE SEE FBC CHAPTER 13 2007 EDITION WITH 2009 GLITCH
 AMENDMENTS. THIS CHAPTER WAS COMPLETELY REVISED FROM
 THE FIRST PRINTING OF THE 2007 FBC. THERE ARE
 SUBSTANTIAL CHANGES WHICH WILL AFFECT THIS PROJECT.
 ** PLEASE SUBMIT LIGHTING PERFORMANCE CALCULATIONS PER
 13-415.2, 13-415.AB.5, 13-415.AB.5.1, 13-415.B
 THESE SECTIONS FOR LIGHTING PERFORMANCE CALCULATIONS
 HAVE BEEN COMPLETELY REVISED.
  
 ** ONCE AGAIN THE SUBMITTED COMCHECK CALCULATIONS ARE
 NOT PERMITTED AND CAN NOT BE USED IN THE STATE OF
 FLORIDA. ONE COPY HAS BEEN RETAINED BY THIS OFFICE.
  
 ** IT IS ALSO IMPORTANT TO KNOW THAT THE INPUT DATA
 REPORT WHICH WILL ACCOMPANY THE SUBMITTED ENERGY
 CALCULATIONS MUST COORDINATE WITH ALL COMPONENTS OF
 CONSTRUCTION AS SHOWN ON PLANS. THIS INCLUDES ALL
 LIGHTING FROM PLANS, FIXTURE LEGEND ETC.
  
 3) NOTE: AS STATED IN PREVIOUS REVIEW PLEASE SUBMIT AND
 SHOW LIGHTING CONTROLS MEETING MINIMUM CODE COMPLIANCE.
 THE RESPONSE MENTIONS TO SEE 210 AND 220 HOWEVER THE
 ONLY ITEM ON THOSE SHEETS ARE NOTES TO PROVIDE A SYSTEM
 OF SOME SORT. PLACING A NOTE ON PLANS IN LIEU OF ACTUAL
 DETAILS OR DESIGN OF A CODE COMPLIANT SYSTEM IS NOT
 PERMITTED. MUST SHOW CODE COMPLIANCE. PLEASE KNOW THE
 CODE SECTIONS UNDER THE 2007 FBC HAVE NOW BEEN REVISED.
 PLEASE SEE THE FOLLOWING SECTIONS. 13-415.AB.1.1, .1.2
 AND .1.3
  
  
 4) NOTE: THIS IS A NEW NOTE: BY DEFINITIONS IN THE FBC,
 ARE THESE TWO SEPARATE BUILDINGS? IS THE WALL WITH NEW
 OPENINGS A FIRE WALL? PLEASE SEE DEFINITIONS OF FIRE
 WALL.
 IF THESE ARE TWO SEPARATE BUILDINGS, ON TWO SEPARATE
 SERVICES AND NOW BECOMING ONE BUILDING THEN SOME
 CLARIFICATION AND CHANGES IN DOCUMENTS MAY BE NEEDED.
 THERE CAN BE OPENINGS IN FIRE WALLS HOWEVER THERE ARE
 REQUIREMENTS FOR OTHERS TRADES INCLUDING ELECTRICAL.
 PLEASE PROVIDE THE COMPLETE RISER DIAGRAM FOR ALL
 SERVICE EQUIPMENT ON THESE BUILDINGS. THE WALMART WHICH
 IS LOCATED IN THIS SAME SHOPPING CENTER IS A SEPARATE
 BUILDING WITH FIRE WALL SEPARATION AND IS NOT PART OF
 THESE TWO BUILDINGS. THE WALMART SECTION IS NOT PART OF
 THIS QUESTION.
 BASED ON THE ARCHITECTURAL SHEETS THESE APPEAR TO BE
 POSSIBLY BE TWO BUILDINGS WHICH EXIST BEING MADE INTO
 ONE.
 BASED ON RISER THERE SEEMS TO BE TWO SEPARATE
 ELECTRICAL SERVICES WHICH WOULD NOW BE FED FROM ONE
 GENERATOR.
 BONDING OF SERVICES, ETC ARE NOT KNOWN.
 THERE IS A 400 AMP BREAKER FEEDING NEW ATS TO PANEL D
 HOWEVER THE CONDUCTORS AS SHOWN ARE ONLY RATED FOR
 200AMPS. 310.16, 240.4 RISER DOES NOT INDICATE PARALLEL
 FEEDERS.
  
 *** PLEASE GO OVER DESIGNS FOR MINIMUM CODE COMPLIANCE.
  
 ** ONCE AGAIN THERE ARE SOME ITEMS NOT SUBMITTED OR
 KNOW AT THIS TIME AND THERE MAY BE NEW COMMENTS ON THE
 FOLLOWING REVIEW WHICH CAN NOT BE MADE AT THIS TIME.
 ONE SET OF PLANS FOR ELECTRICAL WILL ALSO BE RETAINED
 BY THIS OFFICE.
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-12-01 Cont ID  
Sent By dpalmer Date 2008-12-01 Time 17:48 Rev Time 0.00
Received By dpalmer Date 2008-12-01 Time 17:48 Sent To  
Notes
2008-12-01 17:48:27 
 ** DENIED **
  
  
 1) NOTE: PLANS ONLY SUBMITTED FOR PLAN REVIEW. PLEASE
 KNOW EVEN ONCE PLANS ARE FOUND TO BE CODE COMPLIANT AND
 PERMIT APPLICATION HAS NOT BEEN MADE THE REVIEW WILL
 STILL REMAIN IN A FAILED STATUS. VERIFICATION OF
 LICENSING AND SEVERAL OTHER ITEMS WILL TAKE PLACE ONCE
 PERMIT APPLICATION IS MADE.
  
 2) NOTE: PLEASE SEE FLORIDA STATUTES 481.221 AS THE
 ONLY SEAL PERMITTED IS REQUIRED TO BE A RAISED
 IMPRESSION TYPE SEAL. SOME DOCUMENTS AND SHEETS
 SUBMITTED CONTAIN A *RUBBER-STAMPED* SEAL WHICH IS NOT
 PERMITTED.
 ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 ANY OTHER TRADE FOR ALL SHEETS.
  
 3) NOTE: PLEASE SEE THE SEAL ON SHEETS WHICH IS AN
 IMPRESSION TYPE SEAL IS NO LONGER ACCEPTABLE IN THE
 STATE OF FLORIDA. PLEASE SEE FLORIDA ADMINISTRATIVE
 CODE 61G1-16.002 FOR CORRECT TYPE OF SEAL. THE INITIAL
 RULING OF A 2INCH SEAL WAS ADOPTED IN 1989. THIS HAS
 SINCE BEEN UPDATE HOWEVER HAS BEEN A REQUIREMENT FOR
 ALMOST 20YEARS.
 ** THIS IS REQUIRED WHETHER OR NOT THE COMMENT IS MADE
 BY ANY OTHER TRADES FOR ALL SHEETS.
  
 4) NOTE: PLEASE SEE THE TITLE BLOCKS ARE MISSING THE
 REQUIRED CERTIFICATE OF AUTHORIZATION NUMBER FOR THE
 ARCHITECTURAL FIRM. THIS IS REQUIRED ON TITLE BLOCKS
 PER FAC61G1-16.004 AND PER FLORIDA STATUTES 481.219
  
 5) NOTE: PLEASE SEE THE TITLE BLOCKS ARE MISSING THE
 REQUIRED CERTIFICATE OF AUTHORIZATION NUMBER FOR
 ENGINEERING BUSINESS/FIRM PER FLORIDA ADMINISTRATIVE
 CODE (FAC 61G15-23.002) AND FS 471.023
  
 6) NOTE: PLEASE SEE THE TITLE BLOCKS ARE REQUIRED TO
 CONTAIN THE PRINTED NAME AND PRINTED LICENSE NUMBER OF
 THE DESIGNER. FAC 61G1-16.002, 61G15-23.002.
 ** REQUIRED FOR ALL TRADES AND FOR ALL SHEETS WHETHER
 OR NOT COMMENT IS MADE BY OTHER TRADES.
  
 7) NOTE: PLEASE SEE THE RAISED SEAL WHICH DISPLAYS A
 LICENSE NUMBER. THE NUMBER AS PRINTED IN SEAL IS:
 AR90016025. THERE IS NO RECORD OF THIS LICENSE NUMBER
 ON THE DEPARTMENT OF BUSINESS AND PROFESSIONAL
 REGULATION WEBSITE. THE NUMBER AS LISTED ABOVE WITHOUT
 THE *9* IS A RELEVANT NUMBER.
 PLEASE ADJUST SEAL.
 ** REQUIRED FOR ALL TRADES AND FOR ALL SHEETS WHETHER
 OR NOT COMMENTS IS MADE BY OTHER TRADES REVIEWERS.
  
 8) NOTE: PLEASE SEE THE PRINT OUT ATTACHED TO NOTES AS
 THE ADDRESS ON PLANS DOES NOT CORRELATE WITH THE TITLE
 BLOCKS. IN FACT THE STATE SITE LISTS AN ADDRESS OF
 15380 KATA DR. ELM GROVE, WISCONSIN 53122.
 PLEASE CORRECT PLANS AND TITLE BLOCKS OR CONTACT THE
 DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION TO
 UPDATE INFORMATION.
 ** REQUIRED FOR ALL TRADES AND FOR ALL SHEETS WHETHER
 OR NOT COMMENT IS MADE BY OTHER TRADE REVIEWERS.
  
 9) NOTE: THE CODES RELEVANT TO PROJECT ARE REQUIRED TO
 MEET ADOPTED CODES UNDER FS 553.73. PLEASE SEE THAT THE
 PLANS ARE CURRENTLY LISTING CODES WHICH ARE NO LONGER
 ADOPTED IN THE STATE OF FLORIDA. SOME SUCH AS THE 2002
 NATIONAL ELECTRICAL CODE AS SHOWN AS NOT BEEN IN EFFECT
 SINCE DECEMBER 2006.
 THE CODES FOR THIS REVIEWER ALONE SHOULD BE STATED AS
 FOLLOWS.
  
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70. ( NEC)
 2003 NFPA-101
 2002 NFPA-72
 * PLEASE NOTE, THE NFPA-72 MAY OR MAY NOT BE APPLICABLE
 TO THIS PROJECT.
  
 10) NOTE: PLEASE SEE FBC 13-106.1.1. THE SUBMIT ENERGY
 CALCULATIONS ARE METHOD *A* WHICH IS FOR WHOLE BUILDING
 COMPLIANCE. PLEASE SEE DEFINITIONS IN SECTION 202 AS
 THIS IS NOT A WHOLE BUILDING OR NEW CONSTRUCTION.
 PLEASE PROVIDE LIGHTING PERFORMANCE CALCULATIONS PER
 13-415.2,13-415.2.ABC.1.1, .1.2.
  
 11) NOTE: PLEASE SEE 13-413.1.ABC.2.1 AND .2.2 AND
 PLACE NOTES ON PLANS ACCORDINGLY.
  
 12) NOTE: PLEASE SEE FBC 11-4.27.4 AS THE LIGHTING
 CONTROLS NOTED AS *SPRING WOUND* TIMERS ARE NOT
 PERMITTED.
 MUST MEET ADA REQUIREMENTS.
  
 13) NOTE: PLANS INDICATE ELECTRICAL PANELS IN WHAT
 WOULD BE A CLOSET FOR STORAGE OF SUPPLIES.
 PLEASE SEE 110.26,240.24D AND 408.17 AS ELECTRICAL
 EQUIPMENT ALONG WITH OVER CURRENT PROTECTION IS NOTED
 PERMITTED IN AREAS WHERE THERE IS STORAGE OF EASILY
 IGNITABLE MATERIALS OR COMBUSTIBLES.
  
 14) NOTE: PLEASE INCLUDE LIGHTING CONTROLS AS REQUIRED
 PER 13-415.1.ABC.1.1,.1.2 AND .1.3.
  
 15) NOTE: PLEASE SEE FBC 11-4.28.1, .2 AND .3 FOR ALL
 MINIMUM LEVELS FOR DEVICES OF FIRE ALARM SYSTEM.
 PLEASE BE SURE ALL DEVICE HEIGHTS AND LEVELS ARE SHOWN.
 ** NOTE MINIMUM CANDELA LEVELS FOR STROBE DEVICES ARE
 75CD
  
 16) NOTE: PLEASE OBTAIN THE LATEST ELECTRICAL RISER FOR
 THIS SPACE. IT IS UNDERSTOOD THIS SAME TENANT HAS
 OBTAINED PERMITS FOR NEW GENERATOR AND ELECTRICAL
 EQUIPMENT WHICH IS NOT PART OF THE CURRENT SUBMITTED
 ELECTRICAL PLANS.
 230,220,215,240 ETC
 FBC 106.1.1 FOR CLARITY AND COORDINATION OF PLANS.
  
 17) NOTE: PLEASE SHOW ALL CONTINUOUS LOADS SUCH AS
 LIGHTING AT 125%. 215.3,230.42 ETC
  
 ** IT IS IMPORTANT TO KNOW AS THERE ARE SOME ITEMS NOT
 YET SUBMITTED FOR REVIEW THERE MAY BE NEW COMMENTS ON
 THE FOLLOWING REVIEW WHICH CAN NOT BE MADE AT THIS
 TIME.
  
 18) NOTE: DOCUMENTATION HAS BEEN ROUTED TO THE
 ADDRESSING REVIEWER. THIS WILL BE ONE TENANT SPACE AND
 ADDRESS SHOULD BE LISTED UNDER A PRIME SUITE OR UNIT
 NUMBER. THE PLANS AND PLAN REVIEW APPLICATION IS
 PRESENTLY SUBMITTED AS THREE SEPARATE UNITS/SPACES.
 ONCE FINAL ADDRESS IS DETERMINED PLEASE ADJUST TITLE
 BLOCKS.
 FAC 61G1-16.004, 61G15-23.002
 FBC 106.5
  
 19) NOTE: PLEASE BE SURE ALL ELECTRICAL SERVICE
 EQUIPMENT ONCE REVISED IS LABELED ACCORDINGLY. TENANT
 DISCONNECTS AND MAINS NEED IDENTIFICATION IN ANY EVEN
 THE POWER NEEDS TO BE SHUT DOWN.
 230.2E ECT.
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2008-12-26 Time   Rev Time 1.00
Received By   Date 2008-12-26 Time   Sent To ENG
Notes
2008-12-26 13:47:39********* PASSED **********
  
 NO NEED FOR CITY OF WPB ENGINEERING TO SEE.
 LOCATION SERVED THRU MASTER WATER METER TO SHOPPING.
 FIRELINE PROPTECTION IS ALSO AVAILABLE ON-SITE.
 IF ANY CONNECTION IS MADE TO FIRELINE AN ENGINEER OF
 RECORD
 WOULD HAVE TO CERTIFY TO THE CITY. PLUMBING AND FIRE
 DEPARTMENT
 WOULD BE LEAD ON THE REVIEW AND ACCEPTANCE.
  
 ANY QUESTIONS:
  
 MANUEL J GONZALEZ, PROJECT COORDINATOR
 LOCATION ADDRESS:
 CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT
 1000 - 45TH STREET, SUITE 15
 WEST PALM BEACH FL 33407
 MAILING ADDRESS:
 CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT
 P.O. BOX 3506
 WEST PALM BEACH FL 33401
 TELEPHONE:
 45TH STREET OFFICE : 561-494-1040
 45TH DIRECT: 561-494-1085
 FAX: 561-494-1117
 CITY HALL OFFICE: (561) 805-6713
 CITY HALL DIRECT: (561) 805-6313
 CITY HALL FAX: (561) 805-6731 OR 805-6676
  
 NEXTEL CELL: 561-644-7301
  
 NEXTEL DIRECT CONNECT: 159*28165*38
 EMERGENCIES:
 CENTRAL OPERATIONS CENTER (DISPATCH) 561-822-2210
 E-MAIL:
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-05-18 Cont ID  
Sent By mawillia Date 2009-05-18 Time 15:12 Rev Time 0.00
Received By mawillia Date 2009-05-18 Time 14:07 Sent To  
Notes
2009-05-18 15:08:48*****APPROVED*****
  
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED; PLAN SHEETS A210, A211, A810, E210, AND
 E230 WERE STAMPED, INITIALED, AND DATED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2009-04-03 Cont ID  
Sent By mwennerg Date 2009-04-03 Time 14:26 Rev Time 0.00
Received By mwennerg Date 2009-04-03 Time 14:26 Sent To  
Notes
2009-04-03 14:31:44***DENIED***
  
 1) OK PLEASE NOTE THAT PLANS WERE SUBMITTED FOR REVIEW
 ONLY PRIOR TO DEC. 31, 2008 HOWEVER DESIGNS FOR LIFE
 SAFET THAT ARE SUBMITTED FOR PERMIT REVIEW AFTER THAT
 DATE SHALL COMPLY WITH NFPA 101, 2006.
  
 6) SHEET E210 ILLUSTRATES THE EXTERIOR DOOR IN ROOM 107
 AS AN EXIT BUT SHOWS THE DOOR AS BEING REMOVED ON SHEET
 A210.
  
  
 PLANS WILL REMAIN IN FAILED STATUS UNTIL SUBMITTED FOR
 REVIEW UNDER PERMIT APPLICATION.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-12-11 Cont ID  
Sent By mwennerg Date 2008-12-11 Time 12:11 Rev Time 0.00
Received By mwennerg Date 2008-12-11 Time 12:11 Sent To  
Notes
2008-12-11 12:20:35***DENIED***
  
 1) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003
 EDITION. ADD TO APPLICABLE CODES.
  
 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241. ADD TO APPLICABLE CODES.
  
 3) PLEASE INDICATE MINIMUM INTERIOR FINISH
 CLASSIFICATION FOR WALSS AND CEILING IN TERMS OF CLASS
 A,B OR C.
  
 4) IN ADDITION TO SEPARATE PERMIT PROCESS, INDICATE THE
 FIRE SPRINKLER HEAD LAYOUT THAT MAY BE SHOWN ON THE
 RELECTED CEILING PLAN.
  
 5) DUCT SMOKE DETECTORS SHALL BE PROVIDED IN SUPPLY
 DUCT UNLESS UNITS ARE LARGE ENOUGH FOR BOTH SUPPLY AND
 RETURN. DUCT SMOKE DETECTORS SHALL BE TIED INTO THE
 FIRE ALARM SYSTEM IF APPLICABLE AND INITIATE A GENERAL
 FIRE ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS.
  
 6) PLANS SEEM TO SUGGEST EXITING THROUGH STORAGE/WORK
 ROOMS. SPECIFIC AREAS WOULD PROVIDE AN AREA OF GREATER
 HAZARD. PLEASE PROVIDE INFORMATION THAT WOULD ALLOW
 THIS ARRANGEMENT.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-05-08 Cont ID  
Sent By rregueir Date 2009-05-08 Time 09:51 Rev Time 0.00
Received By rregueir Date 2009-05-08 Time 09:51 Sent To  
Notes
2009-05-08 09:51:58C27 PROJECT TO PERMIT

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-02-18 Cont ID  
Sent By adarroug Date 2009-02-18 Time 12:46 Rev Time 0.00
Received By adarroug Date 2009-02-18 Time 12:46 Sent To  
Notes
2009-02-18 12:46:34TO "COMM" BD#32

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2008-12-26 Time   Rev Time 0.00
Received By adarroug Date 2008-11-12 Time 11:53 Sent To  
Notes
2008-11-12 11:56:54TO "COMM" BD#48

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2009-05-27 Cont ID  
Sent By rregueir Date 2009-05-27 Time 08:59 Rev Time 0.00
Received By rregueir Date 2009-05-27 Time 08:59 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2009-05-15 Cont ID  
Sent By rregueir Date 2009-05-15 Time 10:03 Rev Time 0.00
Received By rregueir Date 2009-05-15 Time 09:37 Sent To  
Notes
2009-05-15 10:03:43ALL PREVIOUS REVIEW COMMENTS HAVE BEEN ADDRESSED.
 HOWEVER, ONE OF THE TWO SETS OF PLANS WHICH WERE
 SUBMITTED CONTAINS A PREVIOUS VERSION OF SHEET M210.
 PLEASE PROVIDE TWO COMPLETE UPDATED SETS OF PLANS WITH
 APPLICATION FOR PERMIT ISSUANCE IN ACCORDANCE WITH
 FBC-B 106.1. PLANS WILL BE STAMPED IF THE SECOND SET OF
 PLANS ARE CORRECTED DURING THIS REVIEW CYCLE.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2009-03-27 Cont ID  
Sent By rregueir Date 2009-03-27 Time 11:23 Rev Time 0.00
Received By rregueir Date 2009-03-27 Time 08:10 Sent To  
Notes
2009-03-27 11:23:07REVIEW #: 2ND **PLAN CHECK ONLY**
 ACTION: DENIED
  
 THIS PROJECT REVIEWED FOR COMPLIANCE WITH THE FOLLOWING
 CODES:
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 NOTE: PLANS STILL SUBMITTED FOR PLAN REVIEW WITH NO
 PERMIT APPLICATION. PLANS ARE NOW SUBJECT TO THE
 REQUIREMENTS OF THE 2007 FLORIDA BUILDING CODE WHICH
 WENT INTO EFFECT ON MARCH 1, 2009. PLANS WILL REMAIN IN
 FAIL STATUS PENDING SUBMISSION OF AN ACTUAL PERMIT
 APPLICATION.
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS.
  
 1. OK
  
 2. OK
  
 3. **PREVIOUS COMMENT**PLANS CALL FOR NEW RTU AND
 EXHAUST FAN TO BE INSTALLED ON ROOF. NO INFORMATION
 COULD BE FOUND ON PLANS REGARDING WIND RESISTANCE.
 MECHANICAL APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES ON THE EQUIPMENT AND THE SUPPORTS AS
 DETERMINED IN ACCORDANCE WITH FBCB SECTION 1609 PER
 FBCM 301.13. PROVIDE ATTACHMENT DETAIL SHOWING ROOF
 CURBS TO BUILDING STRUCTURE AND RTU/EF TO ROOF CURB
 ATTACHMENTS. ALSO, PLEASE PROVIDE MANUFACTURER'S DATA
 SHOWING THESE APPLIANCES ARE DESIGNED TO RESIST WIND
 PRESSURES IN ACCORDANCE WITH THIS SECTION.
 **NOT ADDRESSED**: THE WIND LOAD CALCULATIONS PROVIDED
 ARE FOR THE ATTACHMENT OF THE RTU TO THE ROOF AND DO
 NOT PROVIDE INFORMATION REGARDING THE WIND RESISTANCE
 CAPABILITIES OF THE RTU ITSELF. PLEASE SHOW COMPLIANCE
 WITH FBC-M 301.12. ALSO, THE MANUFACTURER'S DATA FOR
 THE ROOTOP FAN INDICATE THE FAN IS DESIGNED FOR 130 MPH
 WINDS. ACCORDING TO THE WIND MAPS FOUND INH FBC-B 1609,
 THE CITY OF WEST PALM BEACH IS IN THE 140 MPH WIND
 ZONE. FAN SHALL BE DESIGNED FOR THE PROPER WIND ZONE IN
 ACCORDANCE WITH THESE SECTIONS.
 NOTE: ALL WIND RESISTANCE DOCUMENTATION PROVIDED WILL
 BE REVIEWED BY THE BUILDING (STRUCTURAL) PLANS
 EXAMINER.
  
 4. OK
  
 5. OK
  
 6. OK
  
 7. OK
  
 NOTE: PLEASE RESPOND TO EACH COMMENT IN WRITING, WITH
 INFORMATION ON HOW EACH COMMENT WAS ADDRESSED AND WHERE
 THE RELEVANT INFOAMTION CAN BE FOUND. THIS WILL HELP TO
 FACILITATE A TIMELY REVIEW UPON RESUBMISSION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-11-22 Cont ID  
Sent By rregueir Date 2008-11-22 Time 16:06 Rev Time 0.00
Received By rregueir Date 2008-11-22 Time 15:30 Sent To  
Notes
2008-11-22 16:06:04REVIEW #: 1ST **PLAN CHECK ONLY**
 ACTION: DENIED
  
 THIS PROJECT REVIEWED FOR COMPLIANCE WITH THE FOLLOWING
 CODES:
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLWING COMMENTS SHALL BE ADDRESSED PRIOR TO
 RESUBMISSION OF PLANS WITH PERMIT APPLICATION:
  
 1. THE DESIGN PROFESSIONAL MUST ELECT ONE OR A
 COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE IN ACCORDANCE
 WITH FBCEB 301.5. PLEASE SHOW THIS ON PLANS WITH THE
 PROJECT INFORMATION.
  
 2. ALL RECONFIGURED SPACES INTENDED FOR OCCUPANCY AND
 ALL SPACES CONVERTED TO HABITABLE OR OCCUPIABLE SPACE
 IN ANY WORK AREA SHALL BE PROVIDED WITH NATURAL OR
 MECHANICAL VENTILATION OR EXHAUST IN ACCORDANCE WITH
 THE FLORIDA BUILDING CODE, MECHANICAL PER FBCEB 609.1.
 PROVIDE VENTILATION CALCULATIONS FOR ALL RECONFIGURED
 SPACES IN ACCORDANCE WITH FBCM SECTION 403.
  
 3. PLANS CALL FOR NEW RTU AND EXHAUST FAN TO BE
 INSTALLED ON ROOF. NO INFORMATION COULD BE FOUND ON
 PLANS REGARDING WIND RESISTANCE. MECHANICAL APPLIANCES
 AND SUPPORTS THAT ARE EXPOSED TO WIND SHALL BE DESIGNED
 AND INSTALLED TO RESIST THE WIND PRESSURES ON THE
 EQUIPMENT AND THE SUPPORTS AS DETERMINED IN ACCORDANCE
 WITH FBCB SECTION 1609 PER FBCM 301.13. PROVIDE
 ATTACHMENT DETAIL SHOWING ROOF CURBS TO BUILDING
 STRUCTURE AND RTU/EF TO ROOF CURB ATTACHMENTS. ALSO,
 PLEASE PROVIDE MANUFACTURER'S DATA SHOWING THESE
 APPLIANCES ARE DESIGNED TO RESIST WIND PRESSURES IN
 ACCORDANCE WITH THIS SECTION.
  
 4. PLANS CALL FOR DUCT SMOKE DETECTOR TO BE INSTALLED
 IN THE RETURN DUCT FOR RTU. SMOKE DETECTORS SHALL BE
 INSTALLED IN SUPPLY AIR SYSTEMS WITH A DESIGN CAPACITY
 GREATER THAN 2,000 CFM, IN THE SUPPLY AIR DUCT IN
 ACCORDANCE WITH FBCM 606.2.1.
  
 5. MECHANICAL FLOOR PLAN SHOWS FLEX DUCTS ATTACHED
 DIRECTLY TO FIRE DAMPERS. PROVIDE FD MANUFACTURER'S
 INSTALLATION INSTRUCTIONS SHOWING HOW FLEX DUCT IS TO
 BE ATTACHED TO THE DAMPERS. FIRE DAMPERS AND
 COMBINATION FIRE/SMOKE DAMPERS SHALL BE INSTALLED IN
 ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS AND LISTING PER FBCM 607.2.
  
 6. SHOW HOW DUCT ACCESS DOORS ARE TO BE INSTALLED AT
 THESE LOCATIONS. A SERVICE OPENING (DUCT ACCESS DOOR)
 SHALL BE PROVIDED IN AIR DUCTS ADJACENT TO EACH FIRE
 DAMPER, SMOKE DAMPER, AND DUCT SMOKE DETECTOR. THE
 OPENING SHALL BE LARGE ENOUGH TO PERMIT MAINTENANCE AND
 RESETTING OF THE DEVICE. SERVICE OPENINGS SHALL BE
 IDENTIFIED WITH LETTERS HAVING A MINIMUM HEIGHT OF 1/2
 INCH TO INDICATE THE LOCATION OF THE FIRE PROTECTION
 DEVICE(S) WITHIN THE DUCT IN ACCORDANCE WITH FBCM
 301.15 AND NFPA 90A-2002.
  
 7. EXHAUST/RETURN DETAIL CALLS FOR LINED GRILL CANS AND
 INSULATED FLEX. ALL EXHAUST DUCTS SHALL BE OF METAL
 (NON-LINED) AND SUCH CONSTRUCTION SHALL COMPLY WITH
 FBCM 501.4.
  
 NOTE: THE SUBMITTED METHOD A ENERGYCALCULATIONS WERE
 NOT REVIEWED FOR COMPLIANCE WITH THE MECHANICAL
 PROVISIONS OF THE FLORIDA ENERGY CODE (FBCB CHAPTER
 13). THIS PROJECT IS NOT NEW CONSTRUCTION, IS NOT A
 WHOLE BUILDING AND DOES NOT MEET THE DEFINITION OF A
 RENOVATION (SEE FBCB SECTION 13-202) AND THEREFORE ONLY
 COMPLIANCE WITH FBCB 13-101.6 NEEDS TO BE DEMONSTRATED.
  
 NOTE: PLEASE RESPOND TO EACH COMMENT IN WRITING, WITH
 INFORMATION ON HOW EACH COMMENT WAS ADDRESSED AND WHERE
 THE RELEVANT INFOAMTION CAN BE FOUND. THIS WILL HELP TO
 FACILITATE A TIMELY REVIEW UPON RESUBMISSION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-05-11 Cont ID  
Sent By kstevens Date 2009-05-11 Time 14:51 Rev Time 0.00
Received By kstevens Date 2009-05-11 Time 14:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2009-03-25 Cont ID  
Sent By kstevens Date 2009-03-25 Time 12:19 Rev Time 0.00
Received By kstevens Date 2009-03-25 Time 12:19 Sent To  
Notes
2009-03-25 14:00:44DENIED
 REFERENCE:
 FBC-2007
  
 **********NEW COMMENT**********
  
 1B. SINCE THE APPLICATION FOR PERMIT WAS NOT SUBMITTED
 PRIOR TO MARCH 1, 2009 THE DESIGN CRITERIA SHALL NOW BE
 FBC-2007. PLEASE CHANGE THE CODE REFERENCE ON SHTS "T",
 P210 OR ANY OTHER SHEET THAT REFERENCES THE FBC-2004
 CODE TO REFLECT THIS CHANGE. -- PLUMBING REVIEW WILL
 REMAIN IN FAILED STATUS UNTIL THIS CHANGE IS MADE AND
 THE APPLICATION IS SUBMITTED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-12-05 Cont ID  
Sent By kstevens Date 2008-12-05 Time 15:02 Rev Time 0.00
Received By kstevens Date 2008-12-05 Time 15:02 Sent To  
Notes
2008-12-05 15:52:46PLAN REVIEW DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 EXISTING BUILDING CODE
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 CITY WPB MUNICIPAL CODE
  
 1. SHT "T" THE DESIGN CRITERIA SHALL INCLUDE THE 2005,
 2006 & 2007 REVISIONS TO THE 2004 FLORIDA BUILDING
 CODE. SECTION 106.1.1.
  
 2. SHT "T" INDICATE THE LEVEL OF ALTERATION AS REQUIRED
 IN CHAPTER 3 OF THE FBC-2004 EXISTING BUILDING CODE.
  
 3. SHT "T" AN IMPRESSION TYPE SEALING COMPLYING WITH
 FAC 61G1-16.001, 61G1-16.002 & FS 481.2055 IS REQUIRED.
 STAMP TYPE SEALS ARE NOT APPROVED.
  
 4. ALL SHEETS REQUIRE THE CERTIFICATE OF AUTHORIZATION
 NUMBER FOR THE ENGINEERING FIRM, (APPLIED FOR - SEE
 ATTACHED SHEET), AND FOR THE ARCHITECT, (NOT FOUND), IN
 THE TITLE BLOCK OF EACH SHEET. FAC 61G15-23.002,
 61G1-16.004(2) & FS 471.025, 481.219, 481.2055.
  
 5. ALL SHEETS REQUIRE THE PRINTED NAME OF THE PERSON
 SEALING THE DOCUMENTS. FAC 61G1-16.004(6), FAC
 61G15-23.002(2) & FS 471.025 & 481.2055.
  
 6. THE SEAL AFFIXED TO THE SHEETS IS NOT APPROVED. SEAL
 SHALL BE APPROXIMATELY 2 INCHES IN DIAMETER. ALSO THE
 ARCHITECTURAL NUMBER ON THE SEAL, AR90016025 DOES NOT
 REFLECT THE NUMBER INDICATED ON THE STATE OF FLORIDA
 DBPR WEBSITE FOR LICENSURE. PLEASE CORRELATE. FAC
 61G1-16.001, 61G1-16.002 & FS 481.2055.
  
 7. SHTS P210 & P215 IN THE INSTALLATION OR REMOVAL OF
 OF ANY PART OF A DRAINAGE SYSTEM, DEAD ENDS SHALL BE
 PROHIBITED. DISCONNECT ALL DRAINAGE A MAXIMUM OF 2 FEET
 FROM ACTIVE BUILDING DRAIN LINES. ALL PIPING CAPPED FOR
 DEMOLITION SHALL REMAIN UNCOVERED UNTIL INSPECTED AND
 APPROVED BY THE FIELD INSPECTOR. SECTION 704.5. PLEASE
 INDICATE ON THE DEMO SHEET THE LOCATION OF ALL
 CAPPED/ABANDONED PIPING.
  
 8. SHT P210 THE ABANDONED GREASE INTERCEPTOR SHALL BE
 PUMPED OUT, AND REMOVED, OR IT SHALL BE PUMPED OUT, THE
 BOTTOM SHALL BE SUITABLY OPENED OR RUPTURED SO AS TO
 PREVENT THE INTERCEPTOR FROM RETAINING WATER AND FILLED
 WITH CLEAN SAND OR OTHER SUITABLE MATERIAL, THE ACTIONS
 BEING TAKEN IN THE ORDER LISTED. ARTICLE III SECTION
 90-123, (CODE 1979 & 31-60).
  
 9. SHT P210 INDICATE WHAT DRAINS INTO FIXTURE P-16 &
 P30 F.S. SECTION 106.1.2.
  
 10. SHT P210 IDENTIFY THE FIXTURES CONNECTING TO DSP
 AND SUBMIT A DETAIL SHOWING HOW THEY ARE CONNECTED.
 SECTION, 106.1.2,
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status N Date 2008-11-14 Cont ID  
Sent By kdfreema Date 2008-11-14 Time 11:56 Rev Time 0.00
Received By kdfreema Date 2008-11-14 Time 11:56 Sent To  
Notes
2008-11-14 11:57:11INTERIOR RENOVATION ONLY.