Plan Review Details - Permit 08110144
Plan Review Stops For Permit 08110144
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2008-11-19 Cont ID  
Sent By shill Date 2008-11-19 Time 15:28 Rev Time 0.00
Received By shill Date 2008-11-19 Time 15:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-12-04 Cont ID  
Sent By dpalmer Date 2008-12-04 Time 13:19 Rev Time 0.00
Received By dpalmer Date 2008-12-04 Time 13:19 Sent To PC
Notes
2008-12-04 13:20:30VALUE ADJUSTED PER MARSHALS AND SWIFT AS ADOPTED BY THE
 FLORIDA BUILDING CODE AND ICC 108.3

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-11-18 Cont ID  
Sent By dpalmer Date 2008-11-18 Time 10:11 Rev Time 0.00
Received By dpalmer Date 2008-11-18 Time 10:11 Sent To B
Notes
2008-11-18 10:12:02 
 ** FAILED REVIEW **
  
  
 1) NOTE: THE VALUE FOR THE COMPLETE SCOPE OF WORK SHALL
 BE FOR MATERIALS, LABOR, ELECTRICAL, DESIGN COST ETC
 EVEN IF ANY OF THESE ITEMS ARE OWNER SUPPLIED. THE
 APPLIED VALUE FOR SCOPE AS SHOWN IS LOW.
 FBC 108.3
  
 2) NOTE: PLAN SUBMITTED INDICATES THIS BEING SIGNED,
 DATED AND SEALED BY THE ENGINEER HOWEVER THE TITLE
 BLOCK FOR THE SAME ENGINEER CLEARLY STATES IT IS FOR
 STRUCTURAL ONLY.
 PLEASE SUBMIT ELECTRICAL PLANS AND DETAILS FOR SIGN IN
 WHICH HAS DESIGN AND RESPONSIBILITY MEETING FS 471.003,
 489.
 MAY NOT USE STRUCTURAL PLANS FOR ELECTRICAL WHEN THE
 ENGINEER CLEARLY STATES THE ELECTRICAL IS NOT A PART OF
 HIS OR HER DESIGN.
  
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-11-25 Cont ID  
Sent By adarroug Date 2008-11-25 Time 09:02 Rev Time 0.00
Received By adarroug Date 2008-11-25 Time 09:02 Sent To E
Notes
2008-11-25 09:02:35TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-11-17 Cont ID  
Sent By adarroug Date 2008-11-17 Time 16:10 Rev Time 0.00
Received By adarroug Date 2008-11-17 Time 16:10 Sent To B
Notes
2008-11-17 16:11:10TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-11-19 Cont ID  
Sent By shill Date 2008-11-19 Time 15:28 Rev Time 0.00
Received By shill Date 2008-11-07 Time 15:39 Sent To  
Notes
2008-11-07 15:39:32TO "Z" BOX

Review Stop Z ZONING
Rev No 1 Status P Date 2008-11-13 Cont ID  
Sent By lfranco Date 2008-11-13 Time 18:23 Rev Time 0.00
Received By lfranco Date 2008-11-13 Time 18:23 Sent To  
Notes
***NONE***