| 2008-12-03 13:23:10 | ENGINEERING REVIEW - FAILED 12/03/08 |
| | |
| | PLEASE RESUBMIT WITH THE FOLLOWING: |
| | |
| | TEMPORARY 10000SF STRUCTURE WITH SLAB MAY IMPACT |
| | PROPERTY PERVIOUS AND IMPERVIOUS CALCULATIONS. |
| | PLEASE CONFIRM THAT A SFWMD PERMIT MODIFICATION IS NOT |
| | REQUIRED. THE TENT IS TEMP STRUCTURE (180 DAYS MAX.) |
| | HOWEVER THE SLAB/FOOTINGS WILL REMAIN. |
| | |
| | TYPE OF CONCRETE AND IT'S PERMEABILITY. THE USE OF |
| | VARIOUS PERVIOUS PAVEMENT ALTERNATIVES ARE AVAILABLE TO |
| | DECREASE THE VOLUME OF RUNOFF AND REDUCE THE VOLUME OF |
| | POLLUTANTS BY ALLOWING INITIAL INFILTRATION AT THE |
| | RUNOFF SOURCE. PERVIOUS CONCRETE OR CONCRETE PAVER |
| | BLOCKS CAN BE CONSIDERED FOR THE PROJECT AS AN |
| | ALTERNATE PAVING MATERIAL. |
| | |
| | WATER SURFACE CALCULATIONS. PERVIOUS IMPERVIOUS CALC. |
| | BMP'S MUST BE IN PLACE IF FILL IS BROUGHT IN OR ANY |
| | SOIL IS DISTURBED. |
| | WHERE WILL STORM RUN-OFF GO? WET DETENTION OR DRY |
| | DETENTION AREAS IDENTIFIED. |
| | WATER QUALITY CRITERIA THAT YOU WILL FOLLOW. |
| | STATE ANY OFF-SITE DISCHARGE. |
| | |
| | |
| | COMMENTS CONCERNING POLLUTION CONTROL: |
| | CODE OF ORDINANCES, CITY OF WEST PALM BEACH, FLORIDA, |
| | CODIFIED THROUGH ORD. NO. 4183-08, ADOPTED SEPT. 22, |
| | 2008. (SUPPLEMENT NO. 18), CHAPTER 90 UTILITIES, |
| | ARTICLE V. STORMWATER POLLUTION PREVENTION |
| | SEC. 90-203. PROHIBITED DISCHARGES; ILLICIT |
| | CONNECTIONS. |
| | (A) GENERAL PROHIBITION. EXCEPT AS PROVIDED IN SECTION |
| | 90-205, AND EXCEPT PURSUANT TO A VALID NPDES |
| | PERMIT, IT SHALL BE UNLAWFUL FOR ANY PERSON TO |
| | DIRECTLY OR INDIRECTLY DEPOSIT, DISCHARGE, SPILL, OR |
| | DUMP INTO |
| | ANY OF THE PUBLIC WATERS OR MUNICIPAL SEPARATE STORM |
| | SEWER SYSTEM WITHIN THE CITY, ANY SUBSTANCE OTHER |
| | THAN THAT COMPOSED ENTIRELY OF STORMWATER. |
| | PER; CODE OF ORDINANCES, CITY OF WEST PALM BEACH, |
| | FLORIDA, CODIFIED THROUGH ORD. NO. 4183-08, ADOPTED |
| | SEPT. 22, 2008. (SUPPLEMENT NO. 18), CHAPTER 90 |
| | UTILITIES, ARTICLE V. STORMWATER POLLUTION PREVENTION, |
| | SEC. 90-203. PROHIBITED DISCHARGES; ILLICIT |
| | CONNECTIONS. (A) GENERAL PROHIBITION. EXCEPT AS |
| | PROVIDED IN SECTION 90-205, AND EXCEPT PURSUANT TO A |
| | VALID NPDES PERMIT, IT SHALL BE UNLAWFUL FOR ANY PERSON |
| | TO DIRECTLY OR INDIRECTLY DEPOSIT, DISCHARGE, SPILL, OR |
| | DUMP INTO ANY OF THE PUBLIC WATERS OR MUNICIPAL |
| | SEPARATE STORM SEWER SYSTEM WITHIN THE CITY, ANY |
| | SUBSTANCE OTHER THAN THAT COMPOSED ENTIRELY OF |
| | STORMWATER. SUPPLY A POLLUTION CONTROL PLAN WITH A |
| | MINIMUM OF THE FOLLOWING INFORMATION; |
| | A) SILT FENCE NEEDS TO BE INSTALLED AROUND ANY AREAS TO |
| | BE DISTURBED. SHOW WHERE SILT SCREENS WILL BE INSTALLED |
| | B) FILTER FABRIC IS REQUIRED UNDER THE CATCH BASIN |
| | GRATES WITH ROCK BAGS AT ANY CURBED INLET ON-SITE TO |
| | STOP SOLIDS FROM ENTERING THE SYSTEM. SHOW THE |
| | PROTECTION OF ALL ON-SITE CATCH BASINS, SHOW PROTECTION |
| | OF ALL OFF-SITE CATCH BASINS, INCLUDE DETAILS AS TO THE |
| | TYPE OF PROTECTION USED ON AND OFF-SITE FOR THE CATCH |
| | BASINS, SUCH AS FILTER FABRIC IS REQUIRED UNDER THE |
| | CATCH BASIN GRATES WITH ROCK BAGS AT ANY CURBED INLET |
| | TO STOP SOLIDS FROM ENTER THE SYSTEM. |
| | C) ADD TURBIDITY BARRIER AT THE OUTFALLS AND ALONG THE |
| | FULL WIDTH OF THE PROJECT, SHOW WHERE SILT SCREENS WILL |
| | BE INSTALLED, HOW THEY WILL BE TIED DOWN AND |
| | MAINTAINED. |
| | D) SHOW HOW SITE DIRT WILL NOT BE TRACKED INTO THE |
| | ROADS. |
| | E) DETAIL HOW AND WHEN ANY CLEAN-UP WILL BE PREFORMED. |
| | |
| | GENERAL SFWMD RETENTION/DETENTION REQUIREMENTS |
| | 1. VOLUME IS CALCULATED AS: |
| | WET DETENTION VOLUME SHALL BE PROVIDED FOR THE FIRST |
| | INCH OF RUNOFF FROM THE DEVELOPED PROJECT, OR THE TOTAL |
| | RUNOFF OF 2.5-INCHES TIMES THE PERCENTAGE OF |
| | IMPERVIOUSNESS, WHICHEVER IS GREATER, B) DRY DETENTION |
| | VOLUME SHALL BE PROVIDED EQUAL TO 75% OF THE ABOVE |
| | AMOUNTS COMPUTED FOR WET DETENTION. |
| | |
| | A) COMMERCIAL OR INDUSTRIAL ZONED PROJECTS SHALL |
| | PROVIDE AT LEAST ONE HALF INCH OF DRY DETENTION OR |
| | RETENTION PRETREATMENT AS PART OF THE REQUIRED |
| | RETENTION/DETENTION, UNLESS REASONABLE ASSURANCES CAN |
| | BE OFFERED THAT HAZARDOUS MATERIALS WILL NOT ENTER THE |
| | PROJECT?S SURFACE WATER MANAGEMENT SYSTEM. B) PROJECTS |
| | HAVING GREATER THAN 40% IMPERVIOUS AREA AND WHICH |
| | DISCHARGE DIRECTLY IN TO SPECIFIC RECEIVING WATERS AS |
| | OUTLINED IN SECTION 5.2.2, VOLUME IV, SHALL PROVIDE AT |
| | LEAST ONE HALF INCH OF DRY DETENTION OR RETENTION |
| | PRETREATMENT AS PART OF THE REQUIRED |
| | RETENTION/DETENTION. C) WATER SURFACE AND ROOFED AREAS |
| | CAN BE DEDUCTED FROM SITE AREAS ONLY FOR WATER QUALITY |
| | PERVIOUS/IMPERVIOUS CALCULATIONS. THE WATER SURFACE |
| | AREA MEETING DIMENSIONAL CRITERIA MAY ALSO BE |
| | SUBTRACTED FROM THE TOTAL SITE AREA WHEN MAKING FINAL |
| | WATER QUALITY TREATMENT VOLUME CALCULATIONS. D) IN |
| | CASES OF WIDENING EXISTING URBAN PUBLIC HIGHWAY |
| | PROJECTS, THE DISTRICT SHALL REDUCE THE WATER QUALITY |
| | REQUIREMENTS, IF THE APPLICANT PROVIDES DOCUMENTATION |
| | WHICH DEMONSTRATES THAT ALL REASONABLE DESIGN |
| | ALTERNATIVES HAVE BEEN CONSIDERED, AND WHICH PROVIDES |
| | EVIDENCE THAT THE ALTERNATIVES ARE ALL |
| | COST-PROHIBITIVE. E) PROJECTS WITHIN CONES OF |
| | DEPRESSION ? RETENTION/DETENTION AREA LOCATIONS SHALL |
| | NOT REDUCE HYDRAULIC RECHARGE DISTANCES TO PUBLIC WATER |
| | SUPPLY WELLS IN EXCESS OF 2%, NOR SHALL WET |
| | RETENTION/DETENTION AREAS BE CLOSER TO PUBLIC WATER |
| | SUPPLY WELLS THAN 300 FEET. |
| | |
| | IMPERVIOUS AREAS: |
| | RUNOFF SHALL BE DISCHARGED FROM IMPERVIOUS SURFACES |
| | THROUGH RETENTION AREAS, DETENTION DEVICES, FILTERING |
| | AND CLEANSING DEVICES, OR SUBJECT TO SOME OTHER TYPE OF |
| | BEST MANAGEMENT PRACTICE (BMP) PRIOR TO DISCHARGE FROM |
| | THE PROJECT SITE. PROJECTS WHICH INCLUDE SUBSTANTIAL |
| | PAVED AREAS, SUCH AS, SHOPPING CENTERS, LARGE HIGHWAY |
| | INTERSECTIONS WITH FREQUENT STOPPED TRAFFIC, AND HIGH |
| | DENSITY DEVELOPMENTS, PROVISIONS SHALL BE MADE FOR THE |
| | REMOVAL OF OIL, GREASE, AND SEDIMENT FROM STORMWATER |
| | DISCHARGES. |
| | _______________________________________________________ |
| | __________________________________ |
| | CODE OF ORDINANCES, CITY OF WEST PALM BEACH, FLORIDA, |
| | CODIFIED THROUGH ORD. NO. 4183-08, ADOPTED SEPT. 22, |
| | 2008. (SUPPLEMENT NO. 18), CHAPTER 94 ZONING AND LAND |
| | DEVELOPMENT REGULATIONS |
| | ARTICLE XIV. LANDSCAPING, LAND CLEARING, AND TREE |
| | PROTECTION |
| | SEC. 94-450. VACANT LOT AND CONSTRUCTION SITE |
| | MAINTENANCE. |
| | (A) INTENT. THE INTENT OF THIS SECTION IS TO MINIMIZE |
| | THE DETRIMENTAL HEALTH, SAFETY, GENERAL WELFARE AND |
| | IMPACTS OF VACANT |
| | LOTS AND CONSTRUCTION ACTIVITIES ON THE RESIDENTS OF |
| | THE CITY OF WEST PALM BEACH; TO ENSURE THAT EACH VACANT |
| | LOT AND |
| | CONSTRUCTION SITE IS MAINTAINED, AND EACH CONSTRUCTION |
| | ACTIVITY IS CONDUCTED IN SUCH A MANNER SO AS TO AVOID |
| | UNNECESSARY INCONVENIENCE AND ANNOYANCE TO THE GENERAL |
| | PUBLIC AND THE OCCUPANTS OF THE NEIGHBORING PROPERTIES; |
| | AND TO REQUIRE MAINTENANCE PRACTICES THAT WILL REDUCE |
| | THE AMOUNT OF SEDIMENT AND OTHER POLLUTANTS LEAVING |
| | CONSTRUCTION SITES DURING LAND DEVELOPMENT OR LAND |
| | DISTURBING CONSTRUCTION ACTIVITIES. |
| | _______________________________________________________ |
| | __________________________________ |
| | |
| | - NO POLLUTION CONTROL PLAN SUBMITTED OR SUBMITTED WITH |
| | OUT ENGINEERING SERVICES DEPARTMENT APPROVED STAMP. |
| | -SUPPLY A POLLUTION CONTROL PLAN WITH A MINIMUM OF THE |
| | FOLLOWING INFORMATION; |
| | A) SILT FENCE NEEDS TO BE INSTALLED AROUND ANY AREAS TO |
| | BE DISTURBED. SHOW WHERE SILT SCREENS WILL BE INSTALLED |
| | B) FILTER FABRIC IS REQUIRED UNDER THE CATCH BASIN |
| | GRATES WITH ROCK BAGS AT ANY CURBED INLET ON-SITE TO |
| | STOP SOLIDS FROM ENTERING THE SYSTEM. SHOW THE |
| | PROTECTION OF ALL ON-SITE CATCH BASINS, SHOW PROTECTION |
| | OF ALL OFF-SITE CATCH BASINS, INCLUDE DETAILS AS TO THE |
| | TYPE OF PROTECTION USED ON AND OFF-SITE FOR THE CATCH |
| | BASINS, SUCH AS FILTER FABRIC IS REQUIRED UNDER THE |
| | CATCH BASIN GRATES WITH ROCK BAGS AT ANY CURBED INLET |
| | TO STOP SOLIDS FROM ENTER THE SYSTEM. |
| | C) ADD TURBIDITY BARRIER AT THE OUTFALLS AND ALONG THE |
| | FULL WIDTH OF THE PROJECT, SHOW WHERE SILT SCREENS WILL |
| | BE INSTALLED, HOW THEY WILL BE TIED DOWN AND |
| | MAINTAINED. |
| | D) SHOW HOW SITE DIRT WILL NOT BE TRACKED INTO THE |
| | ROADS |
| | E) DETAIL HOW AND WHEN ANY CLEAN-UP WILL BE PREFORMED. |
| | |
| | _______________________________________________________ |
| | __________________________________ |
| | COMMENTS CONCERNING STORMWATER SYSTEM: |
| | CODE OF ORDINANCES, CITY OF WEST PALM BEACH, FLORIDA, |
| | CODIFIED THROUGH ORD. NO. 4183-08, ADOPTED SEPT. 22, |
| | 2008. (SUPPLEMENT NO. 18). |
| | SECTION 109.3.10 , IMPACT OF CONSTRUCTION , OF THE CITY |
| | CODE REQUIRES A PROFESSIONAL ENGINEER TO PREPARE A |
| | DRAINAGE PLAN AND CERTIFY THE WORK. MAY BE UNDER THE |
| | BUILDING CODE, LOOK IT UP WHEN YOU GET A CHANCE. |
| | _______________________________________________________ |
| | __________________________________ |
| | - NO STORMWATER SYSTEM PLAN SUBMITTED OR SUBMITTED WITH |
| | OUT ENGINEERING SERVICES DEPARTMENT APPROVED STAMP. |
| | |
| | _______________________________________________________ |
| | __________________________________ |
| | COMMENTS CONCERNING WATER SYSTEM: ANY NEW CITY WATER |
| | SERVICE? IRRIGATION? ETC. |
| | _______________________________________________________ |
| | __________________________________ |
| | CODE OF ORDINANCES, CITY OF WEST PALM BEACH, FLORIDA, |
| | CODIFIED THROUGH ORD. NO. 4183-08, ADOPTED SEPT. 22, |
| | 2008. (SUPPLEMENT NO. 18) |
| | CHAPTER 90 UTILITIES, ARTICLE I. IN GENERAL, |
| | SEC. 90-7. POLICY REGARDING EXTENSION OF WATER OR SEWER |
| | SERVICE FACILITIES OF THE CITY. |
| | _______________________________________________________ |
| | ___________________________________ |
| | |
| | - NO WATER SYSTEM PLAN SUBMITTED OR SUBMITTED WITH OUT |
| | ENGINEERING SERVICES DEPARTMENT APPROVED STAMP. |
| | _______________________________________________________ |
| | __________________________________ |
| | |
| | COMMENTS CONCERNING SANITARY SYSTEM: ANY NEW CITY |
| | SEWER? |
| | _______________________________________________________ |
| | _________________________________ |
| | CODE OF ORDINANCES, CITY OF WEST PALM BEACH, FLORIDA, |
| | CODIFIED THROUGH ORD. NO. 4183-08, ADOPTED SEPT. 22, |
| | 2008. (SUPPLEMENT NO. 18) |
| | CHAPTER 90 UTILITIES, ARTICLE I. IN GENERAL, |
| | SEC. 90-7. POLICY REGARDING EXTENSION OF WATER OR SEWER |
| | SERVICE FACILITIES OF THE CITY. |
| | _______________________________________________________ |
| | __________________________________ |
| | - NO SANITARY SYSTEM PLAN SUBMITTED OR SUBMITTED WITH |
| | OUT ENGINEERING SERVICES DEPARTMENT APPROVED STAMP. |
| | |
| | _______________________________________________________ |
| | __________________________________ |
| | COMMENTS CONCERNING LIGHTING: |
| | _______________________________________________________ |
| | __________________________________ |
| | - NO LIGHTING PLAN SUBMITTED OR SUBMITTED WITH OUT |
| | ENGINEERING SERVICES DEPARTMENT APPROVED STAMP. |
| | |
| | _______________________________________________________ |
| | __________________________________ |
| | COMMENTS CONCERNING IRRIGATION: |
| | _______________________________________________________ |
| | __________________________________ |
| | - IRRIGATION PLAN SUBMITTED OR SUBMITTED WITH OUT |
| | ENGINEERING SERVICES DEPARTMENT APPROVED STAMP. |
| | |
| | _______________________________________________________ |
| | __________________________________ |
| | COMMENTS CONCERNING LANDSCAPING: |
| | _______________________________________________________ |
| | __________________________________ |
| | - NO LANDSCAPING PLAN SUBMITTED OR SUBMITTED WITH OUT |
| | ENGINEERING SERVICES DEPARTMENT APPROVED STAMP. |
| | _______________________________________________________ |
| | __________________________________ |
| | COMMENTS CONCERNING SURVEY ISSUES: |
| | PER; CODE OF ORDINANCES, CITY OF WEST PALM BEACH, |
| | FLORIDA, CODIFIED THROUGH ORD. NO. 4183-08, ADOPTED |
| | SEPT. 22, 2008. (SUPPLEMENT NO. 18), CHAPTER 78 |
| | STREETS, SIDEWALKS AND PUBLIC PLACES, ARTICLE I. IN |
| | GENERAL, SECTION 78-9. CITY DATUM OR PLANE OF |
| | REFERENCE. |
| | (A) THE CITY DATUM OR OFFICIAL CITY BASE OR PLANE OF |
| | REFERENCE FOR ELEVATIONS IN THE CITY IS HEREBY FIXED AS |
| | THE NATIONAL GEODETIC VERTICAL DATUM OF 1929 (NGVD-29), |
| | AS ESTABLISHED BY THE UNITED STATES COAST AND GEODETIC |
| | SURVEY. |
| | (B) ALL OFFICIAL ELEVATIONS, INCLUDING BUT NOT |
| | RESTRICTED TO SIDEWALK, STREET AND SEWER GRADES, |
| | HEREAFTER ESTABLISHED IN THE CITY SHALL BE DESCRIBED |
| | WITH REFERENCE TO THEIR ELEVATIONS, AS COMPARED WITH |
| | THE OFFICIAL CITY DATUM IN FEET AND DECIMALS OF A FOOT. |
| | NO GRADE OR OFFICIAL ELEVATION SHALL BE ESTABLISHED |
| | OTHER THAN IN THE MANNER PRESCRIBED IN THIS SECTION. |
| | PLEASE USE THIS DATUM AND CALL IT OUT ON THE PLAN |
| | SHEETS AS A NOTE. |
| | _______________________________________________________ |
| | __________________________________ |
| | COMMENTS CONCERNING SIDEWALKS AND DRIVEWAY APPROACHES |
| | _______________________________________________________ |
| | __________________________________ |
| | -DRIVEWAY APPROACH AND OR SIDEWALK PLAN NEEDS TO BE |
| | APPROVED BY THE ROW PERMIT REVIEWER AT THE TRAFFIC |
| | ENGINEERING OFFICE PRIOR TO BEING SUBMITTED TO |
| | CONSTRUCTION SERVICES. |
| | - NO SIDEWALK OR DRIVEWAY APPROACH PLAN SUBMITTED OR |
| | SUBMITTED WITH OUT ENGINEERING SERVICES DEPARTMENT |
| | APPROVED STAMP. PRIOR TO SUBMITTING ROW PERMIT ASK THE |
| | RECEPTIONIST TO FAX IT TO YOU OR STOP BY AND PICK UP A |
| | COPY. |
| | CONTACT THE RIGHT-OF-WAY REVIEWER, WINDEL PALMER, |
| | PROJECT COORDINATOR, THE TRAFFIC ENGINEERS OFFICE AT: |
| | 1000 ? 45TH STREET, SUITE 15 |
| | WEST PALM BEACH, FL 33407 |
| | TELEPHONE: (561)494-1041 |
| | FAX: (561) 494-1069 |
| | |
| | FORM CAN BE DOWNLOADED VIA WEB: |
| | HTTP://WWW.CITYOFWPB.ORG/ENGINEERING/ENG_INFO.HTM#RIGHT |
| | OFWAY |
| | |
| | _______________________________________________________ |
| | __________________________________ |
| | COMMENTS CONCERNING STREETS, SIGNAGE, ADA,: |
| | _______________________________________________________ |
| | __________________________________ |
| | - NO STREET, CURB, ADA PLAN SUBMITTED OR SUBMITTED WITH |
| | OUT ENGINEERING SERVICES DEPARTMENT APPROVED STAMP. |
| | _______________________________________________________ |
| | __________________________________ |
| | COMMENTS CONCERNING DUMPSTERS AND ENCLOSURES: |
| | _______________________________________________________ |
| | __________________________________ |
| | - ENCLOSURE DETAIL NOT SUBMITTED OR SUBMITTED WITH |
| | NON-STANDARD DETAIL OR WITH OUT ENGINEERING SERVICES |
| | DEPARTMENT APPROVED STAMP. |
| | DETAIL MUST MATCH WHAT IS TO BE PERMITTED. IF THE CITY |
| | DETAIL IS USED THEN A WOOD ENCLOSURE WILL NEED TO BE |
| | BUILT. IF CHAIN LINK OR A CONCRETE WALL ARE TO BE USED |
| | THEN SUBMIT A DETAIL FOR ONE OF THEM. |
| | _______________________________________________________ |
| | __________________________________ |
| | |
| | THANK YOU FOR YOUR PROMPT ASSISTANCE. |
| | |
| | MANNY GONZALEZ |
| | PROJECT COORDINATOR |
| | CITY OF WPB ENGINEERING SERVICES |
| | (561) 494-1085 |
| | AT CS EXT 561-805-6713 |
| | |
| | |
| | |
| | |