| 2008-11-06 16:24:40 | GAS PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS. PER FBC-2004 |
| | FUEL GAS CODE SECTION 401.1 SCOPE. |
| | *NOTE: THE SUBMITTED GAS ISOMETRIC DOES NOT INDICATE |
| | CORRESPONDING LENGTHS TO ALL CUT SECTIONS OF PIPE. |
| | PLEASE REFERENCE THE YELLOW HIGH LIGHTED CUT SECTIONS |
| | WITH NO CORRESPONDING LENGTHS BEING INDICATED AND |
| | COMPLY ON THE RESUBMITTAL. |
| | |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | PER FBC-2004 FUEL GAS CODE SECTION 401.1 SCOPE. |
| | *NOTE: THE SUBMITTED GAS ISOMETRIC ONLY INDICATES THE |
| | PIPING MATERIAL AND SIZE OF THE UNDERGROUND GAS PIPE. |
| | WHAT ARE THE PIPE SIZES AND MATERIAL TYPE OF THE |
| | PROPOSED ABOVEGROUND GAS PIPE? |
| | |
| | 3. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | *NOTE: THE SUBMITTED GAS ISOMETRIC LONGEST RUN |
| | INDICATES 160', HOWEVER AS WAS STATED IN COMMENT #1 NOT |
| | ALL CUT SECTIONS HAVE CORRESPONDING LENGTHS BEING |
| | INDICATED. PLEASE REFERENCE COMMENT #1 AND CORRECT AND |
| | CORRELATE LONGEST LENGTH ON THE RESUBMITTAL. |
| | |
| | 4. PLEASE KNOW THAT MP REGULATORS (2 PSI TO 0.5 PSI) |
| | SHALL BE REQUIRED FOR THE GAS SYSTEM AND NEED TO BE |
| | CLEARLY INDICATED ON THE RESUBMITTED GAS ISOMETRIC. PER |
| | FBC-2004 FUEL GAS SECTION 410.1 PRESSURE REGULATORS. |
| | |
| | 5. PER FBC-2004 FUEL GAS, SECTION 409.4 MP REGULATOR |
| | VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED |
| | IMMEDIATELY AHEAD OF EACH MP REGULATOR AND CLEARLY |
| | INDICATED ON THE RESUBMITTAL. |
| | |
| | 6. SUBMIT TWO COPIES OF MANUFACTURE SHEETS FOR THE MP |
| | REGULATORS TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, |
| | NFPA 58, AND THE FBC-2004 FUEL GAS CODE SEC 402.2. THE |
| | MANUFACTURE SHEETS SHALL CLEARLY INDICATE THE MP |
| | REGULATORS MAKE, MODEL NUMBER, BTU LOAD CAPACITY, AND A |
| | LISTING FROM A NATIONALLY RECOGNIZED TESTING LABORATORY |
| | SUCH AS CSA, AGA OR UL. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |
| | *PLEASE CALL IF THERE ARE ANY QUESTIONS. |
| | |