Plan Review Details - Permit 08110081
Plan Review Stops For Permit 08110081
Review Stop AD ADDRESSING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2008-11-07 Time 10:04 Rev Time 0.00
Received By   Date 2008-11-06 Time 15:05 Sent To  
Notes
2008-11-07 09:46:31THERE WAS AN ISSUE AS THE CITIZEN CLAIMED THAT THE BACK
 BUILDING HAD AN ADDRESS OF 414 7TH ST ON IT, AND THIS
 PERMIT WAS BEING ATTACHED TO PCN# 74434321060010070
 WITH AN ADDRESSS OF 420 7TH ST. I PHYSICALLY VISITED
 THE SITE ON LOCATION & DETERMINED THAT THE CITIZEN WAS
 ABSOLUTELY CORRECT. I TALKED TO THE CONTRACTOR, GLENN
 S. PERCY OF GSP & ASSOCIATES, INC. & HE SPECIFICALLY
 MENTIONED THAT NO WORK WAS BEING DONE ON THE ADJACENT
 VACANT PARKING LOT (WHICH WAS PCN# 74434321060010070 -
 420 7TH ST). THIS BUILDING ACTUALLY FALLS WITHIN THE
 BOUNDARIES OF PCN# 74434321060010012 AS THE CONTRACTOR
 & I COULD CLEARLY SEE FROM AN AERIAL MAP OF THE
 PARCELS. THIS PERMIT HAS BEEN ATTACHED TO THE WRONG
 PCN# 74434321060010070 WHEN IT SHOULD BE APPLIED
 INSTEAD TO PCN# 74434321060010012, WHICH HAS A PRIMARY
 ADDRESS OF 711 N DIXIE HWY & A NEW SECONDARY ADDRESS OF
 414 7TH ST. I ISSUED THE NEW ADDRESS OF 414 7TH ST FOR
 THE BUILDING & SENT A NOTICE TO ALL RELEVANT PARTIES
 VIA E-MAIL. I CREATED 414 7TH ST AS UNIT 0002 UNDER THE
 CORRECT PCN# 74434321060010012 IN COMMUNITYPLUS, SO
 PLEASE ATTACH THIS PERMIT TO IT.

Review Stop AD ADDRESSING
Rev No 1 Status N Date 2009-01-27 Cont ID  
Sent By lmartine Date 2009-01-27 Time 11:16 Rev Time 0.00
Received By lmartine Date 2008-11-06 Time 15:05 Sent To  
Notes
2008-11-05 15:03:38SENT TO ADDRESSING BECAUSE CUSTOMER STATES THAT THE
 ADDRESS ON THE BUILDING IS 414 7TH ST

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-01-22 Cont ID  
Sent By shill Date 2009-01-22 Time 08:40 Rev Time 0.00
Received By shill Date 2009-01-22 Time 08:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-11-19 Cont ID  
Sent By shill Date 2008-11-19 Time 18:17 Rev Time 0.00
Received By shill Date 2008-11-19 Time 18:17 Sent To  
Notes
2008-11-19 18:22:35****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER OF
 RECORD (SHOP DRAWING REVIEW STAMP OR LETTER),
 FBC*106.3.3.
  
 2. DECLARE LEVEL OF ALTERATION, FBC EB CHAPTER 3.
  
 3. THIS APPEARS TO BE A CHANGE OF OCCUPANCY. PLEASE
 NOTE ON THE PLAN; THIS IS TO COMPLY WITH FBC EB CHAPTER
 8. DECLARE EXISTING OCCUPANCY; SEE FBC EB TABLE
 812.4.1, TABLE 812.4.2, TABLE 812.4.3.
  
 4. SEE OTHER REVIEWERS' COMMENTS REGARDING THE ADDRESS
 AND PARCEL ID. PLEASE REVISE PLANS, NOC, AND
 APPLICATION AS NECESSARY.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-01-12 Cont ID  
Sent By dpalmer Date 2009-01-12 Time 17:00 Rev Time 0.00
Received By dpalmer Date 2009-01-12 Time 17:00 Sent To  
Notes
2009-01-12 17:02:05NO NEW ELECTRICAL WORK BEING DONE. ELECTRICAL DEMO
 PERMIT REQUIRED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-11-19 Cont ID  
Sent By dpalmer Date 2008-11-19 Time 15:16 Rev Time 0.00
Received By dpalmer Date 2008-11-19 Time 15:16 Sent To  
Notes
2008-11-19 15:16:40 
  
  
 ** FAILED REVIEW **
  
  
  
 1) NOTE: PLEASE SUBMIT ELECTRICAL PLANS FOR ELECTRICAL
 SCOPE OF WORK.
 PLANS NEED TO SHOW MINIMUM FOR LIFE SAFETY CODE
 NFPA-101 , NFPA-70 (NEC).
 PLEASE BE SURE TO SEE FBC CHAPTER 13 FOR ANY NEW
 CONTROLS BEING INSTALLED.
 PLEASE SEE THE PLANS REFERENCE THE 2005 NFPA-72 WHICH
 IS NOT YET ADOPTED IN THE STATE OF FLORIDA.
 FBC 106.1.1, 106.1.2 FOR ADDITIONAL INFORMATION
  
 ** IF THERE ARE ANY QUESTIONS PLEASE CALL TO GO OVER TO
 HELP ALLEVIATE ANY DELAYS IN THE PROJECT MOVING
 FORWARD.
  
 2) NOTE: PLEASE BE SURE TO CORRECT ADDRESS ON TITLE
 BLOCKS AND PERMIT APPLICATION ONCE FINAL LOCATION HAS
 BEEN DETERMINED.
 FAC 61G1-16.004
 FBC 106.5.
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-01-14 Cont ID  
Sent By mwennerg Date 2009-01-14 Time 15:17 Rev Time 0.00
Received By mwennerg Date 2009-01-14 Time 15:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-12-02 Cont ID  
Sent By mawillia Date 2008-12-02 Time 16:11 Rev Time 0.00
Received By mawillia Date 2008-12-02 Time 15:41 Sent To  
Notes
2008-12-02 16:10:14*****UNSAT*****
  
  
 1. SPECIFY THE INTERIOR FINISH MATERIALS FOR THE WALLS
 AND CEILINGS IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 2. ON THE APPROPIATE ELEVATION FRONTING 7TH STREET,
 DISPLAY/SHOW THE NUMERICAL ADDRESS NUMBERS FOR THE
 BUILDING. AS PER WEST PALM BEACH CODE, THE ADDRESS
 NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS
 THAN 1" IN WIDTH/STROKE.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-12-23 Cont ID  
Sent By adarroug Date 2008-12-23 Time 14:56 Rev Time 0.00
Received By adarroug Date 2008-12-23 Time 14:56 Sent To  
Notes
2008-12-23 14:59:03TO "COMM" BD#50

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-12-10 Cont ID  
Sent By kstevens Date 2008-12-10 Time 08:17 Rev Time 0.00
Received By kstevens Date 2008-11-06 Time 09:41 Sent To  
Notes
2008-11-06 09:49:31TO "COMM" BD#5

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2008-11-07 Cont ID  
Sent By tgordon Date 2008-11-07 Time 14:07 Rev Time 0.30
Received By tgordon Date 2008-11-07 Time 14:07 Sent To  
Notes
2008-11-07 14:08:30DEMO KITCHEN HOOD, NOT BEING REPLACED MENHANICAL PERMIT
 NOT NEEDED.

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-01-27 Cont ID  
Sent By lwagner Date 2009-01-27 Time 11:09 Rev Time 0.00
Received By lwagner Date 2009-01-27 Time 10:40 Sent To  
Notes
2009-01-27 11:11:02PLUMBING DEMO PERMIT REQUIRED

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-12-09 Cont ID  
Sent By kstevens Date 2008-12-09 Time 16:54 Rev Time 0.00
Received By kstevens Date 2008-12-09 Time 16:54 Sent To  
Notes
2008-12-09 16:57:59DENIED
 REFERENCE:
 FBC-2004 PLUMBING
  
 1. SHT 1 DEMO SHEET, DEMOLITION NOTES STATE CAP ALL
 REMOVED PLUMBING FLUSH WITH THE FLOOR AND BEHIND
 GYPBORD AT CHASE PARTITIONS. PER SECTION 704.5 IN THE
 REMOVAL OF ANY DRAINAGE PIPING, DEAD ENDS ARE
 PROHIBITED. ALL SANITARY DRAINAGE PIPING SHALL BE
 CAPPED OFF WITHIN TWO FEET OF AN ACTIVE BUILDING DRAIN.
 PLEASE INDICATE ON THE PLANS WHERE THE PIPING WILL BE
 CAPPED OFF.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2009-01-13 Cont ID  
Sent By aaponte Date 2009-01-13 Time 12:07 Rev Time 0.00
Received By aaponte Date 2008-12-31 Time 13:12 Sent To  
Notes
2008-12-31 13:13:27APPROVED PERMIT DOES NOT INCLUDE ANY IMPROVEMENTS TO
 LANDSCAPE OR PARKING LOT.

Review Stop Z ZONING
Rev No 1 Status F Date 2008-11-10 Cont ID  
Sent By aaponte Date 2008-11-10 Time 14:42 Rev Time 0.00
Received By aaponte Date 2008-11-10 Time 14:22 Sent To  
Notes
2008-11-10 14:47:52PLEASE PROVIDE A SITE PLAN WITH EXISTING CONDITIONS AND
 PROPOSED IMPROVEMENTS. PLEASE PROVIDE A DEMOLITION PLAN
 INCLUDING FLOOR PLANS AND ELEVATIONS.