Plan Review Details - Permit 08110061
Plan Review Stops For Permit 08110061
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2009-10-29 Cont ID  
Sent By rmcdouga Date 2009-10-29 Time 14:00 Rev Time 0.00
Received By rmcdouga Date 2009-10-29 Time 14:00 Sent To  
Notes
2009-10-29 14:03:42REVISED ENERGY CALCULATIONS AND REVISED PLAN SHEETS 8
 AND 9 HAVE BEEN REVIEWED FOR CODE COMPLIANCE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2009-10-21 Cont ID  
Sent By rmcdouga Date 2009-10-21 Time 07:36 Rev Time 0.00
Received By rmcdouga Date 2009-10-21 Time 06:43 Sent To  
Notes
2009-10-21 07:36:22A. THE METAL ROOF PRODUCT APPROVALS SUBMITTED FOR
 CHANGING TO ANOTHER MANUFACTURER ARE OK.
  
 B. SPECIFICATIONS FOR CHANGING TO ICYNENE SPRAY FOAM
 INSULATION IS APPROVED WITH THE FOLLOWING EXCEPTIONS.
  
 (1) SUBMIT TWO SIGNED AND SEALED SETS OF REVISED WALL
 SECTION DRAWINGS (SHEET 8) SHOWING THE LOCATION OF
 ICYNENE INSULATION, SPECIFY THE R-VALUES, SHOW THAT
 THERE IS NO ATTIC VENTILATION.
  
 2) THE CERTIFICATE OF INSULATION THAT WAS SUBMITTED
 SPECIFIES THAT THE HOUSE ROOF DECK IS INSULATED WITH
 R-20 ICYNENE AND THE ENERGY CALCULATION FORM REQUIRES
 R-30 INSULATION. SUBMIT A REVISED ENERGY CALCULATION
 FORM. THIS PROJECT WAS PERMITTED UNDER THE 2004 FBC,
 THE ENERGY CALCS. ARE ON FORM 600A-2004R. NOT THE 2007
 VERSION.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2009-05-11 Cont ID  
Sent By rmcdouga Date 2009-05-11 Time 10:22 Rev Time 0.00
Received By rmcdouga Date 2009-05-11 Time 10:22 Sent To  
Notes
2009-05-11 10:24:00BUILDING REVISION SHEETS 1, 2, 4 AND NEW SHEET 10 ARE
 OK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-03-31 Cont ID  
Sent By rmcdouga Date 2009-03-31 Time 14:59 Rev Time 0.00
Received By rmcdouga Date 2009-03-31 Time 14:59 Sent To  
Notes
2009-03-31 14:59:54PROCESS PLANS

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-03-27 Cont ID  
Sent By rmcdouga Date 2009-03-27 Time 11:36 Rev Time 0.00
Received By rmcdouga Date 2009-03-27 Time 11:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-02-27 Cont ID  
Sent By rmcdouga Date 2009-02-27 Time 14:33 Rev Time 0.00
Received By rmcdouga Date 2009-02-26 Time 16:46 Sent To  
Notes
2009-02-27 14:36:44A COPY OF THE PAID RECIEPT FOR COUNTY IMPACT FEES IS
 REQUIRED BEFORE PERMIT CAN BE ISSUED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-11-26 Cont ID  
Sent By rmcdouga Date 2008-11-26 Time 07:51 Rev Time 0.00
Received By rmcdouga Date 2008-11-26 Time 07:51 Sent To  
Notes
2008-11-26 09:02:572004 FBC W/2007 REVISIONS
 ADDITION
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED. FS 713
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED. PH#
 561-233-5025
  
 3) SHOW COMPLIANCE WITH R302.1 EXTERIOR WALLS.EXTERIOR
 WALLS SEPARATED BY LESS THAN 6 FEET (1828 MM) SHALL
 HAVE NOT LESS THAN A ONE-HOUR FIRE-RESISTIVE RATING
 WITH EXPOSURE FROM BOTH SIDES. PROJECTIONS SHALL NOT
 EXTEND TO A POINT CLOSER THAN 4 FEET (1220 MM) FROM AN
 ADJACENT PROJECTION OR WALL. THE REAR WALL OF THE
 ADDITION IS LESS THAN 6' FROM THE PROPERTY LINE.
 SPECIFY ON THE SITE PLAN THAT THE DISTANCE TO
 STRUCTURES ON ADJACENT PROPERTY IS MORE THAN SIX FEET.
  
 4) SHOW COMPLIANCE WITH R302.2 OPENINGS. OPENINGS SHALL
 NOT BE PERMITTED IN THE EXTERIOR WALL OF A DWELLING OR
 ACCESSORY BUILDING THAT IS SEPARATED FROM AN ADJACENT
 BUILDING BY A DISTANCE OF LESS THAN 6 FEET (1828 MM).
 THIS DISTANCE SHALL BE MEASURED PERPENDICULAR TO THE
 LINE USED TO DETERMINE THE SEPARATION DISTANCE. SEE
 COMMENT #3.
  
 5) PROVIDE A DOOR BUCK FASTENING DETAIL. R613.6
  
 6) FOR THE SECOND FLOOR BEDROOM, SHOW COMPLIANCE WITH
 R310.1 EMERGENCY ESCAPE AND RESCUE REQUIRED. BASEMENTS
 WITH HABITABLE SPACE AND EVERY SLEEPING ROOM SHALL HAVE
 AT LEAST ONE OPENABLE EMERGENCY ESCAPE AND RESCUE
 OPENING. WHERE EMERGENCY ESCAPE AND RESCUE OPENINGS ARE
 PROVIDED THEY SHALL HAVE A SILL HEIGHT OF NOT MORE THAN
 44 INCHES ABOVE THE FLOOR. THE NET CLEAR OPENING
 DIMENSIONS REQUIRED BY THIS SECTION SHALL BE OBTAINED
 BY THE NORMAL OPERATION OF THE EMERGENCY ESCAPE AND
 RESCUE OPENING FROM THE INSIDE. R310.1.1 MINIMUM
 OPENING AREA. ALL EMERGENCY ESCAPE AND RESCUE OPENINGS
 SHALL HAVE A MINIMUM NET CLEAR OPENING OF 5.7 SQUARE
 FEET.
  
 7) SPECIFY THE WINDOW SIZES ON THE PLANS. R301.2.1
  
 8) ALTHOUGH THE STRUCTURE IS LOCATED IN WIND EXPOSURE
 CATEGORY B, SHEET 5 OF THE PLANS SPECIFIES EXPOSURE C.
 THE PRESSURES SPECIFIED ON THE PLANS FOR THE DOORS AND
 WINDOWS ARE FOR EXPOSURE B. PLEASE REVISE. SEE R301.2.1
 AND TABLE R301.2(2).
  
 9) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 10) SPECIFY THE FLORIDA PRODUCT APPROVAL FL NUMBERS ON
 THE PLANS FOR THE TRUSS CONNECTORS OR SUBMIT TWO COPIES
 OF PRODUCT APPROVALS FOR THEM. FAC RULE 9B-72.
  
 11) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 PGT C-740 CASEMENT WINDOWS ARE EXPIRED. PLEASE SUBMIT
 TWO COPIES OF THE CURRENT ONES (NOA 08-0117.11).
  
 12) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 METAL ROOF (NOA 07-0130.06) ARE FOR A STEEL ROOF DECK.
 THE ADDITION HAS A WOOD DECK. SUBMIT TWO COPIES OF THE
 ROOF COVERING PRODUCT APPROVALS FOR INSTALLATION ON A
 WOOD DECK. FAC RULE 9B-72.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2009-10-26 Cont ID  
Sent By btrobaug Date 2009-10-26 Time 08:50 Rev Time 0.00
Received By btrobaug Date 2009-10-26 Time 08:43 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-03-13 Cont ID  
Sent By dpalmer Date 2009-03-13 Time 16:24 Rev Time 0.00
Received By dpalmer Date 2009-03-13 Time 16:24 Sent To P
Notes
2009-03-13 16:25:11** PROVISO/REDLINED **
  
 1) NOTE: ALTHOUGH THE LOAD FOR THE LAUNDRY CIRCUIT WAS
 REVISED TO 1.5, THE LOAD CALCULATIONS WERE NOT UPDATED.
 PLEASE ALSO SEE THE WASHER CIRCUIT LOAD IS A LAUNDRY
 CIRCUIT. 1.5 REQUIRED.
 EVEN AS THIS ADDITIONAL LOAD WILL NOT AFFECT THE OVER
 ALL SIZE OF THE SERVICE THE CALCULATIONS DO NEED TO BE
 UPDATED.
 220, 210.11C2, 220.52.
  
 2) NOTE: PLEASE SEE THE SECOND SMALL APPLIANCE CIRCUIT
 WHICH DOES NOT INDICATE ANY BREAKER. THE REQUIRED 20AMP
 BREAKER
  
 ** PLEASE REVISE ALONG WITH ANY OTHER REVISIONS BEFORE
 ROUGH ELECTRICAL INSPECTION. THE PLANS WILL NEED TO BE
 SUBMITTED, REVISED AND ON THE JOBSITE BEFORE SCHEDULING
 AN INSPECTION.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-02-12 Cont ID  
Sent By dpalmer Date 2009-02-12 Time 11:04 Rev Time 0.00
Received By dpalmer Date 2009-02-12 Time 11:04 Sent To P
Notes
2009-02-12 11:04:19** DENIED 2ND REVIEW **
  
 ** THERE ARE ITEMS WHICH ARE STILL IN NEED OF
 ADDRESSING FROM THE PREVIOUS REVIEWS.
  
 1) NOTE: PLEASE COORDINATE CIRCUITING ON PLANS WITH
 THAT OF THE PANEL SCHEDULE SUBMITTED. THE FOLLOWING ARE
 SOME EXAMPLES.
  
 FOR EXAMPLE: PLEASE SEE THE CIRCUIT L28/30 ON PLANS FOR
 RANGE/COOK TOP WHICH IS NOTED AS KITCHEN AND FAMILY
 ROOM LTS AS WELL AS DINING ROOM RECEPTACLES.
  
 FOR EXAMPLE: PLEASE SEE CIRCUIT L-25 ON PLANS UNDER
 STAIRS WHICH NOTES ON PANEL SCHEDULE AS BEING THE
 RANGE/COOK-TOP.
  
 FOR EXAMPLE: SMALL APPLIANCE KITCHEN COUNTER
 RECEPTACLES MAY NOT FEED OTHER AREAS AS STATED IN
 210.52B1. SEE OTHER AREAS IN THIS SECTION WHICH ARE
 PERMITTED HOWEVER FAMILY ROOM IS NOT ONE OF THEM.
  
 ** THESE ARE SOME EXAMPLES.
 NEC 408.4
 FBC 106.1.1, 106.1.2, 106.5 FOR COORDINATION, CLARITY
 OF RECORD PLANS.
 PREVIOUS REVIEW
  
 2) NOTE: PLEASE SEE 210.11C2, 220.52 FOR REQUIRED LOAD
 OF LAUNDRY CIRCUIT. THIS IS STILL TOO LOW.
 PREVIOUS REVIEW.
  
 3) NOTE: PLEASE SEE 210.11C1, 220.52A FOR THE ONE O OR
 MORE OF THE SMALL APPLIANCE CIRCUITS AND THE LIKE SUCH
 AS DINING ROOM PER 210.52B1.
 ( MINIMUM VA PER EACH OF THESE IS 1500VA)
 ONLY SHOWS LOAD FOR TWO ON THE LOAD CALCULATIONS.
 PREVIOUS REVIEW.
  
 4) NOTE: PLEASE SEE FBC 13-606.1.ABC.1.2.4 AS THE TYPE
 OF RECESSED CAN NOW NOTED ON PLANS IS NOT THE TYPE
 REQUIRED.
 PLEASE SEE THE SECTION OF THE CODE NOTED AND PLEASE SEE
 THE MANUFACTURES SPECS/CUT SHEETS FOR THE TYPE OF
 FIXTURE AS NOTED ON PLANS. THE PLANS STATE ICIT WHICH
 IS NOT AN AIR TIGHT CAN.
  
 5) NOTE: PLEASE SHOW THE LOCATION OF THE NEW SERVICE
 MAIN. 230.70,230.2,240.24,110.26 ETC
 PLANS SHOW THE METER AND THE SUB PANELS BUT NOT THE
 MAIN DISCONNECT.
  
 6) NOTE: PLEASE SEE 110.26 FOR REQUIRED CLEARANCES FOR
 THE A/C DISCONNECTS.
 THESE ARE CURRENTLY SHOWN BEHIND THE UNITS ON PLANS. IF
 THIS HAD BEEN THE ONLY ITEM IT WOULD HAVE BEEN REDLINED
 ON PLANS.
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-11-17 Cont ID  
Sent By dpalmer Date 2008-11-17 Time 13:54 Rev Time 0.00
Received By dpalmer Date 2008-11-17 Time 13:54 Sent To P
Notes
2008-11-17 13:54:45** FAILED REVIEW **
  
  
 1) NOTE: PLEASE SEE THE FOLLOWING CODES NEED TO BE
 LISTED ON ELECTRICAL PLANS FOR DESIGN.
 2005 NFPA-70 ( NEC)
 2003 NFPA-101
 2002 NFPA-72
  
 ** PLANS INDICATE PALM BEACH COUNTY WHEN THE ACTUAL
 APPLIED LOCATION IS IN THE CITY OF WEST PALM BEACH
  
 2) NOTE: PLEASE INDICATE THE AIC RATING OF NEW SERVICE
 EQUIPMENT. 110.9
  
 3) NOTE: PLEASE SEE THE EQUIPMENT GROUNDING CONDUCTOR
 AS REQUIRED PER 250.110,250.6,250.24 IS MISSING. PLEASE
 SEE 250.122 FOR SIZING.
  
 4) NOTE: PLEASE COMPLETE THE GROUNDING ELECTRODE
 SYSTEM. PLEASE SEE 250.50 AS THE NEW FOOTER STEEL IS A
 REQUIRED ATTACHMENT. PLEASE SEE THE RISER INDICATE
 3-#4. WHY IS THERE THREE OF THESE NUMBER FOUR
 CONDUCTORS? IS THIS A MISPRINT?
 PLEASE REVISE.
 PLEASE INCLUDE METALLIC COLD WATER PIPE.
  
 5) NOTE: PLEASE SEE PLANS AS THE SMOKE DETECTION
 DEVICES ARE SHOWN AS *SD*. THERE IS NO SYMBOL LEGEND
 HOWEVER AS A STANDARD OF INDUSTRY THESE WOULD BE SMOKE
 DETECTORS.
 BY THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE
 DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL
 NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY
 HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF
 SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V AND
 WOULD DETECT AND SOUND AN ALARM. IF THESE ARE IN FACT
 SMOKE DETECTORS PLEASE INCLUDE THE ENTIRE SYSTEM. IF
 THESE ARE IN FACT SMOKE ALARMS PLEASE ADJUST PLANS.
 ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC
 RESIDENTIAL CODE/ FBC AND IN NFPA-72.
 IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE*.
 PLEASE SEE NFPA-72 11.5.1.1, 11.8.3
  
 6) NOTE: PLEASE SEE FBC R313 AS THE EXISTING DWELLING
 IS REQUIRED TO BE BROUGHT UP TO CODE OR THE EXISTING IS
 TO SHOW MEETING THE CURRENT CODE FOR SMOKE
 DETECTION/SOUNDING DEVICES. PLEASE SHOW A LAYOUT OF THE
 EXISTING DWELLING WHICH WILL REQUIRE SMOKE DEVICES
 INSIDE AND OUTSIDE ALL BEDROOMS AND ON EACH LEVEL IF A
 MULTI-LEVEL BUILDING.
 PLEASE SHOW THE SMOKE DEVICES AS SA OR SD DEPENDING ON
 THE TYPE OF DEVICE. PLEASE SEE THE DEFINITIONS IN
 NFPA-72 OR CALL TO GO OVER.
 NFPA-72 11.5.1.1, 11.8.3
 AS NOTED IN NOTE #5 ABOVE PLEASE COORDINATE.
  
 7) NOTE: PLEASE SEE 210.52B1, 210.11C1, 220.52 FOR
 REQUIRED LOADS TO BE FIGURED FOR SMALL APPLIANCE AND
 DINING ROOM RECEPTACLES, BREAKFAST AREAS AND AREAS OF
 THE LIKE. THE LOAD SHOWN AS PORTABLE APPLIANCES IS TOO
 LOW.
  
 8) NOTE: PLEASE SEE 210.11C2, 220.52 AS THE
 WASHER/LAUNDRY CIRCUIT IS ALSO REQUIRED TO BE FIGURED
 FOR A MINIMUM VA LOAD. THE VA LOAD AS SHOWN ON THE
 CALCULATIONS IS TOO LOW.
  
 9) NOTE: PLEASE SEE 422.13 OF THE 2005 NEC. THIS HAS
 BEEN REVISED FROM THE 2002 NEC AS STORAGE TYPE WATER
 HEATERS ARE NOW CONSIDERED CONTINUOUS LOADS. PLEASE SEE
 DEFINITIONS IN NEC ARTICLE 100 AND LOADS UNDER
 2154.3,230.42, 220.40 ETC
 ALL CONTINUOUS LOADS ARE REQUIRED TO BE FIGURED AT
 125%. THIS WAS A CHANGE TO THE 2005 CODE.
  
 10) NOTE: PLEASE SEE THE PLANS SEEM TO SHOW A
 RECEPTACLE FOR ONE OF THE WATER HEATERS. PLEASE SEE
 4220.30,422.31 AS THIS IS REQUIRED TO BE A DISCONNECT.
 MAY NOT USE A CORD AND PLUG FOR THE DISCONNECTING MEANS
 FOR THIS LOAD.
  
 11) NOTE: PLEASE SEE 440.11 AS THE A/C EQUIPMENT IS
 MISSING REQUIRED DISCONNECTS. THIS COMMENT IS FOR ALL
 EQUIPMENT. NOT ALL IS SHOWN.
  
 12) NOTE: PLEASE SEE 210.63 FOR MISSING REQUIRED
 SERVICE RECEPTACLE(S).
 PLEASE SEE 210.8A3 FOR OUTDOOR RECEPTACLES WHICH ARE
 REQUIRED TO BE GFI/ GFI PROTECTED.
  
 13) NOTE: PLEASE SEE 210.52C1-5. THERE ARE A COUPLE OF
 RECEPTACLES MISSING ALONG COUNTER SPACES AS SHOWN.
  
 14) NOTE: PLEASE SEE 210.8A6 AS ALL RECEPTACLES SERVING
 KITCHEN COUNTER SPACE ARE REQUIRED TO BE GFI. AT THIS
 TIME ONLY RECEPTACLES WITHIN 6FT OF THE SINK ARE SHOWN
 AS GFI PROTECTED. THIS CHANGED IN THE 1993 NEC.
  
 15) NOTE: PLEASE LIST THE REQUIRED AFCI ( ARC FAULT)
 PROTECTED CIRCUITS PER 210.12.
 PLEASE KEEP IN MIND THAT ALL OUTLETS INCLUDING
 RECEPTACLES, SMOKE ALARM DEVICES, FANS, LIGHTS ETC ARE
 REQUIRED TO BE PROTECTED.
  
 16) NOTE: PLEASE SEE 424.3B FOR REQUIRED OVER CURRENT
 PROTECTION OF THE HEAT IN THE AIR HANDLING UNITS.
 REQUIRES 125% MINIMUM.
  
 17) NOTE: PLEASE SEE 210.52 FOR SOME MISSING
 RECEPTACLES. PLEASE SEE ONE SET OF PLANS HAS SOME
 REDLINES HOWEVER THESE ARE NOT ALL. PLEASE BE AWARE OF
 THE 2FT, 6FT, 12 FT RULE. SEE PLANS, RECEPTACLES
 REQUIRED WITHIN 6FT OF DOOR.
  
 18) NOTE: PLEASE SEE 210.52D, 210.11C3 FOR REQUIRED
 DEDICATED BATH CIRCUIT(S). MUST BE 20AMP AND #12.
  
 19) NOTE: PLEASE SEE THE REFRIGERATOR IS SHOWN AS #8
 CONDUCTOR ON A 20AMP BREAKER. THIS MUST BE A MISPRINT.
 PLEASE ADJUST.
 PLEASE SEE OTHER CONDUCTOR SIZES ON THE SCHEDULE IF
 THESE ARE SHOWN THEN THE ELECTRICAL CONTRACTOR WILL BE
 REQUIRED TO INSTALL PER PLANS OR PLANS WILL BE REQUIRED
 TO BE REVISED.
 110.3.
 FBC 106.1.1, FOR CLARITY, COORDINATION.
  
 20) NOTE: PLEASE SEE 408.4 AS THE PANEL SCHEDULE IS
 REQUIRED TO BE SPECIFIC TO ROOMS AND AREAS IN WHICH
 THEY FEED. PLEASE SEE THE FOLLOWING TEXT WHICH IS
 EXTRACTED DIRECTLY FROM THE 2005 NEC.
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.1.1,106.3.5.4,106.5
  
 21) NOTE: THIS COMMENT IS BASED ON UNKNOWN LIGHTING IN
 THE REMAINDER OF THE DWELLING. PLEASE SEE THAT THE
 RECESSED LIGHTING IN THE NUMBER AS SHOWN ON PLANS MUST
 BE BASED ON THE NUMBER OF FIXTURES AND MAXIMUM WATTAGE
 PER FIXTURE. PLEASE SEE THE PREVIOUS CODE 2002 WHICH IS
 SECTION 220.3B4. PLEASE SEE 220.14/220.12.
 PLEASE KNOW THIS WAS CONFIRMED AT THE SOUTHERN SECTION
 MEETING AND BROUGHT FORTH TO THE CODE PANELIST. WHEN A
 CONSIDERABLE NUMBER OF RECESSED FIXTURES OR OTHER
 FIXTURES ARE SHOWN THEN THE LOADS NEED TO BE SHOWN IN
 ADDITION TO THE GENERAL LIGHTING LOADS FIGURED.
 PLEASE CALL TO GO OVER.
  
 22) NOTE: PLEASE BE SURE TO STATE THE TYPE OF RECESSED
 LIGHTING FIXTURE TO BE USED FBC 13-606.1.ABC.1.2.4.
 THIS IS TO ALLEVIATE THE AIR MOVEMENT FROM CONDITIONED
 SPACE ETC.
  
  
  
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2009-10-28 Cont ID  
Sent By rmcdouga Date 2009-10-28 Time 10:26 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
2009-10-28 10:27:00BLDG REV TO R MCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2009-10-27 Cont ID  
Sent By shill Date 2009-10-27 Time 08:13 Rev Time 0.00
Received By shill Date 2009-10-27 Time 08:13 Sent To  
Notes
2009-10-27 08:13:41TO ZONING

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2009-10-20 Cont ID  
Sent By btrobaug Date 2009-10-20 Time 15:26 Rev Time 0.00
Received By btrobaug Date 2009-10-20 Time 15:26 Sent To Z
Notes
2009-10-20 15:30:46LANDSCAPE ONLY, TO ZONING BOX./WRT.

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2009-10-20 Cont ID  
Sent By lmartine Date 2009-10-19 Time 15:15 Rev Time 0.00
Received By lmartine Date 2009-10-19 Time 15:15 Sent To  
Notes
2009-10-20 15:16:54****************** EXPEDITED ****************
 GAVE TO ROBBIE

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2009-04-21 Cont ID  
Sent By dpalmer Date 2009-04-21 Time 17:08 Rev Time 0.00
Received By dpalmer Date 2009-04-21 Time 17:08 Sent To Z
Notes
2009-04-21 17:09:57SOKE TO CONTRACTOR, REDLINED SHEETS WHICH HAVE ELEC AND
 PLUMBING AS PER JERRY/CONTRACTOR REVISION IS FOR
 BUILDING ONLY. PLEASE DO NOT ROUTE TO ANY OTHER TRADES.
 PLANS DO NEED ZONING.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2009-03-31 Cont ID  
Sent By adarroug Date 2009-03-31 Time 14:21 Rev Time 0.00
Received By adarroug Date 2009-03-31 Time 14:21 Sent To L
Notes
2009-03-31 14:22:10TO "Z" BOX/SUBMITTAL--FOR LANDSCAPE REV.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-03-05 Cont ID  
Sent By adarroug Date 2009-03-05 Time 13:07 Rev Time 0.00
Received By adarroug Date 2009-03-05 Time 13:07 Sent To L
Notes
2009-03-05 13:08:31TO "Z" BOX/RESUB--FOR LANDSCAPING REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-01-28 Cont ID  
Sent By adarroug Date 2009-01-28 Time 16:36 Rev Time 0.00
Received By adarroug Date 2009-01-28 Time 16:35 Sent To Z
Notes
2009-01-28 16:36:59TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-11-10 Cont ID  
Sent By adarroug Date 2008-11-10 Time 09:41 Rev Time 0.00
Received By adarroug Date 2008-11-10 Time 09:41 Sent To E
Notes
2008-11-10 09:41:23TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-11-26 Cont ID  
Sent By rmcdouga Date 2008-11-26 Time 07:51 Rev Time 0.00
Received By rmcdouga Date 2008-11-05 Time 08:28 Sent To  
Notes
2008-11-05 08:28:37TO "SFR" "Z"

Review Stop L LANDSCAPING
Rev No 5 Status P Date 2009-10-28 Cont ID  
Sent By rkussner Date 2009-10-28 Time 09:12 Rev Time 0.00
Received By rkussner Date 2009-10-28 Time 09:12 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 4 Status P Date 2009-10-21 Cont ID  
Sent By rkussner Date 2009-10-21 Time 15:52 Rev Time 0.00
Received By rkussner Date 2009-10-21 Time 15:39 Sent To  
Notes
2009-10-21 15:59:46***LANDSCAPE PASSED WITH PROVISO*** ____NO FEE
 REVISION____
  
 PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN WRITTEN
 FORMAT.
  
 1. PROVIDE THE TABULATION NECESSARY FOR THE EVALUATION
 OF COMPLIANCE WITH ARTICLE XIV OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS, INCLUDING THE XERISCAPE DESIGN
 OPTIONS.
  
 2. PURSUANT TO SECTION 94-448 (D), ALL RELEVANT ITEMS
 LISTED IN THIS SECTION SHALL BE PART OF THE LANDSCAPE
 PLAN. ON THE LANDSCAPE PLAN, SHOW ALL UTILITIES,
 OVERHEAD LINES, EASEMENTS, OVERHANGING TREE CANOPIES
 AND ANYTHING ELSE THAT MAY INTERFERE WITH THE PROPOSED
 LANDSCAPING.
  
 3. PROVIDE A COST ESTIMATE THAT INCLUDES THE TOTAL COST
 OF ALL LANDSCAPE MATERIALS AND LABOR, BROKEN DOWN INTO
 UNIT COST.
  
 4. PROVIDE SOD AND IRRIGATION IN RIGHT-OF-WAY.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop L LANDSCAPING
Rev No 3 Status P Date 2009-03-30 Cont ID  
Sent By rkussner Date 2009-03-30 Time 08:59 Rev Time 0.00
Received By rkussner Date 2009-03-30 Time 08:59 Sent To PC
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 2 Status F Date 2009-03-06 Cont ID  
Sent By rkussner Date 2009-03-06 Time 17:11 Rev Time 0.00
Received By rkussner Date 2009-03-06 Time 17:11 Sent To PC
Notes
2009-03-06 17:21:09***LANDSCAPE REVIEW FAILED***
  
 1. PURSUANT TO SECTION 94-445 (4)(A), SHADE, FLOWERING
 AND FRUIT TREES PLANTED PURSUANT TO THE PROVISIONS OF
 THIS SECTION SHALL BE A MINIMUM OF EIGHT FEET IN
 HEIGHT, AND POSSESS A MINIMUM OF FIVE FEET OF CLEAR
 TRUNK SPACE. TWO OF THE COCONUT PALMS CAN BE COUNTED
 BUT THREE ADDITIONAL SHADE OR FLOWERING TREES WILL NEED
 TO BE ADDED. FIVE SHADE TREES ARE REQUIRED BUT ONLY 35%
 OF THE REQUIRED TREES CAN BE PALMS.
  
 2. PLEASE SPECIFY WHAT PLANT MATERIAL IS PROPOSED AND
 PROVIDE THE QUANTITY, SIZE AND SPACING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2009-02-11 Cont ID  
Sent By rkussner Date 2009-02-11 Time 16:05 Rev Time 0.00
Received By rkussner Date 2009-02-11 Time 16:05 Sent To PC
Notes
2009-02-11 16:36:25***LANDSCAPE REVIEW FAILED***
  
 1. THE RIGHTS-OF-WAY SHALL BE SHOWN ON THE LANDSCAPE
 PLAN.
  
 2. ALL EXISTING TREES, SHRUBS AND GROUND COVER SHALL BE
 IDENTIFIED. PLEASE CLARIFY WHICH TREES AND SHRUBS ARE
 EXISTING AND WHICH ONES ARE PROPOSED.
  
 3. ALL PLANT MATERIAL, PROPOSED AND EXISTING TO REMAIN,
 SHALL BE FLORIDA #1 GRADE OR BETTER.
  
 4. PROVIDE A PLANT LIST IN TABULAR FORM THAT IDENTIFIES
 ALL PROPOSED AND EXISITNG TREES, SHRUBS AND GROUND
 COVER AND INDICATES THE QUANTITY, SIZE AND SPACING.
  
 5. PURSUANT TO SECTION 94-442 (D), PRIVATE LAND AND
 PUBLIC RIGHTS-OF-WAY BETWEEN STREET OR SIDEWALK
 SURFACES AND REQUIRED BUFFER STRIPS AND LANDSCAPED OPEN
 SPACE AREAS SHALL BE PLANTED WITH GRASS. GRASS AREAS
 SHALL BE SODDED.
  
 6. PURSUANT TO SECTION 94-445 (4) (G) (3), AUTOMATIC
 IRRIGATION SYSTEMS SHAL BE USED OF THE CULTIVATED
 LANDSCAPE AREAS FOR ALL PROPERTIES. PLEASE PROVIDE 120%
 IRRIGATION COVERAGE TO ALL LANDSCAPED AREA INCLUDING
 THE RIGHTS-OF-WAY.
  
 7. ON THE LANDSCAPE PLAN, PLEASE SHOW ALL UTILITIES,
 EASEMENTS, OVERHEAD LINES, OVERHANGING TREE CANOPIES
 FROM NEIGHBORING PROPERTY AND ANYTHING ELSE THAT MAY
 INTERFERE WITH THE PROPOSED LANDSCAPING. IF ANY TREES
 WILL BE IN CLOSE PROXIMITY TO OVERHEAD POWERLINES, YOU
 SHALL ADHERE TO THE RULES SETFORTH IN FPL'S "PLANT THE
 RIGHT TREE IN THE RIGHT PLACE". THIS LIMITS THE TYPES
 OF TREES THAT CAN BE PLANTED NEAR OR UNDER POWER LINES.
  
 8. PROVIDE SCREENING OF THE AIR CONDITIONING UNITS.
 PLEASE NOTE THAT ONE SIDE CAN BE LEFT OPEN FOR ACCESS
 TO THE UNIT.
  
 9. PLEASE PROVIDE ALL LANDSCAPE CALCULATIONS AND
 XERISCAPE DESIGN OPTIONS REQUIRED TO SATISFY THE
 REQUIREMENTS SETFORTH IN ARTICLE XIV OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS. BASED UPON THE GREENSPACE
 PROVIDED, FIVE SHADE OR FLOWERING TREES ARE REQUIRED
 AND 11 SHRUBS ARE REQUIRED.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.-
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-07-23 Cont ID  
Sent By hmoser Date 2009-07-23 Time 07:40 Rev Time 0.00
Received By hmoser Date 2009-07-23 Time 07:40 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-11-22 Cont ID  
Sent By rregueir Date 2008-11-22 Time 09:16 Rev Time 0.00
Received By rregueir Date 2008-11-20 Time 08:43 Sent To B
Notes
2008-11-22 09:16:25MECHANICAL PLANS HAVE PASSED REVIEW WITH THE FOLLOWING
 CONDITION(S):
  
 ******PROVISO******
 PLANS CALL FOR 3"X10" DRYER EXHAUST DUCT. THIS WILL NOT
 BE IN ACCORDANCE WITH DRYER MANUFACTURER'S INSTALLATION
 INSTRUCTIONS. THE DIAMETER OF THE EXHAUST DUCT SHALL BE
 AS REQUIRED BY THE CLOTHES DRYER?S LISTING AND THE
 MANUFACTURER?S INSTALLATION INSTRUCTIONS IN ACCORDANCE
 WITH FBCR M1501.2.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-03-27 Cont ID  
Sent By kstevens Date 2009-03-27 Time 13:39 Rev Time 0.00
Received By kstevens Date 2009-03-27 Time 13:39 Sent To B
Notes
2009-03-27 13:40:13 
  
  
  
  
 PASSED PROVISO: NO DEAD ENDS AT KITCHEN DEMO. SECTION
 704.5.
  
  
  
  
  
 .

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-02-23 Cont ID  
Sent By kstevens Date 2009-02-23 Time 16:06 Rev Time 0.00
Received By kstevens Date 2009-02-23 Time 16:06 Sent To M
Notes
2009-02-23 16:06:39PASSED PROVISO: NO DEAD ENDS AT KITCHEN DEMO. SECTION
 704.5.

Review Stop P PLUMBING
Rev No 1 Status P Date 2008-11-17 Cont ID  
Sent By kstevens Date 2008-11-17 Time 14:39 Rev Time 0.00
Received By kstevens Date 2008-11-17 Time 14:39 Sent To M
Notes
2008-11-17 14:40:41PASSED PROVISO: NO DEAD ENDS AT KITCHEN DEMO. SECTION
 704.5.

Review Stop Z ZONING
Rev No 3 Status P Date 2009-05-04 Cont ID  
Sent By mcruz Date 2009-05-04 Time 09:09 Rev Time 0.00
Received By mcruz Date 2009-05-04 Time 09:09 Sent To B
Notes
2009-05-04 09:09:47ROUTED TO RMC FOR BLDG REVIEW.

Review Stop Z ZONING
Rev No 2 Status P Date 2009-02-10 Cont ID  
Sent By mcruz Date 2009-02-10 Time 14:06 Rev Time 0.00
Received By mcruz Date 2009-02-10 Time 13:59 Sent To E
Notes
2009-02-10 14:00:37AS NOTED ON PLANS: LANDSCAPE PLAN SHALL BE APPROVED
 PRIOR TO FINAL CO.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2008-11-09 Cont ID  
Sent By mcruz Date 2008-11-09 Time 14:47 Rev Time 0.00
Received By mcruz Date 2008-11-09 Time 14:40 Sent To I
Notes
2008-11-09 14:47:24PLANNING AND ZONING DEPT: ***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDR), SECTION
 94-441(C)(2) OF: AS THE VALUE OF THE PROPOSED WORK
 EXCEEDS 50% OF THE STRUCTURE'S VALUE (LISTED AS
 "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY
 APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE
 WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF
 THE ZLDR.
  
 PLEASE SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN
 SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF
 THE ZLDR.
  
 3. INDICATE THE SETBACK DIMENSIONS FROM THE PROPOSED
 ADDITION TO ALL ADJACENT PROPERTY LINES. PURSUANT TO
 THE ZLDR, SECTION 94-72(A)(2): SINGLE-FAMILY LOW
 DENSITY (SF7) RESIDENTIAL DISTRICT - MINIMUM SETBACKS
 FOR PRINCIPAL BUILDING ARE AS FOLLOWS:
  
 A. FRONT: 25 FEET;
  
 B. CORNER: 12.5 FEET;
  
 C. REAR: 15 FEET OR TEN PERCENT OF LOT DEPTH, WHICHEVER
 IS LESS;
  
 D. SIDE: FIVE FEET MINIMUM, 15 FEET TOTAL.
  
 4. INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT TO ALL PROPERTY LINES. PURSUANT THE ZLDR,
 SECTION 94-305(B)(4): MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK.
  
 5. INDICATE OVERHANG DIMENSIONS OF THE PROPOSED
 ADDITION. PURSUANT TO THE ZLDR, SECTION 94-305(B):
 OVERHANGS SHALL NOT PROJECT MORE THAN THREE (3) FEET
 INTO A REQUIRED SETBACK.
  
 6. PROVIDE THE TOTAL HEIGHT OF THE PROPOSED ADDITION ON
 THE ELEVATION PLAN. PURSUANT TO THE ZLDR, SECTION
 94-611, THE HEIGHT SHALL BE MEASURED AS THE VERTICAL
 DISTANCE FROM THE AVERAGE ELEVATION OF THE FINISHED
 GRADE OF THE BUILDING TO THE MEAN HEIGHT LEVEL BETWEEN
 EAVES AND RIDGE FOR GABLE, HIP, AND GAMBREL ROOFS.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  