| 2008-11-20 13:25:47 | BUILDING PLAN REVIEW |
| | PERMIT: 08100686 |
| | ADD: 3415 S DIXIE HWY |
| | CONT: R & D CONSTRUCTORS, INC. |
| | TEL: (561)889-1751 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | ARCHITECT: TREZISEDESIGN ASSOCIATES, INC. |
| | STEVEN A. TREZISE |
| | PHONE (561) 687-4707 |
| | EMAIL: [email protected] |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 1B) IINFORMATIONAL FL S S 713.13 NOTICE OF |
| | COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT. |
| | NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS |
| | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & |
| | VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| | INSPECTION. |
| | |
| | 2) DISCREPANCY IN PLANS SHEET C1, A4 & A5 INDICATE A |
| | MIXED USE BUILDING WITH MERCANTILE AND S-1 STORAGE |
| | WHERE AS THE ELECTRICAL SHEETS E7.1 FIXTURE LEGEND |
| | INDICATE LIGHTING LFIXTURES AS RETAIL AREAS. PLEASE |
| | ALSO SEE ELECTRICAL COMMENTS AS FAR AS LIGHTING LOADS |
| | FOR MERCANTILE USAGE VERSES S-1 STORAGE.SEE ENERGY CODE |
| | 113.400. ALSO NO ENERGY CALCULATIONS WERE PROVIDED AT |
| | THE TIME OF THIS REVIEW. FROM WHAT I UNDERSSTAND OF |
| | THIS PROJECT THIS SPACE IS BEING DESIGNED FOR DISPLAY |
| | AND SALES OF ANTIQUE FURNITURE WHICH WILL FALL UNDER |
| | THE MERCANTILE OCCUPANCY SEE SECTION 309. INCLUDED |
| | UNDER THIS HEADING IS WHOLESALE STORES WHERE THE PUBLIC |
| | ACTUALLY HAS EGRESS TO THE STOCKPILED MERCHANDISE. WHEN |
| | REVIEWING THE REQUIREMENTS OF A STORAGE S-1 OR S-2 |
| | OCCUPANCY IT IS STRICTLY FOR STORAGE WHERE THE PUBLIC |
| | IS NOT ALLOWED TO BE IN THE WAREHOUSE AREA. SEE SECTION |
| | 311 FOR STORAGE. PLEASE REVIEW CODE SECTIONS. |
| | |
| | 3) C1- COVER SHEET PLEASE REVISE OCCUPANT LOADS FOR |
| | MERCANTILE FIRST FLOOR (30 GROSS) AND SECOND FLOOR (60 |
| | GROSS) SEE TABLE 1004.1.2. |
| | |
| | 4) SHEET A-4 ELEVATOR MACHINE ROOM INDICATES A WALL |
| | TYPE (2) NONRATED, PLEASE REFER TO 3006.4 ELEVATOR |
| | MACHINE ROOMS SHALL NOT HAVE A RATING LEASS THAN THE |
| | HOISTWAY ENCLOSURE. 1 HR. |
| | |
| | 5) SHEET A-4 WALL LEGEND ONCE THE OCCUPANCY ISSUES ARE |
| | CLEARED THE WALL RATINGS WILL ALSO CHANGE TO MOST WALLS |
| | NOT REQUIRING FIRE RATINGS. SEE DEFINITION OF |
| | MERCANTILE, 309. |
| | |
| | 6) SHEET A-4 FIRST FLOOR FINISH FLOOR ELEVATION IN SOME |
| | AREAS ARE REPRESENTED BY 0'-0" IN OTHER AREAS THERE IS |
| | A TWO INCH DEPRESSION, PLEASE PROVIDE ADDITIONAL |
| | INFORMATION IF THIS IS FOR MARBLE FLOORS WITH BED OR IS |
| | THE FINISH FLOOR IN THESE AREAS ACTUALLY 2INCHES LOWER. |
| | ADDITIONAL INFORMATION REQUIRED 106.1.2, 11-4.3.7 |
| | SLOPE, 11-4.3.8 CHANGES IN GRADE. |
| | |
| | 7) SHEET A5 UPPER RECEIVING DOOR# 55 THE PLANS DO NOT |
| | INDICATE ANY GAURD RAIL SYSTEM WHEN DOOR IS IN THE OPEN |
| | POSITION, EVEN REMOVABLE. PLEASE SEE 1012.1 THIS |
| | CONFIGURATION DOES NOT MEET ANY OF THE |
| | EXCEPTIONS OF LOADING DOCKS OR PIERS. |
| | |
| | 8) SHEET A6 ROOF PLAN DOES SHOW ROOF DRAINS BUT DOES |
| | NOT INDICATE ANY SECONDARY DRAINS OR OVERFLOW SCUPPERS. |
| | PLEASE REVIEW SECTION 1503.4.3 AND THE ACTUAL HEIGHT |
| | REQUIREMENTS FOR SCUPPERS AND THE AMOUNT OF PONDING |
| | THAT MAY RESULT FROM THE DISTANCE ROOF DRAINS ARE |
| | LOCATED FROM THE PARAPETS AND THE PONDING EFFECTS THAT |
| | MAY OCCUR. |
| | |
| | 9) 609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE DEBRIS |
| | REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE |
| | PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS |
| | SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF |
| | GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE |
| | ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES |
| | POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH |
| | AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS |
| | OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE |
| | TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1. |
| | GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE |
| | SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST. |
| | 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M) |
| | ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL |
| | MISSILE TEST. |
| | |
| | FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, PROVIDE 2 |
| | COPIES OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE |
| | AS FOLLOWS: |
| | |
| | 9A) STOREFRONT FIXED GLAZINGARCH NOA 03-1211.08 NOTE |
| | THIS NOA HAS NOT BEEN REVIEWED TO THE 2004 FBC SEE |
| | SECTION "C" CALCULATIONS HAVE NOT BEEN REVIEWED TO SEE |
| | IF 1/3RD INCREASES WERE TAKEN WITH THE FASTENERS. |
| | |
| | 9B) GLAZED EXTERIOR DOORS ARCH NOA 05-0829.08 NOTE THIS |
| | NOA HAS NOT BEEN REVIEWED TO THE 2004 FBC SEE SECTION |
| | "C" CALCULATIONS HAVE NOT BEEN REVIEWED TO SEE IF 1/3RD |
| | INCREASES WERE TAKEN WITH THE FASTENERS. |
| | |
| | 9C) SKYLIGHTS |
| | |
| | 9D) MULLIONS- IF EXCEEDS LENGTHS TESTED AS AN ASSEMBLY |
| | |
| | 9E) EXTERIOR INSULATED METAL DOORS, SINGLE AND DOUBLE |
| | |
| | 9F) ROLL UP INSULATED DOOR |
| | |
| | 9G) ROOF HATCH |
| | |
| | 9H) WALL LOUVERS- INTAKE GRILLS |
| | |
| | 9I) ROOFING ASSEMBLIES |
| | |
| | |
| | 10) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE |
| | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT |
| | IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT |
| | HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR |
| | LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE |
| | 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 11) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 12) S-5 BUILDING ELEVATIONS AND PRESSURE ZONES, SHEET |
| | S4 INDICATES THIS BUILDING IS DESIGNED AS A "C" COASTAL |
| | EXPOSURE. PLEASE REVIEW END ZONES OF BUILDING AND |
| | ASSCIATED PRESSURES , |
| | TABLE 1609.6.2.1(4) ADJUSTMENT FACTOR FOR BUILDING |
| | HEIGHT AND EXPOSURE, THIS BUILDINGS ROOF HEIGHT IS 27' |
| | WITH A 1.40 FACTOR. |
| | |
| | 13) NOTE ONE SET OF PLANS THE STRUCTURAL SHEETS ARE NOT |
| | SIGNED NOR SEALED( ONMJ) ANTONIO ARTHAY PE. |
| | PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| | PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR |
| | PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE |
| | DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. |
| | FL ADMIN CODE 61G15-23.002 ENGINEERS |
| | |
| | 14) NOTE AWNINGS ARE TO BE UNDER A SEPERATE PERMIT. |
| | INFORMATIONAL ONLY, A LETTER FROM THE OWNER (NOT |
| | TENANT) IS TO ACCOMPANY ALL FABRIC OR MEMBRANE-COVERED |
| | STRUCTURE DESIGNED WITH A QUICK REMOVAL OR BREAKAWAY |
| | MEMBRANE OR FABRIC TO ACKNOWLEDGE THEIR RESPONSIBILITY |
| | TO HAVE THE AWNING COVER REMOVED PRIOR TO ANY WIND |
| | EVENT WITH PROJECTED WIND SPEEDS OF 75 MPH OR GREATER. |
| | THE LETTER MUST BE SIGNED BY THE OWNER NOT TENANT. |
| | 3105.4.2.1 |
| | THE WIND DESIGN LOADS FOR ANY FABRIC OR |
| | MEMBRANE-COVERED STRUCTURE DESIGNED WITH A QUICK |
| | REMOVAL OR BREAKAWAY MEMBRANE OR FABRIC AT WIND |
| | VELOCITIES OF 75 MPH, |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |