Plan Review Details - Permit 08100666
Plan Review Stops For Permit 08100666
Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2009-09-24 Cont ID  
Sent By rmcdouga Date 2009-09-24 Time 16:54 Rev Time 0.00
Received By rmcdouga Date 2009-09-24 Time 16:54 Sent To  
Notes
2009-09-24 17:00:53ENGINEERED ANALYSIS CALCULATIONS WERE SUBMITTED FOR
 INCREASED UPLIFT. REVISION TO INSTALL ENGLERT SERIES
 1300 METAL ROOFING IS CODE COMPLIANT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2009-09-17 Cont ID  
Sent By rmcdouga Date 2009-09-17 Time 07:27 Rev Time 0.00
Received By rmcdouga Date 2009-09-17 Time 07:27 Sent To  
Notes
2009-09-17 07:38:56REVISION TO CHANGE METAL ROOFING PRODUCT APPROVAL IS
 DENIED. THE ENGLERT SERIES 1300 METAL ROOF WITH FL #
 11727.5 HAS A DESIGN UPLIFT PRESSURE OF -60 PSF AND THE
 PLANS REQUIRE -83.1 PSF IN ROOF ZONE 3. THE PRODUCT
 LIMITATIONS REQUIRE ANY RATIONAL ANALYSIS COMPUTATIONS
 TO BE PREPARED BY A QUALIFIED DESIGN PROFESSIONAL IN
 COMPLIANCE WITH 2007 FBC SECTIONS 104, 105, 106. SEE
 PAGE 4 OF 7 OF REPORT NO.08-148-1300-90-A3W-ER. SUBMIT
 SIGNED, SEALED AND DATED CALCULATIONS FOR THIS PRODUCT
 OR PRODUCT APPROVALS FOR ANOTHER ROOF COVERING.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2009-07-20 Cont ID  
Sent By rmcdouga Date 2009-07-20 Time 15:06 Rev Time 0.00
Received By rmcdouga Date 2009-07-20 Time 15:06 Sent To  
Notes
2009-07-20 15:07:58REVISED PLAN SHEETS SP-1 AND A-1 ARE OK PENDING ZONING
 APPROVAL.
 REVISED PLAN SHEET A-2 IS OK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2009-07-09 Cont ID  
Sent By rmcdouga Date 2009-07-09 Time 12:21 Rev Time 0.00
Received By rmcdouga Date 2009-07-09 Time 12:21 Sent To  
Notes
2009-07-09 12:23:02REVISED PRODUCT APPROVAL FOR FLAT ROOF FROM TAMKO TO
 GAF.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-05-04 Cont ID  
Sent By rmcdouga Date 2009-05-04 Time 07:52 Rev Time 0.00
Received By rmcdouga Date 2009-05-04 Time 07:52 Sent To  
Notes
2009-05-04 07:53:29SUBMITTED SUB-SURFACE SOIL REPORT

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-03-06 Cont ID  
Sent By rmcdouga Date 2009-03-06 Time 10:11 Rev Time 0.00
Received By rmcdouga Date 2009-03-06 Time 10:11 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-01-26 Cont ID  
Sent By rmcdouga Date 2009-01-26 Time 14:52 Rev Time 0.00
Received By rmcdouga Date 2009-01-26 Time 14:52 Sent To  
Notes
2009-01-26 13:52:262004 FBC W/2007 REVISIONS
 ADDITION AND LEVEL 2 ALTERATION
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED. FS 713
  
 2) SUBMIT A COPY OF THE PAID RECEIPT FOR THE COUNTY
 IMPACT FEES.
  
 3) THE DETAILS FOR THE CUPOLA ARE INCOMPLETE. PLEASE
 SPECIFY THE DIMENSIONS, THE ROOF FRAMING, ROOF
 SHEATHING, ROOF TO WALL CONNECTIONS, ETC.
  
 4) THE PRODUCT APPROVAL NOA THAT WAS SUBMITTED FOR THE
 CAST-CRETE LINTELS DOES NOT INCLUDE THE 8" WIDE LINTELS
 WHICH ARE FOR THE 8" BLOCK WALLS. PLEASE SUBMIT THE NOA
 FOR 8" WIDE LINTELS. DCA RULE 9B-72
  
 5) THE PRODUCT APPROVAL NOA THAT WAS SUBMITTED FOR THE
 TAMKO MODIFIED ROOF COVERING IS FOR INSTALLATION ON
 CONCRETE DECKS. THE FLAT ROOF OVER THE LOGGIA IS A WOOD
 DECK. PLEASE SUBMIT THE NOA FOR WOOD DECKS. SPECIFY THE
 ASSEMBLY, FASTENING OPTION AND DESIGN PRESSURE THAT
 WILL BE USED. IF ENHANCED FASTENING AT CORNER AND
 PERIMETER AREAS IS REQUIRED, SUBMIT RAS 117
 CALCULATIONS AS REQUIRED BY LIMITATION NUMBER 7 OF THE
 NOA.
  
 NOTE: THE LETTER THAT WAS SUBMITTED IN RESPONSE TO THE
 COMMENTS CONTAINED SEVERAL ERRORS AS TO THE SHEETS OF
 THE PLANS WHERE THE CORRECTIONS WERE MADE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-11-18 Cont ID  
Sent By rmcdouga Date 2008-11-18 Time 10:29 Rev Time 0.00
Received By rmcdouga Date 2008-11-18 Time 10:29 Sent To  
Notes
2008-11-18 10:25:592004 FBC W/2007 REVISIONS
 LEVEL 2 ALTERATIONS AND ADDITION
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED. FS 713
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) ON SHEET A1 THE WALL TYPE SPECIFIED FOR THE NEW
 POWDER ROOM #114 IS INCORRECT. DRYWALL IS SPECIFIED ON
 THE EXTERIOR WALLS. PLEASE CORRECT.
  
 4) THE MASONRY OPENING SIZES SPECIFIED FOR THE OVERHEAD
 GARAGE DOORS IN THE DOOR SCHEDULE ON A6 ARE INCORRECT.
 PLEASE REVISE.
  
 5) SUBMIT PRODUCT APPROVALS OR DESIGN DETAILS FOR THE
 ROOF CUPOLA. RULE 9B-72 AND FBC R801.2
  
 6) SHOW COMPLIANCE WITH R309.1 OPENING PROTECTION.
 OPENINGS BETWEEN THE GARAGE AND RESIDENCE SHALL BE
 EQUIPPED WITH SOLID WOOD DOORS NOT LESS THAN 1-3/8
 INCHES (35 MM) IN THICKNESS, SOLID OR HONEYCOMB CORE
 STEEL DOORS NOT LESS THAN 1-3/8 INCHES (35 MM) THICK,
 OR 20-MINUTE FIRE-RATED DOORS.
  
 7) SPECIFY THE CONNECTORS THAT WILL BE USED TO ANCHOR
 THE 2 X 8 RAFTERS TO THE EXISTING TRUSSES AT THE NEW
 FRONT PORCH ROOF. FBC R801.2
  
 8) THE TRUSS ANCHOR NUMBERS IN THE SCHEDULE ON S4 DO
 NOT CORRESPOND TO THE ID TAGS ON THE ROOF FRAMING
 PLANS. PLEASE CLARIFY. FBC 106.1.1 AND R802.1.6.5
  
 9) ON S2 THE DESIGN CRITERIA SPECIFIES THE 2002 FBC AND
 ASCE 7-98. PLEASE UPDATE TO 2004 FBC AND ASCE 7-02. SEE
 FBC R CHAPTER 43.
  
 10) THE STRUCTURAL NOTES, WIND-LOADING NOTES AND TRUSS
 NOTES ON SHEET S5 SPECIFY ASCE 7-98. PLEASE CORRECT TO
 ASCE 7-02. FBC R CHAPTER 43.
  
 11) PROVIDE A WINDOW BUCK DETAIL. FBC R613.6.1.1
  
 12) SHOW COMPLIANCE OF STAIRS WITH R311.5.3.2 TREAD
 DEPTH. THE MINIMUM TREAD DEPTH, EXCLUSIVE OF NOSING,
 SHALL BE NOT LESS THAN 9 INCHES.TREADS AND RISERS OF
 STAIRS SHALL BE PERMITTED TO BE SO PROPORTIONED THAT
 THE SUM OF TWO RISERS AND A TREAD, EXCLUSIVE OF
 PROJECTION OF NOSING, IS NOT LESS THAN 24 INCHES NOR
 MORE THAN 25 INCHES. THE TREAD DEPTH SHALL BE MEASURED
 HORIZONTALLY BETWEEN THE VERTICAL PLANES OF THE
 FOREMOST PROJECTION OF ADJACENT TREADS AND AT A RIGHT
 ANGLE TO THE TREAD'S LEADING EDGE. THE GREATEST TREAD
 DEPTH WITHIN ANY FLIGHT OF STAIRS SHALL NOT EXCEED THE
 SMALLEST BY MORE THAN 3/8 INCH.
  
 13) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 14) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 GLASS BLOCK. FAC RULE 9B-72
  
 15) NOA NO. 01-0209.03 FOR THE CAST-CRETE LINTELS
 SPECIFIED ON SHEET S1, IS EXPIRED. PLEASE CORRECT. FAC
 RULE 9B-72
  
 16) SPECIFY WHICH ATTACHMENT METHOD LISTED IN THE
 PRODUCT APPROVAL NOA WILL BE USED TO ANCHOR THE
 CONCRETE ROOF TILES. FBC R905.3.7
  
 17) PRODUCT APPROVALS WERE SUBMITTED FOR PGT HORIZONTAL
 ROLLER WINDOWS, HOWEVER, ON SHEET A6 ALL WINDOWS ARE
 SPECIFIED AS CASEMENT. PLEASE INDICATE WHICH WINDOWS
 WILL BE HORIZONTAL ROLLER WINDOWS OR REMOVE THESE
 PRODUCT APPROVALS FROM THE PACKAGE. RULE 9B-72
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2009-10-01 Cont ID  
Sent By jleahy Date 2009-10-01 Time 14:38 Rev Time 0.00
Received By jleahy Date 2009-10-01 Time 14:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2009-07-24 Cont ID  
Sent By btrobaug Date 2009-07-24 Time 16:28 Rev Time 0.00
Received By btrobaug Date 2009-07-24 Time 14:59 Sent To  
Notes
2009-07-24 16:28:40 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE RISER DIAGRAM INDICATES AN OVERHEAD FEED TO THE
 ATS. THE RELOCATED METER AND ATS LOCATION SHOWN ON THIS
 REVISION IS IN VIOLATION OF230.70(A)(1)***READILY
 ACCESSIBLE LOCATION THE SERVICE DISCONNECTING MEANS
 SHALL BE INSTALLED AT A READILY ACCESSIBLE LOCATION
 EITHER OUTSIDE OF A BUILDING OR STRUCTURE OR INSIDE
 NEAREST THE POINT OF ENTRANCE OF THE SERVICE
 CONDUCTORS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-03-06 Cont ID  
Sent By btrobaug Date 2009-03-06 Time 15:13 Rev Time 0.00
Received By btrobaug Date 2009-03-06 Time 14:41 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-01-05 Cont ID  
Sent By btrobaug Date 2009-01-05 Time 14:51 Rev Time 0.00
Received By btrobaug Date 2009-01-05 Time 09:23 Sent To P
Notes
2009-01-05 11:53:29 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 SHEET E-5:
  
 1} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT
 CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE
 EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS
 EQUAL TO OR GREATER THAN THE AVAILABLE FAULT. SHEET
 E-5.
  
 2} 702.5 CAPACITY AND RATING
 AN OPTIONAL STANDBY SYSTEM SHALL HAVE ADEQUATE CAPACITY
 AND RATING FOR THE SUPPLY OF ALL EQUIPMENT INTENDED TO
 BE OPERATED AT ONE TIME. OPTIONAL STANDBY SYSTEM
 EQUIPMENT SHALL BE SUITABLE FOR THE MAXIMUM AVAILABLE
 FAULT CURRENT AT ITS TERMINALS.*** THE OUTPUT OF THE
 GENERATOR IS 125 AMPS, THE CALCULATED LOAD IS 135 AMPS.
 THE GENERATOR IS NOT RATED FOR THIS LOAD. SET A
 SUBPANEL TO SEPARATE THE LOADS OR INCREASE THE
 GENERATOR AMPACITY.
  
 3} THE #6 GROUND RAN TO THE GROUNDING ELECTRODE IS IN
 VIOLATION OF 250.122. THERE MUST BE AN EQUIPMENT GROUND
 FROM THE PANEL, WHERE THE SHORT WILL BE DETECTED, TO
 THE GENERATOR TO ENABLE THE MAIN TO TRIP UNDER A SHORT
 CIRCUIT CONDITION.THE NEUTRAL, TO WHICH THE GENERATOR
 "GROUND" IS CONNECTED THROUGH THE GEC, AND THE GROUND
 WILL BE ISOLATED AFTER THE FIRST MEANS OF DISCONNECT
 PER 210.24(A)(5), WHICH WILL BE THE ATS AS CONFIGURED
 ON THE RISER DIAGRAM.
  
 4} PROVIDE THE MANUFACTURERS SPECIFICATIONS FOR THE
 GENERATOR AND THE TRANSFER SWITCH. NOTE: THE TRANSFER
 SWITCH MUST HAVE AN "OFF" POSITION AS THE FIRST MEANS
 OF DISCONNECT, AND MUST BE 200 AMP RATED WITH AN AIC
 RATING CONCURRENT WITH THE SERVICE EQUIPMENT AND
 GREATER THAN THE FAULT CURRENT CALCULATION. SEE COMMENT
 #1.
  
 5} CIRCUITS #9 & 11 @ 3000 VA ARE IN VIOLATION OF
 310.16 & 210.23(A)(1)- "CORD-AND-PLUG-CONNECTED
 EQUIPMENT NOT FASTENED IN PLACE THE RATING OF ANY ONE
 CORD-AND-PLUG-CONNECTED UTILIZATION EQUIPMENT NOT
 FASTENED IN PLACE SHALL NOT EXCEED 80 PERCENT OF THE
 BRANCH-CIRCUIT AMPERE RATING". 3000/120=25 AMPS.
  
 6} CIRCUITS 3O, 32 ,34, 36 FOR THE CONDENSING UNITS
 HAVE INCORRECT OVERCURRENT PROTECTION PER MANUFACTURERS
 SPECIFICATIONS GIVEN ON SHEET M-5. 110.3(B).
  
 7} CIRCUIT #10 INDICATES THE DISHWASHER/DISPOSER ON THE
 SAME CIRCUIT IN VIOLATION OF 210.23(A)(1).
  
 NOTE: THE SMOKE DETECTOR CIRCUIT # 24 MUST BE ON AN ARC
 FAULT BREAKER PER 210.12(B).
  
 SHEET E-3:
  
 8} 9B-3.0472 CARBON MONOXIDE PROTECTION. (2) EVERY
 BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS
 ISSUED ON OR AFTER 7/1/08 AND HAVING A
 FOSSIL-FUEL-BURNING HEATER OR APPLIANCE, A FIREPLACE,
 OR AN ATTACHED GARAGE SHALL HAVE AN OPERATIONAL CARBON
 MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH ROOM
 USED FOR SLEEPING PURPOSES***ALTHOUGH THE DETECTOR IN
 THE GARAGE IS RECOMMENDED AND PERMISSIBLE, THE
 REQUIREMENT IS FOR THE HALLWAYS OUTSIDE SLEEPING ROOMS.
  
 9} 680.43(A)(3) PROTECTION, SPA OR HOT TUB SUPPLY
 RECEPTACLES THAT PROVIDE POWER FOR A SPA OR HOT TUB
 SHALL BE GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTED.***
 INDICATE ON PLANS.
  
 SHEET E-4:
  
 10} 210.52(D) BATHROOMS IN DWELLING UNITS, AT LEAST ONE
 RECEPTACLE OUTLET SHALL BE INSTALLED IN BATHROOMS
 WITHIN 900 MM (3 FT) OF THE OUTSIDE EDGE OF EACH BASIN.
 THE RECEPTACLE OUTLET SHALL BE LOCATED ON A WALL OR
 PARTITION THAT IS ADJACENT TO THE BASIN OR BASIN
 COUNTERTOP.***BATH #2 DOES NOT COMPLY WITH REQUIRED
 SPACING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-11-14 Cont ID  
Sent By btrobaug Date 2008-11-14 Time 15:12 Rev Time 0.00
Received By btrobaug Date 2008-11-14 Time 10:52 Sent To P
Notes
2008-11-14 14:24:40 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE GENERATOR SHOWN ON THE RISER DIAGRAM MUST BE
 LABELED AS FUTURE OR PROVIDE ALL DOCUMENTATION REQUIRED
 FOR A RESIDENTIAL GENERATOR INSTALLATION WITH THE
 RESUBMITTAL.
  
 2} AN EQUIPMENT GROUNDING CONDUCTOR MUST BE INSTALLED
 FROM THE FIRST MEANS OF DISCONNECT TO THE PANEL PER
 250.118, SIZED PER 250.122.
  
 3} AN EQUIPMENT GROUNDING CONDUCTOR MUST BE INSTALLED
 FROM THE TRANSFER SWITCH TO THE GENERATOR PER 250.122.
  
 4} PANEL "A" IS LISTED AS HAVING A 225 AMP MAIN
 BREAKER, BUT HAS A 200 AMP MAIN DISCONNECT FEEDING IT.
 IT IS ALSO SHOWN AS BEING RECESSED , VERIFY THESE AS A
 REVISION WOULD BE REQUIRED AT A LATER DATE NOT CORRECT.
  
 5} THE A/C EQUIPMENT PANEL DESIGNATION AND CIRCUIT
 NUMBERS ARE SHOWN IN PANEL "A" BUT LISTED IN PANEL "E".
 CORRELATE SAME, 408.4
  
 6} 210.11(C)(3) BATHROOM BRANCH CIRCUITS IN ADDITION TO
 THE NUMBER OF BRANCH CIRCUITS REQUIRED BY OTHER PARTS
 OF THIS SECTION, AT LEAST ONE 20-AMPERE BRANCH CIRCUIT
 SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE
 OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS.
 EXCEPTION: WHERE THE 20-AMPERE CIRCUIT SUPPLIES A
 SINGLE BATHROOM, OUTLETS FOR OTHER EQUIPMENT WITHIN THE
 SAME BATHROOM SHALL BE PERMITTED TO BE SUPPLIED IN
 ACCORDANCE WITH 210.23(A)(1) AND (A)(2)***CIRCUIT A-30
 IN THE POWDER ROOM AND OFFICE BATHROOM, SHEET E-1, AND
 THE NEW BATH VIOLATE THE EXCEPTION AS THE LIGHT AND FAN
 ARE ON THAT CIRCUIT
  
 7} ANOTHER RECEPTACLE MUST BE ADDED IN THE NEW
 BATHROOM, SHEET E-2, TO COMPLY WITH 210.52(D).
  
 8} A SMOKE ALARM MUST BE ADDED OUTSIDE THE EXISTING
 BEDROOM ON SHEET E-1TO COMPLY WITH R313.1.2 "OUTSIDE
 EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE VICINITY
 OF THE BEDROOMS"..
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2009-07-21 Cont ID  
Sent By kstevens Date 2009-07-21 Time 13:25 Rev Time 0.00
Received By kstevens Date 2009-07-20 Time 16:52 Sent To  
Notes
2009-07-21 13:31:31REVISION DENIED
 REFERENCE:
 FBC-2004 RESIDENTIAL
 FBC-2004 FUEL GAS
  
 1. SHT P-3 GAS RISER DIAGRAM AND GAS PIPING CHART. 2
 INCH PIPE IS REQUIRED FOR SECTIONS D, E, F & G ON THE
 RISER DIAGRAM AND ON C, D, E, F, & G ON THE CHART.
 TABLE 402.4(2). -- ALSO 1-1/4" IS REQUIRED FOR THE
 PIPING FOR SECTIONS U & V. TABLE 402.4(2).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2009-03-12 Cont ID  
Sent By lwagner Date 2009-03-12 Time 10:27 Rev Time 0.00
Received By lwagner Date 2009-03-12 Time 10:27 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2009-09-16 Cont ID  
Sent By kstevens Date 2009-09-16 Time 09:21 Rev Time 0.00
Received By kstevens Date 2009-09-16 Time 09:21 Sent To  
Notes
2009-09-16 09:21:57SENT TO RMCDOUGAL.

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2009-09-15 Cont ID  
Sent By kstevens Date 2009-09-15 Time 15:46 Rev Time 0.00
Received By kstevens Date 2009-09-15 Time 15:46 Sent To  
Notes
2009-09-15 15:47:03SENT TO ZONING.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status   Date 2009-07-06 Cont ID  
Sent By btrobaug Date 2009-07-06 Time 14:56 Rev Time 0.00
Received By btrobaug Date 2009-07-06 Time 08:51 Sent To  
Notes
2009-07-24 14:57:02R 10

Review Stop I INCOMING/PROCESSING
Rev No 5 Status   Date   Cont ID  
Sent By   Date 2009-05-01 Time   Rev Time 0.00
Received By lmartine Date 2009-05-01 Time 16:00 Sent To  
Notes
2009-05-01 16:00:46GAVE TO MCDOUGLE

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-02-10 Cont ID  
Sent By adarroug Date 2009-02-10 Time 11:09 Rev Time 0.00
Received By adarroug Date 2009-02-10 Time 11:09 Sent To Z
Notes
2009-02-10 11:09:48TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-12-23 Cont ID  
Sent By hmoser Date 2009-01-26 Time 10:31 Rev Time 0.00
Received By adarroug Date 2008-12-23 Time 10:55 Sent To Z
Notes
2008-12-23 10:55:43TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-11-07 Cont ID  
Sent By adarroug Date 2008-11-07 Time 16:55 Rev Time 0.00
Received By adarroug Date 2008-11-07 Time 16:55 Sent To E
Notes
2008-11-07 16:55:21TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-11-19 Cont ID  
Sent By kstevens Date 2008-11-19 Time 09:04 Rev Time 0.00
Received By kstevens Date 2008-11-03 Time 11:46 Sent To  
Notes
2008-11-03 11:46:52TO "SFR" "Z"

Review Stop L LANDSCAPING
Rev No 2 Status P Date 2009-02-23 Cont ID  
Sent By rkussner Date 2009-02-23 Time 17:08 Rev Time 0.00
Received By rkussner Date 2009-02-23 Time 17:14 Sent To Z
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2008-12-29 Cont ID  
Sent By rkussner Date 2008-12-29 Time 09:11 Rev Time 0.00
Received By rkussner Date 2008-12-29 Time 09:11 Sent To Z
Notes
2008-12-29 09:40:57***LANDSCAPE REVIEW FAILED***
  
 1. PURSUANT TO SECTION 94-442(B)(2)(A), FOR SINGLE
 FAMILY DWELLING UNITS, AT LEAST ONE SHADE, FLOWERING OR
 FRUIT TREE SHALL BE PLANTED FORE EACH 1200 SQUARE FEET
 OF OPEN SPACE, OR PORTION THEREOF. BASED UPON 7,700
 SQUARE FEET OF OPEN SPACE, SEVEN (7) TREES ARE REQUIRED
 AND ONLY FIVE (5) HAVE BEEN PROVIDED.
  
 2. PURSUANT TO SECTION 94-442(D), PRIVATE LAND AND
 PUBLIC RIGHTS-OF-WAY BETWEEN STREET OR SIDEWALK
 SURFACES AND REQUIRED BUFFER STRIPS AND LANDSCAPED OPEN
 SPACE AREAS SHALL BE PLANTED WITH GRASS. GRASS AREAS
 SHALL BE SODDED.
  
 3. PURSUANT TO SECTION 94-445(4)(G)(3), AUTOMATIC
 IRRIGATION SYSTEMS SHALL BE USED FOR THE CULTIVATED
 LANDSCAPE AREAS FOR ALL PROPERTIES. THE ENTIRE SITE
 SHALL BE IRRIGATED, INCLUDING THE RIGHT-OF-WAY.
  
 4. PLEASE PROVIDE THE TABULATION NECESSARY FOR THE
 EVALUATION OF COMPLIANCE WITH ARTICLE XIV OF THE ZONING
 AND LAND DEVELOPMENT REGULATIONS 'XERISCAPE DESIGN
 OPTIONS'. THE LANDSCAPE PLAN MUST SATISFY A MINIMUM
 TOTAL OF 15 POINTS FOR A SINGLE FAMILY DWELLING UNIT.
  
 5. PLEASE PROVIDE SCREENING FOR THE AIR CONDITIONING
 UNITS AND ANY OTHER MECHANICAL EQUIPMENT.
  
 6. PURSANT TO SECTION 94-442(F), LANDSCAPING SHALL BE
 INSTALLED IN ACCORDANCE WITH THE CLEAR VISION
 REQUIREMENTS OF SUBSECTION 94-305(E). THE PROPOSED
 HEDGE SHALL BE MOVED AWAY FROM THE CITY SIDEWALK AND BE
 PLANTED ADJACENT TO THE CIRCULAR DRIVEWAY. THIS WILL
 OPEN UP THE VISTA TO THE DRIVER WHEN EXIITING THE
 DRIVEWAY.
  
 7. PLEASE PROVIDE A PLANT LIST WITH THE PLANT NAMES,
 QUANTITY, SIZE AND SPACING OF ALL PROPOSED PLANT
 MATERIAL.
  
 8. SHOW ALL OVERHEAD LINES, OVERHANGING TREE LIMBS,
 EASEMENTS AND UTILITIES ON THE LANDCAPE PLAN TO AVOID
 CONFLICTS.
  
 9. STAFF RECOMMENDS THAT LANDSCAPING BE INSTALLED ALONG
 THE FRONT BUILDING ELEVATION.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2009-09-10 Cont ID  
Sent By rregueir Date 2009-09-10 Time 13:29 Rev Time 0.00
Received By rregueir Date 2009-09-10 Time 07:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2009-07-17 Cont ID  
Sent By rregueir Date 2009-07-17 Time 16:36 Rev Time 0.00
Received By rregueir Date 2009-07-17 Time 16:35 Sent To  
Notes
2009-07-17 16:36:19REVISED M3 DELTA 6 M4 DELTA 2

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-03-16 Cont ID  
Sent By hmoser Date 2009-03-16 Time 09:09 Rev Time 0.00
Received By hmoser Date 2009-03-16 Time 09:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2009-01-26 Cont ID  
Sent By hmoser Date 2009-01-26 Time 10:32 Rev Time 0.00
Received By hmoser Date 2009-01-26 Time 10:23 Sent To  
Notes
2009-01-26 10:31:2201/26/09
 PLEASE PROVIDE TRANSFER DUCT SIZE ON PLANS SECTION
 M1602.4 BALANCED RETURN AIR # 2 . 2004 RFBC
 PLEASE REFER TO SECTION 13 609.1.ABC.1 IN REGARDS TO
 FRESH AIR INTAKE DETAIL PAGE M-5
 PLAN REVIEW BY HAROLD MOSER 161-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-11-04 Cont ID  
Sent By tgordon Date 2008-11-04 Time 13:33 Rev Time 1.30
Received By tgordon Date 2008-11-04 Time 13:33 Sent To Z
Notes
2008-11-04 14:31:23PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) ENERGY CALCULATIONS NEED TO BE ON FORM 600A-04R, SEE
 2004 FBC 13-600.3.A (12-8-06 REVISION).
  
 2) ENERGY CALCULATIONS LINE 6 NEEDS TO SHOW THE TOTAL
 SQUARE FEET UNDER AIR FOR THE HOUSE, SEE 2004 FBC
 13-600.0 METHOD A AND 13-600.2.A.3.2.
  
 3) ENERGY CALCULATIONS LINE 8A SHOWS R-6 ON SLABS EDGE,
 PLANS SHOW NO INSULATION ON SLABS EDGE. THE TWO MUST
 COINCIDE, PLEASE CORRECT SEE 2004 FBC 13-605.1.ABC.1.2.
  
 4) ENERGY CALCULATIONS LINE 9A SHOWS R-11 ON CONCRETE
 WALLS, PLANS SHOW R-4.1 ON THE CONCRETE WALLS. THE TWO
 MUST COINCIDE, PLEASE CORRECT PER 2004 FBC 13-103.3.
  
 5) ENERGY CALCULATIONS LINE 10A SHOWS UNDER ATTIC,
 PLANS SHOW ICYNENE BEING INSTALLED UNDER THE ROOF THIS
 WOULD BE A SINGLE ASSEMBLY, PLEASE CORRECT SEE 2004 FBC
 13-604.2.A.1.
  
 6) ENERGY CALCULATIONS LINE 12A SHOWS A 60,000 BTU A/C
 SYSTEM IS BEING INSTALLED, MECHANICAL PLANS SHOW THREE
 SYSTEM BEING INSTALLED ONE 3.5 TON AND TWO 2 TON
 SYSTEMS, PLEASE CORRECT PER 2004 FBC-103.3. DO SAME FOR
 LINE 13A HEATING SYSTEMS.
  
 7) ENERGY CALCULATIONS LINE 14C IS TAKING THE CREDIT
 FOR H.R.U. (HEAT RECOVERY UNIT). PLEASE SUBMIT DETAILED
 MANUFACTURER'S SPECIFICATION'S FOR THE UNIT AND SHOW
 WERE THE UNIT WILL BE INSTALLED ON THE MECHANICAL PLAN.
 SEE 2004 FBC 13-612.2.A.3.1.
  
 8) THE COOLING LOAD CALCULATIONS SUBMITTED ARE ONLY FOR
 ONE ZONE. PLEASE SUBMIT COOLING LOAD CALCULATIONS FOR
 ALL THREE ZONES, PER 2004 FBC 13-607.1.ABC.1.
  
 9) MECHANICAL PLAN M-1 SHOWS THE CONDENSATE LINE FROM
 A.H.U. #1 DISCHARGING ON THE FRONT PORCH. THE
 CONDENSATE WATER MAY NOT DISCHARGE THERE, PLEASE
 CORRECT PER 2004 FBC/R M1411.3.
  
 10) A/C SYSTEM MODEL NUMBERS AHU TWE040E CU TWX042D100A
 AND AHU TWE031E CU TWX024C100A LISTED ON THE A/C
 EQUIPMENT SCHEDULE COULD NOT BE FOUND ON THE ARI
 DIRECTORY WEB-SITE, PLEASE CORRECT OR SUBMIT AN ARI
 CERTIFICATE, SEE 2004 FBC 13-607.1.ABC.3.1.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2009-07-21 Cont ID  
Sent By kstevens Date 2009-07-21 Time 13:31 Rev Time 0.00
Received By kstevens Date 2009-07-20 Time 16:52 Sent To  
Notes
2009-07-21 13:38:10REVISIONS OK SHEETS P-3, P-4 & P-5.

Review Stop P PLUMBING
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2009-03-12 Time   Rev Time 0.00
Received By lwagner Date 2009-03-10 Time 14:42 Sent To G
Notes
2009-03-10 15:08:49PLUMBING PLAN REVIEW:
  
 1. OK
 2. OK
 3. OK
 4. OK
 5. OK
 6. OK
 7. OK
 8. OK
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2009-01-20 Cont ID  
Sent By lwagner Date 2009-01-20 Time 10:25 Rev Time 0.00
Received By lwagner Date 2009-01-16 Time 10:46 Sent To  
Notes
2009-01-20 10:12:33PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS/PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. OK
 2. OK
 3. OK
 4. SHEET P-6 WATER RISER DIAGRAM - PLEASE SHOW WATER
 HAMMER ARRESTORS AT DISH WASHER AND ICE MAKER (2).
 (A) 604.9 WATER HAMMER. A WATER-HAMMER
 ARRESTOR SHALL BE INSTALLED WHERE
 QUICK-CLOSING VALVES ARE UTILIZED.
 5. OK (NOTE: RELIEF TO BE INSTALLED IF REQUIRED BY
 TANKLESS MANUFACTURER).
 NEW:
 6. SHEET P-6 GAS RISER - 1. SUBMIT AN ISOMETRIC DRAWING
 THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. (P-3 INDICATES
 PRESSURE AS LESS THAN 2 PSI. PRESSURE SHOULD BE LESS
 THAN 0.5 PSI OR 2 PSI).
 8. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 *IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 LARRY WAGNER
 (561)805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-11-19 Cont ID  
Sent By kstevens Date 2008-11-19 Time 08:55 Rev Time 0.00
Received By kstevens Date 2008-11-18 Time 16:56 Sent To  
Notes
2008-11-19 09:03:39DENIED
 REFERENCE: FBC-2004 PLUMBING
  
 1. SHT P-1 SANITARY RISER DIAGRAM. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL CONNECT TO A BRANCH
 DRAIN OR DRAINAGE STACK A MINIMUM OF 3 INCHES IN
 DIAMETER. SECTION 406.3.
  
 2. SHT P-1 SANITARY RISER DIAGRAM. THE CLEANOUT BEHIND
 THE W/M SHALL BE INSTALLED A MINIMUM 4 FEET ABOVE
 FINISHED FLOOR FOR ACCESS. SECTION 708.9
  
 3. SHT P-1 FLOOR PLAN AND SANITARY RISER DIAGRAM.
 PLEASE SHOW THE CLEANOUTS REQUIRED BY SECTIONS 708.3.4
 & 708.3.5, AT THE BASE OF EACH STACK AND NEAR THE
 JUNCTION OF THE BUILDING DRAINS AND THE BUILDING SEWER.
  
 4. SHT P-2 WATER RISER DIAGRAM. WATER HAMMER ARRESTORS
 ARE REQUIRED ON THE SUPPLY LINES TO THE DISHWASHER AND
 THE ICE MAKER IN THE KITCHEN AREA. SECTION 604.9.
  
 5. SHT P-2 WATER RISER DIAGRAM. THE RELIEF VALVE
 DISCHARGE FOR THE WATER HEATER SHALL NOT HAVE ANY
 TRAPPED SECTIONS AND SHALL HAVE A VISIBLE AIR GAP OR
 AIR GAP FITTING LOCATED IN THE SAME ROOM AS THE WATER
 HEATER. SECTION 504.6.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 4 Status F Date 2009-07-23 Cont ID  
Sent By mcruz Date 2009-07-23 Time 14:30 Rev Time 0.00
Received By mcruz Date 2009-07-23 Time 14:27 Sent To  
Notes
2009-07-23 14:30:07PLANNING AND ZONING DEPT: ***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. INDICATE SETBACK DIMENSIONS FROM THE PROPOSED
 GENERATOR EQUIPMENT TO ALL PROPERTY LINES. PURSUANT THE
 CITY OF WEST PALM BEACH ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), SECTION 94-305(B)(4): MECHANICAL
 EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET INTO A
 REQUIRED SETBACK.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  
 PLACED BACK ON R10

Review Stop Z ZONING
Rev No 3 Status P Date 2009-02-23 Cont ID  
Sent By mcruz Date 2009-02-23 Time 18:02 Rev Time 0.00
Received By mcruz Date 2009-02-23 Time 17:40 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2008-12-29 Cont ID  
Sent By rkussner Date 2009-02-23 Time 17:14 Rev Time 0.00
Received By mcruz Date 2008-12-26 Time 13:24 Sent To E
Notes
2008-12-29 11:30:10PLANNING AND ZONING DEPT: ***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. PLEASE COMPLY WITH THE LANDSCAPE PLAN REVIEWER
 COMMENTS.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2009-01-26 Cont ID  
Sent By mcruz Date 2008-11-07 Time 15:41 Rev Time 0.00
Received By mcruz Date 2008-11-07 Time 15:39 Sent To I
Notes
2008-11-07 15:41:38PLANNING AND ZONING DEPT: ***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDR), SECTION
 94-441(C)(2): AS THE VALUE OF THE PROPOSED WORK EXCEEDS
 50% OF THE STRUCTURE'S VALUE (LISTED AS "IMPROVEMENT
 VALUE" WITH THE P.B.C. PROPERTY APPRAISER'S OFFICE),
 LANDSCAPING SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR.
  
 PLEASE SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN
 SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF
 THE ZLDR.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720