Plan Review Details - Permit 08100615
Plan Review Stops For Permit 08100615
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-01-08 Cont ID  
Sent By rmcdouga Date 2009-01-08 Time 09:47 Rev Time 0.00
Received By rmcdouga Date 2009-01-08 Time 09:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-11-10 Cont ID  
Sent By rmcdouga Date 2008-11-10 Time 13:29 Rev Time 0.00
Received By rmcdouga Date 2008-11-10 Time 13:29 Sent To  
Notes
2008-11-07 15:58:292004 FBC W/2007 REVISIONS
 REPAIRS AND INTERIOR REMODEL
  
 DENIED BY BUILDING
  
 1) THE PROJECT DESCRIPTION ON THE PERMIT APPLICATION IS
 INCORRECT. BASED ON THE PLANS THE SCOPE OF WORK IS TO
 REPAIR EXTERIOR WALLS AND INTERIOR REMODEL. PLEASE
 REVISE.
  
 2) THE VALUE OF THE WORK SPECIFIED ON THE APPLICATION
 IS TOO LOW. THE VALUATION IS TO INCLUDE ALL COSTS FOR
 MATERIALS, FINISHES, LABOR, ELECTRICAL WORK, DESIGN
 FEES, ETC. AS WOULD BE CHARGED BY A LICENSED BUILDING
 CONTRACTOR. THE ACTUAL VALUE SHOULD BE APPROXIMATELY
 $5,000.00. PLEASE REVISE THE VALUE ON THE APPLICATION
 AND PAY ADDITIONAL PERMIT FEES. FBC 108.3* CITY
 AMENDMENTS.
  
 3) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED. FS 713
  
 4) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED. THE PROPERTY
 APPRAISER WEB SITE INDICATES THAT THIS AREA IS AN
 ENCLOSED PORCH.
  
 5) THE CONSTRUCTION TYPE AND BUILDING CODE EDITION
 SPECIFIED ON THE COVERSHEET IS NOT CORRECT. PLEASE
 CHANGE TO SECTION 602.5 OF THE 2004 FBC AND
 CONSTRUCTION TYPE V-B.
  
 6) SPECIFY THE APPLICABLE WINDSPEED AND EXPOSURE
 CATEGORY ON THE PLANS. SEE FBC R 301.2.1 AND
 R301.2.1.4.
  
 7) ON SHEET 1.2 THE WINDOW SCHEDULE SPECIFIES THE
 EGRESS WINDOWS AS 48" IN HEIGHT. THIS WILL NOT PROVIDE
 THE MINIMUM CLEAR OPENING HEIGHT OF 24" REQUIRED BY FBC
 R310.
  
 8) ON THE WINDOW SCHEDULE ON SHEET 1.2 THE SECOND LINE
 LISTS AN EXPIRED NOA (03-0717.03) FOR THE HURRICANE
 SHUTTERS. PLEASE CORRECT.
  
 9) ON SHEET 2.1 THE EXISTING TYPICAL WALL SECTION
 SPECIFIES 3/4" PLYWOOD WALL SHEATHING AND THE OTHER
 DETAILS SPECIFY 5/8" PLYWOOD. PLEASE CORRECT.
  
 10) THE TYPICAL WALL SECTION SPECIFIES R-19 WALL
 INSULATION. THE FRAME WALLS THAT ARE SPECIFIED AS 2 X 4
 HAVE A MAXIMUM INSULATION OF R-11. PLEASE CORRECT.
  
 11) ON SHEET 2.1, THE DOOR FRAME DETAIL SPECIFIES 2 X 6
 WALLS AND THE WINDOW DETAIL HAS 2 X 4 WALLS. ON SHEET
 1.2 THE WALLS ARE SPECIFIED AS 2 X 4. PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-12-29 Cont ID  
Sent By btrobaug Date 2008-12-29 Time 11:28 Rev Time 0.00
Received By btrobaug Date 2008-12-29 Time 10:30 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-11-05 Cont ID  
Sent By btrobaug Date 2008-11-05 Time 14:36 Rev Time 0.00
Received By btrobaug Date 2008-11-05 Time 13:24 Sent To P
Notes
2008-11-05 13:39:13 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE SERVICE ON SHEET 3.1 IS SHOWN AS AN EXISTING BUT
 MUST BE CORRECTED AS IT IS A LIFE SAFETY ISSUE. THERE
 IS A GROUNDING ELECTRODE CONDUCTOR AT THE METER AND A
 GROUNDING ELECTRODE SYSTEM SHOWN AT THE PANEL WITH A
 DISCONNECT IN BETWEEN THE TWO IN VIOLATION OF
 250.24(A)(5)" LOAD-SIDE GROUNDING CONNECTIONS A
 GROUNDING CONNECTION SHALL NOT BE MADE TO ANY GROUNDED
 CONDUCTOR ON THE LOAD SIDE OF THE SERVICE DISCONNECTING
 MEANS EXCEPT AS OTHERWISE PERMITTED IN THIS ARTICLE."
  
 2} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225, 240 AND 230 CAN BE
 REVIEWED.
  
 3} INDICATE HOW THE EQUIPMENT GROUND IS RAN AND WHERE
 IT ORIGINATES, ON THE SERVICE RISER DIAGRAM SEE COMMENT
 #1
  
 4} THE 2005 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE
 EFFECTIVE 8 DECEMBER 2006. THE APPLICATION FOR THIS
 PROJECT WAS AFTER THAT DATE AND THE PLANS ARE SUBJECT
 TO THAT CODE. PLEASE CHANGE NOTE #2 TO REFLECT THIS
 CHANGE.
  
 5} ELECTRICAL NOTE #3 IS INCORRECT REGARDING GFCI
 PROTECTION AT THE SINK***210.8(A) DWELLING UNITS ALL
 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE RECEPTACLES
 INSTALLED IN THE LOCATIONS SPECIFIED IN (1) THROUGH (8)
 SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION
 FOR PERSONNEL. (6) KITCHENS ? WHERE THE RECEPTACLES ARE
 INSTALLED TO SERVE THE COUNTERTOP SURFACES. PLEASE
 CORRECT.
  
 6} ELECTRICAL NOTE #4 REGARDING THE CIRCUITING FOR
 SMOKE ALARMS IS NOT A VIOLATION BUT IT SHOULD BE NOTED
 THAT THE CIRCUIT MUST COMPLY WITH 210.12 AND BE AFCI
 PROTECTED. ALSO SEE THE DEFINITION OF "SMOKE DETECTORS"
 11.8.2.1 NFPA-72, CLARIFY IF USING DETECTORS OR ALARMS,
 TO AVOID CONFUSION IN THE FIELD. IF USING DETECTORS
 INDICATE THE LOCATIONS OF THE SOUNDING DEVICES.
  
 7} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE
 ALARMS SHALL BE INTERCONNECTED AND HARD WIRED. LOCATE
 THE ALARMS ON THE PLAN TO INDICATE COMPLIANCE.
  
 8} NOTE #7 REFERENCES ARTICLE 310.17(A) WHICH IS NOT IN
 THE 2005 NEC, SEE COMMENT #4. THE REFERENCES TO
 210.52(A) AND 210.52(E) ARE FOR OUTLETS, NOT "J" BOXES.
 CORRECT NOTES TO REFERENCE CURRENT CODES.
  
 9} THE ENGINEERING FIRM LISTED ON THE TITLE BLOCK SHALL
 INDICATE THE CERTIFICATE OF AUTHORIZATION NUMBER ALONG
 WITH OTHER INFORMATION REQUIRED BY 61G15-23.002 FLORIDA
 ADMINISTRATIVE CODE.
  
 10} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS
 AMENDED.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-12-18 Cont ID  
Sent By adarroug Date 2008-12-18 Time 16:36 Rev Time 0.00
Received By adarroug Date 2008-12-18 Time 16:36 Sent To E
Notes
2008-12-18 16:37:15TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-11-10 Cont ID  
Sent By rmcdouga Date 2008-11-10 Time 13:29 Rev Time 0.00
Received By rmcdouga Date 2008-10-30 Time 08:58 Sent To  
Notes
2008-10-30 08:59:02TO "SFR" "E"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2008-10-30 Cont ID  
Sent By tgordon Date 2008-10-30 Time 10:25 Rev Time 0.15
Received By tgordon Date 2008-10-30 Time 10:24 Sent To E
Notes
2008-10-30 10:25:41NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 1 Status N Date 2008-11-05 Cont ID  
Sent By mperson Date 2008-11-05 Time 15:32 Rev Time 0.15
Received By mperson Date 2008-11-05 Time 15:32 Sent To B
Notes
2008-11-05 15:54:15NOTE: THERE IS NO PROPOSED PLUMBING BEING INDICATED ON
 THE PLANS AND THERE IS NO PLUMBING PERMIT BEING APPLIED
 FOR AT THIS TIME. *MRPERSON.