| Plan Review Stops For Permit 08100556 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2008-12-19 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-12-19 |
Time |
15:46 |
Rev Time |
0.55 |
| Received By |
jwitmer |
Date |
2008-12-19 |
Time |
15:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-11-20 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-11-20 |
Time |
14:21 |
Rev Time |
1.22 |
| Received By |
jwitmer |
Date |
2008-11-20 |
Time |
14:21 |
Sent To |
|
|
| Notes |
| 2008-11-20 14:41:36 | BUILDING PLAN REVIEW | | | PERMIT: 08100556 | | | ADD: 800 CLEMATIS ST | | | CONT: SURGE SOLUTIONS | | | TEL: (561)309-6030 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW | | | ACTION: DENIED | | | | | | 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE | | | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | 1B) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) | | | AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC | | | BUILDING WITH THE 2007 SUPPLEMENTS. | | | | | | 2) DISCREPANCY BETWEEN THE PERMITED MASTER PLANS SHEET | | | A1.01 SITE PLAN AND THE PROPOSED LOCATION ON THE NEW | | | PLAN FOR INSTALLATION OF A BOVE GROUND FUEL TANK. | | | SHEET# 1 OF THE NEW TANK PERMIT INDICATES THE TANK TO | | | BE LOCATED WITHIN A GENERATOR FUEL TANK ROOM IN A | | | DIFFERENT LOCATION FROM THE ORIGINAL PERMITTED PLANS. | | | THE ORIGINAL PERMITTED PLANS DOES INDICATE A CHILLER | | | ENCLOSURE( NOT ROOFED IN). | | | 106.1.2 ADDITIONAL INFORMATION REQUIRED. | | | | | | 3) IF THE 2,000 GALLON ABOVE GROUND FUEL TANK IS TO BE | | | WITHIN A ROOM THEN SECTION 415.2.2-415.7.2.10 ARETO BE | | | MET. | | | | | | 4) IF THE TANK IS TO BE PLACED OUTDOORS THEN THE | | | REQUIREMENTS OF 414.6 OUTDOOR STORAGE - SHALL BE IN | | | ACCORDANCE WITH THE FLORIDA FIRE PREVENTION CODE. | | | | | | 5) IF OUTDOORS THE WIND REQUIREMENTS ARE MISSING FROM | | | THE PLAN.1603.1.4 WIND DESIGN DATA. | | | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL | | | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE | | | DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE | | | BUILDING: | | | 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR | | | (KM/HR). | | | | | | 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING | | | CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7 | | | AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. | | | | | | 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS | | | UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND | | | DIRECTION SHALL BE INDICATED. | | | | | | 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF | | | DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT. | | | | | | 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES | | | IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION | | | OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT | | | SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN | | | PROFESSIONAL. | | | | | | 6) PLANS DO NOT PROVIDE HOW THE TANK WILL BE SUPPORTED | | | . | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)805-6731 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2009-02-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-02-04 |
Time |
16:23 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-02-04 |
Time |
16:23 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2009-02-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-02-04 |
Time |
10:00 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-02-04 |
Time |
10:00 |
Sent To |
PC |
|
| Notes |
| 2009-02-04 10:00:44 | ** DENIED** | | | | | | 1) NOTE: THE SHOP DRAWING REVIEW STAMP IS REQUIRED TO | | | BE SIGNED BY THE ENGINEER OF RECORD. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2008-12-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-12-24 |
Time |
14:53 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-12-24 |
Time |
14:53 |
Sent To |
|
|
| Notes |
| 2008-12-24 14:53:45 | ** DENIED 2ND REVIEW ** | | | | | | | | | 1) NOTE: PLEASE SEE NOTES FROM PREVIOUS ELECTRICAL | | | REVIEW. | | | THE BASE BUILDING PLANS WERE REVISED FOR THE STRUCTURAL | | | HOWEVER OTHER COMMENTS WITH RESPECT TO NEW PANELS, | | | WIRING, SHOP DRAWING REVIEW STAMPS, LOADS ETC WERE NOT | | | ADDRESSED. IN FACT THE SAME ELECTRICAL PLANS PREVIOUSLY | | | SUBMITTED WERE BROUGHT BACK. | | | | | | | | | **IMPORTANT** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED | | | INTO TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2008-11-20 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-11-20 |
Time |
16:54 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-11-20 |
Time |
16:54 |
Sent To |
|
|
| Notes |
| 2008-11-20 16:54:59 | ** FAILED REVIEW ** | | | | | | | | | | | | 1) NOTE: BASE BUILDING PERMIT # 07050361 DOES NOT SHOW | | | OR CONTAIN THE ROOM WHICH IS BEING NOTED ON THE PLANS. | | | IN FACT PLANS SUBMITTED CLEARLY STATE * GENERATOR FUEL | | | TANK ROOM* HOWEVER THIS ROOM DOES NOT ACTUALLY EXISTS | | | ON ELECTRICAL OR BUILDING PLANS OF BASE BUILDING. | | | THIS ROOM NEEDS TO CONTAIN ALL INFORMATION FOR REVIEW | | | UNDER BASE BUILDING OR SEPARATE PERMIT FOR DESIGNS | | | UNDER NFPA-70 (2005), 2004 FBC W/ 2007 REVISIONS, | | | NFPA-72, NFPA-101, NFPA-30 ETC | | | AS NO ELECTRICAL DETAILS SPECIFIC TO ROOM ARE SHOWN | | | MANY ITEMS FOR CODE COMPLIANT REVIEW COULD NOT BE DONE. | | | THE OTHER ELECTRICAL DETAILS ON PLANS SUCH AS THE ONES | | | ON SHEET #3 ARE NOT RELEVANT UNLESS FUEL PUMPS ARE | | | GOING TO BE INSTALLED. PLEASE INCLUDE DETAILS ONLY FOR | | | NEW SCOPE OF WORK. THE SPECIFIC DETAILS NEED TO | | | COORDINATE FOR SCOPE OF WORK AS APPLIED. | | | NO RISER DIAGRAM SUBMITTED FOR HOW NEW PANELS ARE BEING | | | FED. | | | NO FEEDERS, NO GROUNDING, NO LOADS, ETC. | | | THE BASE BUILDING PLANS DO NOT CONTAIN THESE SAME | | | PANELS AS SHOWN ON THIS SAME SHEET #3. | | | MINIMUM PLANS REQUIRED FOR SCOPE OF WORK. | | | FBC 106.1.1, 106.1.2, 106.3.5.1.2 (AS ADOPTED BY LOCAL | | | AMENDMENTS) | | | | | | 2) NOTE: THE BASE BUILDING AND ALL ELECTRICAL SYSTEMS | | | AS WELL AND OTHER SYSTEMS ARE UNDER THE DESIGN AND THE | | | RESPONSIBILITY OF THE BASE BUILDING DESIGN TEAM UNTIL | | | SUCH TIME OF A CERTIFICATE OF OCCUPANCY IS ISSUED. ANY | | | WORK DONE ON THIS PROJECT UNDER DESIGN FROM OTHER THAN | | | THE BASE BUILDING DESIGNERS OF RECORD SHALL BE REVIEWED | | | AND STAMPED WITH A *SHOP DRAWING REVIEW STAMP*. EACH | | | SHEET MUST CONTAIN THE STAMP FROM RELEVANT DESIGNER. | | | | | | 3) NOTE: PLEASE SEE THE ADDRESS ON TITLE BLOCKS FOR | | | ENGINEERING FIRM AS LISTED DOES NOT CORRELATE WITH THE | | | DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION. | | | PLEASE ADJUST AND REVISE TITLE BLOCKS TO COORDINATE | | | WITH THE STATE OR PLEASE CONTACT STATE TO REVISE. | | | FAC 61G15-23.002, FS 471.023 | | | | | | | | | **IMPORTANT** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED | | | INTO TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2009-02-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-02-04 |
Time |
16:24 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-02-04 |
Time |
16:24 |
Sent To |
|
|
| Notes |
| 2009-02-04 16:25:02 | OK PER PREVIOUS FIRE REVIEW. PLANS STAMPED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2008-12-22 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-12-22 |
Time |
15:27 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-12-22 |
Time |
15:21 |
Sent To |
|
|
| Notes |
| 2008-12-22 15:27:36 | *****APPROVED***** | | | | | | | | | THE COMMENTS FROM THE PREVIOUS REVIEW HAVE BEEN | | | ADDRESSED; PLAN SHEETS 1 & 2 WERE STAMPED, INITIALED, | | | AND DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2008-11-12 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-11-12 |
Time |
13:40 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-11-12 |
Time |
13:40 |
Sent To |
|
|
| Notes |
| 2008-11-12 13:51:08 | ***DENIED*** | | | | | | 1) WORK SHALL COMPLY WITH NFPA 101, 2003 AND NFPA 30, | | | STANDARD FOR FLAMMABLE AND COMBUSTIBLE LIQUIDS. PLEASE | | | ADD TO DRAWINGS. | | | | | | 2) CLEARLY ILLUSRATE LOCATION OF TANK AND EXHAUST | | | TERMINUS AS IT RELATES TO BUILDING OPENINGS AND MEANS | | | OF EGRESS. | | | | | | 3) PROVIDE INFORMTION REGARDING ROOM CONSTRUCTION AND | | | ANY WALL FIRE RATING INFORMATION. | | | | | | 4) PROVIDE MANUFACTURER SPECIFICATION SHEETS AND | | | PRODUCT APPROVALS FOR FUEL TANK. | | | | | | 5) PROVIDE APPLICABLE SIGNAGE IN ACCORDANCE WITH NFPA | | | 704. | | | | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 | | 2008-10-27 10:12:54 | TO "M" BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2009-01-26 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2009-01-26 |
Time |
16:47 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2009-01-26 |
Time |
16:47 |
Sent To |
|
|
| Notes |
| 2009-01-26 16:52:14 | TO "COMM" BD#46 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-11-26 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-11-26 |
Time |
11:02 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-11-26 |
Time |
11:02 |
Sent To |
|
|
| Notes |
| 2008-11-26 11:02:24 | TO "COMM" BD#12 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-11-22 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-11-22 |
Time |
10:56 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-10-27 |
Time |
10:08 |
Sent To |
|
|
| Notes |
| 2008-11-12 14:29:37 | 11/12/08--TO "COMM" BD#47 | | 2008-10-27 10:09:45 | TO "M" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2008-12-14 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-12-14 |
Time |
15:24 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-12-14 |
Time |
15:24 |
Sent To |
|
|
| Notes |
| 2008-12-14 15:24:59 | MASTER PERMIT #07050361 IS BEING REVISED TO SHOW FUEL | | | TANK ENCLOSURE ADJACENT TO CHILLER PLANT. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2008-12-14 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-11-22 |
Time |
08:44 |
Rev Time |
0.35 |
| Received By |
rregueir |
Date |
2008-10-30 |
Time |
08:44 |
Sent To |
PC |
|
| Notes |
| 2008-11-22 14:54:55 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | | | | PLANS SHOW NEW TANK IN ROOM ADJACENT TO CHILLER PLANT. | | | NO SUCH ROOM EXISTS ON MASTER PERMIT #07050361. UNDER | | | WHICH PERMIT IS THIS ROOM TO BE BUILT? ALSO, THE | | | LOCATION OF CHILLER PLANT ON THESE PLANS DOES NOT | | | CORRESPOND WITH THE LOCATION SHOWN ON BASE BUILDING | | | MECHANICAL PLANS. IS THE CHILLER PLANT BEING RELOCATED? | | | | | | PLEASE COORDINATE PLANS AND CLARIFY INTENT AND SCOPE OF | | | WORK BETWEEN THIS PERMIT APPLICATION AND PRIMARY PERMIT | | | 07050361 IN ACCORDANCE WITH FBCB 106.1.1. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2008-12-02 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2008-12-02 |
Time |
13:12 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2008-12-02 |
Time |
13:12 |
Sent To |
|
|
| Notes |
| 2008-12-02 13:13:26 | PROVISO: | | | LANDSCAPE SHALL BE PROVIDED AROUND THE SCREEN WALL. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2008-11-21 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2008-11-21 |
Time |
09:55 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2008-11-21 |
Time |
09:55 |
Sent To |
|
|
| Notes |
| 2008-11-21 09:55:52 | PROVISO: LANDSCAPE AROUND FUEL TANK SHALL BE PROVIDED | | | ACCORDING TO DRAWING LA-1 ON MAIN PERMIT. |
|
|