Plan Review Details - Permit 08100556
Plan Review Stops For Permit 08100556
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-12-19 Cont ID  
Sent By jwitmer Date 2008-12-19 Time 15:46 Rev Time 0.55
Received By jwitmer Date 2008-12-19 Time 15:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-11-20 Cont ID  
Sent By jwitmer Date 2008-11-20 Time 14:21 Rev Time 1.22
Received By jwitmer Date 2008-11-20 Time 14:21 Sent To  
Notes
2008-11-20 14:41:36BUILDING PLAN REVIEW
 PERMIT: 08100556
 ADD: 800 CLEMATIS ST
 CONT: SURGE SOLUTIONS
 TEL: (561)309-6030
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 2) DISCREPANCY BETWEEN THE PERMITED MASTER PLANS SHEET
 A1.01 SITE PLAN AND THE PROPOSED LOCATION ON THE NEW
 PLAN FOR INSTALLATION OF A BOVE GROUND FUEL TANK.
 SHEET# 1 OF THE NEW TANK PERMIT INDICATES THE TANK TO
 BE LOCATED WITHIN A GENERATOR FUEL TANK ROOM IN A
 DIFFERENT LOCATION FROM THE ORIGINAL PERMITTED PLANS.
 THE ORIGINAL PERMITTED PLANS DOES INDICATE A CHILLER
 ENCLOSURE( NOT ROOFED IN).
 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 3) IF THE 2,000 GALLON ABOVE GROUND FUEL TANK IS TO BE
 WITHIN A ROOM THEN SECTION 415.2.2-415.7.2.10 ARETO BE
 MET.
  
 4) IF THE TANK IS TO BE PLACED OUTDOORS THEN THE
 REQUIREMENTS OF 414.6 OUTDOOR STORAGE - SHALL BE IN
 ACCORDANCE WITH THE FLORIDA FIRE PREVENTION CODE.
  
 5) IF OUTDOORS THE WIND REQUIREMENTS ARE MISSING FROM
 THE PLAN.1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
  
 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION
 OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL.
  
 6) PLANS DO NOT PROVIDE HOW THE TANK WILL BE SUPPORTED
 .
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2009-02-04 Cont ID  
Sent By dpalmer Date 2009-02-04 Time 16:23 Rev Time 0.00
Received By dpalmer Date 2009-02-04 Time 16:23 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2009-02-04 Cont ID  
Sent By dpalmer Date 2009-02-04 Time 10:00 Rev Time 0.00
Received By dpalmer Date 2009-02-04 Time 10:00 Sent To PC
Notes
2009-02-04 10:00:44** DENIED**
  
 1) NOTE: THE SHOP DRAWING REVIEW STAMP IS REQUIRED TO
 BE SIGNED BY THE ENGINEER OF RECORD.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-12-24 Cont ID  
Sent By dpalmer Date 2008-12-24 Time 14:53 Rev Time 0.00
Received By dpalmer Date 2008-12-24 Time 14:53 Sent To  
Notes
2008-12-24 14:53:45** DENIED 2ND REVIEW **
  
  
 1) NOTE: PLEASE SEE NOTES FROM PREVIOUS ELECTRICAL
 REVIEW.
 THE BASE BUILDING PLANS WERE REVISED FOR THE STRUCTURAL
 HOWEVER OTHER COMMENTS WITH RESPECT TO NEW PANELS,
 WIRING, SHOP DRAWING REVIEW STAMPS, LOADS ETC WERE NOT
 ADDRESSED. IN FACT THE SAME ELECTRICAL PLANS PREVIOUSLY
 SUBMITTED WERE BROUGHT BACK.
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-11-20 Cont ID  
Sent By dpalmer Date 2008-11-20 Time 16:54 Rev Time 0.00
Received By dpalmer Date 2008-11-20 Time 16:54 Sent To  
Notes
2008-11-20 16:54:59** FAILED REVIEW **
  
  
  
 1) NOTE: BASE BUILDING PERMIT # 07050361 DOES NOT SHOW
 OR CONTAIN THE ROOM WHICH IS BEING NOTED ON THE PLANS.
 IN FACT PLANS SUBMITTED CLEARLY STATE * GENERATOR FUEL
 TANK ROOM* HOWEVER THIS ROOM DOES NOT ACTUALLY EXISTS
 ON ELECTRICAL OR BUILDING PLANS OF BASE BUILDING.
 THIS ROOM NEEDS TO CONTAIN ALL INFORMATION FOR REVIEW
 UNDER BASE BUILDING OR SEPARATE PERMIT FOR DESIGNS
 UNDER NFPA-70 (2005), 2004 FBC W/ 2007 REVISIONS,
 NFPA-72, NFPA-101, NFPA-30 ETC
 AS NO ELECTRICAL DETAILS SPECIFIC TO ROOM ARE SHOWN
 MANY ITEMS FOR CODE COMPLIANT REVIEW COULD NOT BE DONE.
 THE OTHER ELECTRICAL DETAILS ON PLANS SUCH AS THE ONES
 ON SHEET #3 ARE NOT RELEVANT UNLESS FUEL PUMPS ARE
 GOING TO BE INSTALLED. PLEASE INCLUDE DETAILS ONLY FOR
 NEW SCOPE OF WORK. THE SPECIFIC DETAILS NEED TO
 COORDINATE FOR SCOPE OF WORK AS APPLIED.
 NO RISER DIAGRAM SUBMITTED FOR HOW NEW PANELS ARE BEING
 FED.
 NO FEEDERS, NO GROUNDING, NO LOADS, ETC.
 THE BASE BUILDING PLANS DO NOT CONTAIN THESE SAME
 PANELS AS SHOWN ON THIS SAME SHEET #3.
 MINIMUM PLANS REQUIRED FOR SCOPE OF WORK.
 FBC 106.1.1, 106.1.2, 106.3.5.1.2 (AS ADOPTED BY LOCAL
 AMENDMENTS)
  
 2) NOTE: THE BASE BUILDING AND ALL ELECTRICAL SYSTEMS
 AS WELL AND OTHER SYSTEMS ARE UNDER THE DESIGN AND THE
 RESPONSIBILITY OF THE BASE BUILDING DESIGN TEAM UNTIL
 SUCH TIME OF A CERTIFICATE OF OCCUPANCY IS ISSUED. ANY
 WORK DONE ON THIS PROJECT UNDER DESIGN FROM OTHER THAN
 THE BASE BUILDING DESIGNERS OF RECORD SHALL BE REVIEWED
 AND STAMPED WITH A *SHOP DRAWING REVIEW STAMP*. EACH
 SHEET MUST CONTAIN THE STAMP FROM RELEVANT DESIGNER.
  
 3) NOTE: PLEASE SEE THE ADDRESS ON TITLE BLOCKS FOR
 ENGINEERING FIRM AS LISTED DOES NOT CORRELATE WITH THE
 DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION.
 PLEASE ADJUST AND REVISE TITLE BLOCKS TO COORDINATE
 WITH THE STATE OR PLEASE CONTACT STATE TO REVISE.
 FAC 61G15-23.002, FS 471.023
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-02-04 Cont ID  
Sent By dpalmer Date 2009-02-04 Time 16:24 Rev Time 0.00
Received By dpalmer Date 2009-02-04 Time 16:24 Sent To  
Notes
2009-02-04 16:25:02OK PER PREVIOUS FIRE REVIEW. PLANS STAMPED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-12-22 Cont ID  
Sent By mawillia Date 2008-12-22 Time 15:27 Rev Time 0.00
Received By mawillia Date 2008-12-22 Time 15:21 Sent To  
Notes
2008-12-22 15:27:36*****APPROVED*****
  
  
 THE COMMENTS FROM THE PREVIOUS REVIEW HAVE BEEN
 ADDRESSED; PLAN SHEETS 1 & 2 WERE STAMPED, INITIALED,
 AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-11-12 Cont ID  
Sent By mwennerg Date 2008-11-12 Time 13:40 Rev Time 0.00
Received By mwennerg Date 2008-11-12 Time 13:40 Sent To  
Notes
2008-11-12 13:51:08***DENIED***
  
 1) WORK SHALL COMPLY WITH NFPA 101, 2003 AND NFPA 30,
 STANDARD FOR FLAMMABLE AND COMBUSTIBLE LIQUIDS. PLEASE
 ADD TO DRAWINGS.
  
 2) CLEARLY ILLUSRATE LOCATION OF TANK AND EXHAUST
 TERMINUS AS IT RELATES TO BUILDING OPENINGS AND MEANS
 OF EGRESS.
  
 3) PROVIDE INFORMTION REGARDING ROOM CONSTRUCTION AND
 ANY WALL FIRE RATING INFORMATION.
  
 4) PROVIDE MANUFACTURER SPECIFICATION SHEETS AND
 PRODUCT APPROVALS FOR FUEL TANK.
  
 5) PROVIDE APPLICABLE SIGNAGE IN ACCORDANCE WITH NFPA
 704.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756
2008-10-27 10:12:54TO "M" BOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-01-26 Cont ID  
Sent By adarroug Date 2009-01-26 Time 16:47 Rev Time 0.00
Received By adarroug Date 2009-01-26 Time 16:47 Sent To  
Notes
2009-01-26 16:52:14TO "COMM" BD#46

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-11-26 Cont ID  
Sent By adarroug Date 2008-11-26 Time 11:02 Rev Time 0.00
Received By adarroug Date 2008-11-26 Time 11:02 Sent To  
Notes
2008-11-26 11:02:24TO "COMM" BD#12

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-11-22 Cont ID  
Sent By adarroug Date 2008-11-22 Time 10:56 Rev Time 0.00
Received By adarroug Date 2008-10-27 Time 10:08 Sent To  
Notes
2008-11-12 14:29:3711/12/08--TO "COMM" BD#47
2008-10-27 10:09:45TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-12-14 Cont ID  
Sent By rregueir Date 2008-12-14 Time 15:24 Rev Time 0.00
Received By rregueir Date 2008-12-14 Time 15:24 Sent To  
Notes
2008-12-14 15:24:59MASTER PERMIT #07050361 IS BEING REVISED TO SHOW FUEL
 TANK ENCLOSURE ADJACENT TO CHILLER PLANT.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-12-14 Cont ID  
Sent By tgordon Date 2008-11-22 Time 08:44 Rev Time 0.35
Received By rregueir Date 2008-10-30 Time 08:44 Sent To PC
Notes
2008-11-22 14:54:55REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
  
 PLANS SHOW NEW TANK IN ROOM ADJACENT TO CHILLER PLANT.
 NO SUCH ROOM EXISTS ON MASTER PERMIT #07050361. UNDER
 WHICH PERMIT IS THIS ROOM TO BE BUILT? ALSO, THE
 LOCATION OF CHILLER PLANT ON THESE PLANS DOES NOT
 CORRESPOND WITH THE LOCATION SHOWN ON BASE BUILDING
 MECHANICAL PLANS. IS THE CHILLER PLANT BEING RELOCATED?
  
 PLEASE COORDINATE PLANS AND CLARIFY INTENT AND SCOPE OF
 WORK BETWEEN THIS PERMIT APPLICATION AND PRIMARY PERMIT
 07050361 IN ACCORDANCE WITH FBCB 106.1.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2008-12-02 Cont ID  
Sent By aaponte Date 2008-12-02 Time 13:12 Rev Time 0.00
Received By aaponte Date 2008-12-02 Time 13:12 Sent To  
Notes
2008-12-02 13:13:26PROVISO:
 LANDSCAPE SHALL BE PROVIDED AROUND THE SCREEN WALL.

Review Stop Z ZONING
Rev No 1 Status P Date 2008-11-21 Cont ID  
Sent By aaponte Date 2008-11-21 Time 09:55 Rev Time 0.00
Received By aaponte Date 2008-11-21 Time 09:55 Sent To  
Notes
2008-11-21 09:55:52PROVISO: LANDSCAPE AROUND FUEL TANK SHALL BE PROVIDED
 ACCORDING TO DRAWING LA-1 ON MAIN PERMIT.