| 2008-11-03 11:42:38 | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. THE "FLORIDA SOLAR ENERGY CENTER, APPROVED SOLAR |
| | ENERGY SYSTEM" SHEET IS INDICATING FOUR DIFFERENT MODEL |
| | NUMBERS FOR THE PUMP MANUFACTURER. CLEARLY INDICATE ON |
| | THE RESUBMITTAL WHICH MODEL NUMBER PUMP AND IS BEING |
| | USED ON THE PROPOSED SOLAR WATER HEATER. PER FBC-2004 |
| | CHAPTER 1, (W.P.B.) AS AMENDED SECTION 106.1.2 |
| | ADDITIONAL DATA. |
| | |
| | 2. PLEASE CLARIFY ON THE RESUBMITTAL THE LOCATION OF |
| | THE PROPOSED DOMESTIC SOLAR WATER HEATING SYSTEM. IS |
| | THE SYSTEM CONNECTING TO THE EXISTING COLD WATER SUPPLY |
| | AND HOT WATER LINES AT THE EXISTING DOMESTIC WATER |
| | HEATER LOCATION? PLEASE KNOW THAT IF THE PROPOSED |
| | DOMESTIC SOLAR WATER HEATING SYSTEM IS NOT AT THE |
| | EXISTING DOMESTIC WATER HEATER LOCATION THAT A LICENSED |
| | PLUMBING CONTRACTOR WILL BE REQUIRED TO PIPE THE SYSTEM |
| | TO A NEW LOCATION. PER FAC 61G4-15.021 CERTIFICATION OF |
| | SOLAR CONTRACTORE (E) PLUMBING. |
| | |
| | 3. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING |
| | DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE |
| | PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE |
| | ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER |
| | FBC-2004 CHAPTER 1, (W.P.B. AS AMENDED SECTION |
| | *106.3.4.3. |
| | IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR ENGINEER, |
| | THEN HE OR SHE SHALL AFFIX HIS OR HER OFFICIAL SEAL, |
| | SIGNATURE AND DATE TO SAID DRAWINGS, PER FLORIDA |
| | STATUTES 481 AND 471 RESPECTIVELY. |
| | *THE CONTRACTOR OF RECORD MAY BE THE DESIGN |
| | PROFESSIONAL IF EXEMPTIONS UNDER FLORIDA STATUTES |
| | 471.003(H) APPLY. |
| | |
| | 4. PER FS 713.13 (1) THRU (6): A NOTICE OF COMMENCEMENT |
| | IS REQUIRED FROM THE - PALM BEACH COUNTY COURTHOUSE - |
| | 4TH FLOOR RECORDING DEPT. 205 N. DIXIE HWY., BEFORE THE |
| | FIRST INSPECTION. PER FS 713.13 (2): IF THE IMPROVEMENT |
| | DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT ACTUALLY |
| | COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF, |
| | SUCH NOTICE IS VOID AND OF NO FURTHER EFFECT. |
| | |
| | END OF COMMENTS: |
| | |
| | *IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL: [email protected] |
| | |
| | |