Plan Review Details - Permit 08100484
Plan Review Stops For Permit 08100484
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-12-24 Cont ID  
Sent By mjacobs Date 2008-12-24 Time 10:20 Rev Time 0.00
Received By mjacobs Date 2008-12-24 Time 10:20 Sent To  
Notes
2008-12-24 09:52:03PROVISOR: A PORTION OF MAIN COUNTER SHALL HAVE A
 MINIMUM LENGTH OF 36 INCHES AND A MAXIMUM HEIGHT OF 36
 INCHES OR EQUIVALENT FACILITATION SHALL BE PROVIDED.
 FBC 11-7.2 (2)
  
  
  
 PROVISOR: A PORTION OF MAIN COUNTER SHALL HAVE A
 MINIMUM LENGTH OF 36 INCHES AND A MAXIMUM HEIGHT OF 36
 INCHES OR EQUIVALENT FACILITATION SHALL BE PROVIDED.
 FBC 11-7.2 (2)

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-10-27 Cont ID  
Sent By mjacobs Date 2008-10-27 Time 10:04 Rev Time 0.00
Received By mjacobs Date 2008-10-27 Time 10:04 Sent To  
Notes
2008-10-27 10:04:26BUILDING PLAN REVIEW
 PERMIT: 08100484
 ADD: 208 S. OLIVE AVE
 CONT: GRUBER HALL CORP .
 TEL: (561)697-3401
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 10-27-08
 REVIEW: 1ST
 ACTION: DENIED
  
 1) NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 2) SHEET 0.0 THE BUILDING INFORMATION INDICATED ON THE
 PLANS DIFFERS FROM A PREVIOUS PERMIT #07100432. THE
 TYPE OF BUILDING IS A TYPE VI- UNPROTECTED, THE
 EXISTING FIRST FLOOR INDICATES 1774 SQ, EXISTING
 MEZZANINE 645 SQ. THE NEW DRAWINGS BUILDING INFORMATION
 SHOWS THE BUILDING AS A TYPE IIA PROTECTED WITH THE
 GROUND FLOOR AREA 1582 SQ AND THE MEZZANINE 545SQ. IF
 THIS IS THE SAME BUILDING THE SQUARE SHALL BE THE SAME
 IF NO ADDITIONAL SQUARE FOOTAGE WAS ADDED. FOR OUR
 RECORD RETENTION PROGRAM THE BUILDING INFORMATION SHALL
 BE THE SAME ON EACH APPLICATION TO PROVIDE CONFORMITY
 TO ITS RECORD RETENTION PROGRAM. 106.1.3*
  
 3) THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO
 INCLUDE ELECTRIC, PLUMBING, MECHANICAL, INTERIOR
 FINISH, ARCHITECTURAL AND DESIGN FEES MARKETING COST,
 OVERHEAD AND PROFIT. OUR VALUATION REFERENCE IS ICC
 (BVD) MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3*
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-12-24 Cont ID  
Sent By dpalmer Date 2008-12-24 Time 12:57 Rev Time 0.00
Received By dpalmer Date 2008-12-24 Time 12:57 Sent To  
Notes
2008-12-24 12:58:23BUILDING AS DEFINED IS LESS THAN 5K SQ FT.
  
 VIF DISC IN LAUNDRY ROOM MEETING 422.31 FOR WH.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-11-04 Cont ID  
Sent By dpalmer Date 2008-11-04 Time 08:06 Rev Time 0.00
Received By dpalmer Date 2008-11-04 Time 08:06 Sent To  
Notes
2008-11-04 08:06:23 
  
  
  
 ** DENIED REVIEW **
  
 1) NOTE: TITLE BLOCKS FOR ARCHITECT IS MISSING THE
 PRINTED NAME AND PRINTED LICENSE NUMBER OF SAID
 DESIGNER.
 FAC 61G1-16.004.
  
 2) NOTE: PLEASE INCLUDE THE LIGHTING PERFORMANCE
 CALCULATIONS PER 13-415.2, 13-415.2.ABC.1.1,.1.2.
 PLEASE NOTE SECTION FOR TRACK LIGHTING. PLEASE ALSO
 KNOW BEFORE ANY NEW FIXTURES MAY BE INSTALLED THE
 EXISTING LIGHTING LEVELS NEED TO BE DETERMINED BEFORE
 ANY NEW MAY BE INSTALLED.
 THE FIXTURE LEGEND NEEDS TO BE COMPLETED AT THIS TIME
 WITH PRE-DETERMINED FIXTURES SO THAT CODE COMPLIANCE
 MAY BE VERIFIED. THE LIGHTING FIXTURES MAY ALWAYS BE
 REVISED AT A LATER DATE.
  
 3) NOTE: PLEASE INDICATE WHETHER OR NOT THE EXISTING
 STAIRS MEET THE MINIMUM FOR THE LIFE SAFETY CODE FOR
 LIGHTING LEVELS. PLEASE SEE NFPA-101 7.8.1.3 AS THE
 LEVELS SHALL MEET THE MINIMUM LEVELS FOR NORMAL USE AND
 THE MINIMUM UNDER EMERGENCY CONDITIONS.
  
 4) NOTE: PLEASE VERIFY LOAD AND CIRCUITING FOR THE NEW
 PROPOSED TANK LESS WATER HEATER. THE LOAD SHOWN APPEARS
 TO BE VERY LOW HOWEVER THIS COMMENT IS FOR INFORMATION
 ONLY. IF THIS UNIT IS INDEED 4.5KVA THEN NO RESPONSE IS
 NEEDED.
 PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS
 INDICATING THE LISTING OF A NRTL. (NATIONALLY
 RECOGNIZED TESTING LABORATORY.
 110.3
  
 5) NOTE: PLEASE SEE REVISED 2005 NEC AS SECTION 408.4
 REQUIRES ALL CIRCUITING TO BE SPECIFIC TO ROOMS AND
 AREAS IN WHICH THEY FEED. THE USE OF GENERAL LIGHTING
 OR GENERAL RECEPTACLES IS NO LONGER PERMITTED. THESE
 NEE TO BE SPECIFIC TO ROOMS ARE AREAS WITH EITHER AND
 ALPHA OR NUMERIC DESIGNATION.
 FBC 106.1.1, 106.5.
  
 6) NOTE: PLEASE SEE THE OVER CURRENT PROTECTION FOR A/C
 #2 NEEDS TO BE SIZED PER 424.3B.
 IF THIS IS THE HEAT LOAD WHICH IS SHOWN THE MINIMUM OCP
 IS REQUIRED TO BE SIZED AT 125%.
 PLEASE ADJUST.
  
 7) NOTE: PLEASE BE SURE SHOW TRACK LOAD PER 220.43
  
 8) NOTE: PLEASE SEE 13-415.1.ABC.1.2, .1.3 FOR LIGHTING
 CONTROLS
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-12-26 Cont ID  
Sent By mwennerg Date 2008-12-26 Time 13:45 Rev Time 0.00
Received By mwennerg Date 2008-12-26 Time 13:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2008-10-31 Cont ID  
Sent By mwennerg Date 2008-10-31 Time 13:46 Rev Time 0.00
Received By mwennerg Date 2008-10-31 Time 13:46 Sent To  
Notes
2008-10-31 13:50:28***PROVISO***
  
  
 PLANS WILL BE STAMPED WHEN RETURNED WITH CORRECTIONS TO
 OTHER REVIEW COMMENTS. PLEASE SEE THE FOLLOWING:
  
 1) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 2) PLEASE CLARRIFY OCCUPANT LOAD AS ONLY BUSINESS
 FACTOR IS BEING USED, AND BUILDING IS CLASSIFIED AS
 BUSINESS/MERCANTILE.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW\FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-04-09 Cont ID  
Sent By adarroug Date 2009-04-09 Time 14:24 Rev Time 0.00
Received By adarroug Date 2009-04-09 Time 14:24 Sent To P
Notes
2009-04-09 14:25:14TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-03-09 Cont ID  
Sent By adarroug Date 2009-03-09 Time 11:17 Rev Time 0.00
Received By adarroug Date 2009-03-09 Time 11:17 Sent To P
Notes
2009-03-09 11:17:37TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-12-23 Cont ID  
Sent By adarroug Date 2008-12-18 Time 16:09 Rev Time 0.00
Received By adarroug Date 2008-12-18 Time 16:09 Sent To  
Notes
2008-12-23 16:10:17TO "BOB"#4

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-11-04 Cont ID  
Sent By adarroug Date 2008-11-04 Time 14:01 Rev Time 0.00
Received By adarroug Date 2008-10-22 Time 16:52 Sent To  
Notes
2008-10-22 16:55:00TO "BOB"#14

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-01-10 Cont ID  
Sent By rregueir Date 2009-01-10 Time 15:36 Rev Time 0.00
Received By rregueir Date 2009-01-10 Time 15:28 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-10-28 Cont ID  
Sent By tgordon Date 2008-10-28 Time 15:50 Rev Time 0.45
Received By tgordon Date 2008-10-28 Time 15:50 Sent To  
Notes
2008-10-28 16:01:33PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) THE CLOTHES DRYER VENT MAY NOT TERMINATE NEAR THE
 DOOR TO THE EXTERIOR CORRIDOR, PER 2004 FBC/M 501.2
 OUTDOOR DISCHARGE. THE AIR REMOVED BY EVERY MECHANICAL
 EXHAUST SYSTEM SHALL BE DISCHARGED OUTDOORS AT A POINT
 WHERE IT WILL NOT CAUSE A NUISANCE AND FROM WHICH IT
 CANNOT AGAIN BE READILY DRAWN IN BY A VENTILATING
 SYSTEM. THE DRYER EXHAUST WOULD BE A NUISANCE IF
 DISCHARGED IN TO THE EXTERIOR CORRIDOR AND MAY GET BACK
 INTO THE VENTILATION SYSTEM WHEN THE DOOR IS OPENED.
 PLEASE CORRECT.
  
 2) PLEASE SHOW ON MECHANICAL PLAN THE CFM'S FOR EXHAUST
 FAN BROAN L300L, SEE 2004 FBC/M 403.2.
  
 3) PLEASE SHOW ON MECH. PLAN THE CFM'S FOR THE BATHROOM
 EXHAUST FANS, SEE 2004 FBC/M 403.2.
  
 4) SHOW ON MECH. PLAN THAT ONE OF THE NEW EXHAUST FANS
 IS TO EXHAUST THE SHOWER ROOM, SEE 2004 FBC/M TABLE
 403.3.
  
 5) STATE ON MECH. PLAN THE MINIMUM SIZE THE EXISTING
 EXHAUST DUCT GOING TO THE ROOF CAN BE FOR THE THREE NEW
 EXHAUST FANS TO TIE INTO, OR DO YOU WANT THEM EACH TO
 BE DUCTED DIRECTLY TO THE ROOF VENT ON THE ROOF, SEE
 2004 FBC/M 603.2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2009-04-27 Cont ID  
Sent By kstevens Date 2009-04-27 Time 15:25 Rev Time 0.00
Received By kstevens Date 2009-04-27 Time 15:25 Sent To  
Notes
2009-04-27 15:26:07REVISION OK -- SK-1 SANITARY RISER DIAGRAM.

Review Stop P PLUMBING
Rev No 3 Status F Date 2009-04-01 Cont ID  
Sent By kstevens Date 2009-04-01 Time 08:40 Rev Time 0.00
Received By kstevens Date 2009-04-01 Time 08:40 Sent To  
Notes
2009-04-01 08:49:38REVISION DENIED
 REFERENCE:
 FBC-2004 PLUMIING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT SK-1 SANITARY RISER DIAGRAM DOES NOT MEET CODE
 REQUIREMENTS. PLEASE CORRECT THE FOLLOWING:
  
 A. THE FLOOR SINK REQUIRES A TRAP. SECTION 1002.1.
  
 B. THE WATER CLOSET ON THE FIRST FLOOR IS NOT VENTED.
 SECTION 908.3. WHERE THE FIXTURE DRAINS CONNECT AT
 DIFFERENT LEVELS, THE UPPER FIXTURE SHALL NOT BE A
 WATER CLOSET.
  
 C. THERE ARE CONFLICTING NOTES. ONE NOTE STATES "NEW
 HWH RELIEF VALVE & NEW WASHER TO TIE INTO EXISTING
 JANITOR'S SINK DRAIN", BUT ANOTHER NOTE INDICATES "NEW
 WASHER CONNECTION BOX WITH ARRESTORS. ALSO NO JANITOR
 SINK IS SHOWN ON THE RISER DIAGRAM. PLEASE CLARIFY.
 SECTION 106.1.1. IF THERE IS NO JANITOR SINK, THEN
 PLEASE INDICATE WHERE THE RELIEF VALVE DISCHARGE
 TERMINATES. SECTION 504.6.1.
  
 2. THE TITLE BLOCK IS REQUIRED TO NAME OR IDENTIFY THE
 PROJECT PER FAC 61G1-16.004(3) & FS 481.2055. PLEASE
 SHOW COMPLIANCE WITH NAME OF PROJECT OR ADDRESS ETC.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-01-09 Cont ID  
Sent By kstevens Date 2009-01-08 Time 11:09 Rev Time 0.00
Received By kstevens Date 2009-01-07 Time 18:59 Sent To  
Notes
2009-01-08 11:29:28 
  
  
 PASSED/PROVISO -- REVISION REQUIRED
  
 SHT P.1 SANITARY RISER DIAGRAM. THE COMBINATION DRAIN
 AND VENT SYSTEM, (FOR THE PEDICURE DRAINS), SHALL BE
 PROVIDED WITH A DRY VENT CONNECTED AT ANY POINT WITHIN
 THE SYSTEM. A DRY VENT CAN BE INSTALLED IN THE WALL TO
 THE EAST SIDE OF THE DRAINS TO COMPLY. (SEE RED LINE
 MARK UP ON PLANS). SECTION 912.2.2.
  
 SHT P.1 POTABLE WATER ISOMETRIC RISER DIAGRAM. WATER
 HAMMER ARRESTORS ARE REQUIRED AT THE WASH MACHINE WATER
 SUPPLIES. SECTION 604.9. ARRESTORS SHALL BE INSTALLED
 NEAR THE FIXTURES IN AN "EFFECTIVE RANGE" PER PDI-WH
 201.
  
  
  
  
 .

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-10-31 Cont ID  
Sent By mperson Date 2008-11-03 Time 16:34 Rev Time 1.30
Received By mperson Date 2008-10-31 Time 16:34 Sent To  
Notes
2008-10-31 16:58:56PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET A.1 PROPOSED GROUND FLOOR PLAN: PLEASE KNOW
 THAT FOR A BUSSINESS OCCUPANCY THE INDICATED NEW WATER
 COOLER IS UNACCEPTABLE. A DRINKING FOUNTAIN IS REQUIRED
 FOR A BUSSINESS OCCUPANCY PER FBC-2004 PLUMBING TABLE
 403.1 MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES.
 PLEASE KNOW THAT THE DRINKING FOUNTAIN IS REQUIRED TO
 BE ACCESSIBLE AND COMPLIANT WITH THE FOLLOWING FBC-2004
 CHAPTER 11, FLORIDA ACCESSIBILITY CODE SECTIONS.
  
 **SECTION 11-4.15 DRINKING FOUNTAINS AND WATER COOLERS
 (ELEVATION DETAIL REQUIRED WITH THE FOLLOWING
 INFORMATION)
  
 SECTION 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO
 OUTLET MAXIMUM.
  
 SECTION 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER
 FLOW IN TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL
 TO FRONT OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON
 AN ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WATER IS
 WITHIN 3" OF THE FRONT OF FOUNTAIN.
  
 SECTION 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR
 SIDE MOUNTED NEAR FRONT EDGE.
  
 SECTION 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X
 48" FLOOR SPACE.
  
 SECTION 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING
 FOUNTAIN IS PROVIDED ON A FLOOR, THERE SHALL BE A
 DRINKING FOUNTAIN WHICH IS ACCESSIBLE TO INDIVIDUALS
 WHO USE WHEELCHAIRS IN ACCORDANCE WITH SECTION 11-4.15
 AND ONE ACCESSIBLE TO THOSE WHO HAVE DIFFICULTY BENDING
 OR STOOPING.(THIS CAN BE ACCOMMODATED BY THE USE OF A
 HI-LO FOUNTAIN OR BY SUCH OTHER MEANS AS WOULD ACHIEVE
 THE REQUIRED ACCESSIBILITY FOR EACH GROUP ON EACH
 FLOOR).
  
 2. SHEET A.1 PROPOSED GROUND FLOOR PLAN: THE FLOOR IS
 INDICATING A NEW LAVATORY BEING INSTALLED IN A NEW
 LOCATION. PLEASE PROVIDE THE FOLLOWING REQUIRED
 INFORMATION PER THE FBC-2004 CHAPTER 11, FLORIDA
 ACCESSIBILITY CODE SECTIONS THAT ARE MISSING FROM SHEET
 A.4 DETAIL 2B, TOILET ROOM INTERIOR ELEVATIONS. PLEASE
 CLEARLY INDICATE THE FOLLOWING.
  
 SECTION 11-4.19.2 HEIGHT AND CLEARANCES. 29" A.F.F. TO
 THE BOTTOM OF THE APRON. (SEE FIGURE 31 ATTACHED TO
 THESE COMMENTS) KNEE CLEARANCE 8" MIN. DEPTH 17" MIN.
 TOE CLEARANCE 6" MAX OUT FROM WALL MIN 9" A.F.F.
  
 3. SHEET A.1 PROPOSED GROUND FLOOR PLAN INDICATES A
 VESSEL SINK, FAUCET & CABINET. PLEASE CLARIFY THE
 INTENT OF THIS SINK. IS THE SINK WORK RELATED? IF NOT
 THE FOLLOWING IS REQUIRED FOR THE SINK PER THE FBC-2004
 CHAPTER 11, FLORIDA ACCESSIBILITY CODE SECTIONS.
  
 **11-4.24 SINKS (ELEVATION DETAIL REQUIRED WITH THE
 FOLLOWING INFORMATION)
 11-4.24.2 HEIGHT. MAXIMUM 34" A.F.F. TO RIM OR
 COUNTER.
 11-4.24.3 KNEE CLEARANCE. MINIMUM 27" HIGH, 30" WIDE,
 AND 19" DEEP.
 11-4.24.4 DEPTH. MAXIMUM 6-1/2" DEEP.
 11-4.24.5 CLEAR FLOOR SPACE. 30" X 48" AND CLEAR FLOOR
 SPACE SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH THE
 SINK.
 11-4.24.6 EXPOSED PIPES AND SURFACES. INSULATE TO
 PROTECT AGAINST CONTACT.
 11-4.24.7 FAUCETS. LEVER-OPERATED, PUSH-TYPE, OR
 ELECTRONICALLY CONTROLLED ARE ACCEPTABLE DESIGNS.
  
 4. SHEET A.1 PROPOSED MEZZANINE PLAN IS INDICATING A
 NEW FIBERGLASS SHOWER UNIT. PLEASE KNOW THAT THE SHOWER
 SHALL BE COMPLIANT WITH THE FOLLOWING FBC-2004 CHAPTER
 11, FLORIDA ACCESSIBILITY CODE SECTIONS.
  
 **11-4.21 SHOWER STALLS (ELEVATION DETAIL REQUIRED WITH
 THE FOLLOWING INFORMATION)
 11-4.21.2 SIZE AND CLEARANCES. (SEE FIGURES 35(A) OR
 (B) AND FIGURES 57 (A) OR (B)
 11-4.21.3 SEAT. REQUIRED IN A 36" X 36" (17"-19" HIGH)
 11-4.21.4 GRAB BARS. REQUIRED (SEE FIGURE 37)
 11-4.21.5 CONTROLS. REQUIRED (SEE FIGURE 37)
 11-4.21.7 CURBS. 36" X 36" MAXIMUM 1/2" CURB (NO CURB
 REQUIRED IN MINIMUM 30" X 60" STALLS)
 11-4.22.3 CLEAR FLOOR SPACE. WHEELCHAIR TURNING SPACE
 SHALL BE 180-DEGREE WITH A MINIMUM 60" CLEAR FLOOR
 SPACE (PER 11-4.2.3)
  
 5. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3.
 PLUMBING (4)(6)(13): PLEASE SUBMIT A PLUMBING SANITARY
 ISOMETRIC RISER DIAGRAM INDICATING ALL WASTE, VENTS,
 TRAPS AND SIZES WITH CLEANOUT LOCATIONS OF PROPOSED
 FIXTURES.
  
 6. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3,
 PLUMBING (3)(5)(8)(10)(13): AN ISOMETRIC POTABLE WATER
 RISER DIAGRAM IS REQUIRED FOR THE PROPOSED WORK FOR
 BOTH THE HOT AND COLD WATER INDICATING THE PIPE SIZES,
 VALVE LOCATIONS, LOCATION OF THE WATER SUPPLY LINE WITH
 BACKFLOW PREVENTER **608, THERMAL EXPANSION CONTROL FOR
 THE WATER HEATER **607.3, AND LOCATION OF THE
 WATER-HAMMER ARRESTORS (IF APPLICABLE) WHERE QUICK
 CLOSING VALVES ARE UTILIZED (EXAMPLES=WASHING MACHINES,
 DISHWASHERS, ICE MAKERS) **604.9.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2008-11-04 Cont ID  
Sent By mflis Date 2008-11-04 Time 10:43 Rev Time 0.00
Received By mflis Date 2008-11-04 Time 10:43 Sent To  
Notes
2008-11-04 10:44:28ZONING REVIEW: PASSED
  
 ** INTERIOR RENOVATION FOR BOUTIQUE
  
 MATT FLIS - 822-1445


Account Summary | Usage Policy | Privacy Policy