Plan Review Details - Permit 08100447
Plan Review Stops For Permit 08100447
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2008-10-29 Cont ID  
Sent By rmcdouga Date 2008-10-29 Time 13:02 Rev Time 0.00
Received By rmcdouga Date 2008-10-29 Time 13:02 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-11-05 Cont ID  
Sent By btrobaug Date 2008-11-05 Time 15:19 Rev Time 0.00
Received By btrobaug Date 2008-11-05 Time 15:03 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-10-23 Cont ID  
Sent By btrobaug Date 2008-10-23 Time 10:58 Rev Time 0.00
Received By btrobaug Date 2008-10-23 Time 10:50 Sent To M
Notes
2008-10-23 10:58:30 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} PROVIDE A LOAD CALCULATION PER 220.83, INCLUDE ADDED
 LOADS, INDICATE THE SIZE OF THE EXISTING SERVICE
  
 NOTE: AN ELECTRICAL PERMIT IS REQUIRED PER 105.1 FBC AS
 AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-11-03 Cont ID  
Sent By adarroug Date 2008-11-03 Time 11:30 Rev Time 0.00
Received By adarroug Date 2008-11-03 Time 11:30 Sent To E
Notes
2008-11-03 11:30:25TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-10-31 Cont ID  
Sent By mperson Date 2008-10-31 Time 11:26 Rev Time 0.00
Received By mperson Date 2008-10-22 Time 11:39 Sent To PC
Notes
2008-10-22 11:40:24TO "SFR" "E"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2008-10-23 Cont ID  
Sent By tgordon Date 2008-10-23 Time 16:04 Rev Time 0.20
Received By tgordon Date 2008-10-23 Time 16:04 Sent To P
Notes
2008-10-23 16:05:32NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-11-05 Cont ID  
Sent By mperson Date 2008-11-05 Time 08:59 Rev Time 0.45
Received By mperson Date 2008-11-05 Time 08:59 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-10-31 Cont ID  
Sent By mperson Date 2008-10-31 Time 10:42 Rev Time 1.15
Received By mperson Date 2008-10-31 Time 10:42 Sent To I
Notes
2008-10-31 11:26:00PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET 3 OF 8 INDICATES THE PROPOSED STEAM UNIT BEING
 INSTALLED IN THE ATTIC. PLEASE KNOW THAT THE FOLLOWING
 ITEMS ARE REQUIRED FOR THE STEAM UNIT PER THE FBC-2004
 PLUMBING CODE SECTIONS AND MUST BE CLEARLY INDICATED ON
 THE RESUBMITTED PLANS.
  
 A} A PAN IS REQUIRED FOR THE STEAM UNIT. PER SECTION
 504.7 PAN REQUIRED.
  
 B} THE PAN SHALL NOT BE LESS THAN 1-1/2 INCHES DEEP AND
 SHALL BE OF SUFFICIENT SIZE AND SHAPE TO RECEIVE ALL
 DRIPPING OR CONDENSATE FROM UNIT. THE PAN SHALL BE BY
 AN INDIRECT WASTE PIPE HAVING A MINIMUM DIAMETER OF 3/4
 INCH. PER SECTION 504.7.1 PAN SIZE AND DRAIN.
  
 C} THE PAN DRAIN SHALL EXTEND FULL-SIZE AND TERMINATE
 OVER A SUITABLY LOCATED INDIRECT WASTE RECEPTOR OR
 FLOOR DRAIN OR EXTEND TO THE EXTERIOR OF THE BUILDING
 AND TERMINATE NOT LESS THAN 6 INCHES AND NOT MORE THAN
 24 INCHES ABOVE THE ADJACENT GROUND SURFACE. PER
 SECTION 504.7.2 PAN DRAIN TERMINATION.
  
 D} ALL STORAGE WATER HEATERS (STEAM UNITS) OPERATING
 ABOVE ATMOSPHERIC PRESSURE SHALL BE PROVIDED WITH AN
 APPROVED SELF CLOSING (LEVERED) PRESSURE RELIEF AND
 TEMPERATURE RELIEF VALVE OR COMBINATION THEREOF. PER
 SECTION 504.4 RELIEF VALVE.
  
 E} THE RELIEF VALVE SHALL DISCHARGE FULL SIZE TO A SAFE
 PLACE OF DISPOSAL SUCH AS THE FLOOR, STEAM UNIT PAN,
 OUTSIDE THE BUILDING OR AN INDIRECT WASTE RECEPTOR. THE
 DISCHAGE PIPE SHALL NOT HAVE ANY TRAPPED SECTIONS AND
 SHALL HAVE A VISIBLE AIR GAP. THE DISCHARGE SHALL BE
 INSTALLED IN A MANNER THAT DOES NOT CAUSE PERSONAL
 INJURY TO OCCUPANTS IN THE IMMEDIATE AREA OR STRUCTURAL
 DAMAGE TO THE BUILDING. PER SECTION 504.6.1 DISCHARGE.
  
 2. THE SUBMITTED AMERIC AK AND 3K SERIES INSTALLATION
 AND SERVICE INSTRUCTIONS ARE INCOMPLETE. IT APPEARS
 THAT ONLY THE ODD NUMBERED SHEETS WERE SUBMITTED.
 PLEASE PROVIDE TWO COMPLETE COPIES OF THE AMERIC AK AND
 3K SERIES INSTALLATION AND SERVICE INSTRUCTIONS ON THE
 RESUBMITTAL. PER FBC-2004 CHAPTER 1, (W.P.B. AS
 AMENDED) SECTION 106.1.2 ADDITIONAL DATA REQUIRED.
  
 END OF COMMENTS:
  
 *PLEASE CALL IF THERE ARE ANY QUESTIONS.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]