Plan Review Details - Permit 08100437
Plan Review Stops For Permit 08100437
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2009-01-24 Cont ID  
Sent By kstevens Date 2009-01-24 Time 19:53 Rev Time 0.00
Received By kstevens Date 2009-01-24 Time 19:53 Sent To  
Notes
2009-01-24 20:00:34 
  
  
 **********PASSED PROVISO**********
 FIELD INSPECTOR SHALL VERIFY THE BTU LOAD OF THE RANGE.
 INSTALLATION MANUAL DOES NOT INDICATE TOTAL BTU LOAD.
 -- 10,100 CU FT REQUIRED IN THE ROOM WITH THE DRYER AND
 WATER HEATER OR OPENING/OPENINGS PER SECTIONS 304.6.1
 OR 304.6.2 ARE REQUIRED. ALSO SEE SECTION 304.4 FOR
 MAKE UP AIR.
  
  
  
  
  
  
 .

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-10-21 Cont ID  
Sent By mperson Date 2008-10-21 Time 14:07 Rev Time 1.00
Received By mperson Date 2008-10-21 Time 14:07 Sent To I
Notes
2008-10-21 14:55:32GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE AND THE CITY OF
 WEST PALM BEACH GAS PERMIT APPLICATION REQUIREMENTS.
  
 1. PERMIT APPLICATION INDICATES THE FOLLOWING "GAS PER
 PLANS", HOWEVER THE PERMIT APPLICATION OR THE PLANS DO
 NOT INDICATE IF THE APPLIANCES ARE EXISTING OR PROPOSED
 NEW. PLEASE KNOW THAT THE PERMIT APPLICATION STATES
 "DESCRIBE PROJECT IN DETAIL (FAILURE TO DO SO MAY
 RESULT IN DELAYS)". PER FBC-2004 CHAPTER 1, (W.P.B. AS
 AMENDED) SECTION 105 PERMITS.
  
 2. THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS (GAS & PLUMBING) SHALL BE THE TOTAL
 REPLACEMENT COST EXCLUDING LAND VALUE. IF, IN THE
 OPINION OF THE BUILDING OFFICIAL, THE CLAIMED VALUATION
 OF BUILDING, ALTERATION, STRUCTURAL, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED. OUR VALUATION REFERENCES ARE ICC (BVD),
 MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES. PER
 (W.P.B AS AMENDED) SECTION 108.3 BUILDING PERMIT
  
 3. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS. PER
 FBC-2004 FUEL GAS SECTION 401.1 SCOPE.
  
 4. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EDH NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. PER
 FBC-2004 FUEL GAS SECTION 401.1 SCOPE.
  
 5. CLEARLY INDICATE THE TYPE OF GAS, (LP OR NATURAL) ON
 THE DRAWING. PER FBC-2004 FUEL GAS SECTION 401.1 SCOPE.
  
 6. CLEARLY INDICATE THE BTU LOAD OF EACH APPLIANCE AND
 THE TOTAL BTU LOAD ON THE SYSTEM. REFER TO THE FBC-2004
 FUEL GAS SECS. 401.8 THRU 402.6.1 AND TABLES 402.4(1)
 THRU 402.4(33)
  
 7. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2004 FUEL GAS APPENDIX A -
 USE OF CAPACITY TABLES A.3.1(4)
  
 8. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2004 FUEL GAS CODE SEC. 304
  
 9. CLEARLY INDICATE THE DELIVERY PRESSURE (PSI) PER
 FBC-2004 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5
 PSI OR 2 PSI. IF LP GAS SPECIFY 10 PSI OR 11.0 INCH WC.
  
 10. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE
 AND TERMINATION OF THE GAS VENTS PER FBC-2004 FUEL GAS
 CODE SEC. 502 THRU 505.
  
 11. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2004 FUEL GAS SEC. 402.2
  
 12. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP
 TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF
 THE TANK FROM THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOURCES OF IGNITION,
 OTHER CONTAINERS, BUILDINGS, AND THE LOCATION OF ANY
 BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANK
 PER NFPA 58, TABLE 3-2.2.2.
  
 13. CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS
 ABOVE OR BELOW GROUND, AND SHOW REQUIRED PROTECTION OF
 THE TANK AND APPURTENANCES PER NFPA 58. IF THE TANK IS
 BELOW GROUND THE CONTAINER SHALL BE SECURELY ANCHORED
 PER NFPA 58 SECTIONS 6.6.1, 6.6.16, AND 6.6.2.1.
  
 14. PLEASE CLARIFY WHY ELECTRICAL PLANS WERE SUBMITTED
 FOR A GAS PERMIT AS THEY ARE NOT NEEDED. PER FBC-2004
 CHAPTER 1, (W.P.B. AS AMENDED SECTION 106.1.2
 ADDITIONAL DATA.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-10-21 Cont ID  
Sent By mperson Date 2008-10-21 Time 14:56 Rev Time 0.00
Received By mperson Date 2008-10-20 Time 16:38 Sent To PC
Notes
2008-10-20 16:39:17TO $5000,00 OR LESS "P" BOX. *MRPERSON.