Plan Review Details - Permit 08100432
Plan Review Stops For Permit 08100432
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2008-11-12 Cont ID  
Sent By shill Date 2008-11-12 Time 09:49 Rev Time 0.00
Received By shill Date 2008-11-12 Time 09:49 Sent To Z
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-10-23 Cont ID  
Sent By btrobaug Date 2008-10-23 Time 14:03 Rev Time 0.00
Received By btrobaug Date 2008-10-23 Time 14:03 Sent To B
Notes
2008-10-23 14:03:43 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING
  
 AN ELECTRICAL PERMIT IS REQUIRED TO HOOK UP THE WATER
 HEATER TO ELECTRIC PER 105.1 FBC AS AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-11-19 Cont ID  
Sent By adarroug Date 2008-11-18 Time 09:06 Rev Time 0.00
Received By adarroug Date 2008-10-20 Time 16:57 Sent To  
Notes
2008-10-20 16:58:15TO "P" BOX. *MRPERSON.

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-10-22 Cont ID  
Sent By mperson Date 2008-10-22 Time 10:06 Rev Time 0.45
Received By mperson Date 2008-10-22 Time 10:06 Sent To E
Notes
2008-10-22 10:07:36PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET A.1.0 HAS INFORMATION MISSING FROM THE TITLE
 BLOCK. AT A MINIMUM THE ADDRESS OF THE PROJECT SHOULD
 BE ON THE PLAN SHEET. PER FBC-2004
 CHAPTER 1, (W.P.B. AS AMENDED) SECTION 106.1.1
 INFORMATION ON CONSTRUCTION DOCUMENTS. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE
 AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS,
 AS DETERMINED BY THE BUILDING OFFICIAL.
  
 2. SHEET A.1.0 HAS THE WRONG CODE CYCLE OF FBC-2004
 WITH 2006 SUPPLEMENT BEING INDICATED IN SEVERAL PLACES
 ON THE PLAN SHEET. THE CORRECT CODE CYCLE ON THE PLAN
 SHEET SHOULD BE FBC-2004 WITH 2007 SUPPLEMENTS. PER
 FBC-2004 CHAPTER 1, (W.P.B. AS AMENDED) SECTION 106.1.1
 INFORMATION ON CONSTRUCTIONDOCUMENTS.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 *PLEASE CALL IF THERE ARE ANY QUESTIONS.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2008-11-18 Cont ID  
Sent By adavila Date 2008-11-18 Time 17:39 Rev Time 0.00
Received By adavila Date 2008-11-18 Time 17:39 Sent To I
Notes
2008-11-18 17:40:14PER KELLY FREEMAN, PLANNER.
  