Plan Review Details - Permit 08100427
Plan Review Stops For Permit 08100427
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-01-23 Cont ID  
Sent By shill Date 2009-01-23 Time 15:42 Rev Time 0.00
Received By shill Date 2009-01-23 Time 15:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-01-15 Cont ID  
Sent By shill Date 2009-01-15 Time 15:32 Rev Time 0.00
Received By shill Date 2009-01-15 Time 15:32 Sent To  
Notes
2009-01-15 15:33:29****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. PLEASE PROVIDE THE VALUE FOR THIS JOB, INCLUDING
 EQUIPMENT.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-11-13 Cont ID  
Sent By shill Date 2008-11-13 Time 11:53 Rev Time 0.00
Received By shill Date 2008-11-13 Time 11:53 Sent To M
Notes
2008-11-13 14:57:30****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
  
  
 1. DECLARE AN OCCUPANCY CLASSIFICATION. PURPOSE OF THIS
 PUMP AND LINE IS NOT CLEAR.
  
 2. THE DRAWING IS LABELED BOTH CROSS SECTION AND PLAN
 VIEW, BUT SEEMS TO BE ONE DRAWING WHICH IS A
 COMBINATION OF THREE SEPARATE DETAILS. PLEASE PROVIDE
 THESE DETAILS WITH ENOUGH SEPARATION BETWEEN THEM SO
 THAT THEY ARE UNDERSTANDABLE; CROSS SECTIONS SHOULD
 HAVE A REFERENCE ON THE (FLOOR) PLAN TO SHOW HOW THEY
 ARE RELATED. SCOPE OF WORK NOT CLEAR.
  
 3. WHO WILL BE PERFORMING THE INSTALLATION OF AIR RUN
 AND HYDROGEN PUMP? HAVE THIS CONTRACTOR SIGN ON AS A
 SUBCONTRACTOR.
  
 4. SCOPE OF WORK NOT CLEAR. APPLICATION STATES "ADDING
 AN AIR RUN - HYDROGEN PUMP TO EXISTING SYSTEM". IS A
 NEW PUMP BEING INSTALLED? PROVIDE ANCHORING DETAIL TO
 SHOW HOW THIS WILL RESIST WIND LOADS, FBC1609.
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2008-10-23 Cont ID  
Sent By btrobaug Date 2008-10-23 Time 10:24 Rev Time 0.00
Received By btrobaug Date 2008-10-23 Time 10:22 Sent To FIRE
Notes
2008-10-23 10:24:06 
  
 PROVISO
  
 A LOW VOLTAGE PERMIT IS REQUIRED FOR THE MONITORING
 PUMP.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2008-11-04 Cont ID  
Sent By mcarsill Date 2008-11-04 Time 08:09 Rev Time 0.00
Received By mcarsill Date 2008-11-04 Time 08:08 Sent To  
Notes
2008-11-04 08:09:421. INSTALLATION SUBJECT TO FIELD INSPECTION AND
 APPROVAL.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-12-18 Cont ID  
Sent By adarroug Date 2008-12-18 Time 10:56 Rev Time 0.00
Received By adarroug Date 2008-12-18 Time 10:56 Sent To M
Notes
2008-12-18 10:57:06TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-11-10 Cont ID  
Sent By adarroug Date 2008-11-10 Time 15:46 Rev Time 0.00
Received By adarroug Date 2008-11-10 Time 15:46 Sent To B
Notes
2008-11-10 15:47:22TO "MISC" BOX#3

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-11-04 Cont ID  
Sent By adarroug Date 2008-11-04 Time 11:44 Rev Time 0.00
Received By adarroug Date 2008-11-04 Time 11:44 Sent To Z
Notes
2008-11-04 11:44:44TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-12-18 Cont ID  
Sent By adarroug Date 2008-11-22 Time 10:50 Rev Time 0.00
Received By adarroug Date 2008-10-21 Time 11:20 Sent To  
Notes
2008-10-21 11:20:38TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-01-10 Cont ID  
Sent By rregueir Date 2009-01-10 Time 09:40 Rev Time 0.00
Received By rregueir Date 2009-01-10 Time 09:40 Sent To B
Notes
2009-01-10 09:41:46NO SEPARATE MECHANICAL PERMIT NEEDED. FIRE INSPECTION
 REQUIRED PRIOR TO FINAL BUILDING INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-11-22 Cont ID  
Sent By rregueir Date 2008-11-22 Time 10:59 Rev Time 0.00
Received By rregueir Date 2008-11-22 Time 10:30 Sent To PC
Notes
2008-11-22 10:59:05REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. SCOPE OF WORK STATES "ADDING AIR RUN - HYDROGEN
 PUMP..." IS THERE AN AIR LINE OR HYDROGEN LINE BEING
 INSTALLED? SCOPE INDICATES AIR LINE BUT PLANS CALL FOR
 HYDROGEN LINE. PLANS DO NOT SHOW HYDROGEN PUMP, ONLY
 AIR PUMP AND AIR COMPRESOR. PLEASE CLARIFY SCOPE ON
 PERMIT DESCRIPTION AND ON PLANS.
  
 2. NO INFORMATION WAS PROVIDED REGARDING THE
 EQUIPMENT/APPLIANCES BEING INSTALLED. PROVIDE SUBMITTAL
 DATA FOR EACH PIECE OF EQUIPMENT/APPLIANCE BEING
 INSTALLED WITH LISTING INFORMATION. ALL APPLIANCES
 REGULATED BY THIS CODE SHALL BE LISTED AND LABELED IN
 ACCORDANCE WITH FBCM 301.4.
  
 3. IS THIS NEW EQUIPMENT BING INSTALLED OUTDOORS? NO
 INFORMATION WAS PROVIDED REGARDING WIND RESISTANCE.
 MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE
 EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO
 RESIST THE WIND PRESSURES ON THE EQUIPMENT AND THE
 SUPPORTS AS DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING PER FBCM 301.13. SEE FBCB 1609
 FOR WIND RESISTANCE REQUIREMENTS. ALSO, APPLIANCES
 INSTALLED IN OTHER THAN INDOOR LOCATIONS SHALL BE
 LISTED AND LABELED FOR OUTDOOR INSTALLATION IN
 ACCORDANCE WITH FBCM 303.6.
  
 4. IF AIR AND/OR HYDROGEN LINES ARE BEING INSTALLED,
 THIS WORK IS OUT OF THE SCOPE OF GC LICENSE. PROPERLY
 LICENSED CONTRACTORS SHALL SIGN ON TO PERMIT
 APPLICATION OR PROVIDE SEPARATE APPLICATION(S) PRIOR TO
 ISSUANCE IN ACCORDANCE WIT F.S. 489.105(3). SEPARATE
 ELECTICAL AND LOW VOLTAGE PERMITS ALSO REQUIRED FOR
 POWER AND CONTROL/MONITORING WIRING RELATED TO THIS
 WORK.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2008-11-10 Cont ID  
Sent By eschneid Date 2008-11-10 Time 14:54 Rev Time 0.00
Received By eschneid Date 2008-11-10 Time 14:53 Sent To I
Notes
***NONE***