Plan Review Details - Permit 08100397
Plan Review Stops For Permit 08100397
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-11-19 Cont ID  
Sent By mjacobs Date 2008-11-19 Time 13:18 Rev Time 0.00
Received By mjacobs Date 2008-11-19 Time 13:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-10-24 Cont ID  
Sent By mjacobs Date 2008-10-24 Time 08:57 Rev Time 0.00
Received By mjacobs Date 2008-10-24 Time 08:57 Sent To  
Notes
2008-10-24 08:57:51BUILDING PLAN REVIEW
 PERMIT: 08100397
 ADD:?
 CONT:
 TEL: (561)682-9500
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS. THIS INFORMATION
 SHALL BE INDICATED ON THE PLANS.
  
 4) THE PLANS NEED TO INDICATE THE USE AND OCCUPANCY PER
 CHAPTER 3, THE TYPE OF CONSTRUCTION PER CHAPTER 6 AND
 TABLE 601 AND THE HEIGHT OF THE BUILDING PER CHAPTER 5
 AND TABLE 503.
  
 5) 2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE. THE LEVEL OF ALTERATION SHALL BE INDICATED
 ON THE PLANS.
  
 6) THE ADDRESS ON THE APPLICATION AND THE PLANS DO NOT
 MATCH EACH OTHER. FOR RECORD PURPOSES THE ADDRESS ON
 THE APPLICATION NEEDS TO CORRESPOND WITH THE ADDRESS ON
 THE PLANS.106.1.3. CLARIFY
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-11-21 Cont ID  
Sent By btrobaug Date 2008-11-21 Time 16:10 Rev Time 0.00
Received By btrobaug Date 2008-11-14 Time 16:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-10-29 Cont ID  
Sent By btrobaug Date 2008-10-29 Time 17:07 Rev Time 0.00
Received By btrobaug Date 2008-10-29 Time 14:55 Sent To PC
Notes
2008-10-29 17:08:24 
  
  
 APPLICATION #08100397 ELECTRICAL PLAN REVIEW
 717 S OLIVE AVENUE 10/29/08
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE ADDRESS ON THE APPLICATION IS CORRECT BUT DOES
 NOT CORRELATE WITH THE ADDRESS ON THE PLANS.
  
 2} SEE THE DEFINITION OF "SMOKE DETECTORS" 11.8.2.1
 NFPA-72, CLARIFY IF USING DETECTORS OR ALARMS, TO AVOID
 CONFUSION IN THE FIELD. IF USING DETECTORS INDICATE THE
 LOCATIONS OF THE SOUNDING DEVICES.
  
 3} IT APPEARS THAT THE TUB IN THE MASTER BATH HAS BEEN
 REPLACED OR REFITTED WITH A RECIRCULATION PUMP.
 INDICATE COMPLIANCE WITH ARTICLE 680 VII.
  
 4} THE RECEPTACLE IN THE MASTER BATH LOCATED IN THE
 KNEE SPACE IS INDICATED AS NEW PER THE LEGEND, AND DOES
 NOT MEET THE SPACING REQUIREMENT OF 215.52(D).
  
 4} INDICATE THE TYPE OF LUMINAIRES AND THE WATTAGES OF
 SAME, BEING INSTALLED UNDER THIS PERMIT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-11-19 Cont ID  
Sent By mawillia Date 2008-11-19 Time 14:36 Rev Time 0.00
Received By mawillia Date 2008-11-19 Time 14:24 Sent To  
Notes
2008-11-19 14:36:32*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN SATISFIED; PLAN SHEET A1.03 STAMPED, INITIALED,
 AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-10-29 Cont ID  
Sent By mwennerg Date 2008-10-29 Time 11:11 Rev Time 0.00
Received By mwennerg Date 2008-10-29 Time 11:11 Sent To  
Notes
2008-10-29 11:20:34***DENIED***
  
 1) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003
 EDITION.
  
 2) PLEASE CORRELATE THE ADDRESS ON PLANS TO MATCH THE
 PERMIT APPLICATION.
  
 3) THE TERM SMOKE DETECTOR WOULD SUGGEST THAT THE
 DEVICES ARE TIED INTO THE BUILDING FIRE ALARM SYSTEM
 THAT WOULD INITIATE A GENERAL FIRE ALARM. DEVICES
 LOCATED IN THE LIVING UNITS THAT ARE RESPONSIVE TO
 SMOKE WOULD BE SMOKE ALARMS. PLEASE MAKE CORRECTION TO
 PLANS WHERE APPLICABLE.
  
 4) WILL WORK IMPACT THE FIRE SPRINKLER SYSTEM? SEPARATE
 SHOP DRAWINGS AND PERMITS MAY BE REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM REMODEL.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-11-13 Cont ID  
Sent By adarroug Date 2008-11-13 Time 11:47 Rev Time 0.00
Received By adarroug Date 2008-11-13 Time 11:47 Sent To  
Notes
2008-11-13 11:49:31TO "BOB"#15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-11-04 Cont ID  
Sent By btrobaug Date 2008-11-04 Time 07:14 Rev Time 0.00
Received By btrobaug Date 2008-10-20 Time 09:50 Sent To PC
Notes
2008-10-20 09:53:30TO "BOB"#10

Review Stop P PLUMBING
Rev No 2 Status N Date 2008-11-25 Cont ID  
Sent By kstevens Date 2008-11-25 Time 10:39 Rev Time 0.00
Received By kstevens Date 2008-11-25 Time 10:39 Sent To  
Notes
2008-11-25 10:39:39NO PLUMBING WORK INDICATED.

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-10-20 Cont ID  
Sent By mperson Date 2008-10-20 Time 13:28 Rev Time 1.00
Received By mperson Date 2008-10-20 Time 13:28 Sent To  
Notes
2008-10-20 13:57:20PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. PLEASE CLEARLY INDICATE THE BUILDING CLASSIFICATION
 ON THE PLANS.
 PER FBC BUILDING SECTION 302.1 GENERAL. STRUCTURES OR
 PORTIONS OF STRUCTURES SHALL BE CLASSIFIED WITH RESPECT
 TO OCCUPANCY IN ONE OR MORE OF THE GROUPS LISTED BELOW.
  
 A} ASSEMBLY (SEE SECTION 303): GROUPS A-1, A-2, A-3,
 AND A-5
  
 B} BUSSINESS (SEE SECTION 304): GROUP B
  
 C} EDUCATIONAL (SEE SECTION 305): GROUP E
  
 D} FACTORY AND INDUSTRIAL (SEE SECTION 306): GROUPS F-1
 AND F-2
  
 E} HIGH HAZARD (SEE SECTION 307) GROUPS H-1, H-2, H-3,
 H-4, AND H-5
  
 F} INSTITUTIONAL (SEE SECTION 308): GROUP I-1, I-2, AND
 I-3
  
 G} MERCANTILE (SEE SECTION 309): GROUP M
  
 H} RESIDENTIAL (SEE SECTION 310): GROUPS R-1, R-2, R-3
 AS APPLICABLE IN SECTION 101.2, AND R-4
  
 I} STORAGE (SEE SECTION 311): GROUPS S-1 AND S-2
  
 J} UTILITY AND MISCELLANEOUS (SEE SECTION 312): GROUP U
  
 K} DAY CARE (SEE SECTION 313): GROUP D
  
 *NOTE: OCCUPANCY APPEARS TO BE A R-2.
  
 2. CLEARLY INDICATE THE CODE CYCLE ON THE PLANS. PER
 CITY OF WPB AMENDMENTS TO CHAPTER 1, SECTION 106.5
 RETENTION OF CONSTRUCTION DOCUMENTS.
 THE CURRENT CODE CYCLE FOR THE PLANS IS "FBC-2004 WITH
 2007 REVISIONS".
  
 3. DECLARE THE LEVEL OF ALTERATION. PER FBC-2004
 EXISTING BUILDING CHAPTER 3.
  
 4. PLEASE CLARIFY WHY THERE IS A DIFFERENT ADDRESS ON
 THE SUBMITTED PLAN SHEETS (717 S. OLIVE AVE) THAN WHAT
 IS BEING INDICATED ON THE PERMIT APPLICATION (701 S.
 OLIVE AVE.). PLEASE CORRELATE PER FBC-2004 CHAPTER 1,
 (W.P.B. AS AMENDED) SECTION 106.1.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2008-10-22 Cont ID  
Sent By mflis Date 2008-10-22 Time 11:16 Rev Time 0.00
Received By mflis Date 2008-10-22 Time 11:16 Sent To  
Notes
2008-10-22 11:17:03ZONING REVIEW: NOT REQUIRED
  
 ** INTERIOR RENOVATIONS
  
 MATT FLIS - 822-1445


Account Summary | Usage Policy | Privacy Policy