| 2008-10-20 10:01:50 | GAS PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE AND THE CITY OF |
| | WEST PALM BEACH GAS PERMIT APPLICATION REQUIREMENTS. |
| | |
| | |
| | 1. THE VALUE ON THE PERMIT APPLICATION APPEARS LOW. THE |
| | VALUE ON THE PERMIT APPLICATION MUST INCLUDE THE TOTAL |
| | COST OF LABOR, MATERIALS AND DESIGN WHICH ALSO INCLUDES |
| | THE PRICE OF THE FIRE PIT. PLANS ARE INDICATING |
| | "APPLIANCE BY OTHERS", HOWEVER THERE IS NO INDICATION |
| | OF WHO OTHERS IS OR IF THE FIRE PIT HAS BEEN APPROVED |
| | ON ANOTHER PERMIT. PLEASE PROVIDE THIS REQUIRED |
| | INFORMATION OR INCREASE THE VALUE OF THE PERMIT. IF IT |
| | IS THE INTENT OF THIS PERMIT TO MAKE THE FINAL |
| | CONNECTIONS TO THE FIRE PIT THEN THE FIRE PITS COST |
| | SHALL BE INCLUDED. |
| | PER (W.P.B AS AMENDED) SECTION 108.3 BUILDING PERMIT |
| | VALUATION. IF, IN THE OPINION OF THE BUILDING OFFICIAL, |
| | THE CLAIMED VALUATION OF BUILDING, ALTERATION, |
| | STRUCTURAL, ELECTRICAL, GAS, MECHANICAL OR PLUMBING |
| | SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE |
| | APPLICATION, THE PERMIT SHALL BE DENIED. |
| | |
| | 2. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE 401.1 SCOPE. |
| | *NOTE: NOT ALL CUT SECTIONS OF PIPE HAVE CORRESPONDING |
| | LENGTHS. THE ONLY CORRESPONDING LENGTH BEING INDICATED |
| | ON THE ISOMETRIC IS 35' OF 3/4" PE FOR THE UNDERGROUND |
| | PIPING. IS THIS CORRESPONDING LENGTH FROM THE FIRST |
| | STAGE REGULATOR TO THE SECOND STAGE REGULATOR? WHAT ARE |
| | THE ABOVE GROUND CORRESPONDING LENGTHS TO THE CUT |
| | SECTIONS OF PIPE? PLEASE PROVIDE CORRESPONDING LENGTHS |
| | TO ALL CUT SECTIONS OF PIPE AND CLEARLY INDICATE THE |
| | LOCATION OF THE 1ST STAGE REGULATOR ON THE RESUBMITTAL. |
| | |
| | 3. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | PER FBC-2004 FUEL GAS SECTION 401.1 SCOPE. |
| | *NOTE: THE ONLY PIPING MATERIAL BEING INDICATED ON THE |
| | ISOMETRIS IS THE UNDERGROUND PE PIPING. WHAT IS THE |
| | ABOVE GROUND PIPING MATERIAL? CLEARLY INDICATE THIS ON |
| | THE RESUBMITTAL. |
| | |
| | 4. THE SUBMITTED GAS ISOMETRIC IS INDICATING THE 2ND |
| | STAGE REGULATOR AS BEING INSTALLED UNDERGROUND. PLEASE |
| | CLARIFY HOW ACCESS SHALL BE PROVIDED FOR THE REGULATOR |
| | AND HOW THE REGULATOR WILL BE PROTECTED FROM PHYSICAL |
| | DAMAGE IF ITS LOCATED UNDERGROUND. PER FC-2004 FUEL GAS |
| | SECTION 410.1 PRESSURE REGULATOR. HOW WILL THE |
| | REGULATOR VENT IF IT IS LOCATED UNDERGROUND? PRESSURE |
| | REGULATORS THAT REQUIRE A VENT SHALL HAVE AN |
| | INDIPENDENT VENT TO THE OUTSIDE OF THE BUILDING. THE |
| | VENT SHALL BE DESIGNED TO PREVENT THE ENTRY OF WATER OR |
| | FOREIGN OBJECTS. PER FBC-2004 FUEL GAS SECTION 410.3 |
| | VENTING OF REGULATORS. PLEASE CLARIFY THESE ISSUES ON |
| | THE RESUBMITTAL. |
| | |
| | 5. THE SUBMITTED MANUACTURER SHEET FOR THE FIRST AND |
| | SECOND STAGE REGULATORS DO NOT INDICATED A LISTING FROM |
| | A NATIONALLY RECOGNIZED TESTING LABORATORY SUCH AS CSA, |
| | AGA OR UL. PLEASE PROVIDE THIS REQUIRED INFORMATION ON |
| | THE RESUBMITTAL. PER FBC-2004 FUEL GAS SECTION 301.3 |
| | LISTED AND LABELED, STANDARDS NFPA 58. |
| | |
| | 6. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING |
| | DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE |
| | PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE |
| | ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER |
| | FBC-2004 CHAPTER 1, (W.P.B. AS AMENDED) SECTION |
| | *106.3.4.3. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |