Plan Review Details - Permit 08100386
Plan Review Stops For Permit 08100386
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-08-10 Cont ID  
Sent By rmcdouga Date 2009-08-10 Time 09:46 Rev Time 0.00
Received By rmcdouga Date 2009-08-10 Time 09:46 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-02-13 Cont ID  
Sent By rmcdouga Date 2009-02-13 Time 13:45 Rev Time 0.00
Received By rmcdouga Date 2009-02-13 Time 13:45 Sent To  
Notes
2009-02-13 13:45:332004 FBC W/2007 REVISIONS
 STRUCTURAL REPAIRS
  
 DENIED BY BUILDING
  
 1) SUBMIT TWO SETS OF DRAFTSMAN QUALITY PLANS DRAWN TO
 A MINIMUM 1/8" SCALE THAT CLEARLY DESCRIBE THE LOCATION
 AND SCOPE OF WORK TO BE DONE. SPECIFY THE DIMENSIONS,
 SPANS, SPACING ETC. OF THE STRUCTURAL FRAMING. FBC
 106.1.1* CITY AMENDMENTS
  
 2) ON THE PLANS, SPECIFY THE CONNECTORS THAT WILL BE
 USED TO ATTACH THE FRAMING MEMBERS TO PROVIDE A
 CONTINUOUS LOAD PATH TO TRANSFER ALL LOADS TO THE
 FOUNDATION AS REQUIRED BY FBC R301.1.
  
 3) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 CONNECTORS AS REQUIRED BY DCA RULE 9B-72.
  
 4) SUBMIT TWO COPIES OF A FLOOR PLAN INDICATING THE
 AREAS WERE THE PROPOSED WORK WILL BE DONE. FBC 106.1.1*
 CITY AMENDMENTS
  
 5) THE VALUE OF THE WORK ON THE APPLICATION APPEARS TO
 BE TOO LOW. THE VALUE IS TO INCLUDE THE COST OF LABOR,
 MATERIALS, OVERHEAD AND PROFIT AS WOULD BE CHARGED BY A
 CONTRACTOR. PLEASE ADJUST THE VALUE ACCORDINGLY. FBC
 108.3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-08-14 Cont ID  
Sent By btrobaug Date 2009-08-14 Time 12:57 Rev Time 0.00
Received By btrobaug Date 2009-08-14 Time 12:50 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2009-02-09 Cont ID  
Sent By btrobaug Date 2009-02-09 Time 14:56 Rev Time 0.00
Received By btrobaug Date 2009-02-09 Time 14:23 Sent To P
Notes
2009-02-09 14:55:19 
  
  
  
  
 APPLICATION #08100386 ELECTRICAL PLAN REVIEW
 1025 UPLAND ROAD 2/9/09
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
 THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THERE IS NO SCALE FOR THE ELECTRICAL PLAN AND THE
 ROOMS ARE NOT LABELED BUT IT APPEARS THE SPACING
 REQUIREMENTS OF 210.52 ARE NOT BEING MET. CORRECT THE
 ABOVE MENTIONED ISSUES.
  
 2} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS
 AMENDED A PERMIT SHALL NOT BE ISSUED UNTIL FEES
 AUTHORIZED UNDER SECTION 553.80, FLORIDA STATUTES, HAVE
 BEEN PAID. 108.1 FBC. ADJUST THE VALUE AT THE PERMIT
 CLERK???S DESK, AND PAY THE DIFFERENCE IN FEES PRIOR TO
 RESUBMITTING.
  
 3} INDICATE IF THE DEVICES ON THE PLAN ARE NEW OR
 EXISTING. 106.1.1.
  
 4} 408.4 CIRCUIT DIRECTORY OR CIRCUIT IDENTIFICATION,
 PROVIDE A PANEL SCHEDULE WITH WIRE SIZES AND
 OVERCURRENT PROTECTION RATINGS SO THAT COMPLIANCE WITH
 240 AND 310.16 MAY BE REVIEWED.
  
 5} INDICATE THE RATING OF THE EXISTING SERVICE. 215.5
 NEC.
  
 6} LOCATE THE PANEL ON THE PLAN.
  
 7} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A), 210.52(C), AND 210.8(A)(6) GFI.
  
 8} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE
 ALARMS SHALL BE INTERCONNECTED AND HARD WIRED. INDICATE
 INTERCONNECTION AND LOCATE THE ALARMS ON THE PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-08-06 Cont ID  
Sent By rmcdouga Date 2009-08-06 Time 16:14 Rev Time 0.00
Received By rmcdouga Date 2009-08-06 Time 16:14 Sent To  
Notes
2009-08-06 16:15:32TO R.MCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-02-17 Cont ID  
Sent By kstevens Date 2009-02-17 Time 17:42 Rev Time 0.00
Received By kstevens Date 2009-02-09 Time 10:36 Sent To  
Notes
2009-02-09 10:38:16TO "SFR" "E"

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-08-10 Cont ID  
Sent By rmcdouga Date 2009-08-10 Time 09:50 Rev Time 0.00
Received By rmcdouga Date 2009-08-10 Time 09:50 Sent To  
Notes
2009-08-10 09:51:10REPLACE FIXTURES IN SAME LOCATION.

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-02-17 Cont ID  
Sent By kstevens Date 2009-02-17 Time 17:36 Rev Time 0.00
Received By kstevens Date 2009-02-17 Time 17:36 Sent To  
Notes
2009-02-17 17:42:24DENIED
 REFERENCE:
 FBC-2004 CHAPTER 1
  
 1. APPLICATION SHOWS A PLUMBING PERMIT NUMBER WAS
 APPLIED FOR. NO PLUMBING PLANS WERE SUBMITTED OR
 INDICATED. PLEASE INDICATE THE EXTENT OF THE PLUMBING
 PLANS ON THE FLOOR PLAN AND IF MOVING OR ADDING
 FIXTURES, THEN A SANITARY RISER DIAGRAM WILL BE
 REQUIRED SHOWING ALL PIPE SIZES, TRAPS & VENTS. IF
 REPLACING COMMON HOUSEHOLD PLUMBING FIXTURES TO
 EXISTING SUPPLY LINES AND OUTLETS, (NOT INCLUDING WATER
 HEATERS), THEN A PERMIT IS NOT REQUIRED. PLEASE
 CLARIFY. SECTIONS 105.2, 106.1.1 & 106.3.5.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  