Plan Review Details - Permit 08100353
Plan Review Stops For Permit 08100353
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-02-06 Cont ID  
Sent By jgomez Date 2009-02-06 Time 15:55 Rev Time 0.00
Received By jgomez Date 2009-02-06 Time 14:14 Sent To M
Notes
2009-02-06 16:17:53RESIDENTIAL (R3) ADDITION, BUILDING REVIEW SECOND
 CHECKLIST.
 REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007
 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK UP.
  
 2- NEED TO BRING COPY OF PAID RECEIPT FOR PALM BEACH
 COUNTY IMPACT FEES (REPEAT COMMENT). NO COPY SUBMITTED
 AT THIS TIME. NEED COPY OF PAID RECEIPT AND PLANS WITH
 PALM BEACH COUNTY IMPACT FEES STAMP FOR RECORD KEEPING.
  
 3- ELEVATOR & STAIR WALL SECTION: CLEARLY SPECIFY
 FASTENING OF WALL TO SUPPORT ELEVATOR RAIL. "GLUE AND
 SCREW TO WALL FRAMING" ARE NOT ADEQUATE SPECIFICATIONS.
 NEED TO SPECIFY SCREWS SIZES AND SPACING. SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004 TO VERIFY COMPLIANCE WITH
 SEC. R301 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 4- ADDED HAND WRITTEN INFORMATION ON SIGNED AND SEALED
 DRAWINGS ARE NOT ALLOWED. ANY REVISIONS NEED TO BE DONE
 ON ORIGINAL DRAWINGS. REVISE ALL ORIGINAL DRAWINGS
 SHOWING ALL REVISIONS ADDRESSING THE COMMENTS AS
 REQUIRED AND RE-SUBMIT SIGNED AND SEALED COPIES AS
 REQUIRED BY CHAPTER 481 FLORIDA STATUTES AND SEC. 61G15
 FLORIDA ADMINISTRATIVE CODE.
  
 5- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) THERMA-TRU FIBERGLASS DOORS. FL-5262 SUBMITTED IS
 FOR 2007 CODE VERSION. CURRENT CODE VERSION IS 2004.
 ALS0: DOOR WITH GLAZING REQUIRES IMPACT PROTECTION.
 SPECIFY IS USING GLASS DOOR AND PROVIDE INFORMATION FOR
 IMPACT PROTECTION AS REQUIRED.
  
 B) SEALOFLEX WATERPROOFING. PROVIDE THE FOLLOWING
 INFORMATION FOR NOA 05-0901.04 SUBMITTED:
 (A) SELECT FROM PAGES 4 THRU 9 SPECIFIC ASSEMBLY TO BE
 INSTALLED.
  
 (B) PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL
 LIMITATION #7. THESE CALCULATIONS NEED TO BE SIGNED AND
 SEALED AS REQUIRED BY GENERAL LIMITATION #7 ON LAST
 PAGE OF NOA SUBMITTED. (NOTE: KEEP IN MIND EXPOSURE "C"
 WHEN DOING RAS 117 CALCULATIONS).
  
 (C) PROVIDE GARAGE DOORS PRODUCT APPROVAL FOR 2004 CODE
 VERSION. INFORMATION SUBMITTED IS FOR 2007 CODE
 VERSION. ALSO, PROVIDE COMPLETE PRODUCT APPROVAL
 PACKAGE, INCLUDING THE FLORIDA PRODUCT APPROVAL COVER
 PAGE.
  
 6- PLEASE, MAKE SURE ALL PRODUCT APPROVAL ARE REVIEWED
 AND APPROVED BY THE ARCHITECT OF RECORD PRIOR TO
 SUBMITTAL TO THIS OFFICE. SEC. 106.3.3 CITY AMENDMENTS
 TO FBC 2004.
  
 7- INFORMATION SUBMITTED FOR DRIVEWAYS AND DRIVEWAY
 APPROACH ARE DONE UNDER SEPARATE PERMITS. APPLY FOR
 THOSE PERMITS AS REQUIRED. CONTACT ZONING (561)822-1435
 AND ENGINEERING (561) 494-1040 FOR THEIR REQUIREMENTS.
  
 8- PROPERTY IS LOCATED ON FLOOD ZONE A5. ELEVATION
 CERTIFICATE WILL BE REQUIRED PRIOR TO GETTING THE
 CERTIFICATE OF OCCUPANCY (C.O.) SHOWING MINIMUM FINISH
 FLOOR ELEVATION OF 7.5'.
  
 9- OWES $966.54 FOR UPDATED VALUATION AND RADON FEES
 (REPEAT COMMENT).
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-10-31 Cont ID  
Sent By jgomez Date 2008-10-31 Time 16:51 Rev Time 0.00
Received By jgomez Date 2008-10-31 Time 16:50 Sent To PC
Notes
2008-10-31 16:57:58RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST.
 REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007
 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE SUBMITTED LATER AT TIME OF PERMIT
 PICK UP TO AVOID EXPIRATION OF IT.
  
 2- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD. (561)233-5120) TO VERIFY IF
 IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS AND COPY
 OF PAID RECEIPT IF FEES ARE DUE.
  
 3- PROVIDE COMPLETE FRAMING WALL SECTION THRU ELEVATOR
 AND STAIRWAY SHAFT. SPECIFY ALL FRAMING MEMBERS AND
 FASTENERS. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004 TO
 VERIFY COMPLIANCE WITH SEC. R301.1 AND R601.2 OF 2004
 FLORIDA RESIDENTIAL CODE.
 ALSO, PROVIDE COMPLETE FRAMING INFORMATION AND
 SPECIFICATIONS FOR SUPPORT OF ELEVATOR.
  
 4- PROVIDE SPECIFICATIONS FOR ROOF SHEATHING NAIL TYPE
 AND SPACING. INCLUDING NAILING AT ROOF ZONE #3 AS
 REQUIRED BY SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL
 CODE. (NOTE: MIN. 8D RING SHANK NAILS ARE REQUIRED AND
 4" O.C. NAILS ARE REQUIRED ON ROOF ZONE 3).
  
 5- PROVIDE COMPLETE SPECIFICATIONS FOR ELEVATOR TO BE
 INSTALLED.
  
 6- PROVIDE COMPLETE SPECIFICATIONS FOR ICYNENE
 INSULATION..
  
 7- PROVIDE PRODUCT APPROVAL (TWO COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) EXTERIOR SWING DOOR. INFORMATION SUBMITTED FOR THE
 MASONITE FIBERGLASS DOOR IS NOT AN APPROVED PRODUCT
 APPROVAL.
  
 B) CASEMENT WINDOW. NOA 05-1129.11 SUBMITTED EXPIRED ON
 MAY 22, 2008. NEED TO PROVIDE CURRENT ONE.
  
 C) UNDERLAYMENT WATERPROOFING MEMBRANE ON SECOND FLOOR
 DECK. PRODUCT APPROVAL TO SHOW INSTALLATION OF TILE AS
 SPECIFIED ON PLANS.
  
 D) HARDIE TRIM FOR STEEL COLUMNS. PROVIDE
 SPECIFICATIONS OF ATTACHMENT TO STEEL COLUMN.
  
 8- VALUE DECLARED IN THE PERMIT APPLICATION IS TOO LOW.
 SEC. 108.3 CITY AMENDMENTS TO FBC 2004. OWES $966.54
 FOR UPDATED VALUATION AND RADON FEES.
  
 9- ARCHITECT TO PROVIDE HIS LICENSE NUMBER ON THE TITLE
 BLOCK AS REQUIRED BY SEC. 61G1-16.004 OF FLORIDA
 ADMINISTRATIVE CODE AND CHAPTER 481 FLORIDA STATUTE.
  
 10- PLANS NEED TO PROVIDE SPECIFICATIONS FOR TYPE OF
 DRYWALL TO BE USED TO SEPARATE GARAGE FROM BEDROOM
 ABOVE AS REQUIRED BY SEC. R309.2 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 11- LIMITATION #9 ON PRODUCT APPROVAL FOR METAL ROOFING
 UNDERLAYMENT FL3455-R1 STATES THAT ROOF NEEDS TO HAVE
 PROPER VENTILATION. PLANS CALL FOR ICYNENE INSULATION
 AND NO ATTIC VENTILATION. SPECIFY HOW PROVIDING ATTIC
 VENTILATION TO ALLOW THE USE OF THIS UNDERLAYMENT.
  
 12- REVISE THE ENERGY CALCULATIONS:
 A) CONDITIONED FLOOR AREA DOESN'T MATCH CONDITIONED
 FLOOR AREA SPECIFIED ON PLANS.
  
 B) MISSING THE FLOOR CONCRETE SLAB ON ITEM #8.
  
 C) MISSING THE GARAGE ADJACENT WALLS ON ITEM #9.
  
 D) MISSING THE ADJACENT GARAGE CEILING AREA ON ITEM
 #10.
  
 E) UNDER ATTIC AREA IS INCORRECT. REVISE AS REQUIRED.
  
 F) COMPLETE ALL INFORMATION ON TOP OF FORM.
  
 13- SOIL TEST REPORT:
 A) NEED TO HAVE ENGINEER'S ORIGINAL SEAL AND SIGNATURE
 AS REQUIRED BY SEC. 61G15-23.002 OF FLORIDA
 ADMINISTRATIVE CODE AND CHAPTER 471 FLORIDA STATUTE.
  
 B) REPORT NEEDS TO HAVE ENGINEERING FIRM CERTIFICATE OF
 AUTHORIZATION NUMBER AS REQUIRED BY SEC.
 61G15-23.002(2) OF FLORIDA ADMINISTRATIVE CODE AND
 CHAPTER 471 FLORIDA STATUTE.
  
 14- SHEET A1: UPDATE DESIGN CRITERIA. CURRENT REVISIONS
 TO FBC 2004 ARE 2007 REVISIONS NOT 2006. REVISE AS
 REQUIRED.
  
 15- SHEET A2:
 A) SPECIFY FIREBLOCKING ON WALL SECTION AS REQUIRED BY
 SEC. R602.1.2 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 B) WALL SECTION: SPECIFY ALL FASTENERS FOR BEARING
 WALLS BY STAIRWAY. TOP AND BOTTOM.
 ALSO, SPECIFY HOW LONG ARE THE 1/2" ANCHOR BOLTS AT
 BOTTOM PLATE. SEC. R601.2 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 C) SPECIFY SLOPE FOR UPPER DECK.
  
 16- SHEET A3: WALL SECTION 1/3 SHOWS 6" ICYNENE
 INSULATION ON 2X6 WALL. 2X6 WALL HAS 5 1/2" ACTUAL
 THICKNESS. REVISE AS REQUIRED.
  
 17- SHEET A4:
 A) WALL SECTION 1/4: SPECIFY ALL WALL CONNECTORS TO
 VERIFY COMPLIANCE WITH SEC. R301.1 AND R601.2 OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 B) FLOOR FRAMING PLAN: SPECIFY ALL CONNECTORS AT THE
 ENDS OF ALL BEAMS (INCLUDING ONES SUPPORTED ON WOOD
 COLUMNS), GIRDER TRUSSES, FLOOR JOISTS, CANTILEVERED
 BALCONY JOISTS, ETC. TO VERIFY COMPLIANCE WITH SEC.
 R301.1 AND R601.2 OF 2004 FLORIDA RESIDENTIAL CODE.
 ***NOTE: CLEARLY SPECIFY SPECIFIC CONNECTORS.
 SPECIFYING "STRAPS" DOESN'T PROVIDE SPECIFIC
 INFORMATION TO VERIFY COMPLIANCE WITH PROPOSED STRAP
 INSTALLATION AND CALCULATED LOADS.
  
 C) SPECIFY FIREBLOCKING ON WALL SECTION 1/4 AS REQUIRED
 BY SEC. R602.1.2 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 18- SHEET A5:
 A) SPECIFY FIREBLOCKING IN ALL WALL SECTIONS AS
 REQUIRED BY SEC. R602.1.2 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 B) SPECIFY ALL FASTENERS IN WALL SECTIONS TO VERIFY
 COMPLIANCE WITH SEC. 301.1 AND R601.2 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 C) TOTAL LOAD FOR ROOF TRUSSES DON'T ADD UP. IT SHOULD
 BE 65PSF NOT 55PSF. REVISE AS REQUIRED.
  
 19- SHEET A6: SPECIFY ALL CONNECTORS IN WALL SECTION TO
 VERIFY COMPLIANCE WITH SEC. R301.1 AND R601.2 OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-01-06 Cont ID  
Sent By btrobaug Date 2009-01-06 Time 15:50 Rev Time 0.00
Received By btrobaug Date 2009-01-06 Time 15:28 Sent To P
Notes
2009-01-06 15:47:31 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 COMMENTS FROM LAST REVIEW :
  
 1} PANEL "A-1" ON SHEET "E1" IS LISTED AS MLO ON THE
 SCHEDULE AND MCB ON THE RISER . CORRELATE SAME.***THE
 DESIGNER OF RECORD MUST MAKE THIS CORRECTION ON THE
 DRAWING. THE ELECTRICAL CONTRACTOR CANNOT REVISE THE
 DESIGNERS DRAWINGS. FS481.
  
 2} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1) AND
 210.52(A)(2). 2005 NEC. SEE EXISTING STUDY AND LIBRARY.
  
 3} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI
 PROTECTED PER 210.8(A) (1), NEW POWDER ROOM.
  
 4} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), THESE CIRCUITS ARE NOT LISTED IN ANY
 OF THE PANELS.
  
 5} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN
 THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE
 INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS
 DESIGNED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-10-24 Cont ID  
Sent By btrobaug Date 2008-10-24 Time 13:55 Rev Time 0.00
Received By btrobaug Date 2008-10-24 Time 11:31 Sent To M
Notes
2008-10-24 13:54:18 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} PANEL "A-1" ON SHEET "E1" IS LISTED AS MLO ON THE
 SCHEDULE AND MCB ON THE RISER . CORRELATE SAME.
  
 2} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1) AND
 210.52(A)(2). 2005 NEC. SEE EXISTING STUDY AND LIBRARY.
  
 3} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI
 PROTECTED PER 210.8(A) (1), NEW POWDER ROOM.
  
 4} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), THESE CIRCUITS ARE NOT LISTED IN ANY
 OF THE PANELS.
  
 5} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN
 THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE
 INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS
 DESIGNED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-12-29 Cont ID  
Sent By adarroug Date 2008-12-29 Time 12:58 Rev Time 0.00
Received By adarroug Date 2008-12-29 Time 12:58 Sent To Z
Notes
2008-12-29 12:59:22TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-10-23 Cont ID  
Sent By adarroug Date 2008-10-23 Time 09:24 Rev Time 0.00
Received By adarroug Date 2008-10-23 Time 09:24 Sent To E
Notes
2008-10-23 09:24:40TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-10-31 Cont ID  
Sent By jgomez Date 2008-10-31 Time 16:58 Rev Time 0.00
Received By jgomez Date 2008-10-16 Time 14:30 Sent To  
Notes
2008-10-16 14:30:33TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2009-02-09 Cont ID  
Sent By hmoser Date 2009-02-09 Time 13:27 Rev Time 0.00
Received By hmoser Date 2009-02-09 Time 13:27 Sent To  
Notes
2009-02-09 13:32:11ICYNENE INSULATION ON THE WALLS PAGE A-3 AND A-4 OF THE
 PLANS DO NOT MATCH .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-10-28 Cont ID  
Sent By tgordon Date 2008-10-28 Time 10:49 Rev Time 0.45
Received By tgordon Date 2008-10-28 Time 10:49 Sent To P
Notes
2008-10-28 11:02:33PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) PLEASE SHOW ON MECHANICAL PLAN THE LOCATION OF THE
 CONDENSER UNIT, PER 2004 FBC/R M1307.3.
  
 2) A.H.U. MODEL NUMBER FV4BNF030 LISTED ON THE A/C
 EQUIPMENT SCHEDULE COULD NOT BE FOUND ON THE ARI
 DIRECTORY WEB-SITE, PLEASE CORRECT OR SUBMIT AN ARI
 CERTIFICATE, SEE 2004 FBC 13-607.1.ABC.3.1.1.
  
 3) PLEASE SUBMIT ALL OF THE COOLING LOAD CALCULATIONS,
 ONLY ONE PAGE OF THE CALCULATIONS WAS SUBMITTED, PER
 2004 FBC 13-607.1.ABC.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2009-02-03 Cont ID  
Sent By kstevens Date 2009-02-03 Time 08:50 Rev Time 0.00
Received By kstevens Date 2009-02-03 Time 08:50 Sent To M
Notes
2009-02-03 09:58:52PLUMBING PLAN REVIEW:
 DENIED
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 ****FROM PREVIOUS REVIEW:
  
 1. CLEARLY INDICATE THE CORRECT CODE CYCLE ON THE
 PLANS.PER CITY OF WPB AMENDMENTS TO CHAPTER 1, SECTION
 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS AND
 SECTION 106.5 RETENTION OF CONSTRUCTION DOCUMENTS. THE
 CURRENT CODE CYCLE FOR THE PLANS IS 'FBC-2004 WITH 2007
 REVISIONS".
 ****NO WRITTEN RESPONSE, BUT HAND WRITTEN CHANGES TO A
 SIGNED, SEALED SET OF PLANS IS NOT APPROVED. SECTION
 106.1.3.
  
 2. SHEET A1 SANITARY PLUMBING RISER: PLEASE CORRECT/ADD
 THE FOLLOWING PER THE FBC-2004 PLUMBING CODE SECTIONS.
  
 A} A CLEANOUT IS REQUIRED AT THE BASE OF THE SOIL STACK
 ON THE 1ST FLOOR FOR THE PROPOSED 2ND FLOOR PLUMBING.
 PER SECTION 708.3.4 BASE OF STACK.
 ****NO WRITTEN RESPONSE, BUT HAND DRAWN CHANGES TO A
 SIGNED, SEALED SET OF PLANS IS NOT APPROVED. SECTION
 106.1.3.
  
 B} THE HORIZONTAL DRY VENT AT THE BIDET IS NOT ALLOWED.
 PER SECTION 905.3 VENT CONNECTIONS TO DRAINAGE SYSTEMS.
 ****NO WRITTEN RESPONSE, BUT HAND DRAWN CHANGES TO A
 SIGNED, SEALED SET OF PLANS IS NOT APPROVED. SECTION
 106.1.3.
  
 3. SHEET A4 SECOND FLOOR PLAN IS INDICATING A STEAM
 SHOWER. PLEASE PROVIDE THE FOLLOWING INFORMATION
 COMPLIANT TO THE FBC-2004 PLUMBING CODE SECTIONS.
  
 A} CLEARLY INDICATE THE LOCATION OF THE STEAM SHOWER
 UNIT ON THE FLOOR PLAN. PER SECTION 106.1 SCOPE.
 ****NO WRITTEN RESPONSE, BUT HAND WRITTEN CHANGES TO A
 SIGNED, SEALED SET OF PLANS IS NOT APPROVED. SECTION
 106.1.3.
  
 B} CLEARLY INDICATE THE POINT OF DISCHARGE OF THE
 TEMPERATURE AND PRESSURE RELIEF VALVE REQUIRED FOR THE
 STEAM UNIT. PER SECTION 504.6.1 DISCHARGE.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 C} PROVIDE TWO COPIES OF MANUFACTURER'S INSTALLATION
 INSTRUCTIONS FOR THE STEAM UNIT. MANUFACTURE SHEETS
 SHALL CLEARLY INDICATE THE MAKE, MODEL NUMBER, AND A
 LISTING FROM A NATIONALLY RECOGNIZED TESTING LABORATORY
 SUCH AS UL, ETL, ARS, CSA OR AGA. PER FBC-2004 CHAPTER
 1, (W.P.B. AS AMINDED) SECTION 106.1.2 ADDITIONAL DATA
 REQUIRED.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 **********NEW COMMENT**********
  
 1B. WHITE OUT IS NOT APPROVED ON SIGNED & SEALED PLANS.
 SECTION 106.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ****NO RESPONSE TO THE TRANSMITTAL LETTER SUBMITTED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-10-30 Cont ID  
Sent By mperson Date 2008-10-30 Time 15:53 Rev Time 1.00
Received By mperson Date 2008-10-30 Time 15:53 Sent To B
Notes
2008-10-30 16:19:04PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. CLEARLY INDICATE THE CORRECT CODE CYCLE ON THE
 PLANS. PER CITY OF WPB AMENDMENTS TO CHAPTER 1, SECTION
 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS AND
 SECTION 106.5 RETENTION OF CONSTRUCTION DOCUMENTS. THE
 CURRENT CODE CYCLE FOR THE PLANS IS "FBC-2004 WITH 2007
 REVISIONS".
  
 2. SHEET A1 SANITARY PLUMBING RISER: PLEASE CORRECT/ADD
 THE FOLLOWING PER THE FBC-2004 PLUMBING CODE SECTIONS.
  
 A} A CLEANOUT IS REQUIRED AT THE BASE OF THE SOIL STACK
 ON THE 1ST FLOOR FOR THE PROPOSED 2ND FLOOR PLUMBING.
 PER SECTION 708.3.4 BASE OF STACK.
  
 B} THE HORIZONTAL DRY VENT AT THE BIDET IS NOT ALLOWED.
 PER SECTION 905.3 VENT CONNECTIONS TO DRAINAGE SYSTEMS.
  
 3. SHEET A4 SECOND FLOOR PLAN IS INDICATING A STEAM
 SHOWER. PLEASE PROVIDE THE FOLLOWING INFORMATION
 COMPLIANT TO THE FBC-2004 PLUMBING CODE SECTIONS.
  
 A} CLEARLY INDICATE THE LOCATION OF THE STEAM SHOWER
 UNIT ON THE FLOOR PLAN. PER SECTION 601.1 SCOPE.
  
 B} CLEARLY INDICATE THE POINT OF DISCHARGE OF THE
 TEMPERATURE AND PRESSURE RELIEF VALVE REQUIRED FOR THE
 STEAM UNIT. PER SECTION 504.6.1 DISCHARGE.
  
 C} PROVIDE TWO COPIES OF MANUFACTURER'S INSTALLATION
 INSTRUCTIONS FOR THE STEAM UNIT. MANUFACTURE SHEETS
 SHALL CLEARLY INDICATE THE MAKE, MODEL NUMBER, AND A
 LSTING FROM A NATIONALLY RECOGNIZED TESTING LABORATORY
 SUCH AS UL, ETL, ARS, CSA, AGA. PER FBC-2004 CHAPTER 1,
 (W.P.B. AS AMENDED) SECTION 106.1.2 ADDITIONAL DATA
 REQUIRED.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 *PLEASE CALL IF THERE ARE ANY QUESTIONS.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2008-12-31 Cont ID  
Sent By mcruz Date 2008-12-31 Time 09:55 Rev Time 0.00
Received By mcruz Date 2008-12-31 Time 08:15 Sent To Z
Notes
2008-12-31 08:26:06PLANNING AND ZONING DEPT: ***ZONING FAILED - 1ST
 RESUB***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. AS THE VALUE OF THE PROPOSED RENOVATIONS INCREASED
 FROM $80,000 FROM THE PREVIOUS SUBMITTAL TO $173,349 IN
 THE CURRENT RESUBMITTAL THE FOLLOWING PROVISION
 APPLIES.
  
 PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), SECTION 94-441(C)(2)
 OF: AS THE VALUE OF THE PROPOSED WORK EXCEEDS 50% OF
 THE STRUCTURE'S VALUE (LISTED AS "IMPROVEMENT VALUE"
 WITH THE P.B.C. PROPERTY APPRAISER'S OFFICE),
 LANDSCAPING SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR.
  
 PLEASE SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN
 SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF
 THE ZLDR.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2008-10-22 Cont ID  
Sent By mcruz Date 2008-10-22 Time 12:10 Rev Time 0.00
Received By mcruz Date 2008-10-22 Time 12:00 Sent To I
Notes
2008-10-22 12:10:00***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. THE SITE PLAN INDICATES A NEW WALKWAY, DRIVEWAY AND
 CONCRETE APRON WILL BE CONSTRUCTED. PLEASE INDICATE
 SQUARE FOOTAGE OF ALL IMPERMEABLE SURFACES (EXISTING
 AND PROPOSED) LOCATED WITHIN THE FRONT YARD (FROM FRONT
 PROPERTY LINE TO THE FRONT BUILDING FACADE). PURSUANT
 TO THE CITY OF WEST PALM BEACH ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), SECTION 94-482:
 REQUIRED OFF-STREET PARKING SPACES FOR LESS THAN FOUR
 RESIDENTIAL DWELLING UNITS SHALL BE LOCATED ON THE
 PROPERTY ON WHICH THE UNITS ARE CONSTRUCTED. REQUIRED
 PARKING MAY BE LOCATED IN A FRONT YARD; HOWEVER, THE
 LESSER OF 1,000 SQUARE FEET OR 75 PERCENT OF THE FRONT
 YARD AREA MUST BE LANDSCAPED. PARKING AREAS LOCATED IN
 THE FRONT YARD SHALL BE SURFACED WITH A SMOOTH,
 NONDUSTING SURFACE IN COMPLIANCE WITH SUBSECTION
 33-485(E). IT SHALL BE A VIOLATION OF THIS CHAPTER TO
 PARK ON ANY UNPAVED AREAS AS DESCRIBED IN THIS ARTICLE.
  
 IMPORTANT - VERIFY WITH ENGINEERING SERVICES
 (561.494.1040) IF A RIGHT-OF-WAY PERMIT WILL BE
 REQUIRED FOR THE PROPOSED WORK ON THE DRIVEWAY APRON.
 **DO NOT RESUBMIT WITHOUT THEIR WRITTEN
 VERIFICATION/APPROVAL.**
  
 3. INDICATE SETBACK DIMENSIONS FROM PROPOSED OR
 RELOCATED A/C EQUIPMENT TO ALL PROPERTY LINES. AS PER
 THE ZLDR, SECTION 94-305(B)(4): MECHANICAL EQUIPMENT
 MAY NOT PROJECT MORE THAN 4 FEET INTO A REQUIRED
 SETBACK.
  
 4. INDICATE IF ANY TREES WILL BE REMOVED AS A RESULT OF
 THE PROPOSED PROJECT. IF YES, A TREE ALTERATION/REMOVAL
 PERMIT WILL BE REQUIRED. CONTACT ROBERT KUSSNER, CITY
 LANDSCAPE PLANNER, AT (561) 822-1462 FOR THE
 APPLICATION.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  