Plan Review Details - Permit 08100299
Plan Review Stops For Permit 08100299
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2008-11-06 Cont ID  
Sent By jnguyen Date 2008-11-06 Time 11:17 Rev Time 0.00
Received By jnguyen Date 2008-10-31 Time 17:19 Sent To  
Notes
2008-11-03 11:51:1411/03/2008 - JAMES & I HAVE TAKEN A LOOK AT THE AREA OF
 ALTERATIONS ON THE SITE PLANS. THE SITE PLAN LISTED
 1721 OKEECHOBEE RD ON IT, BUT WE WERE NOT SURE IF THIS
 ADDRESS WAS VALID (AS RESEARCH AT THE USPS SITE,
 INDICATED THAT THE ADDRESS WAS CURRENTLY NOT IN
 SERVICE). ALTHOUGH PCN# 74434329190010000 LISTS A
 NUMERICAL ADDRESS RANGE FROM 1701 TO 1743 OKEECHOBEE RD
 FOR THE UNITS ATTACHED TO THIS BUILDING, 1721 DOES NOT
 YET EXIST IN OUR GIS DATABASE (CURRENTLY, WE HAVE THE
 FOLLOWING: 1701, 1707, 1711, 1715, 1719, 1723, 1727,
 1731, 1735, 1739 & 1743). DESPITE THE FACT THAT IT DID
 NOT APPEAR IN THE GIS DATABASE, THERE WAS ALREADY AN
 EXISTING RECORD OF 1721 OKEECHOBEE RD AS A UNIT IN
 COMMUNITYPLUS UNDER THIS ABOVE MENTIONED PCN. WE ARE IN
 THE PROCESS OF TRYING TO DETERMINE IF THE SITE PLANS:
 A) CORRECTLY REFERENCES AN EXISTING 1721 ADDRESS THAT
 IS NOT IN OUR DATABASE (AND IS EXPLICITLY LISTED ON THE
 OUTSIDE OF THE BUILDING), B) REFERENCES AN INCORRECT
 UNIT (INSTEAD POSSIBLY EXISTING 1715 TO 1723) OR C) IF
 A NEW ADDRESS NEEDS TO BE ISSUED AS 1721. I HAVE CALLED
 BABU OF ABTECH ENGINEERING, INC. TO DETERMINE WHERE
 THEY GOT 1721 FROM & IF IT ACTUALLY PHYSICALLY EXISTS
 AS A NUMERICAL LABEL SOMEWHERE ON THE BUILDING. HE TOLD
 ME THAT HE WAS NOT SURE, AND ALSO SAID THAT HE BELIEVED
 THAT THE AREA BEING ALTERED CONSISTED OF THREE UNITS
 (BUT WAS NOT EXACTLY SURE WHICH THREE NUMERICAL
 ADDRESSES). I GAVE HIM MY CONTACT INFORMATION & HE SAID
 THAT HE WOULD GIVE ME A CALL BACK TO CONFIRM MY ADDRESS
 INQUIRIES. I ALSO CALLED SOME OF THE LOCAL BUSINESSES
 OUT THERE AT THAT BUILDING STRUCTURE TO SEE IF 1721 IS
 IN EXISTENCE (LEFT MESSAGES FOR THEM TO CALL ME BACK
 TOO). UNTIL I HEAR BACK FROM ONE OF MY CONTACTS WITH AN
 INFORMED RESPONSE, I WILL NOT CHANGE THE STATUS TO PASS
 IN THE MEANTIME AS I WAIT. 11/04/2008 - I CONTACTED DON
 TORRIERO OF NATIONAL RECYCLING SERVICES, INC., WHO HAD
 A BUSINESS LICENSE FROM 08/12/2008 THAT LISTED 1721
 OKEECHOBEE RD AS ITS ADDRESS IN COMMUNITYPLUS. DON
 E-MAILED ME BACK & SAID THAT HE "BELIEVED" 1727
 OKEECHOBEE RD WAS ACTUALLY HIS OFFICIAL BUSINESS
 ADDRESS, AND THAT HE SAW LABELS OF 1719 TO 1727 ON THE
 BUILDING. HE CALLED ME BACK TO CLARIFY THAT 1721 IS
 ACTUALLY LABELED ON THE BACK DOOR. BASICALLY, HE SAID
 THAT THEY TOOK ALL OF THEIR UNITS & MADE THEM INTO ONE.
 I BELIEVE THE AREA OF ALTERATION ON THE SITE PLANS
 CONSISTS OF 1721, 1723 & 1727 OKEECHOBEE RD, BUT STILL
 DO NOT WANT TO ISSUE A THUMBS UP UNTIL I HEAR BACK FROM
 BABU ON THIS MATTER. 11/05/2008 - I ISSUED A NEW
 ADDRESS POINT FOR 1721 OKEECHOBEE RD & INFORMED ALL
 INTERESTED PARTIES THRU A NOTICE VIA E-MAIL. I ALSO
 CALLED BABU TO HOPEFULLY GET THE EXACT UNITS DESCRIBED
 IN THE PLANS. HOWEVER, MY ATTEMPT WAS UNSUCCESSFUL, SO
 I LEFT HIM A MESSAGE TO PLEASE CONTACT ME ASAP.
 11/06/2008 - I WAS FINALLY ABLE TO GET IN TOUCH WITH
 BABU & HE TOLD ME THAT THE SITE PLANS ADDRESS WOULD BE
 CHANGED TO THE OFFICIAL BUSINESS ADDRESS OF THE
 NATIONAL RECYCLING SERVICES, INC. (1727 OKEECHOBEE RD).
 THE AREA OF ALTERATION CONSISTS OF 1721, 1723 & 1727
 OKEECHOBEE RD. THIS PERMIT SHOULD BE ATTACHED TO UNIT
 0007 - 1727 OKEECHOBEE RD OF PCN# 74434329190010000 IN
 COMMUNITYPLUS SINCE THIS IS THE MAIN ADDRESS OF THE
 NATIONAL RECYCLING SERVICES, INC.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-11-24 Cont ID  
Sent By jwitmer Date 2008-11-24 Time 15:29 Rev Time 1.33
Received By jwitmer Date 2008-11-24 Time 15:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-10-24 Cont ID  
Sent By jwitmer Date 2008-10-24 Time 13:21 Rev Time 2.22
Received By jwitmer Date 2008-10-24 Time 13:16 Sent To  
Notes
2008-10-24 13:37:01BUILDING PLAN REVIEW
 PERMIT: 08100299
 ADD: 1701 OKEECHOBEE RD
 CONT: ELITE CONSTRUCTION INC
 TEL: (561)786-286-1409
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1C) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS. PLEASE
 UPDATE SHEET S-1 BECAUSE THIS WILL GREATLY EFFECT THIS
 REVIEW OF THE PLANS.
  
 2) SHEET S-1 INDICATES THE SCOPE OF WORK WAS DESIGNED
 TO THE 2004FBC WITH 2006 SUPPLEMENTS. THE 2007
 SUPPLEMENTS WILL EFFECT THE TYPE OF ZONE THE BUILDING
 IS LOCATED WITHIN AND THUS SO THE ASSOCIATED PRESSURES.
 PLEASE REVIEW 1609.4(3) EXPOSURE C. UNDER THE 2007
 SUPPLEMENTS THE 1500 FT CLEAR HAS BEEN REDUCED TO 600
 FEET WHEN WIND TRAVELS UNDISTURBED FOR 600 FT IN ANY
 QUADRANT.
 PLEASE UP DATE PLANS AND PRESSURES.
  
 3) COVER SHEET A-1 IS REFRENCING BUILDING TYPES UNDER
 THE STANDARD BUILDING CODE, PLEASE UPDATE THE PLANS TO
 REFERENCE THE BUILDING TYPE UNDER THE 2004 FBC, FOR
 INSTANCE 2001 SBC BUILDING TYPE IV 1 HR PROTECTED IS
 CURRENTLY CONSIDERED A TYPE II-A UNDER THE 2004 FBC
 PLEASE UPDATE REFERENCE, FIGURE 600 2004 FBC CODE
 COMMENTARY.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-12-12 Cont ID  
Sent By dpalmer Date 2008-12-12 Time 12:06 Rev Time 0.00
Received By dpalmer Date 2008-12-12 Time 12:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-12-01 Cont ID  
Sent By dpalmer Date 2008-12-01 Time 09:16 Rev Time 0.00
Received By dpalmer Date 2008-12-01 Time 09:16 Sent To  
Notes
2008-12-01 09:17:07 
 ** FAILED 2ND REVIEW **
  
 SOME ITEMS FROM PREVIOUS REVIEW ARE STILL IN NEED OF
 ADDRESSING.
  
  
  
 1) NOTE: PLEASE SEE RISER AND PLANS STILL DO NOT
 COORDINATE WITH THE ADDRESS OF THIS PROJECT FOR THIS
 TENANT.
 THE RISER DIAGRAM FOR EXAMPLE STILL INDICATES
 ELECTRICAL TO BE IN SPACE 1719 AND 1723 WHEN THE
 APPLIED LOCATION IS 1727 OKEECHOBEE RD.
 IN FACT THE RISER DOES NOT SHOW IN NOTES OR IN RISER
 ANY ELECTRICAL WHICH ACTUALLY HAS 1727 AS THE LOCATION.
 PLEASE COMPLETE THE RISER WITH ALL ELECTRICAL WHICH
 WILL BE LOCATED IN THIS NEW SPACE OF 1727. THIS
 INCLUDES ALL OTHER EXISTING ELECTRICAL SYSTEMS WHICH
 WILL NO LONGER BE A PART OF ANY OTHER TENANT SPACE.
 PLEASE SEE PLANS SUCH AS THE EXISTING PANELS IN 1719
 AND 1723 WHICH WILL NOW BE PART OF 1727.
 PLEASE COMPLETE RISER WITH ALL ELECTRICAL.
 PLEASE BE SURE TO LABEL ALL TENANT DISCONNECTS. RISER
 SHOWS WHAT WOULD APPEAR TO BE ONE NEW AND ONE EXISTING
 FED FROM NEW METER HOWEVER THIS IS NOT THE CASE. THE
 OTHER ELECTRICAL SYSTEMS IN THE SAME TENANT SPACE WOULD
 ALL BE PART OF TENANT AND WOULD REQUIRED DISCONNECTING
 MEANS TO BE LABELED.
 230.2E., 230.70,230.71,230.76,230.79, 215.5 ETC
 FBC 106.1.1, 106.3.5.1.2 FOR ADDITIONAL INFORMATION,
 CLARITY OF PLANS AND COORDINATION.
  
 ** THE NEED OF COORDINATION OF THIS EQUIPMENT IS VITAL
 FOR SAFETY OF THE OCCUPANTS AS WELL AS ANY OTHER
 PERSONNEL. IN THE EVEN OF AN EMERGENCY AND FIRE
 DEPARTMENT PERSONNEL NEEDED TO SHUT DOWN POWER TO SPACE
 1727, THE DISCONNECTS AS SHOWN ON RISER AS SHOWN WOULD
 NOT BE LABELED AS NEEDED. IN FACT SOME WOULD SHOW 1723,
 AND 1719 COULD BE MISTAKEN FOR ANOTHER TENANT.
 THIS IS A LIFE SAFETY HAZARD AND NEEDS TO BE ADDRESSED.
  
 2) NOTE: THE VALUE FOR THE SCOPE OF WORK WAS INCREASED
 ON PERMIT APPLICATION AND BALANCE OF $721.50 WILL BE
 DUE BEFORE PERMIT ISSUANCE.
  
 3) NOTE: THE NEW TRANSFORMER DOES NOT SHOW ANY
 GROUNDING ATTACHMENT LOCATION PER 250.50,250.20,250.30
 ETC.
 PREVIOUS REVIEW:
  
 4) NOTE: PLEASE SUBMIT THE MANUFACTURE SPECS/CUT SHEETS
 FOR NEW EQUIPMENT, CONTROL PANEL. PLEASE BE SURE
 LISTING FROM A NRTL IS LOCATED ON EQUIPMENT SHEETS.
 110.3,90.7.
  
  
  
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-10-31 Cont ID  
Sent By dpalmer Date 2008-10-31 Time 14:47 Rev Time 0.00
Received By dpalmer Date 2008-10-31 Time 14:47 Sent To  
Notes
2008-10-31 14:47:49 
  
  
  
 ** DENIED REVIEW **
  
 1) NOTE: PROJECT INFORMATION HAS BEEN FORWARDED TO THE
 ADDRESSING REVIEW TO CORRECT ADDRESS DISCREPANCIES. THE
 APPLIED LOCATION IS 1701 OLD OKEECHOBEE. THE *OLD* IS
 NOT AN ACCURATE LOCATION AND THE ADDRESS IS *OKEECHOBEE
 RD*. THIS OFFICE IS WELL AWARE OF THE STREET SIGNS
 WHICH MAY CONTAIN THE WORDING OF *OLD* HOWEVER
 OKEECHOBEE RD IS THE LEGAL ADDRESS. ONCE THE CORRECT
 ADDRESS AND UNIT HAS BEEN DETERMINED PLEASE ADJUST
 TITLE BLOCKS ON PLANS ACCORDINGLY.
 FBC 106.5
 FAC 61G1-16.004, 61G15-23.002
  
 2) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE LISTED
 ON PLANS AS WELL AS ON ELECTRICAL PLANS. SOME CODES
 REFERENCE ON PLANS ARE NO LONGER ADOPTED BY THE STATE
 OF FLORIDA AND HAVE NOT BEEN FOR SEVERAL YEARS. PLEASE
 SEE COVER SHEET FOR EXAMPLE WHICH STATES THE *STANDARD
 BUILDING CODE*. SBC. THE FOLLOWING SHALL BE LISTED AT A
 MINIMUM FOR THIS REVIEWER AND FOR THIS TRADE.
  
 2004 FBC W/ 2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 3) NOTE: THE APPLIED VALUE FOR COMPLETE SCOPE OF WORK
 SHALL INCLUDE ALL LABOR, MATERIALS, DESIGN COST,
 EQUIPMENT ETC EVEN IF ANY OF THESE ITEMS ARE OWNER
 SUPPLIED. THE APPLIED TOTAL VALUE OF $19K IS LOW FOR
 SCOPE OF WORK, EQUIPMENT ETC AS SHOWN ON PLANS.
 FBC 108.3
  
 4) NOTE: PLEASE SUBMIT MANUFACTURE SPECS/CUT SHEETS FOR
 NEW PROPOSED EQUIPMENT. MUST CONTAIN A LISTING FROM A
 NRTL. (NATIONALLY RECOGNIZED TESTING LABORATORY).
 110.3,90.7
  
 5) NOTE: ELECTRICAL PLAN SHEET E-1 MENTIONS A NEW METER
 AND MAIN. HOWEVER BY THE RISER THIS IS NOT A NEW MAIN
 AND IS IN FACT A TENANT MEANS OF DISCONNECT. THIS IS
 NOT A MAIN FOR THE SERVICE FEEDING TENANTS. PLEASE
 ADJUST DESIGNATIONS AND LABELING OF EQUIPMENT.
 230.2E
 THIS IS ALL ONE TENANT SPACE YET THE RISER MENTIONS A
 NEW METER AND MAIN FOR TENANT SUITE/UNIT 1723. A NEW
 MAIN FOR THE SAME TENANT IS NOT GRANTED AT THIS TIME.
 NEED TO PROVIDE LOAD ON EXISTING MAIN WITH NEW LOAD
 ADDED IN WHICH NEW 400 TENANT MAIN IS BEING ADDED.
 220.87
 PLEASE BE SURE TO SHOW ANY CONTINUOUS LOADS AND LARGEST
 MOTOR LOADS AT 125%. 215.3,230.42 ETC
 RISER SHOWS ALL EXISTING AND NEW TENANT MAINS AS
 SEPARATE SUITES OR UNIT HOWEVER BASED ON THE PLANS
 SUBMITTED THIS IS NOW GOING TO BE ONE TENANT SPACE.
  
 6) NOTE: PLEASE SEE 250.110,250.24, 250.6, 250.122 ETC.
 THE RISER IS MISSING THE EQUIPMENT GROUNDING CONDUCTOR
 AFTER THE FIRST MEANS OF SERVICE DISCONNECT.
 PLEASE ALSO KNOW ANY METERING EQUIPMENT AFTER THE FIRST
 MEANS OF SERVICE EQUIPMENT DISCONNECT REQUIRES A
 FLOATING NEUTRAL IN METER.
  
 7) NOTE: PLEASE SEE RISER IS MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM PANEL HVE TO THE TRANSFORMER.
 250.20,250.30,250.110,250.122 ETC
  
 8) NOTE: PLEASE SEE THE TRANSFORMER NEEDS TO SHOW THE
 ATTACHMENT LOCATION PER 250.50,250.30,250.20.
  
 9) NOTE: PLEASE SEE THE ADDRESS ON TITLE BLOCKS DO NOT
 MATCH THE ON-LINE WEBSITE FROM DBPR. PLEASE ADJUST.
 FAC 61G15-23.002
  
 10) NOTE: ** PLEASE SEE THE COLOR CODING SHALL MATCH
 EXISTING IN THE BUILD FOR 277/480V SYSTEMS. THE NOTES
 ON E-3 NEED TO BE ADJUSTED TO READ BROWN, PURPLE, AND
 YELLOW. ORANGE IS THE COLOR BY THE NEC WHICH IS SET
 ASIDE FOR DELTA HIGH LEG SYSTEMS. THIS IS NOT SUCH A
 SYSTEM.
 PLEASE REVISE TO MATCH EXISTING.
 90.4
 * CALL FOR QUESTIONS
  
  
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-12-12 Cont ID  
Sent By mwennerg Date 2008-12-12 Time 14:30 Rev Time 0.00
Received By mwennerg Date 2008-12-12 Time 14:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-12-03 Cont ID  
Sent By mawillia Date 2008-12-03 Time 11:09 Rev Time 0.00
Received By mawillia Date 2008-12-03 Time 10:24 Sent To  
Notes
2008-12-03 10:57:56*****UNSAT*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN SATISFIED; HOWEVER, THE PLANS WILL BE FIRE-STAMPED
 (APPROVED) WHEN THE FOLLOWING NEW COMMENTS (BASED ON
 NEW INFORMATION) HAVE BEEN ADDRESSED:
  
  
 1. ON THE APPROPIATE EXTERIOR ELEVATION (SHEET A-3)
 WHICH FRONTS OKEECHOBEE ROAD, DISPLAY THE NUMERICAL
 ADDRESS FOR THIS BUILDING. AS PER WEST PALM BEACH CODE,
 THE NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND NO
 LESS THAN 1" IN WIDTH/STROKE CONTRASTING TO THE
 BACKGROUND OF THE STRUCTURE.
  
 2. ON SHEET E-1, REMOVE/DELETE REFERENCES TO EXISTING
 SPACE # 1723 & EXISTING SPACE # 1719.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-804-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-10-31 Cont ID  
Sent By mwennerg Date 2008-10-31 Time 15:10 Rev Time 0.00
Received By mwennerg Date 2008-10-31 Time 15:10 Sent To  
Notes
2008-10-31 15:28:00***DENIED***
  
 1) IN ADDITION TO APPLICABLE BUILDING CODES, LIFE
 SAFETY SHALL COMPLY WITH NFPA 101, 2003.
  
 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 3) PLEASE SHOW LOCATIONS OF ALL NEW AND EXISTING
 ILLUMINATED EXITS SIGNS AND EMERGENCY LIGHTING
 FACILITIES.
  
 4) PLEASE CORRELATE ADDRESS INFORMATION ON PLANS AND
 PERMIT APPLICATION. PLANS INDICATE '1721' AND DRAWINGS
 SHOW 1719 AND 1723?
  
 5) RAMP SHALL COMPLY WITH 101, SEC. 7.2.5. HANDRAILS
 REQUIRED ON BOTH SIDES OF RAMP.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-12-08 Cont ID  
Sent By adarroug Date 2008-12-08 Time 09:13 Rev Time 0.00
Received By adarroug Date 2008-12-08 Time 09:13 Sent To  
Notes
2008-12-08 09:13:26TO "COMM" BD#5

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-11-12 Cont ID  
Sent By adarroug Date 2008-11-12 Time 11:20 Rev Time 0.00
Received By adarroug Date 2008-11-12 Time 11:20 Sent To  
Notes
2008-11-12 11:24:08TO "COMM" BD#20

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-10-31 Cont ID  
Sent By mwennerg Date 2008-10-31 Time 15:31 Rev Time 0.00
Received By mwennerg Date 2008-10-15 Time 09:42 Sent To  
Notes
2008-10-16 16:13:42TO "COMM" BD#41
2008-10-15 09:42:36WAITING FOR "COMM" BD

Review Stop Z ZONING
Rev No 2 Status P Date 2008-11-21 Cont ID  
Sent By kdfreema Date 2008-11-21 Time 11:05 Rev Time 0.00
Received By kdfreema Date 2008-11-21 Time 11:05 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2008-10-21 Cont ID  
Sent By kdfreema Date 2008-10-21 Time 15:51 Rev Time 0.00
Received By kdfreema Date 2008-10-21 Time 15:51 Sent To  
Notes
2008-10-21 16:24:53***FAILED***
  
 A MINOR PLANNED DEVELOPMENT AMENDMENT MUST BE
 SUBMITTED, AND APPROVED, SHOWING THE EXTENT OF THE
 OUTDOOR IMPROVEMENTS (IE SCALE, FENCE, AND NEW RAMP).
 BEFORE ZONING CAN APPROVE THIS PERMIT.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT
 [email protected] OR AT 561-822-1435 WITH QUESTIONS.