Plan Review Details - Permit 08100299
| Plan Review Stops For Permit 08100299 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
P |
Date |
2008-11-06 |
|
|
Cont ID |
|
| Sent By |
jnguyen |
Date |
2008-11-06 |
Time |
11:17 |
Rev Time |
0.00 |
| Received By |
jnguyen |
Date |
2008-10-31 |
Time |
17:19 |
Sent To |
|
|
| Notes |
| 2008-11-03 11:51:14 | 11/03/2008 - JAMES & I HAVE TAKEN A LOOK AT THE AREA OF | | | ALTERATIONS ON THE SITE PLANS. THE SITE PLAN LISTED | | | 1721 OKEECHOBEE RD ON IT, BUT WE WERE NOT SURE IF THIS | | | ADDRESS WAS VALID (AS RESEARCH AT THE USPS SITE, | | | INDICATED THAT THE ADDRESS WAS CURRENTLY NOT IN | | | SERVICE). ALTHOUGH PCN# 74434329190010000 LISTS A | | | NUMERICAL ADDRESS RANGE FROM 1701 TO 1743 OKEECHOBEE RD | | | FOR THE UNITS ATTACHED TO THIS BUILDING, 1721 DOES NOT | | | YET EXIST IN OUR GIS DATABASE (CURRENTLY, WE HAVE THE | | | FOLLOWING: 1701, 1707, 1711, 1715, 1719, 1723, 1727, | | | 1731, 1735, 1739 & 1743). DESPITE THE FACT THAT IT DID | | | NOT APPEAR IN THE GIS DATABASE, THERE WAS ALREADY AN | | | EXISTING RECORD OF 1721 OKEECHOBEE RD AS A UNIT IN | | | COMMUNITYPLUS UNDER THIS ABOVE MENTIONED PCN. WE ARE IN | | | THE PROCESS OF TRYING TO DETERMINE IF THE SITE PLANS: | | | A) CORRECTLY REFERENCES AN EXISTING 1721 ADDRESS THAT | | | IS NOT IN OUR DATABASE (AND IS EXPLICITLY LISTED ON THE | | | OUTSIDE OF THE BUILDING), B) REFERENCES AN INCORRECT | | | UNIT (INSTEAD POSSIBLY EXISTING 1715 TO 1723) OR C) IF | | | A NEW ADDRESS NEEDS TO BE ISSUED AS 1721. I HAVE CALLED | | | BABU OF ABTECH ENGINEERING, INC. TO DETERMINE WHERE | | | THEY GOT 1721 FROM & IF IT ACTUALLY PHYSICALLY EXISTS | | | AS A NUMERICAL LABEL SOMEWHERE ON THE BUILDING. HE TOLD | | | ME THAT HE WAS NOT SURE, AND ALSO SAID THAT HE BELIEVED | | | THAT THE AREA BEING ALTERED CONSISTED OF THREE UNITS | | | (BUT WAS NOT EXACTLY SURE WHICH THREE NUMERICAL | | | ADDRESSES). I GAVE HIM MY CONTACT INFORMATION & HE SAID | | | THAT HE WOULD GIVE ME A CALL BACK TO CONFIRM MY ADDRESS | | | INQUIRIES. I ALSO CALLED SOME OF THE LOCAL BUSINESSES | | | OUT THERE AT THAT BUILDING STRUCTURE TO SEE IF 1721 IS | | | IN EXISTENCE (LEFT MESSAGES FOR THEM TO CALL ME BACK | | | TOO). UNTIL I HEAR BACK FROM ONE OF MY CONTACTS WITH AN | | | INFORMED RESPONSE, I WILL NOT CHANGE THE STATUS TO PASS | | | IN THE MEANTIME AS I WAIT. 11/04/2008 - I CONTACTED DON | | | TORRIERO OF NATIONAL RECYCLING SERVICES, INC., WHO HAD | | | A BUSINESS LICENSE FROM 08/12/2008 THAT LISTED 1721 | | | OKEECHOBEE RD AS ITS ADDRESS IN COMMUNITYPLUS. DON | | | E-MAILED ME BACK & SAID THAT HE "BELIEVED" 1727 | | | OKEECHOBEE RD WAS ACTUALLY HIS OFFICIAL BUSINESS | | | ADDRESS, AND THAT HE SAW LABELS OF 1719 TO 1727 ON THE | | | BUILDING. HE CALLED ME BACK TO CLARIFY THAT 1721 IS | | | ACTUALLY LABELED ON THE BACK DOOR. BASICALLY, HE SAID | | | THAT THEY TOOK ALL OF THEIR UNITS & MADE THEM INTO ONE. | | | I BELIEVE THE AREA OF ALTERATION ON THE SITE PLANS | | | CONSISTS OF 1721, 1723 & 1727 OKEECHOBEE RD, BUT STILL | | | DO NOT WANT TO ISSUE A THUMBS UP UNTIL I HEAR BACK FROM | | | BABU ON THIS MATTER. 11/05/2008 - I ISSUED A NEW | | | ADDRESS POINT FOR 1721 OKEECHOBEE RD & INFORMED ALL | | | INTERESTED PARTIES THRU A NOTICE VIA E-MAIL. I ALSO | | | CALLED BABU TO HOPEFULLY GET THE EXACT UNITS DESCRIBED | | | IN THE PLANS. HOWEVER, MY ATTEMPT WAS UNSUCCESSFUL, SO | | | I LEFT HIM A MESSAGE TO PLEASE CONTACT ME ASAP. | | | 11/06/2008 - I WAS FINALLY ABLE TO GET IN TOUCH WITH | | | BABU & HE TOLD ME THAT THE SITE PLANS ADDRESS WOULD BE | | | CHANGED TO THE OFFICIAL BUSINESS ADDRESS OF THE | | | NATIONAL RECYCLING SERVICES, INC. (1727 OKEECHOBEE RD). | | | THE AREA OF ALTERATION CONSISTS OF 1721, 1723 & 1727 | | | OKEECHOBEE RD. THIS PERMIT SHOULD BE ATTACHED TO UNIT | | | 0007 - 1727 OKEECHOBEE RD OF PCN# 74434329190010000 IN | | | COMMUNITYPLUS SINCE THIS IS THE MAIN ADDRESS OF THE | | | NATIONAL RECYCLING SERVICES, INC. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2008-11-24 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-11-24 |
Time |
15:29 |
Rev Time |
1.33 |
| Received By |
jwitmer |
Date |
2008-11-24 |
Time |
15:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-10-24 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-10-24 |
Time |
13:21 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2008-10-24 |
Time |
13:16 |
Sent To |
|
|
| Notes |
| 2008-10-24 13:37:01 | BUILDING PLAN REVIEW | | | PERMIT: 08100299 | | | ADD: 1701 OKEECHOBEE RD | | | CONT: ELITE CONSTRUCTION INC | | | TEL: (561)786-286-1409 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW | | | ACTION: DENIED | | | | | | 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE | | | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | 1B) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT, | | | TO BE FILED WITH THE CLERK OF THE COURT. NOTE: | | | 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF | | | COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS | | | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & | | | VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF | | | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST | | | INSPECTION. | | | | | | 1C) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST | | | TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO | | | THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS. PLEASE | | | UPDATE SHEET S-1 BECAUSE THIS WILL GREATLY EFFECT THIS | | | REVIEW OF THE PLANS. | | | | | | 2) SHEET S-1 INDICATES THE SCOPE OF WORK WAS DESIGNED | | | TO THE 2004FBC WITH 2006 SUPPLEMENTS. THE 2007 | | | SUPPLEMENTS WILL EFFECT THE TYPE OF ZONE THE BUILDING | | | IS LOCATED WITHIN AND THUS SO THE ASSOCIATED PRESSURES. | | | PLEASE REVIEW 1609.4(3) EXPOSURE C. UNDER THE 2007 | | | SUPPLEMENTS THE 1500 FT CLEAR HAS BEEN REDUCED TO 600 | | | FEET WHEN WIND TRAVELS UNDISTURBED FOR 600 FT IN ANY | | | QUADRANT. | | | PLEASE UP DATE PLANS AND PRESSURES. | | | | | | 3) COVER SHEET A-1 IS REFRENCING BUILDING TYPES UNDER | | | THE STANDARD BUILDING CODE, PLEASE UPDATE THE PLANS TO | | | REFERENCE THE BUILDING TYPE UNDER THE 2004 FBC, FOR | | | INSTANCE 2001 SBC BUILDING TYPE IV 1 HR PROTECTED IS | | | CURRENTLY CONSIDERED A TYPE II-A UNDER THE 2004 FBC | | | PLEASE UPDATE REFERENCE, FIGURE 600 2004 FBC CODE | | | COMMENTARY. | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2008-12-12 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-12-12 |
Time |
12:06 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-12-12 |
Time |
12:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2008-12-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-12-01 |
Time |
09:16 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-12-01 |
Time |
09:16 |
Sent To |
|
|
| Notes |
| 2008-12-01 09:17:07 | | | | ** FAILED 2ND REVIEW ** | | | | | | SOME ITEMS FROM PREVIOUS REVIEW ARE STILL IN NEED OF | | | ADDRESSING. | | | | | | | | | | | | 1) NOTE: PLEASE SEE RISER AND PLANS STILL DO NOT | | | COORDINATE WITH THE ADDRESS OF THIS PROJECT FOR THIS | | | TENANT. | | | THE RISER DIAGRAM FOR EXAMPLE STILL INDICATES | | | ELECTRICAL TO BE IN SPACE 1719 AND 1723 WHEN THE | | | APPLIED LOCATION IS 1727 OKEECHOBEE RD. | | | IN FACT THE RISER DOES NOT SHOW IN NOTES OR IN RISER | | | ANY ELECTRICAL WHICH ACTUALLY HAS 1727 AS THE LOCATION. | | | PLEASE COMPLETE THE RISER WITH ALL ELECTRICAL WHICH | | | WILL BE LOCATED IN THIS NEW SPACE OF 1727. THIS | | | INCLUDES ALL OTHER EXISTING ELECTRICAL SYSTEMS WHICH | | | WILL NO LONGER BE A PART OF ANY OTHER TENANT SPACE. | | | PLEASE SEE PLANS SUCH AS THE EXISTING PANELS IN 1719 | | | AND 1723 WHICH WILL NOW BE PART OF 1727. | | | PLEASE COMPLETE RISER WITH ALL ELECTRICAL. | | | PLEASE BE SURE TO LABEL ALL TENANT DISCONNECTS. RISER | | | SHOWS WHAT WOULD APPEAR TO BE ONE NEW AND ONE EXISTING | | | FED FROM NEW METER HOWEVER THIS IS NOT THE CASE. THE | | | OTHER ELECTRICAL SYSTEMS IN THE SAME TENANT SPACE WOULD | | | ALL BE PART OF TENANT AND WOULD REQUIRED DISCONNECTING | | | MEANS TO BE LABELED. | | | 230.2E., 230.70,230.71,230.76,230.79, 215.5 ETC | | | FBC 106.1.1, 106.3.5.1.2 FOR ADDITIONAL INFORMATION, | | | CLARITY OF PLANS AND COORDINATION. | | | | | | ** THE NEED OF COORDINATION OF THIS EQUIPMENT IS VITAL | | | FOR SAFETY OF THE OCCUPANTS AS WELL AS ANY OTHER | | | PERSONNEL. IN THE EVEN OF AN EMERGENCY AND FIRE | | | DEPARTMENT PERSONNEL NEEDED TO SHUT DOWN POWER TO SPACE | | | 1727, THE DISCONNECTS AS SHOWN ON RISER AS SHOWN WOULD | | | NOT BE LABELED AS NEEDED. IN FACT SOME WOULD SHOW 1723, | | | AND 1719 COULD BE MISTAKEN FOR ANOTHER TENANT. | | | THIS IS A LIFE SAFETY HAZARD AND NEEDS TO BE ADDRESSED. | | | | | | 2) NOTE: THE VALUE FOR THE SCOPE OF WORK WAS INCREASED | | | ON PERMIT APPLICATION AND BALANCE OF $721.50 WILL BE | | | DUE BEFORE PERMIT ISSUANCE. | | | | | | 3) NOTE: THE NEW TRANSFORMER DOES NOT SHOW ANY | | | GROUNDING ATTACHMENT LOCATION PER 250.50,250.20,250.30 | | | ETC. | | | PREVIOUS REVIEW: | | | | | | 4) NOTE: PLEASE SUBMIT THE MANUFACTURE SPECS/CUT SHEETS | | | FOR NEW EQUIPMENT, CONTROL PANEL. PLEASE BE SURE | | | LISTING FROM A NRTL IS LOCATED ON EQUIPMENT SHEETS. | | | 110.3,90.7. | | | | | | | | | | | | | | | | | | | | | | | | | | | **IMPORTANT** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED | | | INTO TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2008-10-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-10-31 |
Time |
14:47 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-10-31 |
Time |
14:47 |
Sent To |
|
|
| Notes |
| 2008-10-31 14:47:49 | | | | | | | | | | | | | ** DENIED REVIEW ** | | | | | | 1) NOTE: PROJECT INFORMATION HAS BEEN FORWARDED TO THE | | | ADDRESSING REVIEW TO CORRECT ADDRESS DISCREPANCIES. THE | | | APPLIED LOCATION IS 1701 OLD OKEECHOBEE. THE *OLD* IS | | | NOT AN ACCURATE LOCATION AND THE ADDRESS IS *OKEECHOBEE | | | RD*. THIS OFFICE IS WELL AWARE OF THE STREET SIGNS | | | WHICH MAY CONTAIN THE WORDING OF *OLD* HOWEVER | | | OKEECHOBEE RD IS THE LEGAL ADDRESS. ONCE THE CORRECT | | | ADDRESS AND UNIT HAS BEEN DETERMINED PLEASE ADJUST | | | TITLE BLOCKS ON PLANS ACCORDINGLY. | | | FBC 106.5 | | | FAC 61G1-16.004, 61G15-23.002 | | | | | | 2) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE LISTED | | | ON PLANS AS WELL AS ON ELECTRICAL PLANS. SOME CODES | | | REFERENCE ON PLANS ARE NO LONGER ADOPTED BY THE STATE | | | OF FLORIDA AND HAVE NOT BEEN FOR SEVERAL YEARS. PLEASE | | | SEE COVER SHEET FOR EXAMPLE WHICH STATES THE *STANDARD | | | BUILDING CODE*. SBC. THE FOLLOWING SHALL BE LISTED AT A | | | MINIMUM FOR THIS REVIEWER AND FOR THIS TRADE. | | | | | | 2004 FBC W/ 2007 REVISIONS. | | | 2005 NFPA-70 | | | 2003 NFPA-101 | | | 2002 NFPA-72 | | | | | | 3) NOTE: THE APPLIED VALUE FOR COMPLETE SCOPE OF WORK | | | SHALL INCLUDE ALL LABOR, MATERIALS, DESIGN COST, | | | EQUIPMENT ETC EVEN IF ANY OF THESE ITEMS ARE OWNER | | | SUPPLIED. THE APPLIED TOTAL VALUE OF $19K IS LOW FOR | | | SCOPE OF WORK, EQUIPMENT ETC AS SHOWN ON PLANS. | | | FBC 108.3 | | | | | | 4) NOTE: PLEASE SUBMIT MANUFACTURE SPECS/CUT SHEETS FOR | | | NEW PROPOSED EQUIPMENT. MUST CONTAIN A LISTING FROM A | | | NRTL. (NATIONALLY RECOGNIZED TESTING LABORATORY). | | | 110.3,90.7 | | | | | | 5) NOTE: ELECTRICAL PLAN SHEET E-1 MENTIONS A NEW METER | | | AND MAIN. HOWEVER BY THE RISER THIS IS NOT A NEW MAIN | | | AND IS IN FACT A TENANT MEANS OF DISCONNECT. THIS IS | | | NOT A MAIN FOR THE SERVICE FEEDING TENANTS. PLEASE | | | ADJUST DESIGNATIONS AND LABELING OF EQUIPMENT. | | | 230.2E | | | THIS IS ALL ONE TENANT SPACE YET THE RISER MENTIONS A | | | NEW METER AND MAIN FOR TENANT SUITE/UNIT 1723. A NEW | | | MAIN FOR THE SAME TENANT IS NOT GRANTED AT THIS TIME. | | | NEED TO PROVIDE LOAD ON EXISTING MAIN WITH NEW LOAD | | | ADDED IN WHICH NEW 400 TENANT MAIN IS BEING ADDED. | | | 220.87 | | | PLEASE BE SURE TO SHOW ANY CONTINUOUS LOADS AND LARGEST | | | MOTOR LOADS AT 125%. 215.3,230.42 ETC | | | RISER SHOWS ALL EXISTING AND NEW TENANT MAINS AS | | | SEPARATE SUITES OR UNIT HOWEVER BASED ON THE PLANS | | | SUBMITTED THIS IS NOW GOING TO BE ONE TENANT SPACE. | | | | | | 6) NOTE: PLEASE SEE 250.110,250.24, 250.6, 250.122 ETC. | | | THE RISER IS MISSING THE EQUIPMENT GROUNDING CONDUCTOR | | | AFTER THE FIRST MEANS OF SERVICE DISCONNECT. | | | PLEASE ALSO KNOW ANY METERING EQUIPMENT AFTER THE FIRST | | | MEANS OF SERVICE EQUIPMENT DISCONNECT REQUIRES A | | | FLOATING NEUTRAL IN METER. | | | | | | 7) NOTE: PLEASE SEE RISER IS MISSING EQUIPMENT | | | GROUNDING CONDUCTOR FROM PANEL HVE TO THE TRANSFORMER. | | | 250.20,250.30,250.110,250.122 ETC | | | | | | 8) NOTE: PLEASE SEE THE TRANSFORMER NEEDS TO SHOW THE | | | ATTACHMENT LOCATION PER 250.50,250.30,250.20. | | | | | | 9) NOTE: PLEASE SEE THE ADDRESS ON TITLE BLOCKS DO NOT | | | MATCH THE ON-LINE WEBSITE FROM DBPR. PLEASE ADJUST. | | | FAC 61G15-23.002 | | | | | | 10) NOTE: ** PLEASE SEE THE COLOR CODING SHALL MATCH | | | EXISTING IN THE BUILD FOR 277/480V SYSTEMS. THE NOTES | | | ON E-3 NEED TO BE ADJUSTED TO READ BROWN, PURPLE, AND | | | YELLOW. ORANGE IS THE COLOR BY THE NEC WHICH IS SET | | | ASIDE FOR DELTA HIGH LEG SYSTEMS. THIS IS NOT SUCH A | | | SYSTEM. | | | PLEASE REVISE TO MATCH EXISTING. | | | 90.4 | | | * CALL FOR QUESTIONS | | | | | | | | | | | | | | | | | | | | | | | | **IMPORTANT** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED | | | INTO TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2008-12-12 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-12-12 |
Time |
14:30 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-12-12 |
Time |
14:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2008-12-03 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-12-03 |
Time |
11:09 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-12-03 |
Time |
10:24 |
Sent To |
|
|
| Notes |
| 2008-12-03 10:57:56 | *****UNSAT***** | | | | | | THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE | | | BEEN SATISFIED; HOWEVER, THE PLANS WILL BE FIRE-STAMPED | | | (APPROVED) WHEN THE FOLLOWING NEW COMMENTS (BASED ON | | | NEW INFORMATION) HAVE BEEN ADDRESSED: | | | | | | | | | 1. ON THE APPROPIATE EXTERIOR ELEVATION (SHEET A-3) | | | WHICH FRONTS OKEECHOBEE ROAD, DISPLAY THE NUMERICAL | | | ADDRESS FOR THIS BUILDING. AS PER WEST PALM BEACH CODE, | | | THE NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND NO | | | LESS THAN 1" IN WIDTH/STROKE CONTRASTING TO THE | | | BACKGROUND OF THE STRUCTURE. | | | | | | 2. ON SHEET E-1, REMOVE/DELETE REFERENCES TO EXISTING | | | SPACE # 1723 & EXISTING SPACE # 1719. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-804-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2008-10-31 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-10-31 |
Time |
15:10 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-10-31 |
Time |
15:10 |
Sent To |
|
|
| Notes |
| 2008-10-31 15:28:00 | ***DENIED*** | | | | | | 1) IN ADDITION TO APPLICABLE BUILDING CODES, LIFE | | | SAFETY SHALL COMPLY WITH NFPA 101, 2003. | | | | | | 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY | | | WITH NFPA 241. | | | | | | 3) PLEASE SHOW LOCATIONS OF ALL NEW AND EXISTING | | | ILLUMINATED EXITS SIGNS AND EMERGENCY LIGHTING | | | FACILITIES. | | | | | | 4) PLEASE CORRELATE ADDRESS INFORMATION ON PLANS AND | | | PERMIT APPLICATION. PLANS INDICATE '1721' AND DRAWINGS | | | SHOW 1719 AND 1723? | | | | | | 5) RAMP SHALL COMPLY WITH 101, SEC. 7.2.5. HANDRAILS | | | REQUIRED ON BOTH SIDES OF RAMP. | | | | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2008-12-08 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-12-08 |
Time |
09:13 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-12-08 |
Time |
09:13 |
Sent To |
|
|
| Notes |
| 2008-12-08 09:13:26 | TO "COMM" BD#5 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-11-12 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-11-12 |
Time |
11:20 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-11-12 |
Time |
11:20 |
Sent To |
|
|
| Notes |
| 2008-11-12 11:24:08 | TO "COMM" BD#20 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-10-31 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-10-31 |
Time |
15:31 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-10-15 |
Time |
09:42 |
Sent To |
|
|
| Notes |
| 2008-10-16 16:13:42 | TO "COMM" BD#41 | | 2008-10-15 09:42:36 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2008-11-21 |
|
|
Cont ID |
|
| Sent By |
kdfreema |
Date |
2008-11-21 |
Time |
11:05 |
Rev Time |
0.00 |
| Received By |
kdfreema |
Date |
2008-11-21 |
Time |
11:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2008-10-21 |
|
|
Cont ID |
|
| Sent By |
kdfreema |
Date |
2008-10-21 |
Time |
15:51 |
Rev Time |
0.00 |
| Received By |
kdfreema |
Date |
2008-10-21 |
Time |
15:51 |
Sent To |
|
|
| Notes |
| 2008-10-21 16:24:53 | ***FAILED*** | | | | | | A MINOR PLANNED DEVELOPMENT AMENDMENT MUST BE | | | SUBMITTED, AND APPROVED, SHOWING THE EXTENT OF THE | | | OUTDOOR IMPROVEMENTS (IE SCALE, FENCE, AND NEW RAMP). | | | BEFORE ZONING CAN APPROVE THIS PERMIT. | | | | | | PLEASE CONTACT KELLY FREEMAN, PLANNER, AT | | | [email protected] OR AT 561-822-1435 WITH QUESTIONS. |
|
|
|