| 2008-10-27 16:37:17 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | 1. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR |
| | PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS |
| | FS471. SEE THE DOCUMENTS SUBMITTED; "EPS FOAM CORE ROOF |
| | PANELS", "ELITE ROOF/SCREEN WALL MASTER PLAN SHEET", |
| | AND THREE OTHER PAGES ARE PHOTOCOPIES. (NOTE THAT |
| | PRODUCT APPROVALS ARE EXEMPTED FROM THIS REQUIREMENT.) |
| | HOWEVER, THESE SAME SHEETS WERE ALSO SUBMITTED AS |
| | ORIGINALS, TWO SETS. PLEASE REMOVE UNNECESSARY |
| | DOCUMENTS FROM THE PERMIT PACKAGE OR, IF THESE SHEETS |
| | DIFFER IN SOME WAY, SUBMIT ONLY SIGNED, SEALED, DATED |
| | ENGINEERING DOCUMENTS. |
| | |
| | 2. FAC9B72, PRODUCT APPROVALS ARE REQUIRED FOR THE ROOF |
| | PANELS. |
| | |
| | 3. ENGINEERING WAS SUBMITTED FROM TWO DIFFERENT |
| | ENGINEERS. PLEASE DETERMINE WHICH ONE IS THE "ENGINEER |
| | OF RECORD FOR THE STRUCTURE" AND WHICH HAS PROVIDED |
| | "DELEGATED ENGINEERING"; SEE FAC61G15-23.002 (AVAILABLE |
| | AT WWW.FBPE.ORG, LAWS AND RULES). HAVE THE DELEGATED |
| | ENGINEERING REVIEWED BY THE ENGINEER OF RECORD. |
| | |
| | 4. THE ENGINEER OF RECORD IS TO REVIEW THE PRODUCT |
| | APPROVAL. |
| | |
| | 5. A MESSAGE WAS LEFT FOR THE CONTRACTOR; THIS PERMIT |
| | CAN BE ISSUED WITH THE FOLLOWING PROVISOS: |
| | |
| | A. AT CONTRACTOR'S RISK; CONTRACTOR TO SUBMIT THE |
| | FOLLOWING ITEMS AS A REVISION (WITH REVISION FEE): |
| | |
| | B. SUBMIT EOR (ENGINEER OF RECORD) REVIEW OF DELEGATED |
| | ENGINEERING. |
| | |
| | C. SUBMIT ELITE ROOF PANEL PRODUCT APPROVALS, REVIEWED |
| | BY EOR. |
| | |
| | |