Plan Review Details - Permit 08100220
Plan Review Stops For Permit 08100220
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-08-13 Cont ID  
Sent By rmcdouga Date 2009-08-13 Time 10:24 Rev Time 0.00
Received By rmcdouga Date 2009-08-13 Time 10:24 Sent To  
Notes
2009-08-13 10:25:42REVISED ROOFING AND FRENCH DOOR PRODUCT APPROVALS.
 SUBMITTED TRUSS REPAIR AND MODIFICATION DETAILS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-05-18 Cont ID  
Sent By rmcdouga Date 2009-04-30 Time 16:09 Rev Time 0.00
Received By rmcdouga Date 2009-04-30 Time 16:09 Sent To  
Notes
2009-04-30 16:20:302004 FBC W/2007 REVISIONS
  
 DENIED BY BUILDING
  
 1) SUBMIT TWO COPIES OF ENERGY CALCULATIONS FOR THE
 ADDITION AS REQUIRED BY FBC 13-600. THE PREPARER AND
 OWNER/AGENT SIGNATURES ARE REQUIRED ON THE FORMS. 2004
 FBC 13-103.3
  
 2) SHOP DRAWINGS FOR THE EXTERIOR BALCONY WILL BE
 REQUIRED TO BE SUBMITTED FOR APPROVAL PRIOR TO
 INSTALLATION. FBC 106.1.2* CITY AMENDMENTS
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-02-04 Cont ID  
Sent By rmcdouga Date 2009-02-04 Time 11:21 Rev Time 0.00
Received By rmcdouga Date 2009-02-04 Time 07:54 Sent To M
Notes
2009-02-04 11:21:492004 FBC W/2007 REVISIONS
 TWO STORY ADDITION
  
 DENIED BY BUILDING
  
 1) BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION. 233-5025
  
 2) COMMENT WAS ADDRESSED.
  
 3) SUBMIT TWO COPIES OF ENERGY CALCULATIONS FOR THE
 ADDITION AS REQUIRED BY FBC 13-600. THE PREPARER AND
 OWNER/AGENT SIGNATURES ARE REQUIRED ON THE FORMS.
  
 4) COMMENT WAS ADDRESSED.
  
 5) COMMENT WAS ADDRESSED.
  
 6) COMMENT WAS ADDRESSED.
  
 7) COMMENT WAS ADDRESSED.
  
 8) COMMENT WAS ADDRESSED.
  
 9) COMMENT WAS ADDRESSED.
  
 10) COMMENT WAS ADDRESSED.
  
 11) COMMENT WAS ADDRESSED.
  
 12) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 GLASS BLOCK, EXTERIOR FRENCH DOORS AND STRUCTURAL
 WINDOW MULLIONS AS REQUIRED BY FAC RULE 9B-72. NOTE: IF
 PRODUCTS ARE NOT LARGE MISSILE IMPACT RATED, THEN
 PRODUCT APPROVALS, INSTALLATION SCHEDULES AND KEY PLANS
 FOR STORM PANELS WILL BE REQUIRED. FBC R301.2.1.2 NOTE:
 PRODUCT APPROVALS ARE REQUIRED TO BE APPROVED IN
 WRITING DESIGNER OF RECORD.
  
 13) SHOP DRAWINGS FOR THE EXTERIOR BALCONY WILL BE
 REQUIRED TO BE SUBMITTED FOR APPROVAL BEFORE THEY ARE
 INSTALLED. FBC 106.1.2* CITY AMENDMENTS
  
 NOTE: THE NOTICE OF COMMENCEMENT HAS EXPIRED. IT WILL
 NEED TO BE RE-RECORDED BEFORE THE FIRST INSPECTION. FS
 713
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-10-23 Cont ID  
Sent By rmcdouga Date 2008-10-23 Time 10:22 Rev Time 0.00
Received By rmcdouga Date 2008-10-23 Time 07:52 Sent To E
Notes
2008-10-23 10:22:422004 FBC W/2007 REVISIONS
 TWO STORY ADDITION
  
 DENIED BY BUILDING
  
 1) BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION. 233-5025
  
 2) ON SHEET A-1 PLEASE ADD ADDITION TO THE SCOPE OF
 WORK AND REVISE GENERAL NOTE 1 TO 2004 FBC WITH 2007
 REVISIONS. FBC 106.1.1* CITY AMENDMENTS
  
 3) SUBMIT TWO COPIES OF ENERGY CALCULATIONS FOR THE
 ADDITION AS REQUIRED BY FBC 13-600. THE PREPARER AND
 OWNER/AGENT SIGNATURES ARE REQUIRED ON THE FORMS.
  
 4) SHOW COMPLIANCE WITH R807.1 ATTIC ACCESS . IN
 BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF
 CONSTRUCTION, AN ATTIC ACCESS OPENING SHALL BE PROVIDED
 TO ATTIC AREAS THAT EXCEED 30 SQUARE FEET (2.8 M 2 )
 AND HAVE A VERTICAL HEIGHT OF 30 INCHES (762 MM) OR
 GREATER. THE ROUGH-FRAMED OPENING SHALL NOT BE LESS
 THAN 22 INCHES BY 30 INCHES (559 MM BY 762 MM) AND
 SHALL BE LOCATED IN A HALLWAY OR OTHER READILY
 ACCESSIBLE LOCATION. A 30-INCH (762 MM) MINIMUM
 UNOBSTRUCTED HEADROOM IN THE ATTIC SPACE SHALL BE
 PROVIDED AT SOME POINT ABOVE THE ACCESS OPENING. SEE
 SECTION M1305.1.3 FOR ACCESS REQUIREMENTS WHERE
 MECHANICAL EQUIPMENT IS LOCATED IN ATTICS.
  
 5) SPECIFY HOW THE SECOND FLOOR BALCONY FLOOR WILL BE
 WATERPROOFED TO PREVENT WATER INTRUSION INTO THE ROOMS
 BELOW.
  
 6) SPECIFY THE LOCATIONS OF THE FLOOR/CEILING ASSEMBLY
 DRAFTSTOPPING ON THE PLANS. FBC R502.1.2
  
 7) PLEASE CORRECT THE TYPO ON THE LEDGER 1 DETAIL ON
 S-2 FROM 58" DIAMETER ANCHOR BOLTS TO 5/8".
  
 8) PROVIDE STRUCTURAL DETAILS OF THE SECOND FLOOR ROOF
 AREA FOR THE LARGE OVERHANG AT THE CORNER OF THE MASTER
 BATHROOM ABOVE THE ANGLE WALL. R801.2 REQUIREMENTS.
 ROOF AND CEILING CONSTRUCTION SHALL BE CAPABLE OF
 ACCOMMODATING ALL LOADS IMPOSED ACCORDING TO SECTION
 R301 AND OF TRANSMITTING THE RESULTING LOADS TO THE
 SUPPORTING STRUCTURAL ELEMENTS.
  
 9) PROVIDE STRUCTURAL DETAILS OF THE EXISTING ROOF
 FRAMING AT THE AREA WHERE THE NEW FLOOR GIRDERS
 SUPPORTED BY THE STEEL COLUMN WILL BE INSTALLED BELOW
 THE NEW MASTER BATH. R801.2
  
 10) PROVIDE A ROOF FRAMING PLAN AND DETAILS FOR THE
 ROOF CRICKETS THAT WILL BE REQUIRED TO DIVERT THE RAIN
 WATER AWAY FROM THE SECOND FLOOR WALLS OF THE ADDITION.
 R703.1
  
 11) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 12) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 GLASS BLOCK, EXTERIOR FRENCH DOORS AND STRUCTURAL
 WINDOW MULLIONS AS REQUIRED BY FAC RULE 9B-72. NOTE: IF
 PRODUCTS ARE NOT LARGE MISSILE IMPACT RATED, THEN
 PRODUCT APPROVALS, INSTALLATION SCHEDULES AND KEY PLANS
 FOR STORM PANELS WILL BE REQUIRED. FBC R301.2.1.2
  
 13) SHOP DRAWINGS FOR THE EXTERIOR BALCONY WILL BE
 REQUIRED TO BE SUBMITTED FOR APPROVAL BEFORE THEY ARE
 INSTALLED. FBC 106.1.2* CITY AMENDMENTS
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-01-15 Cont ID  
Sent By btrobaug Date 2009-01-15 Time 15:53 Rev Time 0.00
Received By btrobaug Date 2009-01-15 Time 15:21 Sent To P
Notes
2009-01-15 15:53:49 
  
 PROVISO
  
 THE 200 AMP PANEL "A", IS NOT RATED FOR THE 266 AMP
 LOAD IN THE CALCULATIONS. A 150 AMP DISCONNECT MUST BE
 ADDED OUTSIDE AT THE METER. 230230.70(A)(1)

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-10-23 Cont ID  
Sent By btrobaug Date 2008-10-23 Time 12:02 Rev Time 0.00
Received By btrobaug Date 2008-10-23 Time 11:04 Sent To M
Notes
2008-10-23 12:02:31 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 ALL COMMENTS RELATE TO SHEET E-2, UNLESS OTHERWISE
 NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS
 OTHERWISE NOTED.
  
 1} THE FEED FOR PANEL "B"IS SHOWN AS #6 CU WHICH IS
 RATED FOR AN OCP OF 65 AMPS.(310.16) THE CALCULATION
 FOR THAT PANEL INDICATE 141 AMPS. THE FEEDER ON THAT
 PANEL IS LISTED AS A 200 AMP. PLEASE CORRELATE. NOTE:
 THE AHU'S ALONE ARE ON 60 AMP CIRCUITS.
  
 2} THERE IS A WATER HEATER IN THE CALCULATION FOR PANEL
 "B" BUT NONE ON THE PANEL SCHEDULE. NOTE THERE IS ALSO
 A WATER HEATER IN PANEL "A", BUT ONLY ONE SHOWN ON THE
 FLOOR PLANS @ 100 GAL.408.4
  
 3} THE FEED FOR PANEL "B" IS LISTED BOTH AS MAIN LUG
 ONLY AND 200 AMP MAIN BREAKER?
  
 THE FOLLOWING COMMENTS REFER TO SHEET E-1:
  
 4} THERE ARE THREE A/C SYSTEMS IN THE LOAD CALCULATIONS
 BUT ONLY TWO CONDENSING UNITS LOCATED ON THE PLAN. SHOW
 THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN. ALSO
 SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER
 440.14, RECEPTACLE PER 210.63, LIGHT PER 210.70(A) (3).
  
 5} 210.52 (C)(2) ISLAND COUNTER SPACES AT LEAST ONE
 RECEPTACLE SHALL BE INSTALLED AT EACH ISLAND COUNTER
 SPACE WITH A LONG DIMENSION OF 600 MM (24 IN.) OR
 GREATER AND A SHORT DIMENSION OF 300 MM (12 IN.) OR
 GREATER. WHERE A RANGETOP OR SINK IS INSTALLED IN AN
 ISLAND COUNTER AND THE WIDTH OF THE COUNTER BEHIND THE
 RANGETOP OR SINK IS LESS THAN 300 MM (12 IN.), THE
 RANGETOP OR SINK IS CONSIDERED TO DIVIDE THE ISLAND
 INTO TWO SEPARATE COUNTERTOP SPACES AS DEFINED IN
 210.52(C)(4).
  
 6} 210.52(C)(3) PENINSULAR COUNTER SPACES AT LEAST ONE
 RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH PENINSULAR
 COUNTER SPACE WITH A LONG DIMENSION OF 600 MM (24 IN.)
 OR GREATER AND A SHORT DIMENSION OF 300 MM (12 IN.) OR
 GREATER. A PENINSULAR COUNTERTOP IS MEASURED FROM THE
 CONNECTING EDGE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-08-11 Cont ID  
Sent By lmartine Date 2009-08-11 Time 09:07 Rev Time 0.00
Received By lmartine Date 2009-08-11 Time 09:07 Sent To  
Notes
2009-08-11 09:08:21GAVE TO MCDOUGLE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-04-17 Cont ID  
Sent By swurafti Date 2009-04-17 Time 16:08 Rev Time 0.00
Received By swurafti Date 2009-04-17 Time 16:08 Sent To  
Notes
2009-04-17 16:15:15WAITING FOR RESIDENTIAL BOARD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-01-06 Cont ID  
Sent By adarroug Date 2009-01-06 Time 14:18 Rev Time 0.00
Received By adarroug Date 2009-01-06 Time 14:18 Sent To Z
Notes
2009-01-06 14:19:07TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-10-29 Cont ID  
Sent By mperson Date 2008-10-29 Time 10:02 Rev Time 0.00
Received By mperson Date 2008-10-14 Time 11:09 Sent To PC
Notes
2008-10-14 11:10:00TO "SFR" "Z"

Review Stop L LANDSCAPING
Rev No 2 Status P Date 2009-05-14 Cont ID  
Sent By rkussner Date 2009-05-14 Time 11:58 Rev Time 0.00
Received By rkussner Date 2009-05-14 Time 11:58 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2009-01-13 Cont ID  
Sent By rkussner Date 2009-01-13 Time 15:21 Rev Time 0.00
Received By rkussner Date 2009-01-13 Time 13:24 Sent To Z
Notes
2009-01-13 16:15:56***LANDSCAPE REVIEW FAILED***
  
 1. PURSUANT TO SECTION 94-442(C), PALM TREES MAY BE
 SUBSTITUTED FOR NOT MORE THAN 35 PERCENT OF THE SHADE
 OR FLOWERING TREES REQUIRED BY THIS ARTICLE. HOWEVER,
 WHEN PALM TREES ARE SUBSTITUTED FOR SHADE TREES, TWO
 PALM TREES SHALL BE PROVIDED FOR EACH REQUIRED SHADE
 TREE. THIS 2:1 SUBSTITUTION SHALL NOT BE REQUIRED FOR
 ROYAL PALM TREES AND SUCKERING PALM TREES SUCH AS THE
 ARECA PALM, PAUROTIS PALM AND THE SENEGAL DATE PALM.
 WHEN PALMS ARE USED THEY MUST BE PLANTED IN GROUPS OF
 THREE. TWO ADDITIONAL SHADE OR FLOWERING TREES SHALL BE
 ADDED TO MEET MINIMUM REQUIREMENTS.
  
 2. PURSUANT TO SECTION 94-442(D) , PRIVATE LAND AND
 PUBLIC RIGHTS-OF-WAY BETWEEN STREET OR SIDEWALK
 SURFACES AND REQUIRED BUFFER STRIPS AND LANDSCAPED OPEN
 SPACE AREAS SHALL BE PLANTED WITH GRASS. GRASS AREAS
 SHALL BE SODDED.
  
 3. PURSUANT TO SECTION 94-445(4)(G)(3), AUTOMATIC
 IRRIGATION SYSTEMS SHALL BE USED FOR THE CULTIVATED
 LANDSCAPE AREAS FOR ALL PROPERTIES. THIS INCLUDES THE
 RIGHT-OF-WAY.
  
 4. THE GROUND LEVEL AIR CONDITIONING UNITS SHALL BE
 SCREENED.
  
 5. ALL PROPOSED AND EXISTING PLANT MATERIAL SHALL BE
 CLEARLY IDENTIFIED.
  
 6. PLEASE PROVIDE THE TABULATION NECESSARY TO
 DEMONSTATE COMPLIANCE WITH THE XERISCAPE DESIGN OPTIONS
 REQUIRED FOR SINGLE FAMIILY.
  
 7. PROVIDE A PLANT LIST IDENTIFYING ALL PROPOSED TREES,
 SHRUBS AND GROUND COVER. IT SHALL INCLUDE THE QUANTITY,
 SIZE AND SPACING FOR ALL PROPOSED PLANT MATERIAL.
  
 8. PLEASE PROVIDE THE LANDSCAPE INFORMATION IN TABULAR
 FORM. THE TABULATION SHALL INCLUDE TREES REQUIRED AND
 TREES PROPOSED, SHRUBS REQUIRED AND SHRUBS PROPOSED.
 OPEN AREA IS THE DIFFERENCE BETWEEN THE TOTAL LOT AREA
 AND THE FOOTPRINT OF THE BUILDING. THE TREES AND SHRUBS
 REQUIRED IS BASED UPON OPEN AREA AND NOT PERVIOUS AREA.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-05-18 Cont ID  
Sent By hmoser Date 2009-05-18 Time 14:54 Rev Time 0.00
Received By hmoser Date 2009-05-18 Time 14:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2009-02-04 Cont ID  
Sent By hmoser Date 2009-02-04 Time 15:02 Rev Time 0.00
Received By hmoser Date 2009-02-04 Time 15:02 Sent To  
Notes
2009-02-05 07:50:0402/05/2009 PLAN DENIED.
 PLEASE SUBMIT ENERGY CALCULATIONS PER 2004 FBC
 13-101.2.2
 PLEASE SUBMIT COOLING LOAD CALCULATIONS PER 2004 FBC
 13-607.1.ABC.1
 PLEASE SUBMIT MECHANICAL PLANS FOR REVIEW PER 200 FBC
 CITY OF WPB AMEND. 106.3.5.4 (10) .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-10-23 Cont ID  
Sent By tgordon Date 2008-10-23 Time 16:29 Rev Time 0.30
Received By tgordon Date 2008-10-23 Time 16:28 Sent To P
Notes
2008-10-23 16:43:33PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE SUBMIT ENERGY CALCULATIONS, PER 2004 FBC
 13-101.2.2.
  
 2) PLEASE SUBMIT COOLING LOAD CALCULATIONS, PER 2004
 FBC 13-607.1.ABC.1.
  
 3) PLEASE SUBMIT MECHANICAL (A/C) PLANS FOR REVIEW, PER
 2004 FBC CITY OF WPB AMEND. 106.3.5.4 (10).
  
 4) THE MAIN MASTER BATHROOM WILL REQUIRE AN EXHAUST FAN
 (DUE TO THE BATH TUB AND SHOWER) PER 2004 FBC/R R303.3
  
 5) THE WINDOW TO THE EXISTING FIRST FLOOR BATHROOM WILL
 BE ENCLOSED, SHOW ON ELECTRICAL AND MECHANICAL (A/C)
 PLANS AN EXHAUST FAN NEW OR EXISTING, PER 2004 FBC/R
 R303.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-05-18 Cont ID  
Sent By rmcdouga Date 2009-05-18 Time 11:20 Rev Time 0.00
Received By rmcdouga Date 2009-05-18 Time 11:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2009-02-03 Cont ID  
Sent By kstevens Date 2009-02-03 Time 10:54 Rev Time 0.00
Received By kstevens Date 2009-02-03 Time 10:53 Sent To M
Notes
2009-02-03 11:18:38DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT E-2 SANITARY RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN, NOR DOES IT MEET CODE REQUIREMENTS.
 A. THE LAV IN THE POWDER ROOM IS ON THE RIGHT HAND
 WALL. (SHOWN ON THE LEFT HAND WALL), AND IS NOT VENTED.
 SECTIONS 106.1.1 & 901.2.1.
 B. THE DOUBLE LAVS FOR BATH AT BEDROOMS 3 & 4 ARE SHOWN
 PARALLEL TO THE WALL, NOT OUT INTO THE BATHROOM, AND
 THE SHOWER IS NOT VENTED. SECTIONS 106.1.1 & 901.2.1.
 C. THE SECOND FLOOR GUEST BATHROOM TUB IS NOT VENTED.
 SECTION 901.2.1.
  
 2. SEE RED LINE EXAMPLES SHOWN ON NEW SHEET E-2.
  
 3. REMOVE ALL VOIDED, SUPERSEDED SHEETS AND REPLACE
 WITH NEW SHEETS. PLANS SHALL BE SUBMITTED IN TWO BOUND
 SETS. LOOSE SHEETS NOT APPROVED. SECTION 106.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-10-28 Cont ID  
Sent By mperson Date 2008-10-29 Time 16:37 Rev Time 1.30
Received By mperson Date 2008-10-28 Time 16:37 Sent To I
Notes
2008-10-28 16:58:03PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET E-2 SANITARY ISOMETRIC: PLEASE CORRECT THE
 FOLLOWING PER THE FBC-2004 PLUMBING CODE SECTIONS.
  
 A} THE CLEANOUTS BEING INDICATED FOR THE SECOND FLOOR
 ARE BEING INDICATED IN THE WRONG PLACE. THOSE CLEANOUTS
 SHOULD BE CORRECTLY LOCATED AT THE BASE OF THOSE SOIL
 AND WASTE STACKS ON THE FIRST FLOOR. PLEASE CORRECT PER
 SECTION 708.3.4 BASE OF STACK.
  
 B} THE ISOMETRIC DOES NOT REFLECT THE FIRST FLOOR PLAN
 INDICATED ON SHEET A-3. THE WATER CLOSET IS MISSING
 FROM THE FIRST FLOOR BATHROOM (ROOM NOT NUMBERED) BY
 BEDROOM 3 AND BEDROOM 4. PLEASE KNOW THAT THE ISOMETRIC
 IS INDICATING THREE LAVATORIES FOR THIS BATHROOM,
 HOWEVER THE FIRST FLOOR PLAN ON SHEET A-3 ONLY
 INDICATES TWO LAVATORIES. PLEASE CORRECT PER SECTION
 106.1.1 (W.P.B. AS AMENDED) INFORMATION ON CONSTRUCTION
 DOCUMENTS AND SECTION 701.1 SCOPE.
  
 C} THE ISOMETRIC DOES NOT REFLECT THE FIRST FLOOR PLAN
 INDICATED ON SHEET A-3. THE ISOMETRIC SHOULD CLEARLY
 INDICATE THE REQUIRED BRANCH COMBINATION WYE AND EIGHTH
 BEND FITTING FROM THE MAIN TO THE POWDER ROOM BATHROOM.
 PLEASE KNOW AT A MINIMUM THE SANITARY ISOMETRIC RISER
 DIAGRAM SHOULD REFLECT THE FLOOR PLAN. PLEASE CORRECT
 PER SECTION 106.1.1 (W.P.B. AS AMENDED) INFORMATION ON
 CONSTRUCTION DOCUMENTS AND SECTION 701.1 SCOPE.
  
 D} THE SECOND FLOOR BATHTUB IN THE TUB BATHROOM (ROOM
 NOT NUMBERED) IS NOT VENTED. THE BATHTUB WASTE BRANCH
 FITTING SHOULD BE LOCATED ABOVE THE WATERCLOSET AND
 BELOW THE LAVATORY TO BE VENTED. PLEASE CORRECT PER
 SECTION 901.2.1 VENTING REQUIRED.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 *PLEASE CALL IF THERE ARE ANY QUESTIONS.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2009-05-15 Cont ID  
Sent By mcruz Date 2009-05-15 Time 09:37 Rev Time 0.00
Received By mcruz Date 2009-05-15 Time 08:22 Sent To  
Notes
2009-05-15 09:40:01PLACED BACK ON RES RACK (R-7)

Review Stop Z ZONING
Rev No 2 Status F Date 2009-01-14 Cont ID  
Sent By mcruz Date 2009-01-14 Time 08:11 Rev Time 0.00
Received By mcruz Date 2009-01-13 Time 10:04 Sent To E
Notes
2009-01-14 08:12:35PLANNING AND ZONING DEPT: ***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. PLEASE ADDRESS LANDSCAPE PLAN REVIEWER COMMENTS.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2008-10-16 Cont ID  
Sent By mcruz Date 2008-10-16 Time 10:17 Rev Time 0.00
Received By mcruz Date 2008-10-16 Time 10:07 Sent To I
Notes
2008-10-16 10:17:19***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. INDICATE THE SETBACK DIMENSIONS FROM ANY EXTERIOR
 IMPROVEMENTS TO ALL ADJACENT PROPERTY LINES. NOTE:
 PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), SECTION 94-72: SINGLE
 FAMILY LOW DENSITY (SF7) RESIDENTIAL DISTRICT - MINIMUM
 SETBACKS FOR PRINCIPAL BUILDING ARE AS FOLLOWS:
  
 A. FRONT: 25 FEET;
  
 B. CORNER: 12.5 FEET; TEN FEET IF LOT IS LESS THAN 60
 FEET WIDE;
  
 C. REAR: 15 FEET OR TEN PERCENT OF DEPTH, WHICHEVER IS
 LESS;
  
 D. SIDE: FIVE FEET MINIMUM, 15 FEET TOTAL.
  
 3. INDICATE SETBACK DIMENSIONS FROM ANY PROPOSED AND/OR
 RELOCATED A/C EQUIPMENT TO ALL PROPERTY LINES. PURSUANT
 TO THE ZLDR, SECTION 94-305(B)(4): MECHANICAL EQUIPMENT
 MAY NOT PROJECT MORE THAN 4 FEET INTO A REQUIRED
 SETBACK.
  
 4. PURSUANT TO THE ZLDR, SECTION 94-441(C)(2): AS THE
 VALUE OF THE PROPOSED WORK EXCEEDS 50% OF THE
 STRUCTURE'S VALUE (LISTED AS "IMPROVEMENT VALUE" WITH
 THE P.B.C. PROPERTY APPRAISER'S OFFICE), LANDSCAPING
 SHALL BE IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS
 FOUND IN ARTICLE XIV OF THE ZLDR.
  
 PLEASE SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN
 SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF
 THE ZLDR.
  
 5. INDICATE IF ANY TREES WILL BE REMOVED AS A RESULT OF
 THE PROPOSED PROJECT. IF YES, A TREE ALTERATION/REMOVAL
 PERMIT WILL BE REQUIRED. CONTACT ROBERT KUSSNER, CITY
 LANDSCAPE PLANNER, AT (561) 822-1462 FOR THE
 APPLICATION.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  
  
  