Plan Review Details - Permit 08100215
Plan Review Stops For Permit 08100215
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-12-02 Cont ID  
Sent By jwitmer Date 2008-12-02 Time 16:55 Rev Time 0.55
Received By jwitmer Date 2008-12-02 Time 16:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-10-24 Cont ID  
Sent By jwitmer Date 2008-10-24 Time 10:00 Rev Time 0.77
Received By jwitmer Date 2008-10-24 Time 10:00 Sent To  
Notes
2008-10-24 10:07:24BUILDING PLAN REVIEW
 PERMIT: 08100215
 ADD: 901 VILLAGE BLVD
 CONT: L & L INTERIOR & REMODELING
 TEL: (561)#686-5853
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS. PLANS
 FAIL TO INDICATE AS SUCHPLEASE SEE C-1.
  
 1D) SHEET C-1 ALSO FAILS TO INDICATE LEVEL OF
 ALTERAATIONS, EXISTING BUILDING CODE. 301.5
 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE OR A
 COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303 , 304 AND 305 OF THIS CODE.
  
 2) SHEET 1.0A DOES NOT INDICATE COMPLIANCE WITH
 ACCESSIBLITY CODE :
 11-5.1 GENERAL.
 EXCEPT AS SPECIFIED OR MODIFIED IN THIS SECTION,
 RESTAURANTS AND CAFETERIAS SHALL COMPLY WITH THE
 REQUIREMENTS OF SECTION 11-4.1 TO SECTION 11-4.35 .
 WHERE FIXED TABLES (OR DINING COUNTERS WHERE FOOD IS
 CONSUMED BUT THERE IS NO SERVICE) ARE PROVIDED, AT
 LEAST 5 PERCENT, BUT NOT LESS THAN ONE, OF THE FIXED
 TABLES (OR A PORTION OF THE DINING COUNTER) SHALL BE
 ACCESSIBLE AND SHALL COMPLY WITH SECTION 11-4.32 AS
 REQUIRED IN SECTION 11-4.1.3 (18). IN ESTABLISHMENTS
 WHERE SEPARATE AREAS ARE DESIGNATED FOR SMOKING AND
 NONSMOKING PATRONS, THE REQUIRED NUMBER OF ACCESSIBLE
 FIXED TABLES (OR COUNTERS) SHALL BE PROPORTIONALLY
 DISTRIBUTED BETWEEN THE SMOKING AND NONSMOKING AREAS.
 IN NEW CONSTRUCTION, AND WHERE PRACTICABLE IN
 ALTERATIONS, ACCESSIBLE FIXED TABLES (OR COUNTERS)
 SHALL BE DISTRIBUTED THROUGHOUT THE SPACE OR FACILITY.
  
 11-5.2 COUNTERS AND BARS.
 WHERE FOOD OR DRINK IS SERVED AT COUNTERS EXCEEDING 34
 INCHES (865 MM) IN HEIGHT FOR CONSUMPTION BY CUSTOMERS
 SEATED ON STOOLS OR STANDING AT THE COUNTER, A PORTION
 OF THE MAIN COUNTER WHICH IS 60 INCHES (1525 MM) IN
 LENGTH MINIMUM SHALL BE PROVIDED IN COMPLIANCE WITH
 SECTION 11-4.32 OR SERVICE SHALL BE AVAILABLE AT
 ACCESSIBLE TABLES WITHIN THE SAME AREA.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-12-02 Cont ID  
Sent By dpalmer Date 2008-12-02 Time 15:42 Rev Time 0.00
Received By dpalmer Date 2008-12-02 Time 15:42 Sent To  
Notes
2008-12-02 15:47:33*** PROVISO/REDLINED PLANS*****
  
 1) NOTE: CLOSET AREAS WHERE PANELS ARE LOCATED SHALL
 CONTAIN SIGNAGE ON DOORS WHICH STATES. * ELECTRICAL
 EQUIPMENT/ROOM* *NO STORAGE*, OR WORDS TO THAT AFFECT.
 THE LETTERING SHALL BE PART OF PERMANENT SIGN WITH A
 MINIMUM OF 1 INCH LETTERING ON CONTRASTING BACKGROUND.
 408.17, 240.24D, 110.26
  
 2) NOTE: SINCE SPECIFIC FIXTURES WITH RESPECT TO MODEL
 NUMBER BRAND ETC WAS NOT PROVIDED AND ONLY MAXIMUM VA
 THEN PLANS WILL NEED TO BE REVISED WITH ACTUAL FIXTURE
 AT A LATER DATE. THE MAXIMUM VA STILL SHALL MEET DESIGN
 VA OF 75WATTS OR LESS. 13-415.2.ABC.1.1, .1.2.
  
  
 ** SUITE/UNIT NUMBER WAS ADDED TO EACH SHEET. ONLY THE
 MAIN ADDRESS WAS DONE.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-10-30 Cont ID  
Sent By dpalmer Date 2008-10-30 Time 15:54 Rev Time 0.00
Received By dpalmer Date 2008-10-30 Time 15:54 Sent To PC
Notes
2008-10-30 15:54:50 
  
  
  
 ** DENIED REVIEW**
  
 1) NOTE: PLEASE PROVIDE SUITE/UNIT NUMBER ON PERMIT
 APPLICATION AND STATE ON PLANS.
 THE LOCATION AS APPLIED FOR 901 VILLAGE BLVD NEEDS
 SUITE/UNIT.
 FAC 61G1-16.004, FBC 106.5
  
 2) NOTE: PLEASE PROVIDE PLANS AND SUPPORTING
 DOCUMENTATION FOR LAYOUT OF ELECTRICAL AND FLOOR PLANS
 WHICH INDICATE MOST AS EXISTING. THE FILE OF PREVIOUS
 TENANT DOES NOT COORDINATE WITH SOME AREAS WHICH ARE
 SHOWN AS EXISTING/NO NEW WORK.
 PLEASE PROVIDE PERMITTING RECORDS FOR THESE AREAS.
  
 BASED ON RECENT ACTIVITY AT LOCATION WHICH HAS
 COMMENCED THERE IS QUESTIONS ON THE SCOPE OF WORK SHOWN
 AND THE POSSIBLE SCOPE OF WORK WHICH MAY NEED TO BE
 PERMITTED.
 105.1 FBC ADMINISTRATIVE SECTION
  
 3) NOTE: PLEASE VERIFY PANELS WHICH ARE SHOWN IN
 CLOSETS. THE PANEL *A* AND *P*
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-12-08 Cont ID  
Sent By mawillia Date 2008-12-08 Time 15:25 Rev Time 0.00
Received By mawillia Date 2008-12-08 Time 15:00 Sent To  
Notes
2008-12-08 15:25:47*****APPROVED*****
  
  
 PLAN SHEETS 1.0A AND 2.0E WERE STAMPED, INITIALED, AND
 DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2008-10-29 Cont ID  
Sent By mwennerg Date 2008-10-29 Time 15:22 Rev Time 0.00
Received By mwennerg Date 2008-10-29 Time 15:22 Sent To  
Notes
2008-10-29 15:29:40***PROVISO***
  
 1) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM REMODEL.
  
 2) IF NOT ALREADY POSTED OR IF UPDATE IS REQUIRED,
 CONTACT BUREAU OF FIRE PREVENTION AT (561) 804-4724 FOR
 OCCUPANT LOAD SIGN. IF SEATING IS NOT PERMANENT, PLEASE
 PROVIDE CALCULATION THAT ALLOWS FOR 150 PERSONS.
  
 PLANS WILL BE STAMPED WHEN RETURNED WITH OTHER REVIEW
 CORRECTIONS.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-11-14 Cont ID  
Sent By adarroug Date 2008-11-14 Time 08:18 Rev Time 0.00
Received By adarroug Date 2008-11-14 Time 08:18 Sent To  
Notes
2008-11-14 08:20:54TO "COMM" BD#26

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2008-10-30 Time   Rev Time 0.00
Received By adarroug Date 2008-10-10 Time 10:38 Sent To  
Notes
2008-10-10 10:39:10TO "COMM" BD#13

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-12-06 Cont ID  
Sent By rregueir Date 2008-12-06 Time 11:28 Rev Time 0.00
Received By rregueir Date 2008-12-06 Time 11:26 Sent To  
Notes
2008-12-06 11:28:03MECH REVIEW PREVIOUSLY PASSED BUT MECH PAGES WERE
 CHANGED SINCE LAST REVIEW. NEW MECH PAGE M3.0 REVIEWED
 AND STAMPED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-10-23 Cont ID  
Sent By tgordon Date 2008-10-23 Time 08:46 Rev Time 0.30
Received By tgordon Date 2008-10-23 Time 08:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2008-12-16 Cont ID  
Sent By kstevens Date 2008-12-16 Time 11:57 Rev Time 0.00
Received By kstevens Date 2008-12-16 Time 11:57 Sent To  
Notes
2008-12-16 12:03:46 
  
 PASSED/PROVISO
  
 PER CONTRACTOR THE DIPPER WELL, (ITEM 5), IS EXISTING
 AND THE BEVERAGE TABLE W/HAND SINK, (ITEM 31), HAS BEEN
 MOVED ON THE SAME WALL AND WILL USE EXISTING FLOOR SINK
 AND WATER SUPPLY.

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-10-27 Cont ID  
Sent By kstevens Date 2008-10-27 Time 09:49 Rev Time 0.00
Received By kstevens Date 2008-10-23 Time 15:58 Sent To  
Notes
2008-10-27 10:14:21DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 1. SHT C-1 GENERAL NOTES #1 TO INCLUDE 2007 AMENDMENTS
 TO THE FBC-2004. SECTION 106.1.1.
  
 2. SHT C-1 & 1.0A THE SCOPE OF WORK IS DIFFERENT ON
 EACH SHEET. PLEASE CORRELATE INFORMATION OF SCOPE OF
 WORK. SECTION 106.1.1.
  
 3. SHT 1.1A ITEMS 4, 5, 13, 14, 15, 16, 17, 19, 31, 35,
 36.1, 36 & 38 ARE NOT INDICATED AS EXISTING. IF THESE
 ARE NEW INSTALLATIONS, PLEASE SUBMIT REQUIRED SANITARY,
 WATER, GREASE & GAS RISERS & INFORMATION FOR ASSOCIATED
 FIXTURES/APPLIANCES. IF REPLACING FIXTURES/APPLIANCES
 IN THE EXACT LOCATIONS PLEASE INDICATE ON PLANS. IF
 REPLACING GAS APPLIANCES, GAS REQUIREMENTS ARE TO BE
 SUBMITTED. SECTIONS 106.3.5.1.3(2)(3)(4)(6)(10)(13) &
 106.3.5.2(2)(5)(6)(8)(9).
  
 4. NO PLUMBING PLANS SUBMITTED, BUT THE ICE MACHINES
 ARE INDICTED AS BEING RELOCATED TO THE KITCHEN & WAIT
 STATIONS. PLEASE INDICATE HOW THE ICE MACHINES ARE
 SUPPLIED AND HOW THEY WILL BE DRAINED. NO ICE MACHINES
 ARE SHOWN IN THE WAIT STATION. PLEASE CLARIFY. SECTIONS
 106.1.1, 602.1 & 802.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  