Plan Review Details - Permit 08100137
Plan Review Stops For Permit 08100137
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-12-01 Cont ID  
Sent By rmcdouga Date 2008-12-01 Time 16:07 Rev Time 0.00
Received By rmcdouga Date 2008-12-01 Time 16:07 Sent To  
Notes
2008-12-01 16:07:54PROCESS PLANS

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-11-25 Cont ID  
Sent By rmcdouga Date 2008-11-25 Time 12:42 Rev Time 0.00
Received By rmcdouga Date 2008-11-25 Time 12:42 Sent To P
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-10-24 Cont ID  
Sent By rmcdouga Date 2008-10-24 Time 15:38 Rev Time 0.00
Received By rmcdouga Date 2008-10-24 Time 15:38 Sent To  
Notes
2008-10-24 16:28:132004 FBC W/2007 REVISIONS
 SFD
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED. FS 713
  
 2) BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION. 233-5025
  
 3) ON SHEET A01 AND SEVERAL OTHER SHEETS THE 2006
 AMENDMENTS TO THE 2004 IS SPECIFIED. PLEASE UPDATE TO
 THE 2007 AMENDMENTS.
  
 4) THE TYPE OF CONSTRUCTION ON A02 IS INCORRECT. UNDER
 THE 2004 FBC THIS CONSTRUCTION IS TYPE VB. PLEASE
 CORRECT. SEE FBC TABLE 601.
  
 5) ON SHEET A02, PLEASE SPECIFY THE 2002 EDITIONS OF
 THE FOLLOWING STANDARDS AS LISTED IN CHAPTER 43 OF THE
 2004 FBC RESIDENTIAL. ACI 318-02, ACI 301-02 AND ASCE
 5-02.
  
 6) SPECIFY THE REQUIRED NUMBER AND SPACING OF THE
 SOFFIT VENTS ON A07. SHOW COMPLIANCE WITH FBC R806.2
 MINIMUM AREA.
  
 7) ON SHEET A08, PLEASE REVISE THE ROOF SHEATHING
 FASTENERS TO 8D RING SHANK NAILS AS REQUIRED BY FBC
 R803.2.3.1.
  
 8) THE OWNER/AGENT IS REQUIRED TO SIGN AND DATE THE
 ENERGY CALCULATION FORMS. FBC 13-600
  
 9) THE TRUSS ENGINEER'S ORIGINAL WET SIGNATURE IS
 REQUIRED ON THE TRUSS LAYOUT AND TRUSS DRAWING INDEX
 COVER SHEET. FS471 AND FAC 61G15-23.002
  
 10) SUBMIT TWO COPIES OF A SURVEY SPECIFYING THE
 LOCATION OF THE STRUCTURE FROM PROPERTY LINES,
 EASEMENTS, ETC. FBC R 302.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-11-20 Cont ID  
Sent By btrobaug Date 2008-11-20 Time 13:59 Rev Time 0.00
Received By btrobaug Date 2008-11-20 Time 13:18 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-10-08 Cont ID  
Sent By btrobaug Date 2008-10-08 Time 10:50 Rev Time 0.00
Received By btrobaug Date 2008-10-08 Time 09:41 Sent To M
Notes
2008-10-08 10:31:16 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 ALL COMMENTS RELATE TO SHEET A09, UNLESS OTHERWISE
 NOTED.
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN
 THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE
 INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS
 DESIGNED. SEE ABOVE.
  
 2} PLEASE INCLUDE THE ADDRESS OF THE PROJECT ON THE
 PLANS FOR RECORD RETENTION.106.1.3.FBC AS AMENDED.
  
 3} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT
 CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE
 EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS
 EQUAL TO OR GREATER THAN THE AVAILABLE FAULT.
  
 4} PROVIDE A PANEL SCHEDULE SO THAT BRANCH/FEEDER
 CIRCUIT CONDUCTOR AND OVER CURRENT PROTECTION
 COMPLIANCE MAY BE REVIEWED PER 408.4 NEC, 106.3.5.4 FBC
 AS AMENDED.
  
 5} LOCATE THE DISCONNECT ON THE PLAN, SEE 230.70(A)(1)
  
 6} AN EQUIPMENT GROUNDING CONDUCTOR PER 250.122 IS
 REQUIRED FROM THE DISCONNECT TO THE PANEL, NOTE SAME ON
 THE RISER.
  
 NOTE: IT DOES NOT APPEAR THAT THE PANEL LOCATION IN THE
 LAUNDRY ROOM WILL HAVE THE REQUIRED CLEARANCE (3') PER
 110.26 WHEN THE DRYER IS SET. PLEASE VERIFY.
  
 7} LABEL THE ROOMS AS PER USE ON SHEET A09. 106.1.3
 FBC.
  
 8} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A), 210.52(C), AND 210.8(A)(6) GFI.
  
 9} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1) AND
 210.52(A)(2). 2005 NEC. SEE REVIEWED PLAN FOR
 DEFICIENCIES.
  
 10} A RECEPTACLE IS REQUIRED AT THE BACK OF THE
 DWELLING PER 210.52(E).
  
 11} 210.63 HEATING, AIR-CONDITIONING, AND REFRIGERATION
 EQUIPMENT OUTLET
 A 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HEATING,
 AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED ON THE SAME LEVEL AND
 WITHIN 7.5 M (25 FT) OF THE HEATING, AIR-CONDITIONING,
 AND REFRIGERATION EQUIPMENT. THE RECEPTACLE OUTLET
 SHALL NOT BE CONNECTED TO THE LOAD SIDE OF THE
 EQUIPMENT DISCONNECTING MEANS.
  
 12} 9B-3.0472 CARBON MONOXIDE PROTECTION.
 (1) EVERY BUILDING FOR WHICH A PERMIT FOR NEW
 CONSTRUCTION IS ISSUED ON OR AFTER 7/1/08 AND HAVING A
 FOSSIL-FUEL-BURNING HEATER OR APPLIANCE, A FIREPLACE,
 OR AN ATTACHED GARAGE SHALL HAVE AN OPERATIONAL CARBON
 MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH ROOM
 USED FOR SLEEPING PURPOSES.
 (2) IN NEW CONSTRUCTION, ALARMS SHALL RECEIVE THEIR
 PRIMARY POWER FROM THE BUILDING WIRING WHEN SUCH WIRING
 IS SERVED FROM THE LOCAL POWER UTILITY. SUCH ALARMS
 SHALL HAVE BATTERY BACK UP.
 (3) COMBINATION SMOKE/CARBON MONOXIDE ALARMS SHALL BE
 LISTED OR LABELED BY A NATIONALLY RECOGNIZED TESTING
 LABORATORY.
 SPECIFIC AUTHORITY 553.885(2) FS. LAW IMPLEMENTED
 553.72, 553.73(2), (3), (7), (9), 553.885(2) FS.
 HISTORY?NEW 11-18-07 LOCATE DETECTORS ON THE PLAN.
 NOTE: MAY BE COMBINATION SMOKE/CARBON MONOXIDE.
  
 LOCATE DETECTORS ON THE PLAN IF APPLICABLE. NOTE: MAY
 BE COMBINATION SMOKE/CARBON MONOXIDE
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-12-18 Cont ID  
Sent By adarroug Date 2008-12-18 Time 12:46 Rev Time 0.00
Received By adarroug Date 2008-12-18 Time 12:46 Sent To Z
Notes
2008-12-18 12:46:27TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-11-13 Cont ID  
Sent By adarroug Date 2008-11-13 Time 11:27 Rev Time 0.00
Received By adarroug Date 2008-11-13 Time 11:27 Sent To Z
Notes
2008-11-13 11:27:47TO "Z" BOX/RESUB--NEW "Z" SHEET SUBMITTED

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-10-22 Cont ID  
Sent By adarroug Date 2008-10-22 Time 10:30 Rev Time 0.00
Received By adarroug Date 2008-10-22 Time 10:30 Sent To B
Notes
2008-10-22 10:30:40TO "SFR" "B"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-10-24 Cont ID  
Sent By rmcdouga Date 2008-10-24 Time 16:31 Rev Time 0.00
Received By rmcdouga Date 2008-10-07 Time 16:08 Sent To  
Notes
2008-10-07 16:08:22TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-11-22 Cont ID  
Sent By rregueir Date 2008-11-22 Time 09:46 Rev Time 0.00
Received By rregueir Date 2008-11-22 Time 09:46 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-10-08 Cont ID  
Sent By tgordon Date 2008-10-08 Time 12:11 Rev Time 0.45
Received By tgordon Date 2008-10-08 Time 11:57 Sent To Z
Notes
2008-10-08 12:08:57PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) ONLY ONE PAGE OF THE COOLING LOAD CALCULATIONS WAS
 SUBMITTED FOR REVIEW, SUBMIT ALL OF THE COOLING LOAD
 CALCULATIONS, PER 2004 FBC 13-607.1.ABC.1.
  
 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-103.3.
  
 3) THE MECHANICAL PLAN SHOWS THE CONDENSER UNIT IN A
 DIFFERENT LOCATION THAN THE BUILDING AND ELECTRICAL
 PLAN, PLEASE CORRECT.
  
 4) CLOTHES DRYER VENT MAY NOT TERMINATE NEAR THE A/C
 CONDENSER UNIT, PER 2004 FBC/R R303.4.2. PLEASE CORRECT
 BUILDING, ELECTRICAL AND MECHANICAL PLANS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-12-01 Cont ID  
Sent By kstevens Date 2008-12-01 Time 11:41 Rev Time 0.00
Received By kstevens Date 2008-12-01 Time 11:41 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-10-22 Cont ID  
Sent By mperson Date 2008-10-23 Time 16:41 Rev Time 1.30
Received By mperson Date 2008-10-22 Time 16:40 Sent To B
Notes
2008-10-22 16:58:57PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET A01 IS INDICATING THE WRONG CODE CYCLE OF
 FBC-2004 WITH 2006 AMENDMENTS. PLEASE KNOW THAT THE
 CORRECT CODE CYCLE IS FBC-2004 WITH 2007 REVISIONS. PER
 FBC-2004 CHAPTER 1, (W.P.B. AS AMENDED) SECTION 106.5
 RECORD RETENTION.
  
 2. PLEASE INCLUDE THE ADDRESS ON ALL PLAN SHEETS. PER
 FBC-2004 CHAPTER 1, (W.P.B. AS AMENDED) SECTION 106.1.1
 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 3. ENERGY CALCULATIONS NEED TO BE SIGNED BY
 OWNER/AGENT. PER FBC-2003 CHAPTER 13, SECTION 13-103.3
 BUILDING PERMITS.
  
 4. SHEET A04 PLUMBING RISER: THE FOLLOWING ITEMS NEED
 TO BE CORRECTED PER THE FBC-2004 PLUMBING CODE
 SECTIONS.
  
 A} BATH 2: THE BATHTUB IS NOT VENTED. PLEASE REVISE PER
 THE RED LINE CORRECTIONS. PER SECTION 901.2.1 VENTING
 REQUIRED.
  
 B} PLEASE LOCATE THE REQUIRED CLEANOUT FOR THE WASHING
 MACHINE TO BE LOCATED AT FOUR FEET ABOVE FINNISH FLOOR
 (4' A.F.F.) FOR ACCESS. PER SECTION 708.9 ACCESS.
  
 C} CLEARLY INDICATE THE REQUIRED STANDPIPE FOR THE
 WASHING MACHINE DRAIN ABOVE THE TRAP WEIR. PER SECTION
 406.3 WASTE CONNECTIONS.
  
 D} CLEARLY INDICATE THE CLEANOUT AT THE JUNCTION OF THE
 BUILDING DRAIN AND BUILDING SEWER AS BEING A TWO-WAY
 CLEANOUT. PER SECTION 708.3.5 BUILDING DRAIN AND
 BUILDING SEWER JUNCTION.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 *PLEASE CALL IF THERE ARE ANY QUESTIONS.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2008-12-18 Cont ID  
Sent By mflis Date 2008-12-18 Time 13:32 Rev Time 0.00
Received By mflis Date 2008-12-18 Time 13:32 Sent To B
Notes
2008-12-18 13:34:06ZONING REVIEW: PASSED WITH PROVISO:
  
 ** ADJUSTED FRONT SETBACK ONLY; NO OTHER MODIFICATIONS.
 ** SEE PREVIOUS PROVISO NOTES FOR LANDSAPING
 INSTALLATION
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 2 Status P Date 2008-11-19 Cont ID  
Sent By mflis Date 2008-11-19 Time 09:23 Rev Time 0.00
Received By mflis Date 2008-11-19 Time 09:23 Sent To  
Notes
2008-11-19 09:25:27ZONING REVIEW: PASSED WITH PROVISO:
  
 1) SOD AND IRRIGATION SHALL BE PROVIDED IN THE
 RIGHT-OF-WAY ADJACENT TO PROPERTY.
 2) CONFIRM LOCATIONS OF ANY OVERHEAD LINES AND
 COORDINATE TREE PLACEMENT IF NECESSARY (RIGHT TREE,
 RIGHT PLACE).
 3) NO MORE THAN 1" LAYER OF MULCH SHALL BE APPLIED OVER
 THE ROOT BALL OF TREES.
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 1 Status P Date 2008-10-20 Cont ID  
Sent By mflis Date 2008-10-20 Time 14:33 Rev Time 0.00
Received By mflis Date 2008-10-20 Time 14:32 Sent To  
Notes
2008-10-20 15:01:42ZONING REVIEW: PASSED WITH PROVISO
  
 ** FOLLOWING COMMENTS SHALL BE ADDRESS UPON RESUBMITTAL
 OR REVISION:
  
 1) PLEASE CONFIRM COMPLIANCE WITH SEC. 94-482 WHICH
 REQUIRES THE LESSER OF 1,000 SF OR 75% OF FRONT YARD
 SHALL BE LANDSCAPED. IF NECESSARY, PAVED AREAS FOR
 PARKING MAY NEED TO BE REDUCED. PROVIDE CALCULATIONS
 REGARDING COMPLIANCE.
  
 2) PLEASE PROVIDE LANDSCAPE PLAN INDICATING COMPLIANCE
 WITH SEC. 94-442 (2)(A) REQUIRING ONE SHADE, FLOWERING,
 OR FRUIT TREE FOR EACH 1,200 SF OF OPEN SPACE OR
 PORTION THEREOF. ONE SHRUB SHALL BE PLANTED FOR EACH
 500 SF OF OPEN SPACE OR PORTION THEREOF.
  
 3) ANY FENCING SHALL BE SUBMITTED UNDER A SEPARATE
 PERMIT. FENCES SHALL BE NO MORE THAN 4'-0" IN HEIGHT
 WITHIN THE FRONT SETBACK AND NO MORE THAN 6'-0" IN
 HEIGHT AT ALL OTHER LOCATIONS.
  
 4) COMPLETE SURVEY SHOULD BE SUBMITTED WITH PERMIT.
  
 MATT FLIS - 822-1445
  