Plan Review Details - Permit 08100061
Plan Review Stops For Permit 08100061
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-12-15 Cont ID  
Sent By shill Date 2008-12-15 Time 09:47 Rev Time 0.00
Received By shill Date 2008-12-15 Time 09:47 Sent To  
Notes
2008-12-15 09:47:26PROVISO - IN ACCORDANCE WITH FBC1008.1.3.5

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-10-17 Cont ID  
Sent By shill Date 2008-10-17 Time 16:39 Rev Time 0.00
Received By shill Date 2008-10-17 Time 16:39 Sent To  
Notes
2008-10-17 16:40:58****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
  
 1. OPENING 6, C4 CONNECTION, 77PSF (YOU HAVE SPECIFIED
 -75 PSF FOR DESIGN PRESSURE ON INSTALLATION SCHEDULE)
 REQUIRES 7" SPACING, NOT 18". PLEASE CHECK ALL
 OPENINGS. NOTE THAT YOU HAVE USED THE ROW FOR 47.2, BUT
 THIS DOES NOT MEET THE DESIGN PRESSURE REQUIREMENTS
 STATED ON THE INSTALLATION SCHEDULE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-10-07 Cont ID  
Sent By shill Date 2008-10-07 Time 10:57 Rev Time 0.00
Received By shill Date 2008-10-07 Time 10:57 Sent To  
Notes
2008-10-07 11:02:21****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. THE INSTALLATION SCHEDULE PROVIDED DOES NOT
 CORRELATE WITH THE PRODUCT APPROVAL. CONCRETE HAS BEEN
 SPECIFIED, BUT THIS CHART HAS BEEN CROSSED OFF ON THE
 PRODUCT APPROVAL. ANCHOR SPACING OF 6", 3" EDGE
 DISTANCE CIRCLED. PLEASE REVISE SO THE TWO ARE
 CONSISTENT.
  
 2. THE INSTALLATION SCHEDULE, SUBSTRATE, SPECIFIES WOOD
 FOR OPENINGS 1 THROUGH 6, BUT IN EDGE DISTANCE COLUMN
 STATES THIS IS WOOD/CONCRETE. PLEASE REVISE SO THAT THE
 SUBSTRATE INFORMATION IS CORRECT FOR EACH OPENING. CODE
 COMPLIANCE CANNOT BE DETERMINED DUE TO THE FACT THAT
 THIS INFORMATION HAS BEEN CROSSED OFF ON SHEET 7 OF THE
 PRODUCT APPROVAL; IT IS NOT CLEAR IF THE SUBSTRATE IS
 CONCRETE BLOCK AS INDICATED ON THE PRODUCT APPROVAL, OR
 WOOD AND CONCRETE AS STATED IN THE EDGE DISTANCE
 COLUMN, OR WOOD AS STATED IN SUBSTRATE COLUMN.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-12-09 Cont ID  
Sent By adarroug Date 2008-12-09 Time 09:26 Rev Time 0.00
Received By adarroug Date 2008-12-09 Time 09:26 Sent To B
Notes
2008-12-09 09:27:16TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-10-17 Cont ID  
Sent By adarroug Date 2008-10-17 Time 11:35 Rev Time 0.00
Received By adarroug Date 2008-10-17 Time 11:35 Sent To B
Notes
2008-10-17 11:35:25TO "SHILL' DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-10-07 Cont ID  
Sent By shill Date 2008-10-07 Time 11:02 Rev Time 0.00
Received By shill Date 2008-10-06 Time 08:55 Sent To  
Notes
2008-10-06 08:56:09TO "MISC" BOX#1