| 2008-10-09 11:37:33 | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. PLEASE CLEARLY INDICATE THE BUILDING CLASSIFICATION |
| | AND OCCUPANCY LOAD ON THE PLANS. |
| | PER FBC BUILDING SECTION 302.1 GENERAL. STRUCTURES OR |
| | PORTIONS OF STRUCTURES SHALL BE CLASSIFIED WITH RESPECT |
| | TO OCCUPANCY IN ONE OR MORE OF THE GROUPS LISTED BELOW. |
| | |
| | A} ASSEMBLY (SEE SECTION 303): GROUPS A-1, A-2, A-3, |
| | AND A-5 |
| | |
| | B} BUSSINESS (SEE SECTION 304): GROUP B |
| | |
| | C} EDUCATIONAL (SEE SECTION 305): GROUP E |
| | |
| | D} FACTORY AND INDUSTRIAL (SEE SECTION 306): GROUPS F-1 |
| | AND F-2 |
| | |
| | E} HIGH HAZARD (SEE SECTION 307) GROUPS H-1, H-2, H-3, |
| | H-4, AND H-5 |
| | |
| | F} INSTITUTIONAL (SEE SECTION 308): GROUP I-1, I-2, AND |
| | I-3 |
| | |
| | G} MERCANTILE (SEE SECTION 309): GROUP M |
| | |
| | H} RESIDENTIAL (SEE SECTION 310): GROUPS R-1, R-2, R-3 |
| | AS APPLICABLE IN SECTION 101.2, AND R-4 |
| | |
| | I} STORAGE (SEE SECTION 311): GROUPS S-1 AND S-2 |
| | |
| | J} UTILITY AND MISCELLANEOUS (SEE SECTION 312): GROUP U |
| | |
| | K} DAY CARE (SEE SECTION 313): GROUP D |
| | |
| | 2. CLEARLY INDICATE THE CODE CYCLE ON THE PLANS. PER |
| | CITY OF WPB AMENDMENTS TO CHAPTER 1, (W.P.B. AS |
| | AMENDED) SECTION 106.5 RETENTION OF CONSTRUCTION |
| | DOCUMENTS. |
| | THE CURRENT CODE CYCLE FOR THE PLANS IS "FBC-2004 WITH |
| | 2007 REVISIONS". |
| | |
| | 3. DECLARE THE LEVEL OF ALTERATION, PER FBC-2004 |
| | EXISTING BUILDING CHAPTER 3. |
| | |
| | 4. SHEET A-4.01.3, BREAK AREA ELEVATION: CLEARLY |
| | INDICATE THE FOLLOWING REQUIREMENTS TO THE BREAK AREA |
| | SINK PER THE FBC-2004 CHAPTER 11, FLORIDA ACCESSIBILITY |
| | CODE SECTIONS. |
| | |
| | A} SECTION 11-4.24.3 KNEE CLEARANCE. MINIMUM 27" HIGH, |
| | 30" WIDE, AND 19" DEEP. |
| | |
| | B} SECTION 11-4.24.5 CLEAR FLOOR SPACE. 30" X 48" AND |
| | CLEAR FLOOR SPACE SHALL EXTEND A MAXIMUM OF 19" |
| | UNDERNEATH THE SINK. |
| | |
| | C} SECTION 11-4.24.6 EXPOSED PIPES AND SURFACES. |
| | INSULATE TO PROTECT AGAINST CONTACT. |
| | |
| | 5. SHEET A-1.00-1 FLOOR PLAN: CLEARLY INDICATE THE |
| | REQUIRED TURNING SPACE FOR PEOPLE IN WHEELCHAIRS FOR |
| | THE BREAK AREA ROOM #103. PER THE FBC-2004 CHAPTER 11, |
| | FLORIDA ACCESSIBILITY CODE SECTION 11-4.22.3 CLEAR |
| | FLOOR SPACE. WHEELCHAIR TURNING SPACE SHALL BE |
| | 180-DEGREE WITH A MINIMUM 60" CLEAR FLOOR SPACE. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |