Plan Review Details - Permit 08100024
Plan Review Stops For Permit 08100024
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-10-07 Cont ID  
Sent By btrobaug Date 2008-10-07 Time 11:10 Rev Time 0.00
Received By btrobaug Date 2008-10-07 Time 11:06 Sent To M
Notes
2008-10-07 11:09:57 
  
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 AN ELECTRICAL PERMIT IS REQUIRED FOR THE SCOPE OF WORK
 105.1 FBC AS AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-10-07 Cont ID  
Sent By tgordon Date 2008-10-07 Time 12:07 Rev Time 0.00
Received By tgordon Date 2008-10-03 Time 14:37 Sent To  
Notes
2008-10-03 14:40:21TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-10-07 Cont ID  
Sent By tgordon Date 2008-10-07 Time 12:00 Rev Time 1.30
Received By tgordon Date 2008-10-07 Time 12:00 Sent To  
Notes
2008-10-07 12:05:51*** PROVISO ***
 1) PER 2004 FBC/M 407 RETURN AIR INTAKE. IT SHALL BE
 PROHIBITED TO PLACE A RETURN AIR INTAKE IN THE
 FOLLOWING LOCATIONS: PUBLIC BATHROOMS, AND NONDEDICATED
 KITCHEN HVAC SYSTEMS.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]