| 2008-10-02 11:59:17 | GAS PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE AND THE CITY OF |
| | WEST PALM BEACH GAS PERMIT APPLICATION REQUIREMENTS. |
| | PLEASE REFERENCE THE CITY OF WEST PALM BEACH GAS PERMIT |
| | APPLICATION REQUIREMENTS ATTACHED TO THESE COMMENTS TO |
| | HELP IN FUTURE PERMIT APPLICATIONS. |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE SECTION 401.1 SCOPE. |
| | *NOTE: NOT ALL CUT SECTIONS OF PIPE HAVE CORRESPONDING |
| | LENGTHS INDICATED ON THE SUBMITTED GAS ISOMETRIC. |
| | PLEASE REFERENCE THE YELLOW HIGH LIGHTED CUT SECTIONS |
| | WITH NO CORRESPONDING LENGTHS AND COMPLY ON THE |
| | RESUBMITTAL. |
| | |
| | 2. PLEASE CLEARLY INDICATE THE TYPE OF GAS, (LP OR |
| | NATURAL) BEING USED ON THE RESUBMITTED GAS ISOMETRIC. |
| | PER FBC-2004 FUEL GAS CODE SECTION 401.1 SCOPE. |
| | |
| | 3. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | *NOTE: PLEASE REFERENCE COMMENT #1 AND ALSO CLEARLY |
| | INDICATE THE GAS METER LOCATION ON THE RESUBMITTED |
| | ISOMETRIC. |
| | |
| | 4. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR FOR THE WATER HEATER. PER FBC-2004 FUEL |
| | GAS CODE SECTION 304. |
| | |
| | 5. PLEASE CLEARLY INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. NATURAL GAS |
| | SPECIFY .5 PSI OR 2 PSI. LP GAS SPECIFY 10 PSI. PER |
| | FBC-2004 FUEL GAS CODE SECTION 401.1 SCOPE. |
| | NOTE: PLEASE KNOW THAT IF THE GAS TYPE IS NATURAL GAS |
| | AND THE DELIVERY PRESSURE IS 0.5 PSI THE SUBMITTED GAS |
| | ISOMETRIC PIPING IS SIZED WRONG PER FBC-2004 FUEL GAS |
| | TABLE 402.4(8). PLEASE REFERENCE THIS GAS TABLE AND THE |
| | RED LINE CORRECTIONS ON THE GAS ISOMETRIC. |
| | |
| | 6. CLEARLY INDICATE THE TYPE OF COPPER TUBING BEING |
| | USED AS BEING EITHER TYPE K OR L. PER FBC-2004 FUEL GAS |
| | SECTION 403.5.2 COPPER AND BRASS TUBING. |
| | |
| | 7. THE VALUE ON THE PERMIT APPLICATION APPEARS LOW. THE |
| | VALUE ON THE PERMIT APPLICATION MUST INCLUDE THE TOTAL |
| | COST OF LABOR, MATERIALS AND DESIGN. THE REFERENCED |
| | MASER PERMIT #08050395 PLANS HAVE NO INDICATION OF ANY |
| | GAS WORK BEING DONE. THE GAS PERMIT VALUE APPEARS TO BE |
| | FOR THE PIPING MATERIAL, LABOR AND DESIGN, HOWEVER THE |
| | COST OF THE WATER HEATER AND STOVE ARE NOT ON THE |
| | VALUE. PLEASE KNOW THAT THE POOL HEATER WAS APPROVED ON |
| | POOL PERMIT #08060195 AND ITS VALUE DOES NOT NEED TO BE |
| | ADDED TO THIS PERMIT JUST THE STOVE AND WATER HEATER. |
| | PER (W.P.B AS AMENDED) SECTION 108.3 BUILDING PERMIT |
| | VALUATION. IF, IN THE OPINION OF THE BUILDING OFFICIAL, |
| | THE CLAIMED VALUATION OF BUILDING, ALTERATION, |
| | STRUCTURAL, ELECTRICAL, GAS, MECHANICAL OR PLUMBING |
| | SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE |
| | APPLICATION, THE PERMIT SHALL BE DENIED. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |