| 2008-10-20 10:33:11 | BUILDING PLAN REVIEW |
| | PERMIT: |
| | ADD: |
| | CONT: |
| | TEL: (561)###-#### |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS, |
| | PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR |
| | SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL |
| | REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A |
| | THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN |
| | (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED |
| | FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS |
| | WEST PALM BEACH ADMINISTRATIVE CODE. |
| | |
| | 1C) INFORMATIONAL 106.1.1* W.P.B. ADMINISTRATIVE |
| | CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN |
| | INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO |
| | THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO |
| | CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION |
| | SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE |
| | CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR |
| | ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. PLANS SUBMITTED |
| | ARE COPIED PLANS PLEASE PROVIDE ORIGINAL PLANS AND |
| | INDICATE THE AUTHOR OF THE PLANS WITH TELEPHONE NUMBER. |
| | |
| | 1D ) INFORMATIONAL FL S S 713.13 NOTICE OF |
| | COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT. |
| | NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS |
| | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & |
| | VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| | INSPECTION. |
| | |
| | 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) |
| | AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| | BUILDING WITH THE 2007 SUPPLEMENTS. |
| | |
| | 1F) VALUE FOR GENERATOR, TRANSFER SWITCH, 100 GALLON |
| | DEISEL TANK AND SLAB IS EXTREMELY LOW, THE FAIR MARKET |
| | VALUE WILL BE ASSESSED USING MARSHAL & SWIFT OR ICC |
| | VALUATIONS. |
| | W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES. |
| | ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL, |
| | AND PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT, |
| | A FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN |
| | ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE |
| | APPLICABLE GOVERNING AUTHORITY. |
| | |
| | 108.3* BUILDING PERMIT VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | 2) MISSING WIND INFORMATION: 1603.1.4 WIND DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE |
| | BUILDING: |
| | 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR |
| | (KM/HR). |
| | |
| | 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING |
| | CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7 |
| | AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. |
| | |
| | 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS |
| | UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND |
| | DIRECTION SHALL BE INDICATED. |
| | |
| | 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF |
| | DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES |
| | IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION |
| | OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT |
| | SPECIFICALLY DESIGNED BY THE REGISTERED |
| | DESIGN PROFESSIONAL. |
| | |
| | 3) SLAB CUT SHEET HAS INDICATED 1/2 INCH LAG BOLTS INTO |
| | PAD. THE PLANS DO NOT INDICATE THE QUANTITY OF BOLTS TO |
| | BE USED, LOCATION OF LAG BOLTS, LENGHT OF LAG BOLTS |
| | WITH NOT HAVING THE LOCATON OF LAG BOLTS KNOWN IF |
| | DERATING VALUES WOULD BE A CONCERN. 1609.1.3. ANCHORAGE |
| | AGAINST OVERTURNING, UPLIFT AND SLIPPAGE. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | |
| | |