Plan Review Details - Permit 08090760
Plan Review Stops For Permit 08090760
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-11-19 Cont ID  
Sent By shill Date 2008-11-19 Time 09:57 Rev Time 0.00
Received By shill Date 2008-11-19 Time 09:57 Sent To  
Notes
2008-11-19 10:00:54****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. SEE PREVIOUS LIST; WIND DESIGN CRITERIA REQUIRED ON
 THE PLAN FBC1609.6.2.
  
 2. SEE PREVIOUS LIST, EDGE DISTANCE NOT SPECIFIED FOR
 WEDGE ANCHORS.
  
 3. LENGTH OF WEDGE ANCHORS NOT SPECIFIED.
  
 4. SEE PREVIOUS LIST, FBC1609.1.3, ANCHORAGE AGAINST
 UPLIFT, OVERTURNING AND SLIPPAGE NOT DEMONSTRATED.
 PROVIDE ENOUGH INFORMATION (SPEC SHEETS, CALCULATIONS,
 ETC.) TO SHOW THAT THE PROPOSED DESIGN WILL RESIST ALL
 REQUIRED LOADS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-10-15 Cont ID  
Sent By jwitmer Date 2008-10-15 Time 14:11 Rev Time 0.77
Received By jwitmer Date 2008-10-15 Time 14:11 Sent To  
Notes
2008-10-15 14:13:30BUILDING PLAN REVIEW
 PERMIT: 08090760
 ADD: 1220 OKEECHOBEE RD
 CONT: ARMOUR BUILDERS
 TEL: (561)222-6864
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C) INFORMATIONAL 106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. THERE IS NO TITLE
 BLOCK PROVIDING INFORMATION AS TO WHO IS THE DESIGNER
 OF RECORD FOR THIS PLAN, NO CONTACT NUMBER.
  
 1D ) INFORMATIONAL FL S S 713.13 NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS.
  
 2) CONTRACTOR IS WORKING OUT OF SCOPE OF LICENSE: FL S
 S 489.105(3)(C) "RESIDENTIAL CONTRACTOR" MEANS A
 CONTRACTOR WHOSE SERVICES ARE LIMITED TO CONSTRUCTION,
 REMODELING, REPAIR, OR IMPROVEMENT OF ONE-FAMILY,
 TWO-FAMILY, OR THREE-FAMILY RESIDENCES NOT EXCEEDING
 TWO HABITABLE STORIES ABOVE NO MORE THAN ONE
 UNINHABITABLE STORY AND ACCESSORY USE STRUCTURES IN
 CONNECTION THEREWITH.
  
 3) MISSING WIND INFORMATION: 1609.6.2 WIND DESIGN
 PROCEDURES
 1) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE
 ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION.
  
 2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN
 ACCORDANCE WTIH SECTION1609.5.
  
 3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4.
  
 4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4)
  
 4) PLANS DO NOT PROVIDE DIMENSIONS BETWEEN ANCHOR BOLTS
 NOR THE EDGE DISTANCE THE WEDGE ANCHORS SHALL BE PLACED
 APART, 1609.1.3. ANCHORAGE AGAINST UPLIFT, OVERTURNING
 AND SLIPPAGE.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2008-10-09 Cont ID  
Sent By lfranco Date 2008-10-09 Time 16:04 Rev Time 0.00
Received By lfranco Date 2008-10-09 Time 16:04 Sent To  
Notes
2008-10-09 16:05:48PLANNING AND ZONING: **** FAILED- COMMENTS MADE FOR
 MASTER PERMIT 08090686 ****
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. THE SURVEY MUST BE SIGNED AND SEALED, AND NOT BE
 OLDER THAN 1 YEAR.
  
 3. PURSUANT TO SECTION 94-444(B) OF THE ZONING CODE,
 THE GENERATOR MUST BE SCREENED AND LANDSCAPED PER THE
 REQUIREMENTS BELOW:
  
 (B) *** GENERATORS SHALL NOT BE PERMITTED UNLESS
 APPROPRIATE SCREENING IS PROVIDED. SCREENING SHALL BE
 CONSTRUCTED OF BRICK, DECORATIVE CONCRETE, OTHER
 DECORATIVE MASONRY, OR COMPARABLY, DURABLE WOOD AND
 STEEL.
  
 WALLS/FENCES SHALL BE LANDSCAPED WITH SHRUBS AND HEDGES
 PLANTED AT TWO-FOOT INTERVALS. A FOUR-SIDED ENCLOSURE
 WITH MASONRY, OR COMPARABLY DURABLE WOOD AND STEEL, AN
 OBSCURING GATE IS REQUIRED AS A CONDITION FOR SITE PLAN
 APPROVAL.
  
  
 PER THE COMMENTS MADE BY KELLY FREEMAN ON A PREVIOUS
 PERMIT APPLICATION TO INSTALL A GENERATOR, PLEASE
 PROVIDE LOCATION OF PARKING. THE FOLLOWING ARE COMMENTS
 MADE IN 2/16/07 AND 6/19//07 (PERMIT NUMBER: 07020089)
 THAT ARE STILL APPLICABLE:
  
 4. IT WOULD BE IN YOUR BEST INTEREST TO DESIGN A
 COMBINATION GENERATOR/DUMPSTER ENCLOSURE. PRESENTLY,
 CODE ENFORCEMENT IS ISSUING CITATIONS FOR UNSCREENED
 DUMPSTERS THROUGHOUT THE CITY. THIS REPRESENTS A GOOD
 OPPORTUNITY TO TAKE CARE OF THE PROBLEM BEFORE CODE
 ENFORCEMENT COMES THROUGH YOUR AREA.
  
 5. AS THE GENERATOR IS PROPOSED TO BE PLACED IN THE
 PARKING AREA, PLEASE SHOW THE NUMBER OF PARKING SPACES
 PROVIDED BEFORE, AND AFTER THE INSTALLATION OF THE
 GENERATOR. NOTE THAT YOU ARE REQUIRED TO PROVIDE SIX
 (6) PARKING SPACES, INCLUDING ONE HANDICAP ACCESSIBLE
 PARKING SPACE. PROVIDE LOCATION OF PARKING SPACES TO
 COMPLY WITH THESE REQUIREMENTS. I HAVE ATTACHED A COPY
 OF THE CITY?S STANDARD STRIPING PARKING AND DUMPSTER
 ENCLOSURE DETAILS FOR YOUR USE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  