| 2008-09-30 16:30:26 | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | 1. PLEASE KNOW THAT THERE IS NO APPROVED PLUMBING ON |
| | MASTER PERMIT #08070214, WHICH IS REFERENCED ON THE |
| | PLUMBING PERMIT APPLICATION. PLEASE KNOW THAT MASTER |
| | PERMIT #08070214 IS FOR STRUCTURAL ONLY. PLEASE KNOW |
| | THAT ON SHEET 3 OF 3, ON MASTER PERMIT #08070214, IT |
| | CLEARLY INDICATES IN FOUR PLACES THAT "ALL ELECTRICAL |
| | AND PLUMBING WORK BY OTHERS". PLEASE SUBMIT PLANS FOR |
| | THE PROPOSED PLUMBING WORK CLEARLY INDICATING THE |
| | FOLLOWING REQUESTED INFORMATION COMPLIANT WITH THE |
| | FBC-2004 PLUMBING CODE SECTIONS. |
| | |
| | A} PLEASE INDICATE THE LOCATION OF THE PROPOSED |
| | PLUMBING WORK OF THE (2) DOCK PEDESTALS ON A SITE OR |
| | SURVEY PLAN. CLEARLY INDICATE IF THE PROPOSED WORK IS |
| | BEING INSTALLED TO AN EXISTING SYSTEM. CLEARLY INDICATE |
| | THE POINT OF CONNECTION TO THE EXISTING (IF APPLICABLE) |
| | SYSTEM. PER SECTION 601.1 SCOPE. |
| | |
| | B} PLEASE SUBMIT AN ISOMETRIC POTABLE WATER DIAGRAM |
| | THAT CLEARLY INDICATES THE PIPE MATERIAL, PIPE SIZES, |
| | VALVE LOCATIONS, RPZV BACKFLOW PREVENTER LOCATION |
| | (CLEARLY INDICATE IF THE RPZV BACK FLOW PREVENTER IS |
| | EXISTING OR NEW) AND HOW THE PIPING WILL BE SUPPORTED. |
| | PER SECTION 601.1 SCOPE AND (W.P.B. AS AMENDED) SECTION |
| | 106.3.5.1.3 PLUMBING (3), (8), (10), AND (13). |
| | |
| | 2. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING |
| | DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE |
| | PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE |
| | ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER |
| | SECTION *106.3.4.3. |
| | IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR ENGINEER, |
| | THEN HE OR SHE SHALL AFFIX HIS OR HER OFFICIAL SEAL, |
| | SIGNATURE AND DATE TO SAID DRAWINGS, PER FLORIDA |
| | STATUTES 481 AND 471 RESPECTIVELY. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL: [email protected] |