Plan Review Details - Permit 08090690
Plan Review Stops For Permit 08090690
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2008-10-03 Cont ID  
Sent By mjacobs Date 2008-10-03 Time 10:22 Rev Time 0.00
Received By mjacobs Date 2008-10-03 Time 10:05 Sent To  
Notes
2008-10-03 10:11:24 
  
 PROVISOR: FBC 105.9 EACH BUILDING PERMIT FOR DEMOLITION
 OR RENOVATION SHALL CONTAIN AN ASBESTOS NOTIFICATION
 STATEMENT HOLDING THE OWNER OR OPERATOR RESPONSIBLE TO
 COMPLY WITH FLORIDA STATUTES 469.003. THE OWNER OR
 OPERATOR SHALL NOTIFY THE DEPT. OF ENVIRONMENTAL
 PROTECTION WHEN REMOVING ASBESTOS WHEN APPLICABLE, IN
 ACCORDANCE WITH STATE AND FEDERAL LAW.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-10-06 Cont ID  
Sent By btrobaug Date 2008-10-06 Time 13:32 Rev Time 0.00
Received By btrobaug Date 2008-10-06 Time 13:29 Sent To  
Notes
2008-10-06 13:32:11 
  
  
  
  
 PROVISO
 PLEASE NOTE AN ELECTRICAL PERMIT IS REQUIRED FOR THE
 SCOPE OF WORK PURPOSED. 105.1 FBC AS AMENDED. AN
 ELECTRICAL CONTRACTOR MUST REMOVE ALL WIRING IN
 AFFECTED AREAS FOR DEMOLITION AND MAKE SAFE SAME. ALL
 TEMPORARY WIRING FOR THIS DEMOLITION SHALL COMPLY WITH
 ARTICLE 590 NEC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2008-10-07 Cont ID  
Sent By mwennerg Date 2008-10-07 Time 15:18 Rev Time 0.00
Received By mwennerg Date 2008-10-07 Time 15:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-10-09 Cont ID  
Sent By adarroug Date 2008-10-09 Time 16:50 Rev Time 0.00
Received By adarroug Date 2008-09-29 Time 14:55 Sent To  
Notes
2008-09-29 15:13:05TO "BOB"#8

Review Stop P PLUMBING
Rev No 1 Status P Date 2008-10-01 Cont ID  
Sent By mperson Date 2008-10-01 Time 09:17 Rev Time 0.30
Received By mperson Date 2008-10-01 Time 09:17 Sent To  
Notes
2008-10-01 09:20:33******PROVISO******
 PER FBC-2004 PLUMBING, SECTION 704.5 DEAD ENDS: IN
 REMOVAL OF ANY PART OF A DRAINAGE SYSTEM, DEAD ENDS
 SHALL BE PROHIBITED. A PLUMBING PERMIT IS REQUIRED AND
 AN INSPECTION IS REQUIRED OF PLUMBING DEMO WORK PRIOR
 TO COVERING DEMO WORK WITH FINNISH WALLS, CIELINGS, OR
 POURED CONCRETE SLABS.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2008-10-09 Cont ID  
Sent By kdfreema Date 2008-10-09 Time 11:19 Rev Time 0.00
Received By kdfreema Date 2008-10-09 Time 11:19 Sent To  
Notes
***NONE***