Plan Review Details - Permit 08090686
Plan Review Stops For Permit 08090686
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-11-19 Cont ID  
Sent By shill Date 2008-11-19 Time 10:01 Rev Time 0.00
Received By shill Date 2008-11-19 Time 10:01 Sent To  
Notes
2008-11-19 10:01:59****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 PLANS REVIEWED UNDER 08090760
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-10-21 Cont ID  
Sent By jwitmer Date 2008-10-21 Time 14:07 Rev Time 0.22
Received By jwitmer Date 2008-10-21 Time 14:06 Sent To PC
Notes
2008-10-21 14:06:58SEE COMMENTS UNDER 08090760- GENERAOR SLAB

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-11-10 Cont ID  
Sent By dpalmer Date 2008-11-10 Time 13:34 Rev Time 0.00
Received By dpalmer Date 2008-11-10 Time 13:33 Sent To  
Notes
2008-11-10 13:34:22 
 1) NOTE: PLEASE SEE FS 527.02 AS THE PRIME CONTRACTOR
 AS APPLIED ON PERMIT APPLICATION IS THE ELECTRICAL
 CONTRACTOR. IF LICENSED TO SELL AND INSTALL GAS
 GENERATORS ETC, PLEASE SUPPLY LICENSE INFORMATION.
 PLEASE VERIFY MULTIPLE LICENSES REQUIRED BY THE
 DEPARTMENT OF AGRICULTURE IN ORDER TO SELL, INSTALL ETC
 GAS APPLIANCES.
 IF NOT LICENSED THE PRIME CONTRACTOR IS REQUIRED TO BE
 THE GAS CONTRACTOR OR OBTAIN LICENSING AS REQUIRED.
  
 2) NOTE: PLEASE COMPLETE RISER WITH ALL CONDUCTORS. THE
 NUMBER OF PARALLEL CONDUCTORS, MISSING EQUIPMENT
 GROUNDING CONDUCTORS, AIC RATINGS FOR ALL NEW
 EQUIPMENT, AND GROUNDING ELECTRIC SYSTEM
 250.50,250.58, 20.56, 110.9, 250.24, 250.110, 250.122
 ETC.
  
 3) NOTE: PLEASE VERIFY WITH FPL THAT ALL METERING AS
 SHOWN NOW ON THE LOAD SIDE OF THE ATS IS PERMITTED.
 PLEASE SEE FPL SERVICE STANDARDS AVAILABLE ON-LINE AT
 FPL.COM.
 A LETTER FROM FPL IS ACCEPTABLE FOR SERVICE AS SHOWN
 WITH NO METERING AS SHOWN ON THE LOAD SIDE OF THE ATS.
 *** IT IS IMPORTANT TO KNOW, AS SHOWN THE CUSTOMER
 WOULD BE PAYING FOR ELECTRICAL BEING FED FROM THE
 GENERATOR EACH TIME THE GENERATOR IS UNDER TEST,
 RUNNING ETC. IF POWER WAS OUT DUE TO AN EVENT SUCH AS A
 HURRICANE, THE OWNER WOULD STILL BE PAYING AN ELECTRIC
 BILL BASED ON THE ELECTRICITY BEING PROVIDED BY THE
 GENERATOR.
  
 4) NOTE: PLEASE KNOW WHEN PLANS FALL UNDER THE
 EXCEPTIONS TO FS 471.003 AND ALLOWS A CONTRACTOR TO
 DESIGN THEIR OWN PROJECTS THAT CONTRACTOR IS STILL
 REQUIRED TO PRINT NAME OF THE COMPANY, ADDRESS, PRINT
 NAME AND SIGNATURE OF SAID DESIGNER OF RECORD TAKING
 RESPONSIBILITY OF SAID PLANS.
 FS 471, 489, FBC 106.5, 106.1.
  
 5) NOTE: NOTES FOR ALL SIGNAGE WILL BE REQUIRED ON
 PLANS AS THE MEANS OF DISCONNECT FOIR ALL FEEDERS ON
 THE LOAD SIAD OF THE ATS IS REQUIRED. 230.2E,
 225.31-225.39, 702.8
  
 6) NOTE: PLEASE INDICATE DEVICES PER 702.7
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-10-14 Cont ID  
Sent By dpalmer Date 2008-10-14 Time 15:04 Rev Time 0.00
Received By dpalmer Date 2008-10-14 Time 15:04 Sent To  
Notes
2008-10-14 15:15:48 
 ** DENIED REVIEW**
  
  
 1) NOTE: PLEASE SEE FS 527.02 AS THE PRIME CONTRACTOR
 AS APPLIED ON PERMIT APPLICATION IS THE ELECTRICAL
 CONTRACTOR. IF LICENSED TO SELL AND INSTALL GAS
 GENERATORS ETC, PLEASE SUPPLY LICENSE INFORMATION.
 PLEASE VERIFY MULTIPLE LICENSES REQUIRED BY THE
 DEPARTMENT OF AGRICULTURE IN ORDER TO SELL, INSTALL ETC
 GAS APPLIANCES.
 IF NOT LICENSED THE PRIME CONTRACTOR IS REQUIRED TO BE
 THE GAS CONTRACTOR OR OBTAIN LICENSING AS REQUIRED.
  
 2) NOTE: PLEASE COMPLETE RISER WITH ALL CONDUCTORS. THE
 NUMBER OF PARALLEL CONDUCTORS, MISSING EQUIPMENT
 GROUNDING CONDUCTORS, AIC RATINGS FOR ALL NEW
 EQUIPMENT, AND GROUNDING ELECTRIC SYSTEM
 250.50,250.58, 20.56, 110.9, 250.24, 250.110, 250.122
 ETC.
  
 3) NOTE: PLEASE VERIFY WITH FPL THAT ALL METERING AS
 SHOWN NOW ON THE LOAD SIDE OF THE ATS IS PERMITTED.
 PLEASE SEE FPL SERVICE STANDARDS AVAILABLE ON-LINE AT
 FPL.COM.
 A LETTER FROM FPL IS ACCEPTABLE FOR SERVICE AS SHOWN
 WITH NO METERING AS SHOWN ON THE LOAD SIDE OF THE ATS.
 *** IT IS IMPORTANT TO KNOW, AS SHOWN THE CUSTOMER
 WOULD BE PAYING FOR ELECTRICAL BEING FED FROM THE
 GENERATOR EACH TIME THE GENERATOR IS UNDER TEST,
 RUNNING ETC. IF POWER WAS OUT DUE TO AN EVENT SUCH AS A
 HURRICANE, THE OWNER WOULD STILL BE PAYING AN ELECTRIC
 BILL BASED ON THE ELECTRICITY BEING PROVIDED BY THE
 GENERATOR.
  
 4) NOTE: PLEASE KNOW WHEN PLANS FALL UNDER THE
 EXCEPTIONS TO FS 471.003 AND ALLOWS A CONTRACTOR TO
 DESIGN THEIR OWN PROJECTS THAT CONTRACTOR IS STILL
 REQUIRED TO PRINT NAME OF THE COMPANY, ADDRESS, PRINT
 NAME AND SIGNATURE OF SAID DESIGNER OF RECORD TAKING
 RESPONSIBILITY OF SAID PLANS.
 FS 471, 489, FBC 106.5, 106.1.
  
 5) NOTE: NOTES FOR ALL SIGNAGE WILL BE REQUIRED ON
 PLANS AS THE MEANS OF DISCONNECT FOIR ALL FEEDERS ON
 THE LOAD SIAD OF THE ATS IS REQUIRED. 230.2E,
 225.31-225.39, 702.8
  
 6) NOTE: PLEASE INDICATE DEVICES PER 702.7
  
  
  
 ***AS THERE ARE ITEMS NOT YET SHOWN ON PLANS, THERE MAY
 BE NEW COMMENTS ON THE FOLLWOING REVIEW WHICH CAN NOT
 BE MADE AT THIS TIME.
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-11-18 Cont ID  
Sent By mawillia Date 2008-11-18 Time 10:51 Rev Time 0.00
Received By mawillia Date 2008-11-18 Time 10:31 Sent To  
Notes
2008-11-18 10:50:43*****DENIED*****
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW
 (10/21/2008) STILL NEED TO BE ADDRESSED:
  
 1. LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003
 EDITION.
  
 2. WORK TO COMPLY WITH NFPA 110, STANDARD FOR EMERGENCY
 AND STANDBY POWER SYSTEMS 2005.
  
 3. GENERATOR AND ASSOCIATED EQUIPMENT SHALL BE
 PROTECTED BY BOLLARDS IF THE POSSIBILITY OF MECHANICAL
 DAMAGE IS ANTICIPATED.
  
 4. WHAT BUILDING EQUIPMENT AND/OR LIFE SAFETY SYSTEMS
 WILL BE TIED INTO THE GENERATOR?
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUD A RESPONSE
 LETTER INDICATING WHERE/HOW ON THE APPROPITE PLAN SHEET
 EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-10-21 Cont ID  
Sent By mwennerg Date 2008-10-21 Time 13:34 Rev Time 0.00
Received By mwennerg Date 2008-10-21 Time 13:34 Sent To  
Notes
2008-10-21 13:40:30***DENIED***
  
 1) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003.
  
 2) WORK TO COMPLY WITH NFPA 110, STANDARD FOR EMERGENCY
 AND STANDBY POWER SYSTEMS 2005.
  
 3) GENERATOR AND ASSOCIATED EQUIPMENT SHALL BE
 PROTECTED BY BOLLARDS IF THE POSSIBILITY OF MECHANICAL
 DAMAGE IS ANTICIPATED.
  
 4) WHAT BUILDING EQUIPMENT AND OR LIFE SAFETY SYSTEMS
 WILL BE TIED INTO THE GENERATOR?
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756
  
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2008-11-06 Cont ID  
Sent By mperson Date 2008-11-06 Time 11:56 Rev Time 1.00
Received By mperson Date 2008-11-06 Time 11:56 Sent To  
Notes
2008-11-06 12:00:29GAS PLAN REVIEW:
 DENIED **2ND TIME:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 **THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND
 WITH THE PREVIOUS GAS REVIEW COMMENTS AS WELL AS THE
 DESGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. "OK" COMMENT ADDRESSED.
  
 2. "OK" COMMENT ADDRESSED.
  
 3. "OK" COMMENT ADDRESSED.
  
 4. "OK" COMMENT ADDRESSED.
  
 5. THE SITE PLANS SHOWS THE GENERATOR IN THE
 PARKING/DRIVE AREA. PER SECTION 303.4 APPROVED BARRIERS
 ARE REQUIRED TO PROTECT THE GAS APPLIANCE. PLEASE
 INDICATE ON PLANS. SUBMITA DETAIL FOR THE PROTECTION
 METHOD.
  
 **THE RESUBMITTED GAS ISOMETRIC RISER DIAGRAM STATES
 THE FOLLOWING "GENERATOR TO BE PROTECTED FROM TRAFFIC
 BY BARRIERS DETAILED, SUPPLIED, AND INSTALLED BY
 ELECTRICIAN". PLEASE KNOW THAT THERE IS NO INDICATION
 IN THE RESUBMITTAL OF A DETAIL OR A LOCATION OF SAID
 BARRIERS. COMMENT HAS NOT BEEN ADDRESSED.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 *PLEASE CALL IF THERE ARE ANY QUESTIONS.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-10-07 Cont ID  
Sent By kstevens Date 2008-10-07 Time 11:05 Rev Time 0.00
Received By kstevens Date 2008-10-07 Time 11:05 Sent To  
Notes
2008-10-07 11:26:47DENIED
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 1. GAS RISER DIAGRAM SHOWS TWO SEPARATE GAS LINES FROM
 THE GAS METER. PLEASE CLARIFY. METERS USUALLY HAVE ONE
 INLET AND ONE OUTLET. IF THIS IS THE CASE THEN SHOW THE
 1-1/4" PIPE OUT OF THE METER WITH A 1-1/4" X 1-1/4" X
 1" TEE FOR THE GENERATOR ON THE RISER DIAGRAM. SECTIONS
 106.1.1 & 404.
  
 2. A SHUT OFF VALVE IS REQUIRED UPSTREAM OF THE GAS
 REGULATOR TO THE EXISTING GAS SYSTEM. SECTION 409.4. A
 UNION IS REQUIRED DOWNSTREAM OF THE SHUT OFF VALVE.
  
 3. THE RISER DIAGRAM INDICATES THE BTU LOAD FOR THE
 GENERATOR AT 630,000 BTU'S, BUT THE MANUF.
 SPECIFICATIONS SHOW THE LOAD AT 100% AT 1,374,000 CU FT
 HR. PLEASE CORRELATE RISER INFORMATION WITH MANUF.
 INFORMATION. TOTAL BTU'S SHALL ALSO BE INDICATED.
 SECTION 106.1.1 & TABLE 402.4(3).
  
 4. MANUF. SPECIFICATIONS FOR THE REGULATOR INDICATES
 THE CAPACITY TABLE FOR THE MODEL B42 RESIDENTIAL
 REGULATOR MODELS N, R HAVE A MAXIMUM 820 SCHF. THE
 GENERATOR REQUIRES 1,374,000 BTU'S. PLEASE SUBMIT A
 REGULATOR THAT SHOWS THE CAPACITY REQUIRED FOR THE
 GENERATOR.
  
 5. THE SITE PLAN SHOWS THE GENERATOR IN THE
 PARKING/DRIVE AREA. PER SECTION 303.4 APPROVED BARRIERS
 ARE REQUIRED TO PROTECT THE GAS APPLIANCE. PLEASE
 INDICATE ON PLANS. SUBMIT A DETAIL FOR THE PROTECTION
 METHOD.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-11-03 Cont ID  
Sent By adarroug Date 2008-11-03 Time 10:51 Rev Time 0.00
Received By adarroug Date 2008-11-03 Time 10:51 Sent To  
Notes
2008-11-03 10:51:55TO "BOB"#5

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-11-03 Cont ID  
Sent By adarroug Date 2008-10-31 Time 10:42 Rev Time 0.00
Received By adarroug Date 2008-09-30 Time 08:23 Sent To  
Notes
2008-09-30 08:29:40TO "COMM" BD#46

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-10-03 Cont ID  
Sent By tgordon Date 2008-10-03 Time 15:22 Rev Time 0.30
Received By tgordon Date 2008-10-03 Time 15:22 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2008-11-14 Cont ID  
Sent By lfranco Date 2008-11-14 Time 13:56 Rev Time 0.00
Received By lfranco Date 2008-11-14 Time 13:56 Sent To  
Notes
2008-11-14 13:59:33PLANNING AND ZONING: **** FAILED - 2ND TIME REPEAT
 COMMENTS MADE FROM MASTER PERMIT 08090686 ****
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. THE SURVEY MUST BE SIGNED AND SEALED, AND NOT BE
 OLDER THAN ONE (1) YEAR.
  
 3. PURSUANT TO SECTION 94-444(B) OF THE ZONING CODE,
 THE GENERATOR MUST BE SCREENED AND LANDSCAPED PER THE
 REQUIREMENTS BELOW:
  
 (B) *** GENERATORS SHALL NOT BE PERMITTED UNLESS
 APPROPRIATE SCREENING IS PROVIDED. SCREENING SHALL BE
 CONSTRUCTED OF BRICK, DECORATIVE CONCRETE, OTHER
 DECORATIVE MASONRY, OR COMPARABLY, DURABLE WOOD AND
 STEEL.
  
 WALLS/FENCES SHALL BE LANDSCAPED WITH SHRUBS AND HEDGES
 PLANTED AT TWO-FOOT INTERVALS. A FOUR-SIDED ENCLOSURE
 WITH MASONRY, OR COMPARABLY DURABLE WOOD AND STEEL, AN
 OBSCURING GATE IS REQUIRED AS A CONDITION FOR SITE PLAN
 APPROVAL.
  
 RESUBMITTAL: COMMENT WAS NOT ADDRESSED, PROVIDE DETAIL
 OF SCREENING ON PLAN/SURVEY (NOT ONLY ON THE WRITTEN
 RESPONSE).
  
 PER THE COMMENTS MADE BY KELLY FREEMAN ON A PREVIOUS
 PERMIT APPLICATION TO INSTALL A GENERATOR, PLEASE
 PROVIDE LOCATION OF PARKING. THE FOLLOWING ARE COMMENTS
 MADE IN 2/16/07 AND 6/19//07 (PERMIT NUMBER: 07020089)
 THAT ARE STILL APPLICABLE:
  
 RESUBMITTAL NOT ADDRESSED: SURVEY DOES NOT SHOW THE
 PARKING DETAIL AND LOCATION, LOCATION OF GENERATOR TO
 SCALE. EVERYTHING NEEDS TO BE REFLECTED ON PLAN WITH
 DIMENSIONS, ETC.
  
 4. IT WOULD BE IN YOUR BEST INTEREST TO DESIGN A
 COMBINATION GENERATOR/DUMPSTER ENCLOSURE. PRESENTLY,
 CODE ENFORCEMENT IS ISSUING CITATIONS FOR UNSCREENED
 DUMPSTERS THROUGHOUT THE CITY. THIS REPRESENTS A GOOD
 OPPORTUNITY TO TAKE CARE OF THE PROBLEM BEFORE CODE
 ENFORCEMENT COMES THROUGH YOUR AREA. WHERE IS THE
 LOCATION OF THE DUMPSTER?
  
 5. AS THE GENERATOR IS PROPOSED TO BE PLACED IN THE
 PARKING AREA, PLEASE SHOW THE NUMBER OF PARKING SPACES
 PROVIDED BEFORE, AND AFTER THE INSTALLATION OF THE
 GENERATOR. NOTE THAT YOU ARE REQUIRED TO PROVIDE SIX
 (6) PARKING SPACES, INCLUDING ONE HANDICAP ACCESSIBLE
 PARKING SPACE. PROVIDE LOCATION OF PARKING SPACES TO
 COMPLY WITH THESE REQUIREMENTS. I HAVE AGAIN ATTACHED A
 COPY OF THE CITY'S STANDARD STRIPING PARKING AND
 DUMPSTER ENCLOSURE DETAILS FOR YOUR USE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2008-10-09 Cont ID  
Sent By lfranco Date 2008-10-09 Time 14:34 Rev Time 0.00
Received By lfranco Date 2008-10-09 Time 14:34 Sent To  
Notes
2008-10-09 15:50:11PLANNING AND ZONING: **** FAILED- COMMENTS MADE FROM
 MASTER PERMIT 08090686 ****
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. THE SURVEY MUST BE SIGNED AND SEALED, AND NOT BE
 OLDER THAN 1 YEAR.
  
 3. PURSUANT TO SECTION 94-444(B) OF THE ZONING CODE,
 THE GENERATOR MUST BE SCREENED AND LANDSCAPED PER THE
 REQUIREMENTS BELOW:
 :
 (B) *** GENERATORS SHALL NOT BE PERMITTED UNLESS
 APPROPRIATE SCREENING IS PROVIDED. SCREENING SHALL BE
 CONSTRUCTED OF BRICK, DECORATIVE CONCRETE, OTHER
 DECORATIVE MASONRY, OR COMPARABLY, DURABLE WOOD AND
 STEEL.
  
 WALLS/FENCES SHALL BE LANDSCAPED WITH SHRUBS AND HEDGES
 PLANTED AT TWO-FOOT INTERVALS. A FOUR-SIDED ENCLOSURE
 WITH MASONRY, OR COMPARABLY DURABLE WOOD AND STEEL, AN
 OBSCURING GATE IS REQUIRED AS A CONDITION FOR SITE PLAN
 APPROVAL.
  
  
 PER THE COMMENTS MADE BY KELLY FREEMAN ON A PREVIOUS
 PERMIT APPLICATION TO INSTALL A GENERATOR, PLEASE
 PROVIDE LOCATION OF PARKING. THE FOLLOWING ARE COMMENTS
 MADE IN 2/16/07 AND 6/19//07 (PERMIT NUMBER: 07020089)
 THAT ARE STILL APPLICABLE:
  
 4. IT WOULD BE IN YOUR BEST INTEREST TO DESIGN A
 COMBINATION GENERATOR/DUMPSTER ENCLOSURE. PRESENTLY,
 CODE ENFORCEMENT IS ISSUING CITATIONS FOR UNSCREENED
 DUMPSTERS THROUGHOUT THE CITY. THIS REPRESENTS A GOOD
 OPPORTUNITY TO TAKE CARE OF THE PROBLEM BEFORE CODE
 ENFORCEMENT COMES THROUGH YOUR AREA.
  
 5. AS THE GENERATOR IS PROPOSED TO BE PLACED IN THE
 PARKING AREA, PLEASE SHOW THE NUMBER OF PARKING SPACES
 PROVIDED BEFORE, AND AFTER THE INSTALLATION OF THE
 GENERATOR. NOTE THAT YOU ARE REQUIRED TO PROVIDE SIX
 (6) PARKING SPACES, INCLUDING ONE HANDICAP ACCESSIBLE
 PARKING SPACE. PROVIDE LOCATION OF PARKING SPACES TO
 COMPLY WITH THESE REQUIREMENTS. I HAVE ATTACHED A COPY
 OF THE CITY?S STANDARD STRIPING PARKING AND DUMPSTER
 ENCLOSURE DETAILS FOR YOUR USE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved