Plan Review Details - Permit 08090682
Plan Review Stops For Permit 08090682
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-02-06 Cont ID  
Sent By jwitmer Date 2009-02-06 Time 15:30 Rev Time 0.77
Received By jwitmer Date 2009-02-06 Time 15:30 Sent To  
Notes
2009-02-06 15:30:52A1.2 & A1.3 OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-12-22 Cont ID  
Sent By jwitmer Date 2008-12-22 Time 16:13 Rev Time 0.77
Received By jwitmer Date 2008-12-22 Time 16:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-11-20 Cont ID  
Sent By jwitmer Date 2008-11-20 Time 15:25 Rev Time 0.77
Received By jwitmer Date 2008-11-20 Time 15:25 Sent To  
Notes
2008-11-20 15:27:39BUILDING PLAN REVIEW
 PERMIT: 08090682
 ADD: 700 S ROSEMARY AVE# 230
 CONT: SOUTHEAST CERTIFIED CONSTRUCTION (CBC)
 TEL: (561)635-6935 NAT HEALY
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1-5) COMPLIED.
  
 6) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 7) PLANS DO NOT INDICATE THEY HAVE BEEN REVIEWED BY
 CITY PLACE, NO APPROVAL STAMP ON ALL SHEETS.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-10-15 Cont ID  
Sent By jwitmer Date 2008-10-15 Time 11:21 Rev Time 2.22
Received By jwitmer Date 2008-10-15 Time 11:20 Sent To  
Notes
2008-10-15 13:39:42BUILDING PLAN REVIEW
 PERMIT: 08090682
 ADD: 700 S ROSEMARY AVE# 230
 CONT: SOUTHEAST CERTIFIED CONSTRUCTION (CBC)
 TEL: (561)635-6935 NAT HEALY
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1-5) COMPLIED.
  
 6) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-12-26 Cont ID  
Sent By dpalmer Date 2008-12-26 Time 13:51 Rev Time 0.00
Received By dpalmer Date 2008-12-26 Time 13:51 Sent To  
Notes
2008-12-26 13:51:21** PROVISO**
  
 1) NOTE: THE FIXTURE TYPES AND NUMBER OF FIXTURES WILL
 BE REQUIRED TO BE REVISED TO COORDINATE WITH ALL
 FIXTURES ACTUALLY INSTALLED ONCE DETERMINED. SOME
 FIXTURE INFORMATION IS NOT COMPLETED AT THIS TIME. THE
 MANUFACTURE, FINAL WATTAGE LOCATIONS ETC SHALL BE
 COMPLETED BEFORE FINAL INSPECTIONS.
 ALL ALLOWANCES TO BE VERIFIED TO MEET FBC 13-415.2 ON
 PLAN REVIEW.
 AS SHOWN AT THIS TIME SOME FINAL FIXTURE INFORMATION IS
 NOT AVAILABLE EVEN THOUGH THE INFORMATION SHOWN DOES
 SHOW COMPLIANCE.
  
  
 2) NOTE: RISER CONTAINS A NOTE FOR TRANSFORMER TO BE
 EXPOSED HOWEVER THE WORDING AT THE ACTUAL TRANSFORMER
 LOCATION ON PLANS SEEM TO LEND TO THIS BEING ACCESSIBLE
 ABOVE 12FT CEILING.
 NO CEILING, NO PROVISIONS FOR CEILING ETC SHALL BE
 INSTALLED AT THE TRANSFORMER LOCATION. THERE HAVE BEEN
 NUMEROUS INSTALLATIONS DONE AFTER COMPLETION OF
 PREVIOUS BUILD OUTS IN THE AREA OF CITY PLACE.
 PLEASE SEE 450.13B, 450.9.
  
 3) NOTE: PLEASE SEE 600.5, 215.3,230.42 ETC AS ALL
 CONTINUOUS LOADS SHALL BE FIGURED AT 125%. THE SIGN
 CIRCUIT ON PLANS IS SUCH A LOAD WHICH IS REQUIRED TO BE
 SHOWN AT 125%.
  
  
 4) NOTE: PILOT LIGHTS SHALL BE IDENTIFIED ALONE WITH
 SCHEDULE OF LIGHTING PER 13-415.1.ABC.1.1, .1.2 AT
 LOCATIONS. NO REVISION ON PLANS IS NEEDED THIS WILL BE
 VIEWED IN FIELD.
  
 *** IF THERE IS ANY OTHER REVISIONS BEFORE ROUGH
 INSPECTION PLEASE REVISE PLANS FOR NOTES #1, #2 AND #3
 ABOVE. IF NO OTHER REVISIONS ARE MADE, NOTES #1, #2 AND
 #3 ABOVE MAY BE DONE BEFORE FINAL.
 PLEASE BE SURE TO SUBMIT REVISED PLANS FOR REVIEW AND
 STAMPING IN A SUBSTANTIAL AMOUNT OF TIME BEFORE FINAL
 ELECTRICAL INSPECTION IS NEEDED. PLANS NEED TO BE ON
 SITE FOR INSPECTION.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-11-18 Cont ID  
Sent By dpalmer Date 2008-11-18 Time 14:31 Rev Time 0.00
Received By dpalmer Date 2008-11-18 Time 14:31 Sent To  
Notes
2008-11-18 14:31:25 
 ** FAILED 2ND REVIEW **
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
  
 1) NOTE: PLEASE COMPLETE THE LIGHTING FIXTURE LEGEND
 WITH ALL LIGHTING FIXTURES SPECIFIC TO WATTAGE ETC.
 PLANS NEED TO SHOW AT LEAST *MINIMUM* CODE COMPLIANCE
 AT TIME OF ISSUANCE. THE FIXTURES CAN ALWAYS BE REVISED
 AT A LATER DATE ONCE THE FINAL FIXTURE IS KNOWN.
 THIS COMMENT REMAINS MORE SPECIFIC TO TRACK LIGHTING AS
 TRACK LIGHTING IS ACTUALLY BLANK ON THE LEGEND. PLEASE
 ALSO SEE THAT THERE ARE TWO E FIXTURE DESIGNATIONS.
 PLEASE SEE 13-415.2.ABC.1.1,.1.2 FOR TRACK LIGHTING.
 THE VA RATING OF THE FIXTURE OR 30VA PER FT WHICH EVER
 IS GREATER IS REQUIRED TO BE USED.
  
 PLEASE CONFIRM ALL AND REVISE.
  
 2) NOTE: PLEASE SEE 13-415.1.ABC.1.1,.1.2, .1.3. THE
 OCCUPANT IS REQUIRED TO SEE ALL LIGHTING WHICH IS BEING
 CONTROLLED. CONTROLS/OVER RIDES ARE REQUIRED AT POINT
 OF ENTRANCE INTO ANY ONE AREA/SPACE OR MEET EXCEPTIONS.
 PLEASE ADD CONTROL LOCATIONS OR SHOW HOW EXCEPTIONS ARE
 MET.
 THE NOTE ON SHEET 2.1E STATES KEYPADS REQUIRED HOWEVER
 ONLY LOCATED ONE ON PLANS.
  
 3) NOTE: THE TERMINATION OF THE TAPPED CONDUCTORS ON
 THE SECONDARY SIDE OF THE TRANSFORMER DOES NOT MEET
 240.21. THE PANEL *A* IS TOO FAR AWAY.
 PLEASE ADD DISCONNECTING MEANS WITH OVER CURRENT
 PROTECTION. DOES NOT MEET 240.21B3, MUST BE WITHIN
 10FT.
  
 4) NOTE: NOTE #17 ON PLANS MENTIONS INTERLOCK OF ALL
 ELECTRICAL CIRCUITS WITH FIRE SUPPRESSION HOWEVER COULD
 NOT LOCATE THE INDICATION OF ANY SHUNT TRIP TYPE
 BREAKERS?
 NFPA-96
  
 5) NOTE: PLEASE SEE PREVIOUS NOTE WITH RESPECT TO
 APPLIED VALUE FOR THE SCOPE OF WORK. THE VALUE ON
 PERMIT APPLICATION DID NOT CHANGE.
  
 6) NOTE: NEW NOTE: PLEASE SHOW LOCATIONS OF FIRE ALARM
 DEVICES FOR MINIMUM DESIGN ON BASE PLANS. EVEN AS THE
 FIRE ALARM PERMIT WILL BE SEPARATE PER FS 633 THE BASE
 PLANS NEED TO SHOW THE DEVICE LOCATIONS FOR CODE
 COMPLIANCE.
 PLEASE SHOW LOCATIONS AND LEVELS FOR ADA COMPLIANCE PER
 FBC 11-4.2, 11-4.28.1,.2 AND .3.
 RESPONSE TO FIRE REVIEW STATES THESE ARE ALL ON REVISED
 LIFE SAFETY PLANS HOVE
 THIS WAS NOT ON PREVIOUS REVIEW NOTES HOWEVER THIS IS
 REQUIRED.
 FBC 907.2.1, 303.1
  
 7) NOTE: PLEASE COORDINATE NOTE ON COVER SHEET FOR SIZE
 OF ELECTRICAL SERVICE.
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-10-09 Cont ID  
Sent By dpalmer Date 2008-10-09 Time 14:44 Rev Time 0.00
Received By dpalmer Date 2008-10-09 Time 14:44 Sent To  
Notes
2008-10-09 14:45:06 
 ** DENIED **
  
 1) NOTE: PLEASE SEE FS 471.023, FAC 61G15-23.002. THE
 SCOPE OF WORK AS SHOWN IS REQUIRED TO BE DONE BY AN
 ENGINEER. ANY FIRMS PROVIDING THAT SERVICE IS REQUIRED
 TO HAVE AN ENGINEERING BUSINESS LICENSE NUMBER ALSO
 KNOWN AS A CERTIFICATE OF AUTHORIZATION NUMBER. THIS IS
 THE SAME AS AN ARCHITECTURAL FIRM PROVIDING
 ARCHITECTURAL SERVICES. METRO DESIGN GROUP NOW SHOWS
 THE ARCHITECTURAL FIRM LICENSE NUMBER ON PLANS HOWEVER
 NOT INDICATE THE ENGINEERING BUSINESS LICENSE NUMBER.
 PLEASE INCLUDE AS REQUIRED.
 ** THIS WAS CONFIRMED WITH THE STATE BOARD OF ENGINEER
 WHEN PROVIDING ENGINEERING SERVICES.
  
 2) NOTE: PLEASE SEE THE RISER SHOWS A NEUTRAL FROM
 PANEL *H* TO TRANSFORMER WHICH IS NOT PERMITTED AS THIS
 IS A SEPARATELY DERIVED SYSTEM.
 250.6.250.24, 250.20, 250.30, 250.50, 250.66 ETC
  
 3) NOTE: PLEASE PROVIDE THE GROUNDING ELECTRODE SYSTEM
 AND ATTACHMENT FOR NEW TRANSFORMER PER THE SAME CODE
 SECTIONS NOTED IN NOTE #2 ABOVE.
  
 4) NOTE: PLEASE 450.13 AS THE 75KVA TRANSFORMER AS
 SHOWN IS NOT PERMITTED ABOVE THE CEILING AS NOTED ON
 RISER.
  
 5) NOTE: PLEASE INDICATE THE SIZE OF THE EXISTING
 SERVICE WITH THE CURRENT EXISTING LOADS WITH NEW LOADS
 BEING ADDED.
 NEC 220.87, 220 PART II, III, IV.
  
 6) NOTE: PLEASE SEE 220.43A FOR SHOWS WINDOWS AND THE
 AMOUNT OF LOAD REQUIRED FOR SERVICE. THE LOAD SHOWN ON
 PANEL SCHEDULE IS THE LOADS PER 220.14G WHICH IS THE
 BRANCH CIRCUIT.
  
 7) NOTE: PLEASE COMPLETE PLANS/PANEL SCHEDULE FOR
 SHUNT/SHUT DOWN OF ALL ELECTRICAL UNDER HOOD. NFPA-96
 FOR EXAMPLE: PLEASE SEE THE HOOD LIGHTS DO NOT INDICATE
 SHUNT BREAKER?
  
 8) NOTE: PLEASE SUBMIT A COMPLETE LIGHTING CONTROL
 SYSTEM SHOWING ALL OVER RIDE LOCATIONS AND ALL OVER
 RIDE DEVICES FOR GENERAL LIGHTING AS WELL AS OTHER
 ACCENT/DECRETIVE LIGHTING ETC.
 PLEASE BE SURE TO ALSO SEE THE SECTION FOR EXTERIOR
 LIGHTING CONTROLS.
 13-415.1.ABC.1.1, .1.2 AND .1.3.
 EXTERIOR PER 13-415.1.ABC.1.4.
  
 9) NOTE: PLEASE SUBMIT A COMPLETED LIGHTING FIXTURE
 LEGEND. PLEASE SUBMIT COMPLETE LIGHTING PERFORMANCE
 CALCULATIONS PER 13-415.2, 13-415.2.ABC.1.1, .1.2 AND
 .1.3.
 PLEASE KNOW THE FIXTURE SCHEDULE MUST BE COMPLETE AT
 THIS TIME FOR LIGHTING PERFORMANCE VERIFICATION.
 ** AREAS AND ROOMS NOTED ON THE LIGHTING CONTROL PANEL
 DOES NOT COORDINATE WITH ANY ROOMS DESIGNATED ON PLANS.
  
 10) NOTE: PLEASE SEE THE CODES NOTED ON PLANS SHALL BE
 CODES ADOPTED BY THE FBC 2004 W/2007 REVISION PER FS
 553.73.
 PLEASE SEE THE JURISDICTION FOR EXAMPLE NOTES ROYAL
 PALM BEACH HOWEVER JOB LOCATION IS IN THE CITY OF WEST
 PALM BEACH. (MISPRINT).
  
 11) NOTE: PLEASE SEE THE APPLIED VALUE SHALL INCLUDE
 ALL LABOR, MATERIALS, EQUIPMENT, DEISGN COSTS ETC PER
 FBC 108.3 EVEN IF ANY OF THESE ITEMS ARE OWNER
 SUPPLIED. THE VALUE FOR SCOPE OF WORK AS SHOWN IS LOW.
  
  
  
 ** IT IS IMPORTANT TO UNDERSTAND AS THERE ARE SOME
 ITEMS NOT YET SUBMITTED OR SHOWN FOR REVIEW THERE MAY
 VERY WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH
 CAN NOT BE MADE AT THIS TIME.
  
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2009-02-18 Cont ID  
Sent By mwennerg Date 2009-02-18 Time 10:49 Rev Time 0.00
Received By mwennerg Date 2009-02-18 Time 10:49 Sent To  
Notes
2009-02-18 10:49:34REVISION DATED 1/28/09

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-12-29 Cont ID  
Sent By mwennerg Date 2008-12-29 Time 13:49 Rev Time 0.00
Received By mwennerg Date 2008-12-29 Time 13:49 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-11-25 Cont ID  
Sent By mwennerg Date 2008-11-25 Time 13:55 Rev Time 0.00
Received By mwennerg Date 2008-11-25 Time 13:55 Sent To  
Notes
2008-11-25 14:06:11***DENIED***
  
 SOME COMMENTS HAVE NOT BEEN ADDRESSED FROM THE FIRST
 FIRE REVIEW:
  
 2) THERE STILL APPEARS TO BE CONFLICTING INFORMATION
 REGARDING THE OCCUPANT LOAD. SHEET 1.2A, NOTE #11
 INDICATES MAXIMUM OCCUPANT LOAD OF 229 WHICH DIFFERS
 FROM TOTAL INSIDE OCCUPANCY OF 68. PLEASE CONTACT THE
 BUREAU OF FIRE PREVENTION AT (561) AT 804-4724 FOR
 ASSISTANCE WITH OCCUPANT LOAD CALCULATION. AN OCCUPANT
 LOAD SIGN WILL BE REQUIRED PRIOR TO FINAL LICENSE
 INSPECTION.
  
 4) A NOTE REGARDING FIRE ALARM WORK HAS BEEN ADDED TO
 SHEET 1.2A BUT THE LAYOUT AS REQUESTED FROM THE FIRST
 FIRE REVIEW IS STILL MISSING.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-10-20 Cont ID  
Sent By mawillia Date 2008-10-20 Time 14:09 Rev Time 0.00
Received By mawillia Date 2008-10-20 Time 13:36 Sent To  
Notes
2008-10-20 14:04:08******DENIED*****
  
 1. ON SHEET C-1 GENERAL NOTE #1, REFERENCE IS MADE TO
 THE CITY OF ROYAL PALM BEACH. PLEASE BE ADVISED THAT
 THE AUTHORITY HAVING JURISDICTION IN THIS PROJECT
 LOCATION IS THE CITY OF WEST PALM BEACH.
  
 2. ON SHEET 1.2A, LIFE SAFETY NOTE #11 STATES "MAXIMUM
 OCCUPANCY SHALL BE 229 PEOPLE" WHEREAS THE TOTAL INSIDE
 OCCUPANCY HAS BEEN LISTED IN YOUR CALCULATION AS 68
 PEOPLE. PLEASE EXPLAIN.
  
 3. PROVIDE A SPRINKLER HEAD LAYOUT OF THE PROPOSED
 TENANT SPACE. THESE DEVICES MAY BE SHOWN ON THE
 REFLECTED CEILING PLAN SHEET.
  
 4. PROVIDE A LAYOUT OF THE FIRE ALARM DEVICES FOR THE
 PROPOSED TENANT SPACE. THESE DEVICES MAY BE SHOWN ON
 THE LIFE SAFETY PLAN SHEET.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE/HOW EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2009-01-06 Cont ID  
Sent By kstevens Date 2009-01-06 Time 08:32 Rev Time 0.00
Received By kstevens Date 2009-01-05 Time 15:09 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2008-11-19 Cont ID  
Sent By kstevens Date 2008-11-19 Time 16:09 Rev Time 0.00
Received By kstevens Date 2008-11-19 Time 16:09 Sent To  
Notes
2008-11-19 16:10:06DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. A SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE
 FOLLOWING INFORMATION FOR PERMIT:
  
 A. OK
  
 B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, BUT THE MANUF. SHEETS FOR THE WOK
 DOES NOT REFLECT THE BTU LOAD INDICATED ON THE GAS LOAD
 CALCULATIONS. PLEASE INDICATE WHICH MODEL WILL BE USED
 AND SHOW THAT THE BTU LOAD REFLECTS THE GAS LOAD
 CALCULATIONSL. NO MANUF. SHEETS SUBMITTED FOR THE GAS
 WATER HEATER.
  
 C. OK
  
 D. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE
 REGULATOR. SHEETS SHALL SHOW A LISTING AND INDICATED
 THE TOTAL BTU LOAD APPLICABLE FOR THE REGULATOR MODEL.
 INDICATE MODEL.
 ****RESPONSE NOTED, BUT NO LISTING IS INDICATED AND NO
 1-1/2" OUTLET IS INDICATED ON ANY MODEL. INDICATE THE
 MODEL NUMBER, (MUST SHOW 1-1/2" OUTLET), AND HIGHLIGHT
 THE MAXIMUM CAPACITY FOR THE REGULATOR FOR MULTIPLE
 APPLIANCES.
  
 E. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-10-02 Cont ID  
Sent By kstevens Date 2008-10-02 Time 10:56 Rev Time 0.00
Received By kstevens Date 2008-10-01 Time 17:55 Sent To  
Notes
2008-10-02 10:59:18DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. A SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE
 FOLLOWING INFORMATION FOR PERMIT:
  
 A. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). THIS IS REQUIRED FOR THE 2
 PSI SYSTEM AND THE .5 PSI SYSTEMS.
  
 B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 C. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. THIS IS ALSO REQUIRED FOR
 THE S.O.V AND REGULATOR. A UNION IS REQUIRED AND ALL
 SHALL BE INSTALLED BELOW THE CEILING.
  
 D. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE
 REGULATOR. SHEETS SHALL SHOW A LISTING AND INDICATED
 THE TOTAL BTU LOAD APPLICABLE FOR THE REGULATOR MODEL.
 INDICATE MODEL.
  
 E. MINIMUM SIZE 1" REQUIRED TO THE RANGE. 3/4" IS
 INDICATED IN GAS LOAD CALCULATIONS. TABLE 402.4(2).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-01-30 Cont ID  
Sent By adarroug Date 2009-01-30 Time 08:25 Rev Time 0.00
Received By adarroug Date 2009-01-30 Time 08:25 Sent To  
Notes
2009-01-30 08:28:35TO "COMM" BD#25

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-12-17 Cont ID  
Sent By adarroug Date 2008-12-17 Time 10:32 Rev Time 0.00
Received By adarroug Date 2008-12-17 Time 10:32 Sent To  
Notes
2008-12-17 10:34:36TO "COMM" BD#26--EXPEDITED--

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-11-14 Cont ID  
Sent By adarroug Date 2008-11-14 Time 08:37 Rev Time 0.00
Received By adarroug Date 2008-11-14 Time 08:37 Sent To  
Notes
2008-11-14 08:37:53TO "COMM" BD#44

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-10-20 Cont ID  
Sent By mawillia Date 2008-10-20 Time 10:16 Rev Time 0.00
Received By mawillia Date 2008-09-30 Time 08:52 Sent To  
Notes
2008-09-30 08:56:29TO "COMM" BD#29--EXPEDITED--

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-10-18 Cont ID  
Sent By rregueir Date 2008-10-18 Time 16:18 Rev Time 0.00
Received By rregueir Date 2008-10-18 Time 16:13 Sent To  
Notes
2008-10-18 16:18:38NO INFORMATION WAS PROVIDED ON PLANS FOR KITCHEN HOOD
 SYSTEM OR WALK-IN COOLERS. SEPARATE PERMITS WITH
 COMPLETE PLANS REQUIRED FOR THESE SYSTEMS. PERMITS FOR
 WALK-IN COOLER AND KITCHEN HOOD SHALL BE OBTAINED PRIOR
 TO COMMENCEMENT OF ANY WORK RELATED TO THESE SYSTEMS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-01-05 Cont ID  
Sent By kstevens Date 2009-01-05 Time 15:09 Rev Time 0.00
Received By kstevens Date 2009-01-05 Time 15:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-11-19 Cont ID  
Sent By kstevens Date 2008-11-19 Time 15:48 Rev Time 0.00
Received By kstevens Date 2008-11-19 Time 15:48 Sent To  
Notes
2008-11-19 16:06:35DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 CITY WPB MUNICIPAL CODE
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
  
 2. SHT 1.1A EQUIPMENT SCHEDULE. PLEASE CLARIFY THE
 FOLLOWING:
 ITEM NO. 4 OK
 ITEM BETWEEN 9 & 10 SHOWS 1/2" WATER SUPPLIES BUT SHOWS
 NO ITEM.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED.
 ITEM NO. 15 OK
 ITEM NO. 30 OK
 ITEM BETWEEN 31 & 32 SHOWS 3/4" INDIRECT WASTE BUT NO
 ITEM.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED.
 SECTIONS 106.1.1, 601.1 & 701.1.
  
 3. OK
 4. OK
 5. OK
 6. OK
  
 7. SHT 3.0P PLUMBING PLAN SHOWS NO WATER SUPPLY PIPING
 TO THE 3 COMPARTMENT SINK & SHOWS 2 HOT SUPPLY LINES TO
 THE HAND SINK. PLEASE CORRELATE WITH RISER DIAGRAM.
 SECTIONS 106.1.1 & 601.1.
 ****RESPONSE NOTED, BUT COMMENTS NOT ADDRESSED.
  
 8. SHT 3.2P WATER RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN. THE HAND SINK NEXT TO THE WOK SHOWS 2 HOT
 SUPPLY LINES.
 ****RESPONSE NOTED, BUT ALL COMMENTS ADDRESS EXCEPT THE
 ONE CONCERNING THE HAND SINK ABOVE.
  
 9. A SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE
 FOLLOWING INFORMATION FOR PERMIT:
  
 A. OK
  
 B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, BUT THE MANUF. SHEETS FOR THE WOK
 DOES NOT REFLECT THE BTU LOAD INDICATED ON THE GAS LOAD
 CALCULATIONS. PLEASE INDICATE WHICH MODEL WILL BE USED
 AND SHOW THAT THE BTU LOAD REFLECTS THE GAS LOAD
 CALCULATIONSL. NO MANUF. SHEETS SUBMITTED FOR THE GAS
 WATER HEATER.
  
 C. OK
  
 D. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE
 REGULATOR. SHEETS SHALL SHOW A LISTING AND INDICATED
 THE TOTAL BTU LOAD APPLICABLE FOR THE REGULATOR MODEL.
 INDICATE MODEL.
 ****RESPONSE NOTED, BUT NO LISTING IS INDICATED AND NO
 1-1/2" OUTLET IS INDICATED ON ANY MODEL. INDICATE THE
 MODEL NUMBER, (MUST SHOW 1-1/2" OUTLET), AND HIGHLIGHT
 THE MAXIMUM CAPACITY FOR THE REGULATOR FOR MULTIPLE
 APPLIANCES.
  
 E. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-10-02 Cont ID  
Sent By kstevens Date 2008-10-02 Time 10:17 Rev Time 0.00
Received By kstevens Date 2008-10-01 Time 17:55 Sent To  
Notes
2008-10-02 10:55:47DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 CITY WPB MUNICIPAL CODE
  
 1. SHT C-1 GENERAL NOTES #1 TO INCLUDE 2005, 2006 &
 2007 REVISIONS/AMENDMENTS TO THE 2004 FLORIDA BUILDING
 CODE AND THE JURISDICATION OF AUTHORITY IS THE CITY OF
 WEST PALM BEACH, NOT ROYAL PALM BEACH. PLEASE UPDATE
 GENERAL NOTE #1. SECTION 106.1.3.
  
 2. SHT 1.1A EQUIPMENT SCHEDULE. PLEASE CLARIFY THE
 FOLLOWING:
 ITEM NO. 4 MOP SINK SHOWS NO WATER SUPPLIES NOR DRAIN.
 ITEM BETWEEN 9 & 10 SHOWS 1/2" WATER SUPPLIES BUT SHOWS
 NO ITEM.
 ITEM NO. 15 HAND SINKS SHOWS NO WATER SUPPLIES NOR
 DRAIN.
 ITEM NO. 30 HAND SINK SHOWS NO WATER SUPPLIES NOR
 DRAIN.
 ITEM BETWEEN 31 & 32 SHOWS 3/4" INDIRECT WASTE BUT NO
 ITEM.
 SECTIONS 106.1.1, 601.1 & 701.1.
  
 3. SHT 3.0P SANITARY RISER. DISH WASHER SHALL DRAIN
 INTO THE SANITARY SYSTEM, NOT THE GREASE SYSTEM.
 ARTICLE III SECTION 90-124(7)(B).
  
 4. SHT 3.0P SANITARY RISER SHALL BE LABELED AS THE
 GREASE RISER DIAGRAM. FIXTURE SHOWN TO THE RIGHT OF THE
 TRENCH DRAIN SHALL BE IDENTIFIED, (INDICATED AS
 "STUDOR").
  
 5. THE GREASE INTERCEPTOR SHALL BE SIZED BY THE UTILITY
 DEPARTMENT, INDUSTRIAL PRETREATMENT. PLEASE CONTACT
 HOLLY MCGRATH LABORATORY SUPERVISOR BY PHONE AT (561)
 822-2271, OR BY FAX AT (561) 822-2279, OR BY E-MAIL AT
 [email protected]. A WRITTEN DETERMINATION OR E-MAIL
 FROM ENVIRONMENTAL COMPLIANCE IS REQUIRED. ARTICLE III
 SECTION 90-124(7).
  
 6. SHT P3.0P PLUMBING PLAN. EXPLAIN THE SANITARY LINE
 SHOWN PAST THE FLOOR SINK TO THE 3 COMPARTMENT SINK.
 SECTIONS 106.1.1, 701.1 & 901.1.
  
 7. SHT 3.0P PLUMBING PLAN SHOWS NO WATER SUPPLY PIPING
 TO THE 3 COMPARTMENT SINK & SHOWS 2 HOT SUPPLY LINES TO
 THE HAND SINK. PLEASE CORRELATE WITH RISER DIAGRAM.
 SECTIONS 106.1.1 & 601.1.
  
 8. SHT 3.2P WATER RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN. THE TOILET ROOM W/C & LAV SHOWN ON THE
 RIGHT SIDE OF THE TENANT SUPPLY LINE ON THE PLUMBING
 PLAN IS SHOWN ON THE LEFT SIDE OF THE TENANT SUPPLY
 LINE ON THE RISER DIAGRAM. THE SUPPLY LINE TO THE W/C
 IN THE OTHER TOILET ROOM IS NOT SHOWN ON THE RISER
 DIAGRAM. IDENTIFY THE LAV IN THE SECOND BATH. THE HAND
 SINK NEXT TO THE WOK SHOWS 2 HOT SUPPLY LINES. THE GATE
 VALVE AND SUBMETER INDICATED ON THE RISER DIAGRAM IS
 NOT SHOWN ON THE PLUMBING PLAN. PLEASE CORRELATE.
 SECTIONS 106.1.1 & 106.1.
  
 9. A SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE
 FOLLOWING INFORMATION FOR PERMIT:
  
 A. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). THIS IS REQUIRED FOR THE 2
 PSI SYSTEM AND THE .5 PSI SYSTEMS.
  
 B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 C. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. THIS IS ALSO REQUIRED FOR
 THE S.O.V AND REGULATOR. A UNION IS REQUIRED AND ALL
 SHALL BE INSTALLED BELOW THE CEILING.
  
 D. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE
 REGULATOR. SHEETS SHALL SHOW A LISTING AND INDICATED
 THE TOTAL BTU LOAD APPLICABLE FOR THE REGULATOR MODEL.
 INDICATE MODEL.
  
 E. MINIMUM SIZE 1" REQUIRED TO THE RANGE. 3/4" IS
 INDICATED IN GAS LOAD CALCULATIONS. TABLE 402.4(2).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2008-11-19 Cont ID  
Sent By eschneid Date 2008-11-19 Time 10:58 Rev Time 0.00
Received By eschneid Date 2008-11-19 Time 09:32 Sent To  
Notes
2008-11-19 10:58:43RESTAMP

Review Stop Z ZONING
Rev No 1 Status P Date 2008-10-01 Cont ID  
Sent By eschneid Date 2008-10-01 Time 13:32 Rev Time 0.00
Received By eschneid Date 2008-10-01 Time 13:32 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved