Plan Review Details - Permit 08090622
Plan Review Stops For Permit 08090622
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-11-17 Cont ID  
Sent By shill Date 2008-11-17 Time 09:32 Rev Time 0.00
Received By shill Date 2008-11-17 Time 09:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-10-09 Cont ID  
Sent By shill Date 2008-10-09 Time 16:17 Rev Time 0.00
Received By shill Date 2008-10-09 Time 16:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-10-24 Cont ID  
Sent By btrobaug Date 2008-10-24 Time 14:05 Rev Time 0.00
Received By btrobaug Date 2008-10-24 Time 14:04 Sent To G
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-10-06 Cont ID  
Sent By btrobaug Date 2008-10-06 Time 12:05 Rev Time 0.00
Received By btrobaug Date 2008-10-06 Time 12:05 Sent To G
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2008-10-27 Cont ID  
Sent By mperson Date 2008-10-27 Time 15:14 Rev Time 0.30
Received By mperson Date 2008-10-27 Time 15:14 Sent To M
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-10-07 Cont ID  
Sent By mperson Date 2008-10-07 Time 14:22 Rev Time 0.45
Received By mperson Date 2008-10-07 Time 14:22 Sent To B
Notes
2008-10-07 14:36:48GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. A GAS PERMIT CAN NOT BE ISSUED UNTIL THE GEN/RES
 PERMIT APPLICATION HAS BEEN APPROVED BY ZONING FOR THE
 GENERATOR LOCATION. PLEASE KNOW THAT THE LOCATION OF
 THE PROPOSED GENERATOR MAY NEED TO MOVE DUE TO ZONING
 COMMENTS. PLEASE KNOW THAT IF THE PROPOSED GENERATOR
 NEEDS TO BE RELOCATED DUE TO ZONINGS COMMENTS THEN
 REVISED GAS PLANS WILL BE REQUIRED. PER FBC-2004
 CHAPTER 1, (W.P.B. AS AMENDED) SECTION 106.1.1
 INFORMATION ON CONSTRUCTION DOCUMENTS AND FBC-2004 FUEL
 GAS SECTION 401.1 SCOPE.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-10-17 Cont ID  
Sent By adarroug Date 2008-10-17 Time 11:19 Rev Time 0.00
Received By adarroug Date 2008-10-17 Time 11:19 Sent To Z
Notes
2008-10-17 11:19:53TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-10-03 Cont ID  
Sent By adarroug Date 2008-10-03 Time 15:11 Rev Time 0.00
Received By adarroug Date 2008-10-03 Time 15:11 Sent To E
Notes
2008-10-03 15:12:10TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-10-09 Cont ID  
Sent By shill Date 2008-10-09 Time 16:18 Rev Time 0.00
Received By shill Date 2008-09-25 Time 16:49 Sent To  
Notes
2008-09-25 16:50:02TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-10-28 Cont ID  
Sent By tgordon Date 2008-10-28 Time 13:49 Rev Time 0.30
Received By tgordon Date 2008-10-28 Time 13:49 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-10-06 Cont ID  
Sent By tgordon Date 2008-10-06 Time 09:22 Rev Time 0.30
Received By tgordon Date 2008-10-06 Time 09:22 Sent To E
Notes
2008-10-06 09:31:39PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) SHOW ON THE SURVEYS THE PURPOSED LOCATION OF THE
 GENERATOR.
  
 NOTICE; PER 2004 FBC, FUEL GAS - POWERED EQUIPMENT
 PERMANENTLY INSTALLED EQUIPMENT POWERED BY INTERNAL
 COMBUSTION ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURER'S INSTALLATION INSTRUCTIONS AND NFPA
 37.
  
 NFPA 37 INSTALLATION & USE OF STATIONARY COMBUSTION
 ENGINES & GAS TURBINES: 4.1.4 ENGINES (GENERATORS)
 LOCATED OUTDOORS SHALL BE MINIMUM OF 5 FT FROM OPENINGS
 IN WALLS (DOORS AND WINDOWS) & AT LEAST 5 FT FROM
 STRUCTURES HAVING COMBUSTIBLE WALLS. A MINIMUM
 CLEARANCE IS NOT REQUIRED WHEN (1) THE ADJACENT WALL
 HAS A MINIMUM FIRE RESISTANCE RATING OF 1 HOUR OR (2)
 THE WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF
 NON-COMBUSTIBLE MATERIALS, AND IT HAS BEEN DEMONSTRATED
 THAT A FIRE WITHIN THE ENCLOSURE WILL NOT IGNITE
 COMBUSTIBLE MATERIALS OUTSIDE THE ENCLOSURE.
 INFORMATIVE: A.8.2.3.1 EXHAUST SYSTEMS SHOULD NOT
 TERMINATE UNDER STRUCTURES OR WHERE THE EXHAUST MIGHT
 BE DRAWN INTO THE VENTILATION INTAKES.
  
 2004 FMC 804.3.5 #3, WHERE THE TERMINATION IS LOCATED
 BELOW AN ADJACENT ROOF STRUCTURE, THE TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE ROOF STRUCTURE.
  
 PLEASE NOTE, WHILE ZONING ALLOWS MECHANICAL EQUIPMENT
 TO ENCROACH 4 FT INTO THE REQUIRED SETBACK, GENERATORS
 SHALL MAINTAIN THE REQUIRED ABOVE MENTIONED CLEARANCES
 TO THE ADJACENT PROPERTY STRUCTURES, I.E. FENCE,
 BUILDING, WINDOWS, DOORS, OR OPENINGS.
 FOLLOW MANUFACTURER'S RECOMMENDED CLEARANCES AROUND
 EQUIPMENT FOR SERVICING,AND PROVIDE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS AT THE JOBSITE FOR THE FIELD
 INSPECTOR.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2008-10-24 Cont ID  
Sent By mcruz Date 2008-10-24 Time 11:55 Rev Time 0.00
Received By mcruz Date 2008-10-24 Time 11:55 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2008-10-03 Cont ID  
Sent By mcruz Date 2008-10-03 Time 12:19 Rev Time 0.00
Received By mcruz Date 2008-10-03 Time 12:17 Sent To I
Notes
2008-10-03 12:19:23***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. INDICATE ON THE SURVEY THE LOCATION OF THE PROPOSED
 GENERATOR AND THE SETBACK DIMENSION TO ALL ADJACENT
 PROPERTY LINES. NOTE: PURSUANT TO THE CITY OF WEST PALM
 BEACH ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDR),
 SECTION94-305(B)(4): MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN FOUR (4) FEET INTO A REQUIRED
 SETBACK.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  