Plan Review Details - Permit 08090611
Plan Review Stops For Permit 08090611
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2008-12-26 Cont ID  
Sent By jnguyen Date 2008-12-26 Time 09:01 Rev Time 0.00
Received By jnguyen Date 2008-12-26 Time 07:55 Sent To  
Notes
2008-12-26 09:12:43UPDATE 12-26-2008: I CHECKED OUT THE SITE PLANS &
 REALIZED THAT THE PROSPECTIVE ICE RINK WAS INDEED
 TAKING PLACE AT THE TENANT SPACE DESIGNATED AS 1590 N
 FLORIDA MANGO RD (NOT 1600 N FLORIDA MANGO RD). I ALSO
 CALLED & TALKED TO THE CONTRACTOR, NAT HEALY. WE BOTH
 REALIZED THAT BACK IN MID-OCTOBER THAT WE ERRED IN
 CONFIRMING 1600 N FLORIDA MANGO RD AS THE OFFICIAL
 ADDRESS. I SAW THAT THE NOW CONFIRMED ADDRESS OF 1590 N
 FLORIDA MANGO RD WAS CORRECTED ON THE ORIGINAL PERMIT
 APPLICATION. HOWEVER, IT STILL NEEDS TO BE ADJUSTED IN
 THE COMMUNITYPLUS DATABASE. SINCE I DO NOT HAVE
 AUTHORIZATION, PLEASE ATTACH THIS PERMIT IN TO ITS
 CORRECT LOCATION, PCN# 74434329000001120 FOR SEQUENTIAL
 UNIT RECORD 0001 - 1590 N FLORIDA MANGO RD.

Review Stop AD ADDRESSING
Rev No 1 Status P Date 2008-10-17 Cont ID CBC058291
Sent By jnguyen Date 2008-12-26 Time 9:01 Rev Time 1.00
Received By jnguyen Date 2008-10-15 Time 11:30 Sent To  
Notes
2008-12-26 09:00:27UPDATE 12-26-2008: I CHECKED OUT THE SITE PLANS &
 REALIZED THAT THE PROSPECTIVE ICE RINK WAS INDEED
 TAKING PLACE AT THE TENANT SPACE DESIGNATED AS 1590 N
 FLORIDA MANGO RD (NOT 1600 N FLORIDA MANGO RD). I ALSO
 CALLED & TALKED TO THE CONTRACTOR, NAT HEALY. WE BOTH
 REALIZED THAT BACK IN MID-OCTOBER THAT WE ERRED IN
 CONFIRMING 1600 N FLORIDA MANGO RD AS THE OFFICIAL
 ADDRESS. I SAW THAT THE NOW CONFIRMED ADDRESS OF 1590 N
 FLORIDA MANGO RD WAS CORRECTED ON THE ORIGINAL PERMIT
 APPLICATION. HOWEVER, IT STILL NEEDS TO BE ADJUSTED IN
 THE COMMUNITYPLUS DATABASE. SINCE I DO NOT HAVE
 AUTHORIZATION, PLEASE ATTACH THIS PERMIT IN TO ITS
 CORRECT LOCATION, PCN# 74434329000001120 FOR SEQUENTIAL
 UNIT RECORD 0001 - 1590 N FLORIDA MANGO RD.
2008-10-17 10:00:3810-17-2008: VERIFIED 1600 N FLORIDA MANGO AS THE
 PRIMARY ADDRESS FOR PCN# 74434329000001120 IN GIS &
 PAPA; WAS TOLD ON THE PHONE BY THE CONTRACTOR THAT THIS
 SPECIFIC LOCATION WAS GOING TO BE UTILIZED AS THE ICE
 RINK (NOT THE UNIT BLDG) & WAS THEIR MAILING ADDRESS
 TOO.

Review Stop B BUILDING (STRUCTURAL)
Rev No 16 Status P Date 2009-12-02 Cont ID  
Sent By shill Date 2009-12-02 Time 12:08 Rev Time 0.00
Received By shill Date 2009-11-30 Time 07:42 Sent To Z
Notes
2009-12-02 12:33:28****PROVISO ITEMS FROM PREVIOUS LISTS*****
 ***REVISION, SHEETS T, 001, 212, 222, DOCS FROM DCA***
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 4. ADDRESSED - FBC1024.12, PER BUILDING OFFICIAL, SEATS
 CANNOT BE REMOVABLE. THIS WILL BE ISSUED WITH PROVISO,
 ALL SEATS FIXED, REMOVE SEATS AT ACCESSIBLE AREA.
  
 8. ADDRESSED - (VERTICAL ACCESSIBILITY AND ACCESSIBLE
 SEATING IS REQUIRED TO EAST MEZZANINE AND FIRST FLOOR
 RAISED SEATING. EITHER PROVIDE A WAIVER OR REVISE PLAN
 TO SHOW COMPLIANCE.
  
 9. PLEASE HAVE EOR REVIEW THE DELEGATED ENGINEERING ON
 THIS JOB, FAC61G15-31. THIS MAY BE DONE BY LETTER.
  
 ARCHITECT'S RESPONSE THAT TAVARES IS PHASE 2 EOR, ALI
 IS THRESHOLD INSPECTOR IS ACKNOWLEDGED. ALL "PHASES"
 WERE COMPLETED UNDER ONE PERMIT, ONE STRUCTURE. PLEASE
 HAVE ENGINEERS SEE FAC61G15-31, RESPONSIBILITY RULES
 FOR PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF
 STRUCTURES. THERE IS TO BE ONE ENGINEER OF RECORD FOR
 THE STRUCTURE. THAT ENGINEER SPECIFIES DESIGN CRITERIA,
 AND REVIEWS THE DELEGATED ENGINEERING TO COMFIRM
 CONFORMANCE WITH EOR'S DESIGN CRITERIA. THROUGHOUT THIS
 PROJECT, REVISIONS HAVE BEEN PROCESSED WITH PROVISO
 THAT EOR REVIEW THE DELEGATED ENGINEERING. FOUNDATIONS
 WERE DESIGNED BY ONE ENGINEER, EXTERIOR, MEZZANINES,
 STAIRS, ETC. DESIGNED BY ANOTHER ENGINEER. IT IS NOT
 CLEAR WHICH ENGINEER IS ENGINEER OF RECORD FOR THE
 STRUCTURE, WHICH ENGINEER HAS DELEGATED, WHICH ENGINEER
 IS RESPONSIBLE FOR THE OVERALL DESIGN. PLEASE HAVE THE
 ENGINEERS REVIEW FAC61G15-31 AND CONFIRM THAT EOR HAS
 REVIEWED DELEGATED ENGINEERING (MAY BE DONE BY LETTER).
 PLEASE FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS.
  
 10. ADDRESSED - FBC1023.6, EITHER PROVIDE SAFE
 DISPERSAL AREA OR ACCESSIBLE ROUTE TO THE PUBLIC WAY
 (EXIT DISCHARGE).
  
 11. FBC1019.1.4, SEE PROVISO ON PLAN, STAIRS TO COMPLY
 WITH FBC1019.1.4.
  
 SHEET 722 ON HOLD PENDING RECEIPT OF SPRINKLER HEAD
 SPEC SHEETS; UPON RECEIPT THE REQUEST FOR ALTERNATE
 MATERIALS & METHODS TO BE FORWARDED TO BUILDING
 OFFICIAL. PLEASE NOTE THAT SHEET 722 REFERS TO FP3 &
 FP4 WHICH HAVE NOT YET BEEN REVIEWED AND WHICH WERE NOT
 SUBMITTED WITH THIS REVISION. I HAVE TAKEN ONE SET FROM
 THE MECHANICAL/FIRE/ELEC REVISION FOR REFERENCE.
  
 13. ADDRESSED - COMPLY WITH FBC1006.1, MEANS OF EGRESS
 ILLUMINATION, INCLUDING BLEACHER STAIRS.
  
 14. ADDRESSED FOR ARCHITECT; STATEMENT OF COMPLIANCE
 FOR THRESHOLD BUILDING REQUIRED, FS553.79(7)(D).
  
 IS THE ARCHITECT MAKING THIS STATEMENT ON BEHALF OF THE
 ENGINEERS AS WELL, OR WILL THEY PROVIDE THEIR OWN
 STATEMENT IF THIS WAS NOT INCLUDED ON THEIR PLANS?
 PLEASE ADVISE
  
 15. ADDRESSED - EXIT FROM DOOR (FIRST FLOOR) TO PUBLIC
 WAY IS BLOCKED BY LANDSCAPING AND ELECTRIC EQUIPMENT.
 CONTINUOUS PATH REQUIRED FBC10. SITE PLAN 001 REVISED
 TO SHOW BLDG CODE COMPLIANCE
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 15 Status P Date 2009-10-13 Cont ID  
Sent By shill Date 2009-10-13 Time 12:19 Rev Time 0.00
Received By shill Date 2009-10-06 Time 07:11 Sent To  
Notes
2009-10-13 12:19:36****PROVISOS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 4. FBC1024.12, PER BUILDING OFFICIAL, SEATS CANNOT BE
 REMOVABLE. THIS WILL BE ISSUED WITH PROVISO, ALL SEATS
 FIXED, REMOVE SEATS AT ACCESSIBLE AREA.
  
 8. VERTICAL ACCESSIBILITY AND ACCESSIBLE SEATING IS
 REQUIRED TO EAST MEZZANINE AND FIRST FLOOR RAISED
 SEATING. EITHER PROVIDE A WAIVER OR REVISE PLAN TO SHOW
 COMPLIANCE.
  
 9. PLEASE HAVE EOR REVIEW THE DELEGATED ENGINEERING ON
 THIS JOB, FAC61G15-31. THIS MAY BE DONE BY LETTER.
  
 10. FBC1023.6, EITHER PROVIDE SAFE DISPERSAL AREA OR
 ACCESSIBLE ROUTE TO THE PUBLIC WAY (EXIT DISCHARGE).
  
 11. FBC1019.1.4, SEE PROVISO ON PLAN, STAIRS TO COMPLY
 WITH FBC1019.1.4.
  
 13. PROVISO - COMPLY WITH FBC1006.1, MEANS OF EGRESS
 ILLUMINATION, INCLUDING BLEACHER STAIRS.
  
 14. STATEMENT OF COMPLIANCE FOR THRESHOLD BUILDING
 REQUIRED, FS553.79(7)(D).
  
 15. REVISE SHEET LP1 AS DISCUSSED - EXIT FROM DOOR
 (FIRST FLOOR) TO PUBLIC WAY IS BLOCKED BY LANDSCAPING
 AND ELECTRIC EQUIPMENT. CONTINUOUS PATH REQUIRED FBC10
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 14 Status P Date 2009-09-30 Cont ID  
Sent By shill Date 2009-09-30 Time 15:55 Rev Time 0.00
Received By shill Date 2009-09-30 Time 15:55 Sent To  
Notes
2009-09-30 15:55:45REVISION, S8
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 13 Status P Date 2009-09-29 Cont ID  
Sent By shill Date 2009-09-29 Time 16:27 Rev Time 0.00
Received By shill Date 2009-09-29 Time 16:27 Sent To  
Notes
2009-09-29 16:42:01****PROVISOS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 NUMBERING FROM PREVIOUS BUILDING REVIEW #11
  
 4. FBC1024.12, PER BUILDING OFFICIAL, SEATS CANNOT BE
 REMOVABLE. THIS WILL BE ISSUED WITH PROVISO, ALL SEATS
 FIXED, REMOVE SEATS AT ACCESSIBLE AREA.
  
 8. VERTICAL ACCESSIBILITY AND ACCESSIBLE SEATING IS
 REQUIRED TO EAST MEZZANINE AND FIRST FLOOR RAISED
 SEATING. EITHER PROVIDE A WAIVER OR REVISE PLAN TO SHOW
 COMPLIANCE.
  
 9. PLEASE HAVE EOR REVIEW THE DELEGATED ENGINEERING ON
 THIS JOB, FAC61G15-31. THIS MAY BE DONE BY LETTER.
  
 10. FBC1023.6, EITHER PROVIDE SAFE DISPERSAL AREA OR
 ACCESSIBLE ROUTE TO THE PUBLIC WAY (EXIT DISCHARGE).
  
 11. FBC1019.1.4, SEE PROVISO ON PLAN. EAST STAIR HAS
 OPENINGS WITHIN 10FT; REVISE TO SHOW COMPLIANCE WITH
 FBC1019.1.4.
  
 13. PROVISO - COMPLY WITH FBC1006.1, MEANS OF EGRESS
 ILLUMINATION, INCLUDING BLEACHER STAIRS.
  
 14. STATEMENT OF COMPLIANCE FOR THRESHOLD BUILDING
 REQUIRED, FS553.79(7)(D).
  
 15. REVISE SHEET LP1 AS DISCUSSED - EXIT FROM DOOR
 (FIRST FLOOR) TO PUBLIC WAY IS BLOCKED BY LANDSCAPING
 AND ELECTRIC EQUIPMENT. CONTINUOUS PATH REQUIRED FBC10

Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status P Date 2009-08-06 Cont ID  
Sent By shill Date 2009-08-06 Time 17:37 Rev Time 0.00
Received By shill Date 2009-08-03 Time 19:53 Sent To  
Notes
2009-08-06 17:38:10****PROVISOS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 NUMBERING FROM PREVIOUS BUILDING REVIEW #11
  
 4. FBC1024.12, PER BUILDING OFFICIAL, SEATS CANNOT BE
 REMOVABLE. THIS WILL BE ISSUED WITH PROVISO, ALL SEATS
 FIXED, REMOVE SEATS AT ACCESSIBLE AREA.
  
 8. VERTICAL ACCESSIBILITY AND ACCESSIBLE SEATING IS
 REQUIRED TO EAST MEZZANINE AND FIRST FLOOR RAISED
 SEATING. EITHER PROVIDE A WAIVER OR REVISE PLAN TO SHOW
 COMPLIANCE.
  
 9. PLEASE HAVE EOR REVIEW THE DELEGATED ENGINEERING ON
 THIS JOB, FAC61G15-31. THIS MAY BE DONE BY LETTER.
  
 10. FBC1023.6, EITHER PROVIDE SAFE DISPERSAL AREA OR
 ACCESSIBLE ROUTE TO THE PUBLIC WAY (EXIT DISCHARGE).
  
 11. FBC1019.1.4, SEE PROVISO ON PLAN. EAST STAIR HAS
 OPENINGS WITHIN 10FT; REVISE TO SHOW COMPLIANCE WITH
 FBC1019.1.4.
  
 13. PROVISO - COMPLY WITH FBC1006.1, MEANS OF EGRESS
 ILLUMINATION, INCLUDING BLEACHER STAIRS.
  
 14. STATEMENT OF COMPLIANCE FOR THRESHOLD BUILDING
 REQUIRED, FS553.79(7)(D).
  
 15. IMPACT FEES REQUIRED FOR NEW MEZZANINES, 233-5025.
 THIS REVISION IS SUBJECT TO RECEIPT OF STAMPED PLANS
 AND RECEIPT.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status P Date 2009-07-28 Cont ID  
Sent By jwitmer Date 2009-07-27 Time 07:52 Rev Time 2.75
Received By jwitmer Date 2009-07-25 Time 14:32 Sent To  
Notes
2009-07-27 07:52:01BUILDING PLAN REVIEW
 PERMIT: 08090611
 ADD: 1590 FLORIDA MANGO
 CONT: SOUTHEAST CERTIFIED
 TEL: (561)635-6935
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 PHASE II REVIEW
 ACTION:
 BUILDING PROVISO:
 7-28-09
  
 1-10) COMPLIED.
  
 11) A NEW EXTERIOR STAIR ON THE EAST END OF THE
 BUILDING APPEARED TO HAVE UNPROTECTED OPENINGS WITHIN
 10 FT OF THE STAIR AND LANDINGS, INDICATING REVIEWING
 1019.1.4.
  
 1019.1.4 VERTICAL ENCLOSURE EXTERIOR WALLS.
 EXTERIOR WALLS OF A VERTICAL EXIT ENCLOSURE SHALL
 COMPLY WITH THE REQUIREMENTS OF SECTION 704 FOR
 EXTERIOR WALLS. WHERE NONRATED WALLS OR UNPROTECTED
 OPENINGS ENCLOSE THE EXTERIOR OF THE STAIRWAY AND THE
 WALLS OR OPENINGS ARE EXPOSED BY OTHER PARTS OF THE
 BUILDING AT AN ANGLE OF LESS THAN 180 DEGREES (3.14
 RAD), THE BUILDING EXTERIOR WALLS WITHIN 10 FEET (3048
 MM) HORIZONTALLY OF A NONRATED WALL OR UNPROTECTED
 OPENING SHALL BE CONSTRUCTED AS REQUIRED FOR A MINIMUM
 1-HOUR FIRE-RESISTANCE RATING WITH ??-HOUR OPENING
 PROTECTIVES. THIS CONSTRUCTION SHALL EXTEND VERTICALLY
 FROM THE GROUND TO A POINT 10 FEET (3048 MM) ABOVE THE
 TOPMOST LANDING OF THE STAIRWAY OR TO THE ROOF LINE,
 WHICHEVER IS LOWER.
  
 SHEET 722 THE NEW ELEVATION CLEARLY INDICATES BENEATH
 THE STAIR LANDING OF THE MEZZANINE, A ROLL UP DOOR, THE
 MEZZANINE LEVEL THE EXTERIOR EXIT DOOR, NEITHER DOOR IS
 INDICATED IN THE DOOR SCHEDULE NOR DOES THE ELEVATION
 INDICATE ANY FIRE RATING. THE PLANS ALSO FAIL TO
 INDICATE FIRE RATINGS ON THE WINDOWS DIRECTLY NEXT TO
 THE EXIT DOOR OF THE MEZZANINE LEVEL. IN BOTH CASES THE
 OPENING PROTECTIVES WILL NEED TO BE ONE HOUR RATING.
 THE OTHER WINDOWS THAT ARE ADJACENT (WITHIN 10 FT OF
 THE LANDING) WILL NEED TO BE 45 MINUTE RATED OPENINGS,
 THE LOUVER TO THE RIGHT OF THE LANDING. PLEASE PROVIDE
 THE VERTICAL DISTANCE FROM THE WINDOWS DIRECTLY OVER
 THE LANDING AND LEFT OF THE LANDING, ONCE THIS
 DIMENSION IS KNOWN THEY ALSO MAY NEED TO BE FIRE RATED
 OPENINGS.
  
 I SPOKE WITH BOTH ERIC ANDERSON AN CHRIS HAIR ABOURT
 THE UNPROTECTED OPENING REQUIREMENTS. THEY WILL BE
 WORKING ON THESE REQUIREMENTS AND WILL SUBMIT REVISIONS
 TO THIS OFFICE BEFORE A CERTIFICATE OF OCCUPANCY WILL
 BE ISSUED FOR THIS PHASE OF WORK.
  
 11-15 COMPLIED.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status F Date 2009-07-22 Cont ID  
Sent By shill Date 2009-07-22 Time 10:42 Rev Time 0.00
Received By shill Date 2009-07-20 Time 20:33 Sent To  
Notes
2009-07-22 10:46:34****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
  
 1. EACH PORTION OF A STRUCTURE IS TO BE CLASSIFIED AS
 TO USE, FBC302.1. SHEET T, A4 IS DECLARED, BUT PLAN
 SHOWS STORAGE, ARCADE (FBC302.2.1), CONCESSION
 W/DINING. PLEASE CLARIFY SQUARE FOOT AREA PER OCCUPANCY
 CLASSIFICATION.
  
 2. PLEASE SHOW COMPLIANCE WITH FBC CHAPTER 5. PLAN
 STATES THAT FBC507.2 ALLOWS UNLIMITED AREA; PLEASE SEE
 COMMENT 1. PLEASE DECLARE BUILDING AS SEPARATED OR NON
 SEPARATED USE, FBC302.
  
 3. PLEASE NOTE THAT COMPLIANCE FOR THE ENTIRE BUILDING
 IS TO BE SHOWN ON THE PLAN. SHEET T ACCOUNTS FOR THE
 RINK AREAS ONLY, BUT THIS IS ONLY A PORTION OF THE
 BUILDING. PLEASE REVISE AREA CALCULATIONS TO INCLUDE
 ALL PARTS OF THE BUILDING, UNLESS SEPARATED BY A FIRE
 WALL, FBC502.
  
 4. FBC1024.12, SEATS SHALL BE SECURELY FASTENED TO THE
 FLOOR. THE PLANS NOTE THAT SOME SEATS SHALL BE
 REMOVABLE TO ACCOMMODATE ACCESSIBLE SEATING, SHEET 212.
 PLEASE ADDRESS. ALSO NOTE THAT THIS PAGE IS LABELED
 SECOND FLOOR SEATING PLAN; ISN???T THIS THE FIRST
 FLOOR?
  
 5. PLEASE CLARIFY HOW OCCUPANT LOAD HAS BEEN
 CALCULATED. FOR INSTANCE, FIRST FLOOR STATES THAT
 OCCUPANT LOAD HAS BEEN DETERMINED BY 36,225 SF, 50 SF
 PER OCCUPANT, TOTAL OF 725. THE FIRST FLOOR CONSISTS OF
 THE SKATING RINK (50 SF GROSS), FIXED SEATING (SEE
 FBC1004.7), ARCADE (11 GROSS PER FBC TABLE 1004.1.2),
 ETC. IT APPEARS THAT THE TOTAL OCCUPANT LOAD MAY BE
 CONSERVATIVE, BUT PLEASE PROVIDE CALCULATIONS OF
 OCCUPANTS PER AREA TO CONFIRM COMPLIANCE WITH
 FBC1004.1.
  
 SHEET T DECLARES 271 OCCUPANTS, SHEET 120 SHOWS 268
 TOTAL. PLEASE CONFIRM THAT LIFE SAFETY PLAN CORRELATES
 WITH OTHER SHEETS.
  
 6. AS THE ARCHITECT OF RECORD HAS CHANGED, PLEASE
 EITHER PROVIDE EITHER A LETTER TO CONFIRM THAT
 COMPLIANCE WITH FAC61G1-18.002 HAS BEEN MET IF REUSING
 THE PREVIOUS ARCHITECT???S PLANS, OR PROVIDE NEW SIGNED
 AND SEALED SHEETS FOR ALL SHEETS REQUIRED TO SHOW CODE
 COMPLIANCE.
  
 7. FBC1004.3, OCCUPANT LOAD FOR EVERY ROOM OR SPACE
 SHALL BE POSTED. THIS WILL BE A PROVISO ITEM.
  
 8. FBC11-4.33.3, ACCESSIBLE SEATING CAPACITY IS OVER
 300; WHEELCHAIR SPACES TO BE PROVIDED IN MORE THAN ONE
 LOCATION. ALL ACCESSIBLE SEATING IS SHOWN IN ONE
 MEZZANINE. ARCHITECT ADVISED THAT HE WILL APPLY FOR A
 WAIVER FOR THE EAST MEZZANINE, BUT WHEELCHAIR SEATING
 IS TO BE PROVIDED AT THE FIRST FLOOR ALSO. VERTICAL
 ACCESSIBILITY IS REQUIRED TO THE EAST MEZZANINE,
 FBC11-4.1.3(5), AND ACCESSIBLE SEATING IS REQUIRED IN
 THE EAST MEZZANINE, UNLESS OTHERWISE APPROVED BY
 WAIVER.
  
 9. PLEASE HAVE EOR REVIEW THE DELEGATED ENGINEERING ON
 THIS JOB, FAC61G15-31.
  
 10. FBC1023.6, IT APPEARS THAT THE EXCEPTION APPLIES TO
 THIS PROJECT (SAFE DISPERSAL AREA). THIS WILL BE A
 PROVISO ITEM.
  
 11. SEE FBC106, MINIMUM PLAN REVIEW CRITERIA. PLEASE
 PROVIDE ELEVATIONS OF BUILDING EXTERIOR. IT APPEARS
 THAT THE PROPOSED NEW STAIRS ARE WITHIN 10FT OF
 UNPROTECTED OPENINGS, SEE FBC1019.1.4.
  
 12. PLEASE PROVIDE UPDATED VALUE FOR INCREASED SCOPE OF
 WORK.
  
 13. PLEASE SHOW COMPLIANCE WITH FBC1006.1, MEANS OF
 EGRESS ILLUMINATION. IT IS NOT CLEAR HOW THE STAIRS
 (INCLUDING THE FIXED SEATING) WILL COMPLY.
  
 14. ENERGY CALCS GIVE A SF AREA OF 9600, PLANS STATE
 36,225. PLEASE REVISE OR EXPLAIN.
  
 15. PLEASE CONTACT ME WHEN ALL REVIEWS ARE COMPLETE IF
 ISSUANCE OF THIS REVISION WITH PROVISOS IS DESIRED. THE
 PREFERENCE IS THAT ALL ITEMS BE ADDRESSED PRIOR TO
 ISSUANCE; HOWEVER, TO AVOID FIELD DELAYS, IT IS
 POSSIBLE THAT THIS REVISION MAY BE ISSUED WITH PROVISO.
 PLEASE CONTACT ME WHEN ALL REVIEWS ARE COMPLETE TO
 DISCUSS HOW YOU WISH TO PROCEED.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status F Date 2009-06-15 Cont ID  
Sent By shill Date 2009-06-15 Time 08:09 Rev Time 0.00
Received By shill Date 2009-06-15 Time 08:09 Sent To Z
Notes
2009-06-15 08:16:05****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. AS THIS HAS BEEN SUBMITTED AS A REVISION, FBC2004 IS
 GOVERNING CODE, ASCE7-02 IS CORRECT ASCE STANDARD,
 FBC35. EITHER REVISE THE PLAN OR PROVIDE A LETTER
 STATING THAT THE DESIGN COMPLIES WITH THE REQUIREMENTS
 OF ASCE7-02.
  
 2. FS553.79(7)(D), AS THIS IS A THRESHOLD BUILDING,
 THIS STATEMENT IS REQUIRED. IF THE STATEMENT IS NOT
 INCLUDED ON EACH SHEET, THE STATEMENT SHOULD BE
 INCLUDED ON THE INDEX SHEET SO THAT IT IS CLEAR WHICH
 "PLANS" THE STATEMENT REFERS TO.
  
 (D) ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED TO BE
 SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE
 ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRESAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS CHAPTER AND CHAPTER 633.
  
 3. PROVIDE THE VALUE FOR THE ADDITIONAL SCOPE OF WORK.
  
 4. IT APPEARS THAT THIS AREA IS TO BE A CHANGE OF
 OCCUPANCY, FROM S1 TO A4. IMPACT FEES MAY BE DUE;
 PLEASE CONTACT PALM BEACH COUNTY, 561-233-5025 FOR MORE
 INFORMATION. THE PLANS ARE TO BE STAMPED AND THE
 RECEIPT, IF FEES ARE DUE, INCLUDED AT TIME OF
 RESUBMITTAL. IMPACT FEES ARE DUE PRIOR TO ISSUANCE OF A
 FOUNDATION PERMIT.
  
 5. SHEET S5 REFERS TO FBC2007 AND HVZ. GOVERNING CODE
 (DUE TO APPLICATION DATE) IS FBC2004 WITH 2007
 SUPPLEMENTS, AND PALM BEACH COUNTY IS NOT WITHIN THE
 HVHZ. PLEASE NOTE THAT IN SOME INSTANCES, HVHZ IS LESS
 STRINGENT THAN NON-HVHZ. PLEASE REVISE OR CLARIFY
 INTENT.
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2009-06-01 Cont ID  
Sent By dwise Date 2009-06-01 Time 21:53 Rev Time 0.00
Received By dwise Date 2009-06-01 Time 21:53 Sent To PC
Notes
2009-06-01 21:55:12APPROVED AS NOTED ON PLANS. MUST REVISE MEP PLANS TO
 REFLECT RELOCATION OF STAIRS, MOST IMPORTANTLY SHEETS
 E-2B AND E-4 TO REFLECT NEW REQUIREMENTS FOR MEANS OF
 EGRESS LIGHTING OVER RELOCATED STAIR AND EXISTING MEANS
 OF EGRESS CORRIDOR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2009-05-27 Cont ID  
Sent By dwise Date 2009-05-22 Time 19:40 Rev Time 0.00
Received By dwise Date 2009-05-22 Time 19:40 Sent To  
Notes
2009-05-27 19:42:331. STAIRWAY IS BLOCKING PRIMARY MEANS OF EGRESS FOR
 ASSEMBLY OCCUPANCY.
 CONTACTED ARCHITECT REQUESTING CORRECTIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2009-03-30 Cont ID  
Sent By shill Date 2009-03-30 Time 18:01 Rev Time 0.00
Received By shill Date 2009-03-30 Time 18:01 Sent To  
Notes
2009-03-30 18:02:59REVISION #3 DATED 3/20/9
 SHEETS A.01, A01.1,A.02,A.06,A.07,A.10.1
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2009-03-04 Cont ID  
Sent By shill Date 2009-03-04 Time 17:10 Rev Time 0.00
Received By shill Date 2009-03-04 Time 17:10 Sent To  
Notes
2009-03-04 17:12:46****PROVISOS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 PROVISO - SHOP DRAWINGS FOR THE FIRE RATED GLAZING WILL
 BE REQUIRED PRIOR TO INSTALLATION.
  
 PROVISO - E3, E4, LS01 MISSING STROBES IN SOME
 BATHROOMS - REVISE ACCORDINGLY PRIOR TO FIRE ALARM
 INSTALLATION
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2009-03-04 Cont ID  
Sent By shill Date 2009-03-03 Time 17:07 Rev Time 0.00
Received By shill Date 2009-03-03 Time 17:08 Sent To  
Notes
2009-03-04 17:07:56****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 COMMENTS FROM PREVIOUS REVIEWS:
  
  
 37. SEE ENERGY CALCS; NO DOORS SHOWN, ICE RINK FLOOR IS
 SHOWN AS CARPET. PLEASE REVISE THESE ITEMS AND CHECK
 ALL INFORMATION ON THE ENERGY CALC INPUT DATA REPORT.
  
 2ND REVIEW, THIS HAS BEEN ADDRESSED. HOWEVER, PLEASE
 EXPLAIN THE ROOF R VALUE; R19 BATT INSULATION IS SHOWN
 (MULTIPLIED BY BTU) THAT IT HAS AN R VALUE OF 30.
 PLEASE CLARIFY HOW R30.3 WILL BE ACHIEVED.
 3RD REVIEW, THIS HAS NOT BEEN REVISED OR EXPLAINED.
 FEEL FREE TO CONTACT ME VIA EMAIL OR TELEPHONE TO
 CLARIFY THIS NUMBER (R30). ALSO PLEASE NOTE THAT DOORS
 AND WINDOWS HAVE NOW BEEN REMOVED FROM THE ENERGY
 CALCS. PLEASE CONFIRM THAT ALL BUILDING DATA IS CORRECT
 PRIOR TO RESUBMITTING.
  
 CALLED ENGINEER; WILL BRING NEW CALCS
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2009-02-10 Cont ID  
Sent By shill Date 2009-02-10 Time 17:00 Rev Time 0.00
Received By shill Date 2009-02-10 Time 17:00 Sent To  
Notes
2009-02-10 17:16:09****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 COMMENTS FROM FIRST REVIEW:
  
 1. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY REQUIRED
 PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD. PLEASE CALL
 561-233-5025 FOR MORE INFORMATION. THE PLANS MUST BE
 STAMPED AND THE RECEIPT IS TO BE INCLUDED WITH THE
 PERMIT APPLICATION.
  
 NOT COMPLETED AT THIS TIME. PLEASE NOTE THAT THIS ITEM
 MUST BE DONE PRIOR TO PERMIT ISSUANCE, BUT MAY BE DONE
 AFTER ALL PLAN REVIEWS HAVE BEEN COMPLETED (NO RESUB
 FEE IF SUBMITTAL IS FOR IMPACT FEE ONLY, AND HAS PASSED
 ALL TRADES).
  
 2-25. ADDRESSED.
  
 27. FBC13-101.3, BUILDING SHALL COMPLY WITH FBC13-4.
  
 3RD REVIEW, TOTAL SF AREA TOTAL 46709, BUT THE PLANS
 STATE THE RENOVATED AREA IS 44714. PLEASE REVISE.
  
 28. ADDRESSED.
  
 29. PROVISO - SHOP DRAWINGS FOR THE FIRE RATED GLAZING
 WILL BE REQUIRED PRIOR TO INSTALLATION.
  
 30-35. ADDRESSED (SEPARATE PERMIT REQUIRED FOR
 AWNINGS).
  
 36. SOILS REPORT, ALL INFORMATION REQUIRED BY
 FAC61G15-23.002(2) REQUIRED (CERTIFICATE OF
 AUTHORIZATION). PLEASE NOTE THAT THIS REQUIREMENT HAS
 RECENTLY BEEN REVISED.
  
 37. SEE ENERGY CALCS; NO DOORS SHOWN, ICE RINK FLOOR IS
 SHOWN AS CARPET. PLEASE REVISE THESE ITEMS AND CHECK
 ALL INFORMATION ON THE ENERGY CALC INPUT DATA REPORT.
  
 2ND REVIEW, THIS HAS BEEN ADDRESSED. HOWEVER, PLEASE
 EXPLAIN THE ROOF R VALUE; R19 BATT INSULATION IS SHOWN
 (MULTIPLIED BY BTU) THAT IT HAS AN R VALUE OF 30.
 PLEASE CLARIFY HOW R30.3 WILL BE ACHIEVED.
 3RD REVIEW, THIS HAS NOT BEEN REVISED OR EXPLAINED.
 FEEL FREE TO CONTACT ME VIA EMAIL OR TELEPHONE TO
 CLARIFY THIS NUMBER (R30). ALSO PLEASE NOTE THAT DOORS
 AND WINDOWS HAVE NOW BEEN REMOVED FROM THE ENERGY
 CALCS. PLEASE CONFIRM THAT ALL BUILDING DATA IS CORRECT
 PRIOR TO RESUBMITTING.
  
 38. PLEASE HAVE THE ARCHITECT SIGN THE ENERGY CALC,
 FBC103.1.1.1. IF A TYPED NAME IS PROVIDED IN LIEU OF A
 SIGNATURE, PLEASE CONFIRM THAT ALL RELEVANT INFORMATION
 (INCLUDE THE EXISTING COMPONENTS, SUCH AS EXISTING
 INSULATION) IS INCLUDED.
  
 2ND REVIEW, NOT ADDRESSED. ARCHITECT?S RESPONSE LETTER
 STATES HE WILL COMPLY. PLEASE REVISE ENERGY CALCS PER
 REVIEW COMMENTS AND, WHEN RESUBMITTING, CONFIRM THAT
 ARCHITECT HAS SIGNED THE APPROPRIATE LINE.
 3RD REVIEW, NOT ADDRESSED. SIGNATURE NOT INCLUDED,
 PRINTED NAME NOT INCLUDED.
  
 39-40. ADDRESSED.
  
 41. PROVISO - AT RISK (EXTERIOR PERMIT NOT YET ISSUED)
  
 42-44. ADDRESSED.
  
 45. PROVISO - LOUVER PRODUCT APPROVALS REQUIRED,
 REVIEWED BY DESIGNER OF RECORD
  
 46. ADDRESSED.
  
 47. PROVISO - E3, E4, LS01 MISSING STROBES IN SOME
 BATHROOMS - REVISE ACCORDINGLY PRIOR TO FIRE ALARM
 INSTALLATION
  
 48. ADDRESSED.
  
 NEW COMMENTS:
  
 49. INFORMATIONAL ONLY; LEVEL III ALTERATION DECLARED.
 SEE DEFINITION OF LEVEL III; THIS IS DEFINED AS HAVING
 A WORK AREA OVER 50% OF BUILDING AREA, BUT THE NEW
 INFORMATION REGARDING BUILDING AREA SHOWS THIS IS LESS
 THAN 50%. PLEASE NOTE THAT IT IS ACCEPTABLE TO EXCEED
 CODE COMPLIANCE; HOWEVER, IF LEVEL III IS DECLARED, IT
 SHALL BE ENFORCED BOTH IN PLAN REVIEW AND IN THE FIELD
 (INSPECTIONS).
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-12-30 Cont ID  
Sent By shill Date 2008-12-30 Time 09:00 Rev Time 0.00
Received By shill Date 2008-12-27 Time 14:50 Sent To  
Notes
2008-12-30 09:00:16****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 COMMENTS FROM FIRST REVIEW:
  
 1. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY REQUIRED
 PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD. PLEASE CALL
 561-233-5025 FOR MORE INFORMATION. THE PLANS MUST BE
 STAMPED AND THE RECEIPT IS TO BE INCLUDED WITH THE
 PERMIT APPLICATION.
  
 NOT COMPLETED AT THIS TIME. PLEASE NOTE THAT THIS ITEM
 MUST BE DONE PRIOR TO PERMIT ISSUANCE.
  
 2-5. ADDRESSED.
  
 6. A01 SPECIFIES WP1200 WALL; PROVIDE A DETAIL FBC 7,
 FBC*106.
  
 2ND REVIEW, DETAIL W6 WAS ADDED TO A.10.1 BUT IS NOT
 COMPLETE WITH ALL DETAILS AND SPECIFICATIONS. FOR
 INSTANCE, DETAIL STATES THAT METAL STUD IS TO BE ?AS
 REQUIRED?. UL U497 HAS A MINIMUM GAUGE FOR METAL STUD.
 PLEASE INCLUDE ALL SPECIFICATIONS FOR CONSTRUCTION OF
 THIS WALL, AND CHECK ALL OTHER UL ASSEMBLY DETAILS.
  
 7. CV01 STATES THAT OFFICES, STORAGE, AND MERCANTILE
 AREAS ARE ACCESSORY. DECLARE TOTAL SQUARE FOOT AREA FOR
 EACH FBC 5.
  
 2ND REVIEW, ACCESSORY AREAS ARE NOT TO EXCEED 10%,
 FBC302.2. THE STORAGE AREA SHOULD BE DECLARED S1, AND
 THE BUILDING AS A MIXED OCCUPANCY, SEE FBC302.1,
 FBC302.2. AS THE STORAGE AREAS EXCEED 20%, THEY CANNOT
 BE DECLARED AS ACCESSORY USE. PLEASE SEE ALSO
 FBC302.3.1.
  
 8. THIS ITEM WAS ADDRESSED, BUT PLEASE SEE OTHER
 COMMENTS REGARDING ISSUES WITH THE BUILDING CODE
 SUMMARY.
  
 9. NOTE ALL REQUIRED FIRE RATED WALLS ON THE PLAN.
 OPENING AND PENETRATION PROTECTION REQUIREMENTS, ETC.
 ARE NOT READILY APPARENT WITHOUT THIS INFORMATION FBC7.
  
 2ND REVIEW, PLEASE INCLUDE FIRE RATING REQUIREMENT FOR
 WALL TYPE W11. PLEASE SEE MECHANICAL COMMENTS REGARDING
 MISSING FIRE DAMPERS (M SHEETS).
  
 IT APPEARS THAT THE ARCHITECT IS SPECIFYING A 2 HOUR
 OCCUPANCY SEPARATION (HORIZONTAL AND VERTICAL) AS WELL
 AS A 1 HOUR CORRIDOR. SEE SHEET A13, FBC712.4.1.2,
 SPECIFY LOCATIONS OF PENETRATIONS WITH A T RATING OF 0
 OR 1, OR OTHERWISE NOTE LIMITATION OF USE OF THESE
 DETAILS.
  
 PLEASE ALSO SEE FBC706.1 AND FBC708.1, OCCUPANCY
 SEPARATIONS ARE TO BE FIRE BARRIERS, NOT FIRE
 PARTITIONS AS NOTED ON THE PLAN.
  
 10. DECLARE OCCUPANT LOAD FBC 1004.
  
 THIS ITEM WAS ADDRESSED, BUT SEE SHEETS E4 AND A01. THE
 BREAK ROOM (A01) IS SHOWN AS A VIEWING ROOM (E4). IT IS
 UNCLEAR AS TO HOW THIS AREA HAS BEEN CLASSIFIED ON
 CV01. ALTHOUGH THE AREA IS SMALL, THIS MAY AFFECT
 OCCUPANT LOAD; IT APPEARS THAT 100SF PER OCCUPANT HAS
 BEEN USED, BUT POSSIBLY OCCUPANT LOAD AS HIGH AS 7SF
 PER OCCUPANT MAY BE REQUIRED.
  
 11. ADDRESSED.
  
 12. SP01 SHOWS THREE DIFFERENT BUILDINGS. PLEASE SEE
 FBC TABLE 503, FBC TABLE 601, FBC TABLE 602. DO FIRE
 WALLS EXIST SEPARATING THESE BUILDINGS OR ARE THEY ONE
 BUILDING FOR PURPOSES OF FBC CHAPTERS 5 AND 6? AN
 OPENING IS SHOWN BETWEEN THE NORTH AND CENTER
 BUILDINGS; SEE FBC TABLE 704.8, NO OPENINGS PERMITTED
 WITH A SEPARATION OF 0 TO 3 FEET.
  
 2ND REVIEW, PLEASE SEE ROCAMAR ENGINEERING RESPONSES TO
 ELECTRIC COMMENTS. HE STATES THAT THESE ARE THREE
 SEPARATE BUILDINGS, YET THE ARCHITECT ON THE PLAN AND
 IN THE RESPONSE LETTER STATES THAT THEY ARE ONE
 BUILDING. PLEASE COORDINATE WITH OTHER DESIGN
 PROFESSIONALS. THIS REVIEW HAS BEEN DONE ON THE
 ASSUMPTION THAT THE ARCHITECT IS CORRECT, AND THE THREE
 BUILDING AREAS ARE TO BE TREATED AS ONE BUILDING. IF
 THE THREE BUILDING AREAS ARE TO BE CONSIDERED THREE
 SEPARATE BUILDINGS, THEY MUST BE SEPARATED WITH FIRE
 WALLS FBC705.
  
 13. ADDRESSED.
  
 14. CV01, DECLARE TOTAL SQUARE FOOT AREA FOR THE
 BUILDING OR BUILDINGS (SEE OTHER COMMENTS), FBC5, FBC6,
 FBC EB8.
  
 2ND REVIEW, PLEASE EXPLAIN BUILDING AREA DECLARED ON
 CV01. THE ICE RINK AREA APPEARS TO BE APPROXIMATELY
 42,250, TOTAL SF AREA DECLARED ON CV1 IS 43,310. THIS
 APPEARS TO BE LESS THAN HALF THE SIZE OF THE BUILDING.
 SEE DEFINITION OF AREA, BUILDING, FBC502. IT APPEARS
 THAT ONLY THE ICE RINK AREA WAS TAKEN INTO ACCOUNT, YET
 BY DEFINITION THIS IS NOT THE ENTIRE BUILDING.
 INFORMATION REGARDING THE ENTIRE BUILDING, ALL THREE
 SPACES, MUST BE SHOWN AS WELL AS COMPLIANCE WITH FBC
 CHAPTER 5, BUILDING HEIGHT AND AREA.
  
 PLEASE NOTE THAT THE PLAN SHOWS A 2 HR DEMISING WALL,
 NOT A 3 HOUR FIRE WALL SEPARATING BUILDINGS, SEE
 DEFINITION FBC705, FBC TABLE 705. UNLIMITED AREA
 BUILDING REQUIREMENT IS OPEN SPACE AROUND THE
 PERIMETER, BUT IF THIS IS DESIGNED AS A ?SEPARATE
 BUILDING?, ONE SIDE LACKS THE OPEN SPACE (THE SIDE
 AGAINST THE OTHER BUILDING). IF THE ENTIRE BUILDING
 AREA IS TAKEN INTO ACCOUNT, INFORMATION REGARDING THE
 OTHER PORTION(S) OF THE BUILDING MUST BE SHOWN TO
 DEMONSTRATE COMPLIANCE WITH FBC 5, FBC 6.
  
 CV.01 STATES THAT TWO STORIES ARE ALLOWED PER FBC503.
 ONLY ONE STORY PERMITTED FOR UNLIMITED AREA BUILDINGS
 FBC507.2; IF YOU CHOOSE TO DESIGN USING FBC TABLE 503
 PLEASE SHOW COMPLIANCE WITH THE TABLE ALONG WITH
 CALCULATIONS FOR ALLOWABLE INCREASES (SPRINKLER, OPEN
 SPACE).
  
 INFORMATIONAL ONLY; PLEASE NOTE THAT S2 OCCUPANCY IS
 FOR NON COMBUSTIBLE STORAGE AS DEFINED IN FBC311.3. IF
 THIS OCCUPANCY CLASSIFICATION IS DECLARED FOR THE OTHER
 SPACES, SUPPORTING DOCUMENTATION WILL BE REQUIRED. S1
 IS THE MORE TYPICAL CLASSIFICATION FBC311.2.
  
 15. CV01, PROVIDE TOTAL SQUARE FOOT AREAS FOR THE
 PROPOSED MEZZANINES AS WELL AS OCCUPANCY CLASSIFICATION
 FOR THE USE OF THESE SPACES, FBC 3, FBC10, FBC11.
  
 2ND REVIEW, PLEASE SEE ELECTRIC COMMENTS, MEP AND
 STRUCTURAL SHEETS. STAIRS ARE STILL SHOWN ON THE PLAN
 TO A MEZZANINE AREA, YET THE ARCHITECT STATES THAT
 THERE IS NO MEZZANINE AT THIS TIME AND HAS REMOVED THE
 MEZZANINE FROM THE ARCHITECTURAL AND LIFE SAFETY
 SHEETS. PLEASE COORDINATE. ALL PLANS SHOULD REFLECT THE
 SAME FLOOR PLAN.
  
 S2 STILL REFERS TO THE EQUIPMENT PLATFORM AS A
 MEZZANINE. SEE PREVIOUS COMMENT LIST REGARDING CODE
 ISSUES FOR MECHANICAL EQUIPMENT IN A MEZZANINE. PLEASE
 COORDINATE ALL TRADES; A THOROUGH REVIEW CANNOT BE DONE
 DUE TO CONFLICTING INFORMATION.
  
 ALSO PLEASE SEE OTHER COMMENTS REGARDING THIS AREA.
  
 16. THE MEZZANINE AREAS MUST MEET THE DEFINITION
 FBC502. PLEASE DEMONSTRATE COMPLIANCE ON THE PLAN.
  
 2ND REVIEW, SEE COMMENT 15. PLANS SUBMITTED ARE NOT
 CONSISTENT AND CODE COMPLIANCE FBC502 HAS NOT BEEN
 SHOWN.
  
 17-19. ADDRESSED.
  
 20. SEE FBC*109.3.6.4.4, FS553.79(7)(D) AND INCLUDE THE
 STATEMENT ATTESTING TO COMPLIANCE.
  
 2ND REVIEW, LANDSCAPE ARCHITECT?S PLAN SHOWS CODE
 COMPLIANCE FOR BUILDING AREA, ACCESSIBLE ROUTE,
 ACCESSIBLE PARKING, ETC. THIS SHEET SHOULD ALSO INCLUDE
 THE STATEMENT REQUIRED BY FLORIDA STATUTE, OR HAVE
 OTHER DESIGN PROFESSIONALS TAKE RESPONSIBILITY FOR
 THESE ITEMS.
  
 22. PLANS ARE TO BE SIGNED, SEALED, AND DATED FS481.
 PLEASE INCLUDE A DATE ON THE SEAL.
  
 2ND REVIEW, PLANS ARE NOW SIGNED AND DATED BUT ONE SET
 IS NOT SEALED, FS481.
  
 23-24. ADDRESSED.
  
 25. FP SHEETS DO NOT HAVE A FIRE SPRINKLER PLAN FOR THE
 MEZZANINE AREAS.
  
 THIS WAS PROVIDED FOR THE MECHANICAL PLATFORM, BUT NOT
 FOR THE STRUCTURAL DECK (FUTURE MEZZANINE). PLEASE
 REVISE OR SHOW WHERE IN NFPA13 THIS AREA IS EXEMPTED.
 THE SAME SPACE IS BEING CREATED, BUT WITHOUT ACCESS
 STAIRS, IT SEEMS THAT THE FIRE RISK REMAINS.
  
 26. A01 SPECIFY FIRE RATING (TIME) REQUIRED FOR THE
 WP1200 WALL, SOUTH SIDE.
  
 ARCHITECT?S RESPONSE LETTER STATES THAT THIS WAS ADDED.
 SEE A01, UNABLE TO FIND INFORMATION REGARDING FIRE
 RATING FOR THE EXISTING DEMISING WALL.
  
 27. FBC13-101.3, BUILDING SHALL COMPLY WITH FBC13-4.
  
 ENERGY CALCS WERE SUBMITTED. PLEASE NOTE THE FOLLOWING:
  
 A. THE ENERGY CALCS DO NOT APPEAR TO INCLUDE THE SHELL
 FOR UNIT B. PLEASE REVISE. SQUARE FOOT AREA AND
 COMPONENTS ARE TO CORRELATE WITH THE PLANS. SEE
 FBC13-101.1.6.
  
 28. ADDRESSED.
  
 29. ADDRESSED; PLEASE NOTE THAT SHOP DRAWINGS FOR THE
 FIRE RATED GLAZING WILL BE REQUIRED PRIOR TO
 INSTALLATION (PROVISO ITEM).
  
 30-32. PLEASE SEE OTHER COMMENTS REGARDING THE
 MEZZANINE. IF MEZZANINES ARE INCLUDED IN THIS PROJECT,
 PLEASE ADDRESS COMMENTS.
  
 33. A03, AS CANOPY INFORMATION WAS NOT PROVIDED, A
 SEPARATE PERMIT WILL BE REQUIRED (INFORMATIONAL ONLY).
  
 34. PROVIDE MORE INFORMATION REGARDING THE UPPER LEVEL
 AREAS. SEE FBC505.5, INDUSTRIAL EQUIPMENT PLATFORMS ARE
 NOT TO BE A PART OF ANY MEZZANINE. ALSO DECLARE
 OCCUPANCY CLASSIFICATION FOR THESE AREAS, FBC CHAPTER
 3.
  
 2ND REVIEW, SEE FBC 502DEFINITIONS, INDUSTRIAL
 EQUIPMENT PLATFORMS ARE LIMITED TO USE IN INDUSTRIAL
 OCCUPANCIES. PLEASE RECLASSIFY THIS AREA OR REVISE AS
 REQUIRED IN FBC CHAPTER 5. NOTE THAT THE ENTIRE SPACE
 WAS CLASSIFIED AS A4, SEE SHEET CV.01. SEE ALSO OTHER
 COMMENTS REGARDING OCCUPANCY CLASSIFICATION.
  
 MEP AND STRUCTURAL SHEETS SHOW STAIRS TO THE WEST
 MEZZANINE AREA, ARCHITECTURALS HAVE REMOVED ACCESS.
 EQUIPMENT PLATFORM SHOWN AS MEZZANINE ON STRUCTURAL
 DRAWINGS. PLEASE COORDINATE.
  
 35. ADDRESSED.
  
 36. SOILS REPORT, ALL INFORMATION REQUIRED BY
 FAC61G15-23.002(2) REQUIRED (CERTIFICATE OF
 AUTHORIZATION). PLEASE NOTE THAT THIS REQUIREMENT HAS
 RECENTLY BEEN REVISED.
  
 2ND REVIEW, NOT ADDRESSED.
  
 37. SEE ENERGY CALCS; NO DOORS SHOWN, ICE RINK FLOOR IS
 SHOWN AS CARPET. PLEASE REVISE THESE ITEMS AND CHECK
 ALL INFORMATION ON THE ENERGY CALC INPUT DATA REPORT.
  
 2ND REVIEW, THIS HAS BEEN ADDRESSED. HOWEVER, PLEASE
 EXPLAIN THE ROOF R VALUE; R19 BATT INSULATION IS SHOWN
 (MULTIPLIED BY BTU) THAT IT HAS AN R VALUE OF 30.
 PLEASE CLARIFY HOW R30.3 WILL BE ACHIEVED.
  
 SEE SHEET A06, WALL SECTION DOES NOT SPECIFY BATT
 INSULATION. IT SPECIFIES NEW INSULATED EXTERIOR WALL
 AND ROOF PANELS, BUT R VALUE HAS NOT BEEN PROVIDED OR
 SPECIFIED ON THE PLAN. FBC*106, FBC13.
  
 38. PLEASE HAVE THE ARCHITECT SIGN THE ENERGY CALC,
 FBC103.1.1.1. IF A TYPED NAME IS PROVIDED IN LIEU OF A
 SIGNATURE, PLEASE CONFIRM THAT ALL RELEVANT INFORMATION
 (INCLUDE THE EXISTING COMPONENTS, SUCH AS EXISTING
 INSULATION) IS INCLUDED.
  
 2ND REVIEW, NOT ADDRESSED. ARCHITECT?S RESPONSE LETTER
 STATES HE WILL COMPLY. PLEASE REVISE ENERGY CALCS PER
 REVIEW COMMENTS AND, WHEN RESUBMITTING, CONFIRM THAT
 ARCHITECT HAS SIGNED THE APPROPRIATE LINE.
  
 NEW COMMENTS:
  
 39. PLEASE PROVIDE MORE INFORMATION REGARDING THE
 EXISTING ASPHALT ENTRY ROAD. IS THIS ENTIRELY ASPHALT
 OR IS THERE AN EXISTING SIDEWALK? SEE FBC11-1.2,
 FBC11-4.1.2(1), FBC11-4.1.6(1)(K), SHEET SP1. IT
 APPEARS THAT A SIDEWALK IS TO BE REMOVED TO ACCOMMODATE
 BERMS. ALSO IT APPEARS THAT THE SLIDING GATE (TO BE
 RELOCATED) BLOCKS THE ACCESSIBLE ROUTE FROM THE PUBLIC
 WAY TO THE BUILDING. PLEASE REVISE SITE PLAN TO CLARIFY
 SCOPE OF WORK.
  
 40. REGARDING THE PROPOSED BERMS, PLEASE SEE
 FBC*109.3.10, IMPACT OF CONSTRUCTION. PLEASE SHOW HOW
 THE DRAINAGE FOR THE ADJACENT PARCEL WILL BE AFFECTED
 BY THE PROPOSED BERM CONSTRUCTION.
  
 41. THE PLANS STATE THAT THE EXTERIOR IS ON A SEPARATE
 PERMIT, VARIOUS SHEETS INCLUDING SHEET CV01 WHICH
 REFERS TO 08090571. AT THIS TIME, ONLY DEMO FOR THE
 EXTERIOR HAS BEEN ISSUED. PLEASE RESUBMIT THE EXTERIOR
 RENOVATION PLANS UNDER PERMIT 08090571, OR PROVIDE ALL
 INFORMATION FOR THE BUILDING EXTERIOR WITH THIS
 RESUBMITTAL, OR AS A REVISION TO THE DEMO PERMIT. THIS
 MUST BE DONE PRIOR TO ISSUANCE OF THIS PERMIT;
 INFORMATION AND COMPLIANCE FOR 140MPH MUST BE
 DEMONSTRATED FBC1609.
  
 42. THE LIFE SAFETY PLAN DOES NOT INCLUDE THE ICE RINK
 AREA IN THE TRAVEL DISTANCE. THIS MUST BE INCLUDED,
 FROM WORST CASE (DISTANCE FARTHEST FROM RINK EGRESS).
  
 SEE SHEET LS01. IT STATES LIFE SAFETY IS PER TABLE 1004
 AND 704. TABLE 1004 IS TO DETERMINE OCCUPANT LOAD, 704
 SPECIFIES FIRE RATING REQUIREMENTS FOR EXTERIOR WALL.
 SHEET CV01 CORRECTLY STATES THAT EXIT ACCESS TRAVEL
 DISTANCE LIMITATION IS 200FEET. IT ALSO STATES THAT
 MAXIMUM IS 168FEET. SHEET LS01 STATES THAT REQUIRED
 TRAVEL DISTANCE IS 325FEET, 179 FEET PROVIDED. SEE FBC
 TABLE 1015.1. 200 FEET IS THE MAXIMUM ALLOWED (NOT
 REQUIRED). WHY WOULD CV01 STATE 168 FEET, WHICH IS LESS
 THAN 179 FEET? IT APPEARS THAT THE TRAVEL DISTANCE OF
 179 FEET DOES NOT INCLUDE THE ICE ARENA, PLEASE REVISE.
  
 THE SAME TABLE STATES THAT ? HR FIRE RATING IS REQUIRED
 FOR CORRIDORS, BUT 1 HOUR IS REQUIRED. IT STATES THAT
 25FT DEAD END CORRIDOR IS REQUIRED, BUT ONLY 20FEET IS
 PERMITTED FBC1016. PLEASE CHECK ALL INFORMATION ON THE
 LIFE SAFETY PLAN AND CONFIRM COMPLIANCE.
  
 43. FBC717.2.3, A02, FIREBLOCKING REQUIRED, SOFFIT
 DETAIL (INTERIOR WALLS).
  
 44. FBC11-4.13.11, DOORS IN THE ACCESSIBLE ROUTE TO
 COMPLY WITH THIS REQUIREMENT (PULLING FORCE). THIS
 WOULD NORMALLY BE A REDLINE ITEM; HOWEVER, AS PLANS
 NEED TO BE REVISED, PLEASE ADDRESS AT THIS TIME. IMPACT
 DOORS ARE SPECIFIED; DO THEY MEET THIS REQUIREMENT?
  
 45. LOUVER PRODUCT APPROVALS ARE INCOMPLETE. PRODUCT
 APPROVALS ARE TO BE REVIEWED BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL, FBC*106. PLANS DO NOT SPECIFY
 DESIGN PRESSURES, SEE A05.
  
 46. PLEASE SEE PLUMBING COMMENTS, FIRST REVIEW. THE
 EXECUTIVE OFFICE PRIVATE BATH IS TO BE ADAPTABLE,
 FBC11-4.1.3(11). THE ARCHITECT'S RESPONSE LETTER STATES
 THAT THIS WILL BE "EASILY CONVERTIBLE". THIS REQUIRES
 THAT NO STRUCTURAL ALTERATIONS BE NECESSARY TO BE MADE
 FROM ADAPTABLE TO ACCESSIBLE, INCLUDING TURNING RADIUS,
 FIXTURE DISTANCES AND CLEARANCES, AND BACKING IN THE
 WALL FOR FUTURE GRAB BAR INSTALLATION. PLEASE SHOW
 COMPLIANCE WITH THESE REQUIREMENTS.
  
 47. E4 AND LS01, SEE FBC11-4.28.1, VISUAL SIGNAL
 APPLIANCE SHALL BE PROVIDED IN RESTROOMS AND ANY
 GENERAL USAGE AREA. THIS IS NOT SHOWN IN THE MEN AND
 WOMEN RESTROOM ADJACENT TO THE LOCKER ROOMS #1 AND #2,
 ALARMS NOT SHOWN IN UNIT B. PLEASE CHECK ALL AREAS FOR
 COMPLIANCE.
  
 48. PLEASE CLARIFY, DOES THE GATE AT THE RINK SWING IN
 BOTH DIRECTIONS? PROVIDE MORE INFORMATION ABOUT THE
 ?DASHER BOARD?. SEE FBC1003.6, PATH OF EGRESS IS NOT TO
 BE INTERRUPTED BY ELEMENT OTHER THAN A MEANS OF EGRESS
 COMPONENT. OCCUPANT LOAD IS GREATER THAN 50, SO DOORS
 SHOULD SWING IN THE DIRECTION OF TRAVEL FBC1008.1.2,
 FBC1008.
  
 49. PLEASE SEE ATTACHED FS553.80(2)(B). A 4X PLAN
 REVIEW FEE IS REQUIRED BY FLORIDA STATUTE TO BE CHARGED
 IF ANY CODE COMMENT IS MADE A THIRD TIME.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-10-27 Cont ID  
Sent By shill Date 2008-10-27 Time 09:35 Rev Time 0.00
Received By shill Date 2008-10-27 Time 09:35 Sent To  
Notes
2008-10-27 09:38:25****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY REQUIRED
 PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD. PLEASE CALL
 561-233-5025 FOR MORE INFORMATION. THE PLANS MUST BE
 STAMPED AND THE RECEIPT IS TO BE INCLUDED WITH THE
 PERMIT APPLICATION.
  
 2. FBC EB301.5, A DESIGN PROFESSIONAL MUST ELECT ONE OR
 A COMBINATION OF LEVELS OF ALTERATION.
  
 3. NOTE ANY CHANGE OF OCCUPANCY ON THE PLAN IF
 APPLICABLE, FBC EB CHAPTER 8. DECLARE CURRENT
 (EXISTING) AND PROPOSED OCCUPANCY AND HAZARD CATEGORY
 FOR LIFE SAFETY AND EXITS, HEIGHT AND AREA, EXPOSURE OF
 EXTERIOR WALLS FBC EB TABLES 812.4.1, 812.4.2, 812.4.3.
 REQUIREMENTS CANNOT BE DETERMINED DUE TO INSUFFICIENT
 INFORMATION PROVIDED.
  
 4. ADDITIONS ARE TO COMPLY WITH FBC EB 9. PLEASE NOTE
 ON PLAN CV01.
  
 5. SHOW THE DISTANCE FROM THE PROPERTY LINE TO THE
 BUILDING(S), FBC 507, FBC 6, FBC EB 8. PLEASE REVISE
 THE SITE PLAN SP01 TO INCLUDE THE REQUIRED INFORMATION.
  
 6. A01 SPECIFIES WP1200 WALL; PROVIDE A DETAIL FBC 7,
 FBC*106.
  
 7. CV01 STATES THAT OFFICES, STORAGE, AND MERCANTILE
 AREAS ARE ACCESSORY. DECLARE TOTAL SQUARE FOOT AREA FOR
 EACH FBC 5.
  
 8. CV01 STATES THAT THIS BUILDING IS TYPE IIIB, 1 HOUR
 FOR EXTERIOR BEARING WALLS. SEE FBC TABLE 601, 2 HOUR
 REQUIRED FOR EXTERIOR BEARING WALLS TYPE IIIB. PLEASE
 CLARIFY BUILDING TYPE. PROVIDE A DETAIL FOR THE
 EXISTING EXTERIOR BEARING WALLS TO CLARIFY BUILDING
 TYPE.
  
 9. NOTE ALL REQUIRED FIRE RATED WALLS ON THE PLAN.
 OPENING AND PENETRATION PROTECTION REQUIREMENTS, ETC.
 ARE NOT READILY APPARENT WITHOUT THIS INFORMATION FBC7.
  
 10. DECLARE OCCUPANT LOAD FBC 1004.
  
 11. FBC1004.3, OCCUPANT LOAD TO BE POSTED. PROVIDE A
 DETAIL AND LOCATION ON THE PLAN.
  
 12. SP01 SHOWS THREE DIFFERENT BUILDINGS. PLEASE SEE
 FBC TABLE 503, FBC TABLE 601, FBC TABLE 602. DO FIRE
 WALLS EXIST SEPARATING THESE BUILDINGS OR ARE THEY ONE
 BUILDING FOR PURPOSES OF FBC CHAPTERS 5 AND 6? AN
 OPENING IS SHOWN BETWEEN THE NORTH AND CENTER
 BUILDINGS; SEE FBC TABLE 704.8, NO OPENINGS PERMITTED
 WITH A SEPARATION OF 0 TO 3 FEET.
  
 13. A.01 SHOWS A NEW DEMISING WALL ADJACENT TO AN
 EXISTING WALL. DOESN?T THIS CREATE A LARGE CONCEALED
 SPACE?
  
 14. CV01, DECLARE TOTAL SQUARE FOOT AREA FOR THE
 BUILDING OR BUILDINGS (SEE OTHER COMMENTS), FBC5, FBC6,
 FBC EB8.
  
 15. CV01, PROVIDE TOTAL SQUARE FOOT AREAS FOR THE
 PROPOSED MEZZANINES AS WELL AS OCCUPANCY CLASSIFICATION
 FOR THE USE OF THESE SPACES, FBC 3, FBC10, FBC11.
  
 16. THE MEZZANINE AREAS MUST MEET THE DEFINITION
 FBC502. PLEASE DEMONSTRATE COMPLIANCE ON THE PLAN.
  
 17. THERE IS A STATEMENT, UPPER LEVEL FLOOR PLAN, A.03,
 TOP LEFT, ?COORDINATE EXTENTS WITH FIRST FLOOR PLAN.?
 WHAT DOES THIS MEAN? WHAT ARE EXTENTS?
  
 18. AS THIS IS A THRESHOLD BUILDING AS DEFINED IN
 FS553.71(7), PLEASE ARRANGE WITH KEN CONRAD, CHIEF
 BUILDING INSPECTOR, 561-805-6666, A MEETING INVOLVING
 THE OWNER, SPECIAL INSPECTOR, JOB INSPECTOR, CONTRACTOR
 AND ENGINEER. THIS MUST BE DONE PRIOR TO PERMIT
 ISSUANCE. THREE ORIGINAL SETS OF ALL DOCUMENTS ARE
 REQUIRED FOR PERMITTING AND FOR ALL SUBSEQUENT
 SUBMITTALS. SEE FBC*109.3.6, FS553.79(5)(A).
  
 19. PROVIDE A STRUCTURAL INSPECTION PLAN FOR THIS
 THRESHOLD BUILDING, FBC*109.3.6, FS553.79(5)(A).
  
 20. SEE FBC*109.3.6.4.4, FS553.79(7)(D) AND INCLUDE THE
 STATEMENT ATTESTING TO COMPLIANCE.
  
 21. FBC*109.3.6.4, THRESHOLD INSPECTOR IS TO BE
 APPROVED BY KEN CONRAD, CHIEF BUILDING INSPECTOR. A
 COPY OF THE CONTRACT IS TO BE INCLUDED IN THE PERMIT
 PACKAGE. THIS IS REQUIRED PRIOR TO PERMIT ISSUANCE,
 FS553.79.
  
 22. PLANS ARE TO BE SIGNED, SEALED, AND DATED FS481.
 PLEASE INCLUDE A DATE ON THE SEAL.
  
 23. SEE FP1, FBC 35, INCORRECT NFPA13 VERSION
 REFERENCED; PLEASE REVISE.
  
 24. SEE FP1, INCORRECT BUILDING CODE DECLARED. PLEASE
 REVISE.
  
 25. FP SHEETS DO NOT HAVE A FIRE SPRINKLER PLAN FOR THE
 MEZZANINE AREAS.
  
 26. A01. SPECIFY FIRE RATING (TIME) REQUIRED FOR THE
 WP1200 WALL, SOUTH SIDE.
  
 27. FBC13-101.3, BUILDING SHALL COMPLY WITH FBC13-4.
  
 28. WALL TYPE W4B IS NOT INCLUDED IN THE LEGEND A01.
 SEE FBC TABLE 1016.1, MINIMUM OF 1 HOUR REQUIRED FOR
 THIS CORRIDOR.
  
 29. WALL TYPE NOT SPECIFIED FOR THE WALL AT DOORS 3A
 AND 3B.
  
 30. A03, EGRESS NOT CLEAR FOR THE UPPER LEVEL, WEST
 SIDE. PROVIDE A LIFE SAFETY PLAN.
  
 31. SHOW VERTICAL ACCESSIBILITY, UPPER LEVEL. IF AN
 EXCEPTION APPLIES, COMPLIANCE MUST BE SHOWN ON THE
 PLAN.
  
 32. C A08, EXTENSION SHOWN AT THE BOTTOM OF THE STAIR
 WHICH IS NOT SHOWN ON THE DETAIL 5 A08. PLEASE REVISE 5
 A08, FBC 11 4.9.4(2).
  
 33. A03, AS CANOPY INFORMATION WAS NOT PROVIDED, A
 SEPARATE PERMIT WILL BE REQUIRED (INFORMATIONAL ONLY).
  
 34. PROVIDE MORE INFORMATION REGARDING THE UPPER LEVEL
 AREAS. SEE FBC505.5, INDUSTRIAL EQUIPMENT PLATFORMS ARE
 NOT TO BE A PART OF ANY MEZZANINE. ALSO DECLARE
 OCCUPANCY CLASSIFICATION FOR THESE AREAS, FBC CHAPTER
 3.
  
 35. A10, THE SPECIFY FIRE DOOR RATING IN TIME RATHER
 THAN LETTER, FBC TABLE 715.3.
  
 36. SOILS REPORT, ALL INFORMATION REQUIRED BY
 FAC61G15-23.002(2) REQUIRED (CERTIFICATE OF
 AUTHORIZATION). PLEASE NOTE THAT THIS REQUIREMENT HAS
 RECENTLY BEEN REVISED.
  
 37. SEE ENERGY CALCS; NO DOORS SHOWN, ICE RINK FLOOR IS
 SHOWN AS CARPET. PLEASE REVISE THESE ITEMS AND CHECK
 ALL INFORMATION ON THE ENERGY CALC INPUT DATA REPORT.
  
 38. PLEASE HAVE THE ARCHITECT SIGN THE ENERGY CALC,
 FBC103.1.1.1. IF A TYPED NAME IS PROVIDED IN LIEU OF A
 SIGNATURE, PLEASE CONFIRM THAT ALL RELEVANT INFORMATION
 (INCLUDE THE EXISTING COMPONENTS, SUCH AS EXISTING
 INSULATION) IS INCLUDED.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 14 Status P Date 2009-12-03 Cont ID  
Sent By dpalmer Date 2009-12-03 Time 14:00 Rev Time 0.00
Received By dpalmer Date 2009-12-03 Time 14:00 Sent To  
Notes
2009-12-03 14:00:55OK ONCE ZONING HAS REVIEWED AND PASSED ES SHEETS.
 STAMPED ELECTRICAL

Review Stop E ELECTRICAL
Rev No 13 Status F Date 2009-10-09 Cont ID  
Sent By dpalmer Date 2009-10-09 Time 14:39 Rev Time 0.00
Received By dpalmer Date 2009-10-09 Time 14:39 Sent To  
Notes
2009-10-09 14:38:56 
 ** DENIED REVISION **
  
 1) NOTE: PLEASE BE SURE ALL SETS ARE COMPLETE WITH ALL
 REVISED SHEETS. ONE SET WAS MISSING A REVISED SHEET
 ES-1
  
 2) NOTE: PLEASE SEE SECOND FLOOR CORRIDOR WHERE
 OCCUPANCY SENSORS HAVE BEEN REMOVED AS THE METHOD OF
 CONTROLS. WHERE ARE THE REQUIRED OVER RIDES IF LIGHTING
 IS NOW GOING TO BE CONTROLLED BY TIMED SCHEDULING?
 PLEASE TAKE A LOOK AT ROOM 222, 223, WHERE ARE LIGHTING
 CONTROLS?
 WHAT ABOUT ROOM 125? WHAT TYPE OF CONTROL DEVICE IS
 THIS?
 CONTROLS IN MAIN ENTRANCE/LOBBY AREAS HAVE HAD CONTROLS
 REVISED HOWEVER IT IS NOT CLEAR WHERE ALL LIGHTING IS
 BEING CONTROLLED. PLEASE PROVIDE AN ENLARGED LAYOUT FOR
 THE COMMON AREAS. PLANS CONTAIN MANY ITEMS AND IT IS
 NOT CLEAR WHERE CONTROLS AND OVER RIDES ARE ALL
 LOCATED.
 13-415.1.ABC.1.1,.1.2, .1.3
  
 3) NOTE: PLEASE PROVIDE AN ENLARGED LAYOUT FOR NEW
 ELECTRICAL IN WAREHOUSE *B* AREA.
 PLANS INDICATE AN EXISTING FIRE PUMP HOWEVER IT IS NOT
 CLEAR IF THIS IS A LEGALLY REQUIRED FIRE PUMP. IT IS NO
 CLEAR OF THE LOCATION IN THE BUILDING IN WHICH THIS
 FIRE PUMP IS LOCATED. PLEASE SEE NFPA-70 695 AND
 NFPA-20 FOR LOCATIONS AND RATINGS OF WALLS ETC.
  
 4) NOTE: PLEASE EXPLAIN HOW PANEL RWB HAS NOW HAD LOAD
 INCREASED BY THE EXISTING PANELS AND LOADS BEING ADDED
 HOWEVER THE MAIN SERVICE LOAD CALCULATIONS HAVE NOT
 BEEN UPDATED. THE LOADS ARE THE SAME AS ON PREVIOUS E-6
 PLANS.
 THE SAME COMMENT IS FOR PANEL R1B WHICH NOW HAS REVISED
 LOAD FOR NEW PANEL R1BA, YET THE SERVICE LOADS HAVE NOT
 CHANGED?
 PLEASE SEE NEC 220 IN GENERAL AND UPDATE LOADS.
  
 5) NOTE: NO INFORMATION HAS YET BEEN SUBMITTED WITH
 RESPECT TO TWO SEPARATE PROPERTIES. NO ELECTRICAL SUCH
 AS SITE LIGHTING MAY CROSS PROPERTY LINES.
  
 6) NOTE: AS NO INFORMATION WAS SUBMITTED ON THE
 EXISTING FIRE PUMP AND JOCKEY PUMP THE NEW UNDER
 SERVICE ENTRANCE CONDUCTORS ETC COULD NOT BE VERIFIED
 AS BEING CODE COMPLIANT.
 ALSO COULD NOT VERIFY BONDING OF SERVICES AS NO
 INFORMATION WAS SHOWN. NEW SERVICE FOR FIRE PUMP AND
 THE EXISTING/NEW SERVICE NEEDS TO BE BONDED. 250.92,94
 ETC, 250.66
  
  
  
  
  
 **IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 12 Status P Date 2009-08-26 Cont ID  
Sent By dpalmer Date 2009-08-26 Time 18:50 Rev Time 0.00
Received By dpalmer Date 2009-08-26 Time 18:50 Sent To  
Notes
2009-08-26 18:51:09** PROVISO/REDLINED PLANS**
  
 *** THE FOLLOWING ARE SET FORTH AS A PROVISO. SOME
 ITEMS *MUST BE COMPLETED FOR PHASE #1.
  
 1) NOTE: PHASE #1, EM-1 FIXTURES SHALL BE INSTALLED AT
 TEMPORARY EXIT, ENTRANCE ON THE EAST SIDE OF BUILDING
 FOR OCCUPANCY. EM-1 FIXTURES SHALL ALSO BE INSTALLED AT
 THIS TIME ON SOUTH SIDE OF BUILDING WHERE EGRESS FROM
 ICE RINK AREA TO PARKING LOT IS TAKING PLACE. THIS WAS
 CONFIRMED WITH FIRE MARSHAL.
 THIS WAS REVISED ON TCO TO BE DONE AT THIS TIME AS A
 CONDITION.
 NFPA- 101 7.8.1.3, 7.9.1.2, .2.2.
  
 2) NOTE: THE ELECTRICAL LIGHTING AND ANY OTHER POWER
 CROSSING PROPERTY LINE SHALL NOT BE DONE UNTIL
 RE-PLAT/UNITY OF TITLE HAS TAKEN PLACE. THIS WAS NOTED
 ON PREVIOUS REVIEW AND REVIEW BACK ON DECEMBER 25TH
 2008.
 THIS IS FOR PCN 74434329000001230.
 INFORMATION HAS BEEN GIVEN TO ATTORNEY FOR OWNER.
  
 3) NOTE: INFORMATION ON UPS TO PROVIDE BACK UP POWER
 FOR THE *D* TYPE FIXTURES IS STILL NEEDED. PLEASE SEE
 NEC 700.12 FOR ACCEPTABLE MEANS OF BACK UP POWER. THE
 GENERATOR MAY NOT BE USED AS IT IS AN OPTIONAL STAND-BY
 SYSTEM UNDER NEC 702.
  
 ** FIRE ALARM, LOW VOLTAGE SYSTEMS ARE UNDER SEPARATE
 PERMITS.
  
 **** IMPORTANT:
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 11 Status F Date 2009-08-21 Cont ID  
Sent By dpalmer Date 2009-08-21 Time 19:50 Rev Time 0.00
Received By dpalmer Date 2009-08-21 Time 19:47 Sent To  
Notes
2009-08-21 19:50:35 
  
  
 ** DENIED REVIEW **
  
 ** THE ELECTRICAL NOTES BELOW WERE GONE OVER WITH
 ENGINEER???S OFFICE ON 8/21/09. CHANGES ARE TO BE MADE
 AND SHEETS REVISED.
  
  
  
 1) NOTE: ELECTRICAL SITE PLANS NOW ONCE AGAIN INCLUDE
 LIGHTING BEING FED FROM THIS BUILDING ACROSS PROPERTY
 LINE TO PCN 74434329000001230. SPOKE TO ZONING,
 ADDRESSING, ARCHITECT AND ENGINEER???S OFFICE.
 RECORDED UNITY OF TITLE OR RE-PLAT OF PROPERTY NEEDS TO
 BE PROVIDED.
 IF THIS IS NOT DONE, NO LIGHTING, GATES OR OTHER
 ELECTRICAL SYSTEMS MAY CROSS THE PROPERTY LINES.
  
 2) NOTE: ALL PREVIOUS SUBMITTED ENERGY CALCULATIONS
 WERE UNDER METHOD *B*. THE NEW SUBMITTED CALCULATIONS
 ARE NOW SUBMITTED UNDER METHOD *A* FOR WHOLE BUILDING
 COMPLIANCE. THIS IS NOT A WHOLE BUILDING PER
 DEFINITIONS UNDER CHAPTER 2 AND SECTION 202 OF CHAPTER
 13.
 PLEASE PROVIDE METHOD B PER 13-400.B.0.4
 SEE DEFINITION OF RENOVATION.
  
 ** IDR MISSING P-5 FOR EXTERIOR. THIS ALONG WITH FRONT
 ENTRANCE IS NOT CONSIDERED A GROSS ERROR PER 13-103.3,
 PLEASE UPDATE METHOD.
  
 3) NOTE: PLEASE ADJUST LIGHTING CONTROLS TO MEET
 13-415.1.ABC.1.1, .1.2 AND .1.3. ALL LIGHTING WITH THE
 EXCEPTION OF THE DESIGNATED NIGHT LIGHTS AS GONE OVER
 IN MEETING AND ON PHONE ARE REQUIRED TO TURN OFF
 AUTOMATICALLY WHEN BUILDING IS NOT OCCUPIED.
  
 A) RIBBON LIGHTING CONTROLS TO MEET .1.3 OF SECTION
 NOTED ABOVE.
  
 B) G FIXTURES NEED TO HAVE SEPARATE WITH AUTOMATIC SHUT
 OFFS.
  
 C) CONTROLS FOR SECOND FLOOR EAST CORRIDOR LIGHTS NEED
 TO MEET SECTION .1.1, .1.2 ABOVE. THE DLT SWITCHES
 LOCATED ON FIRST FLOOR NEEDS TO MEET THE REQUIREMENT OF
 THE OCCUPANT SEEING THE LIGHTING WHICH IS BEING
 CONTROLLED OR MEET EXCEPTIONS.
 PER CONVERSATION WITH DESIGNER THESE MAY BE CHANGED TO
 OCCUPANCY SENSORS ON FAIL-SAFE OPERATION.
  
 D) SEE NOTES BELOW WITH RESPECT TO CIRCUITING OF OTHER
 EMERGENCY LIGHTING BEING CONTROLLED. FOR EXAMPLE:
 CIRCUITS SUCH AS HPA-9, EH1A-16, WHICH ARE THROUGH THE
 LIGHTING CONTROL PANEL NEED TO BE * HOT* ALL THE TIME.
  
 4) NOTE: PLEASE PROVIDE HOW THE *D* FIXTURES WILL MEET
 LIFE SAFETY FOR BACK UP POWER. THE PLANS INDICATE THESE
 FIXTURES WILL BE ON TRANSFORMERS HOWEVER THERE ARE NO
 UPS SYSTEM(S)/ UNITS ON PLANS FOR THE BACK UP OF THESE
 FIXTURES.
 PLEASE SEE NFPA-101 7.8.1.3, 7.9,.1.2, .2.2 AND NFPA-70
 700.12A, 700.12C, 700.12F ETC
 THIS WAS GONE OVER WITH THE DESIGNER.
  
 5) NOTE: PLEASE SEE THAT EXIT AREAS LOCATED OUTSIDE
 WHERE STEPS ARE PRESENT NEED TO CONTAIN LIGHTING FOR
 EGRESS. PLEASE SEE ES-1 AND E2-B, THE SOUTHEAST FIRST
 FLOOR EXIT AND THE SOUTH EXIT. THIS WAS GONE OVER ON
 PREVIOUS MEETINGS AND WITH DESIGNER ON PHONE. THESE ARE
 ALSO TO BE CIRCUITED PER 700.12F.
  
 6) NOTE: THE NIGHT-LIGHT CIRCUITS ON PLANS INDICATE
 CIRCUITING THROUGH *EH1B-7*, HOWEVER THERE IS NO EH1B
 PANEL. THESE WERE GONE OVER WITH DESIGNER AND SHOULD BE
 EH1A-15; ALSO PANEL SCHEDULE DESIGNATION STATES ICE
 RINK WHEN ACTUALLY THIS IS FIRST AND SECOND FLOOR NIGHT
 LIGHTS WEST.
 THIS WAS GONE OVER WITH DESIGNER.
 PLEASE ALSO SEE CIRCUIT H1B-7 FOR *D* FIXTURES ABOVE IN
 NOTE #4 WHICH ARE ACTUALLY BLANK ON PANEL SCHEDULE.
 THIS WAS GONE OVER WITH DESIGNER.
  
  
 ** NOTES WERE GONE OVER WITH DESIGNER AND CORRECTIONS
 WILL BE BROUGHT IN THE WEEK OF 8/24.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 10 Status F Date 2009-08-09 Cont ID  
Sent By dpalmer Date 2009-08-09 Time 11:45 Rev Time 0.00
Received By dpalmer Date 2009-08-09 Time 9:23 Sent To  
Notes
2009-08-09 11:35:38 
  
  
  
 ** DENIED REVIEW OF REVISIONS**
  
 ** AT PREVIOUS MEETING HELD WITH ARCHITECT, OWNER
 REPRESENTATIVE, CONTRACTOR, PERMIT EXPEDITOR AND OTHER
 CITY STAFF IT WAS NOTED THAT NO MEP DESIGN TEAM MEMBERS
 WERE PRESENT. AT THIS TIME IT IS STRONGLY RECOMMENDED
 THAT A MEETING BE HELD BEFORE PLANS ARE RESUBMITTED
 ONCE AGAIN.
 SOME OF THE NOTES BELOW WILL HAVE AN AFFECT ON PHASE I
 TCO.
  
 1) NOTE: THE PREVIOUS REVIEW REQUESTED A VALUE UPDATE
 FOR THE PROJECT AS THE COMPLETE SCOPE OF WORK HAS
 SUBSTANTIALLY INCREASED. THE NEW VALUE STATED ON
 RESPONSE IS ACTUALLY LOWER THAN THE ORIGINAL APPLIED
 VALUE. HOW IS THIS POSSIBLE? THE COMPLETE SCOPE OF WORK
 VALUE IS REQUIRED TO INCLUDE ALL LABOR, MATERIALS,
 EQUIPMENT, DESIGN COSTS. THIS INCLUDES ALL EQUIPMENT
 WHICH MAY BE OWNER PURCHASED OR SUPPLIED.
 FBC 108.3
 COMPLETE CONTRACTS WITH ALL RELEVANT PARTIES INCLUDING
 DETAILED LISTS OF ALL EQUIPMENT AND MATERIALS CAN BE
 REQUESTED.
  
 2) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS IN
 COMPLIANCE WITH THE FLORIDA BUILDING CODE.
 PLEASE SEE FBC 13-415.AB.2.2, .5 AS THE SUBMITTED
 LIGHTING PERFORMANCE CALCULATIONS ARE NOT COORDINATING
 WITH THE SUBMITTED PLANS FOR THIS PROJECT. THE SEPARATE
 PERMIT SUBMITTED FOR SITE LIGHTING DOES NOT HAVE *ANY*
 LIGHTING PERFORMANCE CALCULATIONS MEETING MINIMUMS. THE
 NEW SUBMITTED REVISED ENERGY CALCULATIONS DO NOT SHOW
 ANY EXTERIOR LIGHTS. THIS IS NOT POSSIBLE WHEN THE SITE
 AS WELL AS THE BUILDING CONTAINS NUMEROUS LIGHT
 FIXTURES AND NONE ARE SHOWN IN THE CALCULATIONS. IN
 FACT THE INPUT DATA REPORT IS ACTUALLY BLANK. THIS IS
 NOT POSSIBLE.
  
 A) THE INTERIOR LIGHTING DOES NOT COORDINATE WITH THE
 SUBMITTED PLANS. THERE ARE MANY MORE FIXTURES ON PLANS
 THAN IN THE IDR.
 13-415.B.1
  
 B) FOR INFORMATION, THE WATTAGE USE ON PLANS IS
 SUBSTANTIALLY HIGHER ON E-1 FOR EXAMPLE.
  
 3) NOTE: PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR ALL
 LIGHTING FOR EGRESS AREAS UNDER NORMAL AND EMERGENCY
 CONDITIONS AS NOTED PREVIOUSLY.
  
 A) SPECIFICALLY SHEET EP-1, THE STAIRS CHANGED AND
 REVISED PHOTO-METRICS MEETING MINIMUM FOR LIFE SAFETY
 AND NORMAL OR EMERGENCY WAS SUBMITTED IN THE REVISIONS
 FOR PHASE 1. THE REVIEW WAS NOT COMPLETED BY THIS
 REVIEWER HOWEVER AS OF THE REVIEW PREVIOUSLY DONE UNDER
 PHASE II THIS WAS NOTED AS NEEDING TO BE REVISED.
 NFPA- 101 7.8.1.3, 7.9.1.2, .2.2.
  
 B) NO LEVELS SUBMITTED OR SHOWN FOR LEVELS FOR NORMAL
 EXTERIOR STAIRS (EAST). ONE EXAMPLE WOULD BE THESES
 STAIRS. THE SECTIONS OF THE CODES NOTED ABOVE FOR
 MINIMUM LIFE SAFETY REQUIREMENTS REQUIRED 10FT CANDLES,
 PLEASE SUBMITTED ONLY SHOW LEVELS UNDER EMERGENCY. THE
 LEVELS ARE REQUIRED AT EACH STAIR TREAD, NOT ONE, TWO,
 OR THREE POINTS.
  
 C) PLEASE INDICATE WHAT HAPPENED TO LEVELS OF LIGHTS
 DURING PERFORMANCES? PREVIOUS NOTES GAVE INFORMATION AS
 TO THE SPECIFIC SECTIONS OF THE LIFE SAFETY CODE.
 MANY OF THESE LIGHTING LEVELS ARE SHOWN UNDER NORMAL
 CONDITIONS HOWEVER LIGHTING IS ON *DIMMING PANELS*
  
 D) PLACE INFORMATION ON PLANS ON ACTIVATION OF
 EMERGENCY CONDITIONS/FIRE ALARM ACTIVATION AS PLANS ARE
 BEING CORRECTED AT THIS TIME.
  
 E) ANOTHER EXAMPLE: UNDER EMERGENCY CONDITIONS, ONLY
 FIXTURES WHICH CONTAIN THE EMERGENCY BATTERY BACK UP
 MAY BE USED FOR LEVELS. PLEASE SEE FUTURE FRONT
 ENTRANCE FOR EXAMPLE. HOW IT IS POSSIBLE FOR THE
 LIGHTING IN AREAS TO CONTAIN A HIGHER LEVEL OF LIGHT
 WHEN PER THE LIGHTING PLANS THOSE AREAS DO NO CONTAIN
 FIXTURES WHICH ARE BATTERY BACK UP.
  
 F) PLEASE EXPLAIN THE KE FIXTURE LOCATED OUTSIDE. THIS
 IS A FIXTURE NOTED INSIDE HOWEVER THIS IS LOCATED
 OUTSIDE ON FIRST FLOOR IN AREA WHICH WOULD BE A WET
 LOCATION. MANUFACTURE SPECS ON SITE DOES NOT INDICATE
 THIS AS A WET LOCATION FIXTURE.
  
  
 PLEASE SEE NFPA-101 7.8.1.2.2 , FBC 1006.1.2, FOR
 OCCUPANCY SENSORS ON EGRESS LIGHTING AND ALSO LIGHTING
 CONTROLS ON NORMAL LIGHTING FOR EGRESS AREAS.
  
 4) NOTE: PREVIOUS REVIEW NOTES WERE GIVEN WITH RESPECT
 TOP ASME-17 2004 FOR MINIMUM ELEVATOR CODES. HOWEVER
 THERE ARE AREAS IN WHICH MINIMUM LEVELS FOR THE
 REFERENCED CODE WOULD NOT BE MET.
 ** THIS IS ONLY NOTED.
  
 5) NOTE: THE GENERATOR ON THE SUBMITTED RISER IS STILL
 SHOWING GROUND FAULT PROTECTION ON THE GENERATOR
 BREAKER. THE BACK UP SYSTEM WHICH IS AN OPTIONAL
 STAND-BY SYSTEM WILL NOT WORK BASED ON THE SYSTEM
 SUBMITTED WITH THE 3-POLE ATS.
 ** THIS WAS REVISED ON THE GENERATOR SUB PERMIT HOWEVER
 NOT ON THIS RISER. PLEASE CORRECT AT THIS TIME.
  
 6) NOTE: AS NOTED AND GONE OVER IN MEETING HELD BEFORE
 PLANS WERE RESUBMITTED. THE EGRESS PATH ON THE FIRST
 FLOOR WEST AREAS STILL INDICATES THE CONDENSING UNITS
 AND OTHER A/C EQUIPMENT NOT PERMITTED IN EGRESS PATH
 ALONE SIDE WALK.
 THIS WAS NOTED BY THE FIRE MARSHAL YET STILL SHOWN IN
 PATH.
  
 7) NOTE: NO INFORMATION SHOWN FOR LOAD BANK ON
 GENERATOR. THE FRESH AIR MAKE UP IS LOCATED IN REAR OF
 BUILDING. THIS IS A 500KW DIESEL GENERATOR WITH NO LOAD
 BANK INFORMATION. PLEASE PROVIDE THE MANUFACTURE
 RECOMMENDED LOAD TO PREVENT WET STACKING. THIS
 INFORMATION WILL BE FORWARDED TO MECHANICAL AND FIRE
 MARSHAL. ** THIS IS NOTED ONLY BY THIS REVIEWER.
 PLEASE SEE THAT INSTALLATION OF GENERATOR SHALL BE PER
 MANUFACTURES RECOMMENDATIONS PER LISTING.
 110.3, 90.7
  
 8) NOTE: PLEASE COORDINATE RISER. THE LOAD CALCULATION
 FOR TWB STATES MINIMUM SERVICE REQUIRED 200AMPS YET THE
 RISER INDICATES 150AMP.
 THIS COULD HAVE REDLINED HOWEVER COMMENTS FOR OTHER
 ITEMS ON REVIEW.
  
 9) NOTE: REVISIONS TO FUNCTION OF LIGHTING CONTROL
 SYSTEM UNDER PHASE 1 NOT SUBMITTED. SYSTEM FUNCTION
 BEFORE TCO OF PHASE I SYSTEM LIGHTING WILL BE REQUIRED.
 13-415.1.ABC.1.1,.1.2, .1.3 AND .1.4.
  
  
 ** PLANS ARE NO LONGER RELEASED PER BUILDING DIRECTOR.
 A TIME WILL NEED TO BE SET UP TO BRING IN NEW REVISIONS
 AND CHANGE OUT SHEETS.
  
  
  
  
  
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 9 Status F Date 2009-07-19 Cont ID  
Sent By dpalmer Date 2009-07-19 Time 10:58 Rev Time 0.00
Received By dpalmer Date 2009-07-19 Time 08:01 Sent To  
Notes
2009-07-19 10:58:33 
  
  
  
  
  
 ** DENIED REVISION **
  
  
 1) NOTE: PLEASE SUBMIT COPIES OF DOCUMENTS FOR
 SUCCESSOR ARCHITECT. THERE APPEARS TO HAVE BEEN
 PREVIOUS REVISIONS WITH NEW ARCHITECT ALSO HOWEVER NOT
 LETTERS FOR NEW ARCHITECT COULD BE LOCATED.
 FS 481, FAC 61G1-18.002
  
  
 2) NOTE: PLANS ARE CONFUSING FOR WHICH CODE THE PROJECT
 WILL BE UNDER. THE COVER SHEET SPECIFICALLY STATES THE
 LIFE SAFETY CODE AND THE FLORIDA FIRE PREVENTION CODES
 AS THE 2007 EDITIONS. PLEASE KNOW THERE IS NO 2007
 EDITION OF NFPA-101. AS OF DECEMBER 31ST,2008 THE NEW
 ADOPTED EDITION OF NFPA-101 IS THE 2006 EDITION.
 AS OF THE SAME DATE THE 2007 FFPC IS ACCURATE. HOWEVER
 THIS CONFUSING BASED ON THE FACT THE PLANS ARE
 SUBMITTED REVISIONS WITH THE 2004 FBC STATED AT SEVERAL
 LOCATIONS.
 PHASE ONE NEEDS TO BE COMPLETED AND/OR HAVE NO AFFECT
 ON THE PHASE TWO PROPOSED SCOPE OF WORK. BASED ON THE
 SUBMITTED FLA COM REPORT ALONE THIS IS NOT PERMITTED AT
 THIS TIME. IT WAS THE UNDERSTANDING OF THIS REVIEWER
 BASED ON INFORMATION GIVEN THAT PHASE II WOULD BE UNDER
 SEPARATE PERMIT AND NOT A PHASED REVISION TO THE BASE
 PERMIT.
 THE REVIEW IS BEING DONE UNDER THE CODES STATED ON
 PLANS BASED ON REVISIONS SUBMITTED TO BASE PERMIT.
 ** THIS IS BEING NOTED AS THE INTENT AND SEQUENCE OF
 PERMITTING AND PHASING IS NOT CLEAR AT THIS TIME.
 ** IT IS IMPORTANT TO KNOW IF THE APPLIED SCOPE OF WORK
 IS TO BE UNDER NEW PERMIT AS IT IS UNDERSTOOD THIS
 WOULD PLACE PROJECT UNDER THE 2007 FBC WITH 2009
 REVISIONS ALONG WITH OTHER NEW ADOPTED CODES. THIS
 WOULD AFFECT CALCULATIONS AND SOME OTHER ITEMS ON
 PLANS.
  
 3) NOTE: PLEASE SUBMIT COMPLETE NEW LIGHTING
 PERFORMANCE CALCULATIONS PER 13-415.AB.5 (2007) OR
 13-415.2.ABC.1.1, .1.2, .1.3 FOR 2004
 THE INFORMATION SUBMITTED ON THE IDR, SUMMARY SHEETS,
 AND COVER SHEETS OF THE FLA COM DOES NOT COORDINATE
 WITH THE SUBMITTED PLANS. PLANS. SQ FT FOR THE ENTIRE
 REVISED PLAN NEEDS TO BE UPDATED.
 ONE EXAMPLE BESIDES THE ITEMS ABOVE IS THE PRO-SHOP
 ROOM. THE IDR DOES NOT COORDINATE WITH PLANS.
 ** KEEP IN MIND ALL FIXTURES SHALL BE SPECIFIC AT THIS
 TIME WITH ALL DETAILS. IF A FIXTURE HAS NOT YET BEEN
 DETERMINED THEN PLEASE FIND A FIXTURE WHICH MEET CODE
 COMPLIANCE AT THIS TIME. THE FIXTURE LEGEND MAY ALWAYS
 BE UPDATED AT A LATER DATE ALONG WITH THE CALCULATIONS.
 AS LONG AS PLANS AND CALCULATIONS MEET MINIMUM CODES
 FOR ISSUANCE ( IF UNDER SEPARATE PERMIT).
  
 4) NOTE: IF THE PROPOSED SCOPE OF WORK IS GOING TO BE A
 REVISION TO THE BASE PERMIT THE COMPLETE VALUE FOR THE
 COMPLETE SCOPE OF WORK IN PHASE ONE AND PHASE TWO NEEDS
 TO BE UPDATED. FBC 108.3. THE BASE VALUE HAS NOT BEEN
 INCREASED TO DATE.
 VALUE SHALL INCLUDE DESIGN COSTS, ALL LABOR, MATERIALS
 AND EQUIPMENT (PERMANENT) EVEN IF ANY OF THESE ITEMS
 ARE OWNER SUPPLIED. THE ORIGINAL APPLIED VALUE IS
 EXTREMELY LOW BASED ON THE SCOPE, EQUIPMENT ETC AND
 NEEDS TO BE ADJUSTED.
  
 5) NOTE: PLEASE SEE NOTES FROM ELECTRICAL REVIEW DATED
 4/17/2009. PLEASE COORDINATE ALL PLANS INCLUDING SITE
 LIGHTING, SITE PLANS ETC. PLEASE SEE COMMENTS FROM
 OTHER TRADES WHICH WILL AFFECT THE ELECTRICAL PLANS.
 ONE EXAMPLE ALONG IS THE LOCATION OF THE PROPOSED
 GENERATOR WHICH IS NOT PERMITTED.
  
 6) NOTE: PLEASE SUBMIT COMPLETE NEW PHOTO-METRICS FOR
 ALL EGRESS PATHS MEETING NFPA-101 7.8.1.3, 7.9.1.1,
 .1.2. PLEASE SEE 7.8.1.2.2 FOR ANY OCCUPANCY DEVICES
 USED FOR EGRESS LIGHTING. THERE ARE SEVERAL NEW
 INTERIOR STAIRS WHICH NEED TO BE UPDATED.
 **IMPORTANT, THE EXTERIOR EGRESS STAIRS SHALL ALSO
 COMPLY AS THIS IS ALSO REQUIRED TO THE RIGHT OF WAY.
 THE LANDING IS NOT THE RIGHT OF WAY.
 ** IMPORTANT, IF MEETING ANY EXCEPTIONS TO STAIR AREAS
 DURING PERFORMANCES THEN PLANS NEED TO PROVIDE MORE
 INFORMATION ON ALL LEVELS. NORMAL, EMERGENCY,
 PERFORMANCE ETC.
 ** KEEP IN MIND STAIR AREAS IN ELEVATED SEATING AREAS
 SHALL ALSO BE CONSIDERED.
  
 7) NOTE: PLEASE SEE ASME-17 UNDER THE 2004 EDITION FOR
 STATE ELEVATOR CODE REQUIREMENTS. THIS DEPARTMENT DOES
 NOT REVIEW FOR THESE ITEMS FOR CODE COMPLIANCE. HOWEVER
 THERE ARE ITEMS ON THE PLANS WHICH DO NOT APPEAR TO
 MEET SOME CHANGES IN THE ELEVATOR CODE. SEE NEW
 LIGHTING LEVELS REQUIRED FOR PITS, MACHINE ROOMS, SILLS
 ETC.
 ** THIS IS ONLY NOTED FOR INFORMATION. THIS IS NOT
 SOMETHING THAT WOULD WANT TO COME UP AT THE FINAL
 INSPECTION BY THE STATE ELEVATOR INSPECTOR.
  
 8) NOTE: PLEASE SEE SECTIONS 620.21-620.25. DEDICATE
 BRANCH CIRCUITS ARE REQUIRED FOR SEVERAL AREAS. ONE OF
 THE ITEMS SHOWN ON PLANS IS THE LIGHTING IN THE
 ELEVATOR EQUIPMENT ROOM WHICH IS NOT SHOWN ON A
 DEDICATED BRANCH CIRCUIT AS REQUIRED BY 620.23. KEEP IN
 MIND THE NOTE ABOVE WITH RESPECT TO THE ASME-17 CHANGES
 IN THE 2004 CODE. THE LIGHTING SHOWN WOULD NOT MEET NEW
 MINIMUMS.
  
 9) NOTE: PLEASE SEE 13-415.1.ABC.1.1,.1.2 AND .1.3 FOR
 INTERIOR LIGHTING CONTROLS. INTERIOR LIGHTING FOR ITEMS
 SUCH AS ACCENT LIGHTING SHALL HAVE SEPARATE CONTROLS.
 SEE SECTION .1.3.
 PLEASE SEE 2007 FBC IF PROJECT IS GOING TO BE UNDER
 SEPARATE PERMIT.
 NEED TO PROVIDE UPDATED ZONE PLANS FOR ALL LIGHTING
 CONTROLS AND SYSTEM. AS PHASE I IS NOT YET COMPLETED
 AND PHASE II WILL DIRECTLY AFFECT THE EXISTING SYSTEM
 ALL OF THESE ITEMS NEED TO BE UPDATED. THE ENTIRE BUILD
 OUT LCP SCHEDULE WITH ZONES NEEDS TO BE UPDATED.
  
 10) NOTE: PLEASE SEE 240.21C. A NOTE #1 ON THE
 TRANSFORMER SCHEDULE MENTIONS ALL PANEL BOARDS ON THE
 SECONDARY SIDE SHALL CONTAIN MAIN CIRCUIT BREAKERS.
 HOWEVER PLEASE SEE PANELS SW AND SE AS BOTH OF THESE
 INDICATE THESE PANELS A MAIN LUG ONLY. BOTH OF THESE
 PANELS NEED TO BE UPDATED.
  
 11) NOTE: PLEASE UPDATE FEEDERS ON THE SBA SWITCHBOARD
 FOR *H1B*.
 215.5,310.16 ETC
  
 12) NOTE: PLEASE ADJUST NOTE FOR TRANSFORMER GROUNDING
 ELECTRODE ATTACHMENT FOR ACTUAL ATTACHMENT LOCATION.
 250.20,250.30,250.50.
 PLEASE ADD NOTE TO PLANS FOR FRAMING BONDS PER FBC
 2704.1
  
 13) NOTE: PLEASE ADD NOTE FOR LIGHTING DISCONNECT
 REQUIRED PER 410.73G. THIS IS AT THE REQUEST OF
 INSPECTORS TO BE SHOWN ON PLANS AS THIS HAS BECOME A
 COMMON FAILURE ITEM IN THE FIELD.
  
 14) NOTE: PLEASE BE SURE THE LIGHTING AS NOTED ABOVE
 FOR ELEVATOR MACHINE ROOM IS UPDATED TO MEET 700.16
 ALSO. THE SINGLE FIXTURE AS SHOWN ONCE BURNT OUT OR NOT
 WORKING WOULD LEAVE THIS AREA IN TOTAL DARKNESS.
 PLEASE BE SURE OTHER AREAS ONCE UPDATED FOR EGRESS
 NOTES ABOVE ARE ALSO UPDATED.
  
 15) NOTE: PHASE I PLANS WOULD NEED TO BE UPDATED.
  
 ** AS THERE IS INFORMATION NOT YET SUBMITTED,
 DETERMINED OR COMPLETE, THERE MAY VERY WELL BE NEW
 COMMENTS WHICH CAN NOT YET BE MADE.
  
 ** PLANS ARE NO LONGER RELEASED PER NEW BUILDING
 OFFICIAL.
  
 16) NOTE: IT IS TO BE NOTED ONCE AGAIN PLANS STILL
 INDICATE A 3POLE ATS. THERE MAY BE A LOSS OF
 COORDINATION FROM NORMAL AND GENERATOR POWER TRANSFER.
 THIS IS NOTED ONLY AND DOES NOT VIOLATE CODE AS BACK UP
 IS STRICTLY OPTIONAL STAND-BY. THIS WILL REMAIN IN
 NOTES UNTIL COMPLETION OF PROJECT. THERE IS NO NEED FOR
 A RESPONSE BY DESIGNER.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2009-05-22 Cont ID  
Sent By dwise Date 2009-05-22 Time 19:47 Rev Time 0.00
Received By dwise Date 2009-05-22 Time 19:47 Sent To  
Notes
2009-05-27 19:47:45APPROVED AS NOTED ON PLANS.

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2009-04-17 Cont ID  
Sent By dpalmer Date 2009-04-17 Time 08:34 Rev Time 0.00
Received By dpalmer Date 2009-04-17 Time 08:34 Sent To  
Notes
2009-04-17 09:25:39 
  
 *** DENIED SITE PLANS****
  
 1) NOTE: ALL ES, ESP SHEETS HAVE BEEN STAMPED WITH A
 VOID STAMP. BASED ON TEH ZONING AND LANDSCAPE REVIEW
 COMMENTS THERE ARE DIRECT CONFLICTS IN THE SITE AND
 SITE PLANS. INSTALLATION OF ELECTRICAL AS SHOWN ON SITE
 COULD CAUSE CONFLICT WIHT INSTALLATIONS OF OTHER
 SYSTEMS SUCH AS LANDSCAPING, ETC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 BUILDING PLANS EXAMINER II/ ELECTRICAL
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2009-04-12 Cont ID  
Sent By dpalmer Date 2009-04-12 Time 11:28 Rev Time 0.00
Received By dpalmer Date 2009-04-12 Time 11:28 Sent To  
Notes
2009-04-12 11:28:38** TEMPORARY FAILED**
  
 1) NOTE: WHEN PLANS WERE BEING SUBMITTED THERE WAS A
 THIRD SET OF ESP-1, E5 AND ES-1 MISSING. THIS WAS
 CONFIRMED WITH THE PERMIT EXPEDITOR WHEN PLANS WERE
 BEING SUBMITTED. A THIRD SET WAS GOING TO BE BROUGHT IN
 BEFORE REVIEWS COMMENCED. HOWEVER TO THIS DATE OF
 REVIEW THE THIRD SET WAS NOT SUBMITTED. CALLED AND LEFT
 MESSAGE FOR THIRD SET TO BE BROUGHT IN.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2009-03-24 Cont ID  
Sent By dpalmer Date 2009-03-24 Time 21:21 Rev Time 0.00
Received By dpalmer Date 2009-03-24 Time 21:21 Sent To PC
Notes
2009-03-24 21:21:52** PROVISO **
  
 1) NOTE: SHEET E-6 FROM PREVIOUS REVIEW WITH NOTES FROM
 3/3/09 WAS NOT REVISED.
  
 2) NOTE: PLEASE SEE SHEET E-4 WHICH INDICATES TWO
 1600AMP MAINS. THERE IS ONE LOCATED IN THE MIDDLE OF
 THE PARKING LOT AND ONE ON THE REAR WALL OF THE
 BUILDING. THE ONE IN THE PARKING LOT AREA WAS CROSSED
 OUT BY REVIEW AS AN OVERLAY MIS-PRINT.
  
 3) NOTE: ALL ADDITIONS OF LIGHTING FIXTURES WILL
 REQUIRE UPDATED ENERGY CALCULATIONS.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2009-03-03 Cont ID  
Sent By dpalmer Date 2009-03-03 Time 20:58 Rev Time 0.00
Received By dpalmer Date 2009-03-03 Time 20:58 Sent To  
Notes
2009-03-03 20:58:31*** PROVISO/ REDLINED PLANS***
  
 1) NOTE: PLEASE TAKE A LOOK AT REVISED SHEET E-6. THE
 NEW LOAD CALCULATIONS WHICH WERE REQUESTED ON PREVIOUS
 REVIEW ARE NOW ADDED TO PLANS. HOWEVER THE 1600AMP LOAD
 CALCULATIONS STATES THE SERVICE IS GOING TO BE
 1200AMPS. THE NOTES AT THE BOTTOM OF THE SAME 1600AMP
 LOAD CALCULATIONS STATES THE SERVICE ENTRANCE
 CONDUCTORS BASED ON THE 1200AMP SERVICE NOT THE 1600AMP
 MAIN SERVICE.
 THE RISER CLEARLY INDICATES 4- SETS OF 600MCM FROM FPL
 TO MAIN AND FROM MAIN TO GUTTER YET THE NOTES ON THE
 BOTTOM OF THE CALCULATIONS STATE 3-SETS OF 600MCM WHICH
 ARE ONLY RATED FOR 1260AMPS. PER 310.16 AND 110.14.
 THIS WOULD ALSO BE IN VIOLATION OF 240.4.C AS DEVICES
 RATED OVER 800AMPS SHALL HAVE CONDUCTORS RATED AT THE
 OVER CURRENT PROTECTION PROVIDED OR ABOVE. THE 4-SETS
 OF CONDUCTORS ON THE RISER AT 420AMPS FOR EACH PARALLEL
 RUN IS ABOVE THE 1600AMPS PER 310.16, 110.14 AND
 240.4C. THE CONDUCTORS ON RISER NOT IN NOTES MUST BE
 INSTALLED.
 AS THE RISER DOES INDICATE THE CORRECT CONDUCTORS THIS
 MUST BE A MISPRINT AND A NEED OF REVISED PLANS AND
 COORDINATION IS REQUIRED.
 PLEASE REVISE PLANS BEFORE ROUGH ELECTRICAL INSPECTION.
 THIS NOTE WILL BE E-MAILED TO THE ENGINEERING FIRM.
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2009-02-08 Cont ID  
Sent By dpalmer Date 2009-02-08 Time 12:56 Rev Time 0.00
Received By dpalmer Date 2009-02-08 Time 10:45 Sent To  
Notes
2009-02-08 12:57:21** DENIED 3RD REVIEW **
  
 ** THERE ARE ITEMS WHICH ARE STILL IN NEED OF
 ADDRESSING FROM THE PREVIOUS REVIEWS.
  
  
 1) NOTE: THE ARCHITECT'S TITLE BLOCKS HAVE STILL NOT
 BEEN REVISED. AS NOTED ON PREVIOUS REVIEW PLEASE SEE
 FAC 61G1-16.004. THIS IS REQUIRED WHETHER OR NOT
 COMMENT IS MADE BY ANY OTHER TRADES. THIS COMMENT IS
 FOR THE ARCHITECT.
 PLEASE SEE SECTION ABOVE AS THE PRINTED NAME AND
 PRINTED LICENSE NUMBER IS REQUIRED ON EACH AND EVERY
 SHEET WHICH CONTAINS THE ARCHITECTS INFORMATION
 THE OTHER OPTION IS TO REMOVE ARCHITECT'S INFORMATION
 FROM TRADE SHEETS.
  
 2) NOTE: PLEASE SEE PREVIOUS REVIEWS AS THE MANUFACTURE
 SPECS/CUT SHEETS WERE REQUESTED FOR THE NEW PROPOSED
 ATS. THE PREVIOUS PLANS CONTAINED THE INFORMATION
 HOWEVER AS THE PRINTING WAS NOT CLEAR IT WAS ASKED FOR
 THE SHEETS TO BE SUBMITTED OR TO CLEAR UP THE
 INFORMATION NOTED ON PLANS. THE PLANS NOW DO NOT SHOW
 THE INFORMATION AND COULD NOT LOCATE THIS IN THE
 PACKAGE.
 110.3, 702.6, 90.7
 FBC 106.1.2, 106.1.1 FOR INFORMATION, CLARITY ETC
  
 4) NOTE: PLEASE SEE NOTES FROM PREVIOUS REVIEW WITH
 RESPECT TO SYSTEMS SUCH AS LIGHTING AND GATES WHICH ARE
 STILL BEING SHOWN ON PLANS BEING FED FROM THIS
 PROPERTY. THIS IS NOT PERMITTED. THESE PROPERTIES WOULD
 BE REQUIRED TO CONTAIN A UNITY OF TITLE. PLEASE SEE
 LANDSCAPE PLANS AND BE SURE ALL PLANS COORDINATE.
 NEC 230.2 ETC
 FBC TABLE 601
 THIS NEEDS TO BE COORDINATED WITH ALL TRADES SUCH AS
 ZONING, BUILDING ETC.
  
 5) NOTE: PLEASE SEE ALL NOTES FROM PREVIOUS REVIEW WITH
 RESPECT TO FBC CHAPTER 13. COMPLIANCE FOR MINIMUM HAS
 NOT BEEN MET.
  
 THE SQUARE FOOTAGE ON PLANS AND CALCULATIONS SUBMITTED
 DO NOT COORDINATE.
  
 THE IDENTIFICATION OF THE SPACES DOES NOT COORDINATE.
 FOR ONE IS THE METHOD *C* SUBMITTED FOR WAREHOUSE
 STATES UNIT *A* HOWEVER UNIT *A* BASED ON THE
 ARCHITECTURAL PLANS IS THE ICE RINK AREA.
  
 THE PLANS CONTAINS A METHOD *B* TABLE CALCULATION FOR
 SPACE BY SPACE. IT IS NOT PERMISSIBLE TO MIX METHODS OF
 CALCULATIONS. PLEASE SEE 13-415.2.ABC.1
  
 PLEASE SEE THE INFORMATION ON THE INPUT DATA REPORT
 ALSO NEEDS TO COORDINATE WITH THE SUBMITTED PLANS. THE
 INPUT DATA REPORT WILL BE NOTED AS IDR ON THE REMAINDER
 OF THIS COMMENT.
 THERE ARE STILL LIGHTING FIXTURES ON PLANS WHICH ARE
 NOT IN THE IDR OR FIXTURE WATTAGES WHICH DO NOT
 COORDINATE.
  
 FOR EXAMPLE: PLEASE SEE INTERIOR LIGHTING OF THE IDR.
 PLEASE SEE THE PLANS WHICH INDICATE THE *A* FIXTURES
 ALONG WITH OTHERS AS 648 WATTS. THE IDR INDICATES 324.
 BASED ON THE WATTAGE OF THE ACTUAL FIXTURE THE DOES NOT
 SEEM TO BE POSSIBLE.
  
 FOR EXAMPLE: PLEASE SEE OTHER FIXTURES SUCH AS AE1, AND
 H.
 THIS IS ONLY TWO BEING NOTED WHICH ARE NOT IN THE IDR
 AT ALL.
  
 FOR EXAMPLE: PLEASE SEE THE EXTERIOR LIGHTING SUBMITTED
 ON THE IDR. THE ONLY FIXTURE WATTAGE LISTED IS THE 250W
 FIXTURES. THIS IS NOT POSSIBLE WHEN FIXTURES ON THE
 PLANS SUCH AS SHEET ESP-1 STATES 250W AND 400WATT
 FIXTURES.
 WHAT ABOUT OTHER FIXTURES SUCH AS EXTERIOR LIGHTING
 FIXTURE *H* WHICH IS SHOWN ON PLANS ON SHEET E-2B YET
 THESE ARE NOT ON THE IDR.
  
 FOR EXAMPLE: INTERIOR LIGHTING ON PLANS IS GREATER THAN
 THE AMOUNT AND TYPE OF FIXTURES ON THE IDR. SEE LOCKERS
 AS ONE LOCATION FOR MEN, WOMEN, AT ALL LOCATIONS.
  
  
 *** THESE ARE SOME EXAMPLES ONLY GIVEN AS A BENEFIT TO
 HELP. THESE MAY NOT BE ALL ITEMS.
 PLEAS BE SURE TO GO OVER AND CALL WITH ANY COMMENTS OR
 QUESTIONS FOR COORDINATION.
 13-415.2,13-415.2.ABC.1.1,.1.2 AND .1.3.
  
 6) NOTE: PLEASE COORDINATE SHEET E-4 AND E-6. ALL MAINS
 SEEM TO COME FROM THE SAME GUTTER, HOWEVER BASED ON
 SHEET E-4 THE OTHER METER AND MAIN FOR THE HOUSE PANEL
 IS ON THE OTHER SIDE OF THE OPENING FOR THE ICE PT
 DOOR.
 THIS CONFLICTS WITH THE REVISED RISER.
 THIS IS A NEW COMMENT AS THE RISER HAS BEEN COMPLETELY
 REVISED.
  
 7) NOTE: WHERE IS THE LOAD CALCULATIONS ON THE NEW
 1600AMP MAIN?
 NEC 220
 FBC 106.1.1, 106.1.2 FOR ADDITIONAL INFORMATION AND
 CLARITY.
  
 8) NOTE: PLANS MAKE NOTE FOR FLOATING NEUTRAL AS GONE
 OVER IN MEETING HOWEVER THIS IF FOR THE METERS ON THE
 SECONDARY SIDE OF THE 1600AMP MAIN. THIS COULD BE
 REDLINED TO INDICATE THIS FOR THE METERS. IT SEEMS TO
 BE PART OF THE FEEDERS SHOWN ON RISER.
 250.6, 250.24 ETC
  
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-12-25 Cont ID  
Sent By dpalmer Date 2008-12-25 Time 11:25 Rev Time 3.25
Received By dpalmer Date 2008-12-25 Time 08:01 Sent To  
Notes
2008-12-25 11:26:08** DENIED 2ND REVIEW **
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING.
 THERE ARE ALSO SOME NEW COMMENTS AS THERE ARE SEVERAL
 ASPECTS OF DESIGN CHANGING ALONG WITH NEW ITEMS WHICH
 WERE NOT PART OF THE PREVIOUS REVIEW.
  
  
 1) NOTE: THE ARCHITECTURAL PLANS SUBMITTED CONTAIN A
 SIGNATURE AND DATE HOWEVER NONE OF THE SHEETS CONTAIN
 THE RAISED SEAL AS REQUIRED BY FLORIDA STATUTES
 481.221.
 THIS IS REQUIRED FOR ALL TRADES AND ALL REVIEWERS
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADES.
  
 2) NOTE: LANDSCAPE ARCHITECTURAL PLANS ARE MISSING
 INFORMATION REQUIRED ON THE TITLE BLOCKS. PLEASE SEE
 FLORIDA ADMINISTRATIVE CODE 61G1-16.004 AND FLORIDA
 STATUTES 481.219.
 MISSING CERTIFICATE OF AUTHORIZATION NUMBER.
 MISSING PRINTED NAME OF SAID DESIGNER.
 MISSING PRINTED LICENSE NUMBER OF ARCHITECT.
  
 ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE ANY
 OTHER TRADE OR THE LANDSCAPE REVIEWER.
  
 3) NOTE: IN PREVIOUS MEETINGS HELD IT WAS DISCUSSED
 WHETHER OR NOT THE BUILDING WAS GOING TO BE ADJUSTED TO
 SEPARATE INTO MORE THAN ONE BUILDING BY DEFINITION. BY
 THE RESPONSE FROM THE ARCHITECT THE INTENT AS SHOWN AND
 NOTED IS THIS IS A SEPARATE BUILDING. HOWEVER BY
 DEFINITION IN CHAPTER 2 OF THE FLORIDA BUILDING CODE
 WHICH WILL DIRECT YOU TO 702.1 FOR FIRE RESISTIVE
 CONSTRUCTION DEFINITIONS. THIS IS ALSO IN THE
 DEFINITIONS IN CHAPTER 13 SECTION 202 OF THE SAME CODE.
 THIS WOULD REQUIRE A ** RATED FIRE WALL*. PLEASE SEE
 THE DEFINITION OF A FIRE WALL. THE FOLLOWING TEXT IS
 EXTRACTED DIRECTLY FROM THE CODE.
  
 ****
 FIRE WALL. FIRE-RESISTANT WALL, HAVING PROTECTIVE
 OPENINGS, WHICH RESTRICTS THE SPREAD OF FIRE AND
 EXTENDS CONTINUOUSLY FROM THE FOUNDATION TO OR THROUGH
 THE ROOF, WITH SUFFICIENT STRUCTURAL STABILITY UNDER
 FIRE CONDITIONS TO ALLOW COLLAPSE OF CONSTRUCTION ON
 EITHER SIDE WITHOUT COLLAPSE OF THE WALL.****
  
 PLEASE BE SURE TO SEE THE SECOND PART OF THE SENTENCE
 WHICH THE CONSTRUCTION WILL ALLOW THE COLLAPSE OF THE
 CONSTRUCTION ON EITHER SIDE WITHOUT THE COLLAPSE OF THE
 WALL.
 A 2HR RATED DEMISING WALL DOES NOT MEET THIS
 REQUIREMENT. THIS WILL AFFECT OTHER ASPECTS OF THE
 STRUCTURE AND BUILDING. SEE OTHER COMMENTS BELOW.
 THIS COMMENT IS ENTIRELY BASED ON THE DECLARED SQ FT ON
 PLANS AND CALCULATIONS WHICH DO NOT COORDINATE WITH THE
 ACTUAL BUILDING.
 PLEASE ALSO SEE SHEET SP-1 WHICH ALSO DECLARES THREE
 SEPARATE BUILDINGS WHICH BASED ON STRUCTURAL AND
 ARCHITECTURAL PLANS IS NOT THE CASE.
 WHAT IS THE INTENT OF DESIGN? ELECTRICAL PLANS HAVE
 BEEN REVISED HOWEVER NOW SHOWING THREE SEPARATE
 SERVICES BEING PROPOSED, ONE FOR EACH TENANT SPACE. SEE
 ELECTRICAL COMMENTS BELOW AS THREE SERVICES ARE NOT
 PERMITTED TO THIS ONE BUILDING AS SHOWN.
 COORDINATION OF UNITS NEEDS TO BE DONE ON PLANS.
 WHERE A SHEETS INDICATE WAREHOUSE *B*, THE ELECTRICAL
 SHEETS INDICATE WAREHOUSE *A*> ETC
  
 4) NOTE: PLEASE SEE THE NEW SUBMITTED METHOD *C* FLA
 COM FORM DOES NOT CORRELATE WITH PLANS. PLEASE SEE THE
 SQ FT FOR BUILDING AREA ON PLANS IS SUBSTANTIALLY
 GREATER THAN THAT ON THE CALCULATIONS SUBMITTED.
 PLEASE ALSO SEE THE FOLLOWING TEXT FOR BUILDING WITH
 MULTIPLE OCCUPANCY USE IN AREAS. ONLY WHEN THE
 ADDITIONAL AREAS ARE LESS THAN 5% MAY THE MAJORITY AREA
 USE BE PERMITTED.
 METHOD *C* IS FOR BUILDING AREA, YET THERE ARE SEVERAL
 AREAS WHICH THE OCCUPANCY IS GREATER THAN 5% OF THE
 MAIN USE.
 PLEASE ADJUST. THE FOLLOWING TEXT IS TAKEN DIRECTLY
 FROM THE FLORIDA BUILDING CODE.
  
 ****
 13-101.1.4 BUILDINGS WITH MULTIPLE OCCUPANCY TYPES.
 WHEN A BUILDING CONTAINS MORE THAN ONE OCCUPANCY TYPE,
 EACH PORTION OF THE BUILDING SHALL CONFORM TO THE
 REQUIREMENTS FOR THE OCCUPANCY HOUSED THEREIN.
 EXCEPTIONS:
 1. WHERE MINOR OCCUPANCY USE DOES NOT OCCUPY MORE THAN
 5 PERCENT OF THE FLOOR AREA OF THE BUILDING, THE MAJOR
 USE SHALL BE CONSIDERED THE BUILDING OCCUPANCY. ****
  
 5) NOTE: PLEASE BE SURE ALL INFORMATION ON PLANS WITH
 RESPECT TO BUILDING COMPONENTS AND LIGHTING CORRELATE
 WITH THE PLANS. ONE EXAMPLE GIVEN IS THE EXTERIOR
 LIGHTING WHICH DOES NOT CORRELATE.
 ** ONE EXAMPLE IS THE INFORMATION ON THE LIGHTING
 FIXTURE LEGEND IS NOT CLEAR. WATTAGES, TYPES ETC SHOWN.
 NO DETERMINATION FOR CODE COMPLIANCE AND COORDINATION
 OF THE IDR CAN BE DONE.
 ** ANOTHER EXAMPLE:
 THE SUBMITTED PLANS FOR EXTERIOR LIGHTING NOTE 100W
 FIXTURES, THE IDR INDICATES 250WATT FIXTURES AND THE
 FIXTURE LEGEND DOES NOT INDICATE ANY SPECIFIC TYPE OF
 EXTERIOR FIXTURES DETERMINATION FOR CODE COMPLIANCE CAN
 NOT BE ACHIEVED.
 13-415.2, 13-415.2.ABC.1.3, 13-415.2.ABC.1.1, .1.2.
  
 6) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO
 REQUIRED LIGHTING CONTROLS PER FBC 13-415.1.ABC.1.1,
 .1.2 AND .1.3.
 PLEASE PROVIDE MORE INFORMATION ON THE LIGHTING CONTROL
 PANEL. THE SYMBOL LEGEND STATES THE OVER RIDE SHALL BE
 HIGH BAY OCCUPANCY SENSORS WITH AN OVER RIDE TIME OF
 4HRS.
 THIS IS NOT CLEAR HOW THIS IS POSSIBLE WHEN EVERY KNOWN
 OCCUPANCY SENSOR DEVICE TO THIS OFFICE FROM MOST
 MANUFACTURES IS MAXIMUM 30MINS AFTER THE LAST SENSING
 OF THE OCCUPANT. PLEASE SEE SECTION 13-415.1.ABC.1.1 OF
 THE FBC WHICH DOES NOT PERMIT AN OVER RIDE OF MORE THAN
 30MINS WITH THE USE OF OCCUPANCY SENSORS AS OVERRIDES.
 PLEASE ALSO SEE PLANS WHICH INDICATE A *S* WHICH BY THE
 SYMBOL LEGEND IS A SINGLE POLE SINGLE THROW SWITCH.
 THIS TYPE OF DEVICE WILL NOT MEET THE MINIMUM
 REQUIREMENTS OF THE FBC SECTIONS GIVEN NOR WILL IT
 PROVIDE AUTOMATIC SHUT OFF DURING AN OVER RIDE.
 THERE MAY BE SOME SORT OF MISPRINT WITH THE WORDING ON
 SYMBOL LEGEND.
 PLEASE SEE THERE ARE ROOMS AND AREAS WHICH ARE MISSING
 LIGHTS AND CONTROLS PER SECTIONS GIVEN. ARCHITECTURAL
 PLANS INDICATE LIGHTS NEXT TO AHU ROOM YET NO
 INFORMATION ON ELECTRICAL PLANS IN FACT THIS ROOM IS
 BLANK.
 IN MEETING HELD BEFORE PLANS WERE SUBMITTED IT WAS
 REQUESTED TO SUPPLY THE MANUFACTURES SPECS/CUT SHEETS
 ON THE PROPOSED LIGHTING CONTROL PANEL(S) AND ALL
 EQUIPMENT. THE SHEETS SUBMITTED DO NOT PROVIDE
 INFORMATION ON REQUIRED LIGHTING CONTROLS PER SECTIONS
 OF THE CODE GIVEN ABOVE. IN FACT THE SHEETS EXPAND ON
 THE DIMMING POSSIBILITIES WHICH IS OK HOWEVER DOES NOT
 PROVIDE INFORMATION ON CONTROLS OF LIGHTS TO MEET
 MINIMUM SHUT OFF REQUIREMENTS OF THE FLORIDA BUILDING
 CODE FOR ENERGY EFFICIENCY.
 ALSO AS GONE OVER IN MEETING PLEASE BE SURE DOCUMENTS
 CONTAIN A LISTING FROM ONE OF THE ADOPTED NATIONALLY
 RECOGNIZED TESTING LABORATORIES. ( NRTL) PER 110.3.
 IE: UL, ETL< MET< TUV< TUV AMERICA< CSA ETC.
  
 7) NOTE: THE PLANS NOW SHOW NEW ELECTRICAL GATE AND
 LIGHT POLE OUTSIDE THE PROPERTY LING BASED ON SURVEY
 AND SITE PLANS. THIS IS NOT PERMITTED. THE MAY BE FED
 FROM A SEPARATE OFF THE PROPERTY HOWEVER IT MAY NOT
 CROSS THE PROPERTY. THE PROPOSED GATE IS ALSO NOT PART
 OF THE SHOWN PROPERTY AND IS NOT INCLUDED.
 PLEASE KNOW THIS INFORMATION WILL BE ROUTED TO FIRE
 MARSHAL, ZONING AND BUILDING REVIEWERS.
 230, FBC SEE NOTES FROM OTHER TRADES.
  
 8) NOTE: PLEASE SEE NEC 230.2. THE RISER NOW SHOWS A
 PROPOSED THREE SEPARATE SERVICES WHICH CAN NOT BE
 GRANTED BASE ON 230.2. THE SERVICE SIZE, VOLTAGE,
 OCCUPANCY ETC DOES NOT MEET ALLOWANCE FOR OTHER TWO
 ADDITIONAL SERVICES. THIS IS ONE BUILDING BY ALL
 DEFINITIONS LISTED ABOVE IN THE FLORIDA BUILDING CODE.
 PLEASE ALSO SEE 2005 NEC HANDBOOK DIAGRAM. BY
 ILLUSTRATIONS THIS IS ONE BUILDING AND BY RISER THESE
 ARE THREE SEPARATE SERVICES.
 PLEASE REVISE RISER.
  
 9) NOTE: PLEASE SEE PREVIOUS NOTES AND IN MEETING HELD
 BEFORE PLANS WERE RESUBMITTED IT WAS DISCUSSED THAT ANY
 CONTROLS FOR EGRESS LIGHTING SHALL BE FAIL SAFE ON PER
 NFPA-101 7.8.1.2.2, FBC 1006.1.2
  
 10) NOTE: PLEASE KNOW THERE MAY ALSO BE NEW COMMENTS
 WITH RESPECT TO AREA ABOVE OFFICES. THIS AREA IS SHOWN
 TO CONTAIN A NEW 42 INCH HIGH WALL HOWEVER CLEAR STAIRS
 ARE SHOWN TO AREA YET NO OTHER INFORMATION IS SHOWN. IN
 FACT THE ARCHITECTURAL PLANS DO NOT SHOW OR NOTE ANY
 STAIRS THEY IN FACT INDICATE THIS SAME ROOM AS *STORAGE
 AREA*. THE ELECTRICAL PLANS CLEARLY NOTE THIS SAME ROOM
 AS STAIR WITH LIGHTING TO ABOVE. HOWEVER THEY DO NOT
 SHOW THE ACTUAL STAIRS.
 ELECTRICAL PLANS ALSO INDICATE FUTURE ELEVATOR YET
 INFORMATION ON OTHER PLANS AND SHEETS DO NOT SHOW ANY
 OF THESE ITEMS.
 PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR EGRESS AREAS.
 PLEASE SEE 13-415.1.ABC.1.1,.1.2 WITH RESPECT TO MORE
 THAN ONE FLOOR. SEE FBC FOR FLOOR DEFINITIONS.
 AS SPECIFICALLY NOTED ON PREVIOUS REVIEW TO PROVIDE
 EGRESS LIGHTING FOR STAIRS THE RESPONSE FROM DESIGNER
 WAS THIS WAS PREVIOUSLY SUBMITTED. THE PHOTO-METRICS
 SUBMITTED TO NOT SHOW LEVELS FOR EITHER STAIRS.
 PLEASE SEE NFPA-101 7.8.1.3, 7.9.2.1, .2.2.
 SEE SHEET E-2B WHICH INDICATES TO LIGHTS ABOVE FOR
 CONTROLS ETC HOWEVER THERE IS NO 2ND FLOOR LIGHTING OR
 POWER PLANS FOR THIS END OF THE BUILDING.
 SEE COMMENTS FROM OTHER TRADES AND BE AWARE OF NOTED
 REQUIREMENTS FOR EGRESS, LIGHTING CONTROLS ETC.
 PLEASE SEE FBC13-415.1.ABC.1, FOR AREAS CONSIDERED
 SEPARATE FLOORS.
  
 ** ONE SET OF THE PLANS WILL BE RETAINED.
  
 11) NOTE: PLEASE CLARIFY THE GROUNDING ELECTRODE
 SYSTEMS AS SHOWN. RISER INDICATES ALL GOING TO FOOTER
 STEEL. THIS IS AN EXISTING BUILDING AND IF THERE IS NOT
 CURRENTLY A BOND TO FOOTER STEEL NEW ONES WILL NOT BE
 REQUIRED INTO EXISTING FOOTING STEEL. THIS IS ONLY
 NOTED AS ALL NEW FOOTER STEEL IS REQUIRED TO BE BONDED.
 ** NOTED FOR INFORMATION ONLY.
  
 12) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO
 MINIMUM REQUIREMENTS OF DEVICES FOR FIRE ALARM SYSTEM.
 RESPONSE MENTIONS CANDELA LEVELS AND HEIGHTS ARE ON ICE
 RINK PLANS HOWEVER BASED ON THE PLANS SUBMITTED ONLY
 THE CD LEVELS AND HEIGHTS IN RINK ARE SHOWN. PLEASE SEE
 SECTIONS 11-4.28.1, .2 AND .3. ALL LOCATIONS FOR ADA
 ARE REQUIRED TO BE MET; ALL PULL STATION HEIGHTS,
 STROBE HEIGHTS, ETC.
 PLEASE KNOW THERE ARE MORE THAN THE ICE RINK AREAS
 WHICH REQUIRE DEVICES.
 SEE COMMENTS FROM FIRE REVIEW FOR MINIMUM NFPA-72
 REQUIREMENTS AS FULL PROTECTION OF ANY FIRE ALARM
 SYSTEM MAY NOT ONLY BE RINK AREA.
  
 13) NOTE: PLEASE SEE 210.70 FOR MISSING LIGHTING
 REQUIRED IN AHU ROOM.
 PLEASE SEE 210.63, 210.8 FOR SERVICE RECEPTACLE.
  
 14) NOTE: THE AIC RATINGS AND FAULT CURRENTS ARE SHOWN
 HOWEVER THE RATINGS AT MAINS NEED TO BE SHOWN.
 110.9
 THE ANALYSIS SUBMITTED IS FOR MAINS AT EACH UNIT. IF 42
 K IS THE RATING FOR SBA, THE RATING FOR THE MAIN WILL
 BE SUBSTANTIALLY HIGHER AND NO INFORMATION FOR ANY OF
 THE MAINS IS SHOWN.
  
 15) NOTE: PLANS INDICATE HWB WHICH IS NOTED FOR HOUSE
 ELECTRICAL SITE LIGHTING ETC YET THIS PANEL IS IN ONE
 OF THE TENANT SPACES.
 THE WAREHOUSE SPACE *B* IS CURRENTLY OCCUPIED HOW CAN
 IT POSSIBLE THE PANELS ARE BLANK WITH NO CIRCUITING?
 HOUSE POWER/SITE LIGHTING MAY NOT BE FED FROM PANEL IN
 TENANT SPACE.
  
 16) NOTE: PLEASE ADJUST DESIGNATIONS OF FUTURE BACK UP
 POWER PANELS. THESE ARE NOT *EMERGENCY* BACK UP
 SYSTEMS. PLEASE SEE DEFINITIONS IN NEC 700, 701 AND
 702.
 THESE PANELS ARE OPTIONAL STAND-BY.
  
 17) NOTE: PLEASE COORDINATE THE LOADS FOR THE WATER
 HEATERS ON THE LOAD CALCULATIONS WITH THAT OF THE LOADS
 ON THE PANELS. THE LOADS ON PANELS FAR EXCEED THAT OF
 THE LOAD ON CALCULATIONS. ONE WATER HEATER ALONE
 EXCEEDS LOAD SHOWN FOR ALL THREE.
 PLEASE ALSO SEE 422.13 FOR THE 2005 NEC AS THE LOAD IS
 A CONTINUOUS LOAD AND SHALL BE FIGURED AT 125%.
  
 18) NOTE: PLEASE SEE FBC 3006.2 FOR FUTURE ELEVATOR
 LIFT.
  
 19) NOTE: PLEASE SEE 620.22,23 AND 24 FOR FUTURE
 ELEVATOR EQUIPMENT ROOM. THIS IS NOTED AS COMMENTS FROM
 OTHER REVIEWS AND USE OF SECOND FLOOR AREA HAS NOT BEEN
 DETERMINED AT THIS TIME AS VERTICAL ACCESSIBILITY MAY
 BE REQUIRED AT THIS TIME.
  
 20) NOTE: PLEASE SEE PREVIOUS REVIEW AS IT WAS
 REQUESTED TO SUBMIT THE MANUFACTURES SPECS/CUT SHEETS
 FOR THE PROPOSED ATS. THIS WAS GONE OVER IN MEETING
 ALSO. THE PLANS NOW SHOW THIS PROPOSED ATS ON SHEET E-6
 HOWEVER THE INFORMATION IS NOT CLEAR AND VERY FAINT AND
 BLURRY.
 PLEASE SUBMIT SEPARATE SHEETS OR IMPROVE ON PRINTED
 SHEET.
 110.3, 90.7
 FBC 106.1.1, 106.1.2 FOR ADDITIONAL INFORMATION,
 CLARITY ETC.
  
 21) NOTE: PLEASE SUBMIT/SHOW SCHEDULE FOR SBA AS OTHER
 PANELS ARE SHOWN GIVING THE SPECIFIC INFORMATION FOR
 EQUIPMENT.
 408.4, 110.9, 90.7 ETC
 FBC 106.1.1, 106.1.2 FOR ADDITIONAL INFORMATION,
 CLARITY AND COORDINATION.
  
 22) NOTE: PLEASE PROVIDE VOLTAGE DROP CALCULATIONS FOR
 FEEDERS/BRANCH CIRCUITS PER 13-413.1ABC.1.
 VOLTAGE DROP.
 13-413.1.ABC.1.1 FEEDERS.
 FEEDER CONDUCTORS SHALL BE SIZED FOR A MAXIMUM VOLTAGE
 DROP OF 2 PERCENT AT DESIGN LOAD.
 13-413.1.ABC.1.2 BRANCH CIRCUITS.
 BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED FOR A MAXIMUM
 VOLTAGE DROP OF 3 PERCENT AT DESIGN LOAD.
  
 ** SUBMITTED FOR WAREHOUSE A AND B, HOWEVER NEED SITE
 BRANCH CIRCUIT(S)
  
 23) NOTE: PLEASE BE SURE THE FOLLOWING IS LISTED ON
 ELECTRICAL PLANS. THIS IS TAKEN FROM THE FBC SECTIONS.
 **13-413.1.ABC.2.1 DRAWINGS.
 CONSTRUCTION DOCUMENTS SHALL REQUIRE THAT WITHIN 30
 DAYS AFTER THE DATE OF SYSTEM ACCEPTANCE, RECORD
 DRAWINGS OF THE ACTUAL INSTALLATION SHALL BE PROVIDED
 TO THE BUILDING OWNER, INCLUDING:
 1. A SINGLE-LINE DIAGRAM OF THE BUILDING ELECTRICAL
 DISTRIBUTION SYSTEM AND
 2. FLOOR PLANS INDICATING LOCATION AND AREA SERVED FOR
 ALL DISTRIBUTION.
 13-413.1.ABC.2.2 MANUALS.
 CONSTRUCTION DOCUMENTS SHALL REQUIRE THAT AN OPERATING
 MANUAL AND MAINTENANCE MANUAL BE PROVIDED TO THE
 BUILDING OWNER. THE MANUALS SHALL INCLUDE, AT A
 MINIMUM, THE FOLLOWING:
 1. SUBMITTAL DATA STATING EQUIPMENT RATING AND SELECTED
 OPTIONS FOR EACH PIECE OF EQUIPMENT REQUIRING
 MAINTENANCE.
 2. OPERATION MANUALS AND MAINTENANCE MANUALS FOR EACH
 PIECE OF EQUIPMENT REQUIRING MAINTENANCE. REQUIRED
 ROUTINE MAINTENANCE ACTIONS SHALL BE CLEARLY
 IDENTIFIED.
 3. NAMES AND ADDRESSES OF AT LEAST ONE QUALIFIED
 SERVICE AGENCY.
  
 24) NOTE: PLEASE BE SURE PANEL SCHEDULES ARE COMPLETE
 WITH LOADS AND SPECIFIC APPLIANCES. FOR EXAMPLE: R1B8
 WHICH BY THE PANEL SCHEDULE ONLY LIST VIEWING ROOM
 RECEPTACLES LOOKS TO BE A HALF SWITCH RECEPTACLE UNDER
 THE SINK WHICH WOULD LEND TO A DISPOSAL. DISPOAL WOULD
 BE REQUIRED TO BE ON A SEPARATE CIRCUIT WITH LOADS
 FIGURED.
 PLEASE ALSO VERIFY LOAD SHOWN FOR WASHER AS THIS IS
 NOTED A 1KVA.
 THE PLANS APPEAR TO SHOW A REFRIGERATOR FOR CIRCUIT
 R1B20 YET THE PANEL SCHEDULE DOES NOT INDICATE ANY
 CIRCUIT. IN FACT THE SCHEDULE IS BLANK FOR THIS
 LOCATION.
  
 PLEASE COORDINATE ALL, THESE ARE A FEW EXAMPLES AND ARE
 NOT ALL.
 PLEASE SEE 408.4,240.4,310.16, AND 220.
  
  
 25) NOTE: ** IT IS IMPORTANT TO KNOW THAT AS THERE IS A
 SUBSTANTIAL AMOUNT OF INFORMATION NOT YET CLEAR FOR
 USE, OCCUPANCY, FLOORS, LIGHTING ETC THERE MAY VERY
 WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH CAN
 NOT BE MADE AT THIS TIME.
 PLEASE ALSO BE AWARE OF FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY NOTED
 AT THIS TIME AS THERE WERE SOME CODE SECTIONS REPEATED
 FROM PREVIOUS REVIEW WHICH WAS NOT ADDRESSED.
 ** ONE COMPLETE SET OF PLANS WILL BE RETAINED BY THIS
 OFFICE ALONG WITH ENERGY CALCULATIONS.
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-10-15 Cont ID  
Sent By dpalmer Date 2008-10-15 Time 17:08 Rev Time 0.00
Received By dpalmer Date 2008-10-15 Time 17:08 Sent To  
Notes
2008-10-15 17:08:18 
 ** DENIED REVIEW**
  
  
  
  
 1) NOTE: PLEASE SEE THE APPLIED ADDRESS IS AT 1600 N.
 FLORIDA MANGO HOWEVER THE PLANS INDICATE 1590 SAME
 ROAD. THE PACKAGE WILL BE ROUTED TO ADDRESSING FOR AN
 EXTENSION FOR THIS TENANT SPACE. AS THE APPLIED SCOPE
 OF WORK IS BEING SHOWN WHAT APPEARS TO BE IN MULTIPLE
 TENANT SPACES THE APPLIED ADDRESS IS UNCLEAR AND THERE
 ARE SEVERAL UNANSWERED QUESTIONS.
  
 2) NOTE: PLEASE BE SURE THE PLANS CONTAIN THE FOLLOWING
 DESIGN CODES AT A MINIMUM. THE FLORIDA STATUTES 553.73
 GIVES THE ADOPTION OF THE LATEST CODES THROUGH THE
 FLORIDA BUILDING CODE. IN ANY CASE SEE THE FP SHEETS AS
 THESE CLEARLY STATE THE SOUTH FLORIDA BUILDING CODE
 WHICH HAS NOT BEEN AN ADOPTED CODE IN THE STATE OF
 FLORIDA FOR MANY YEARS.
 THE FOLLOWING SHALL BE LISTED AT A MINIMUM FOR THIS
 REVIEWER. PLEASE BE AWARE OF OTHER CODES FROM OTHER
 TRADES.
 2004 FBC W/2007 REVISIONS.
 2003 NFPA-101
 2002 NFPA-72
 2005 NFPA-70
 2002 NFPA-110
  
 3) NOTE: THE PLANS ARE UNCLEAR FOR THE SCOPE OF WORK.
 IS THIS ONE BUILDING WITH THREE TENANT SPACES OR ARE
 THESE THREE SEPARATE BUILDINGS? PLEASE KNOW THE SERVICE
 FOR INSTANCE FOR THE NUMBER OF SERVICES, GROUPING OF
 MAINS ETC CAN NOT BE DETERMINED AS CODE COMPLIANT AT
 THIS TIME. 230.2, 230.70, 230.70, 230.72, 230.76,
 230.79 ETC
 PLEASE SEE THE FLORIDA BUILDING CODE FOR DEFINITIONS OF
 A BUILDING INCLUDING THE DEFINITIONS FOR THE NEXT
 COMMENT WITH RESPECT TO THE ENERGY CALCULATIONS.
  
 4) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS
 ARE NOT CODE COMPLIANT. PLEASE SEE THERE WILL BE SOME
 EXAMPLES NOTED HOWEVER IT IS NOT A COMPLETE LIST OF ALL
 INCONSISTENCIES. IT IS ALSO IMPORTANT TO SEE COMMENTS
 FROM OTHER TRADES WITH RESPECT TO ALL BUILDING
 COMPONENTS. SOME WILL BE NOTED IN THIS REVIEW FOR
 EXAMPLES.
 THE SUBMITTED VERSION IS METHOD *A* FOR WHOLE BUILDING
 COMPLIANCE. HOW IS THIS POSSIBLE? BASED ON PLANS THIS
 IS A RENOVATION TOT AN EXISTING BUILDING WHICH MEETS
 THE DEFINITIONS IN SECTION 202 OF CHAPTER 13. WHOLE
 BUILDING COMPLIANCE MAY ONLY BE USED *IF* ALL SYSTEMS
 FOR THE ENTIRE BUILDING IS BEING USED AND KNOWN. PLEASE
 SEE 13-101.1.3 RENOVATIONS.
 RENOVATED COMMERCIAL BUILDINGS SHALL, WHEN APPLICABLE
 (SEE SECTION 202), COMPLY WITH THE PRESCRIPTIVE
 REQUIREMENTS CONTAINED IN FORM 400C OR WITH METHOD B OF
 SUBCHAPTER 13-4 FOR INSULATION, HVAC SYSTEMS, LIGHTING,
 WATER HEATING SYSTEMS AND EXTERIOR ENVELOPE COMPONENTS
 BEING RETROFITTED OR REPLACED.
 PLEASE SEE THE INPUT DATA REPORT WHICH DOES NOT
 COORDINATE WITH THE SUBMITTED PLANS. SOME EXAMPLES WILL
 BE GIVEN AND THE INPUT DATA REPORT WILL BE NOTED AS IDR
 IN COMMENTS.
  
 FOR EXAMPLE: HOW IS IT POSSIBLE THAT THE METHOD OF
 CONTROL FOR ALL LIGHTING BE SHOWN AS MANUAL ON/OFF WHEN
 THE PLANS CLEARLY SHOW AUTOMATED SYSTEMS AS REQUIRED
 PER 13-415.1.ABC.1.1, .1.2, .1.3
  
 FOR EXAMPLE: PLEASE BE SURE ALL INTERIOR LIGHTS ARE THE
 SAME ON THE IDR AS ON THE PLANS FOR THE SAME WATTAGE,
 NUMBER OF FIXTURES AND TYPES. PLEASE BE SURE TO SEE
 13-415.2, 13-415.2.ABC.1.1, .1.2 AND .1.3. PLEASE SEE
 TABLE 13-415.2.B, 13-415.2.C. PLEASE BE SURE TO SEE
 NOTE ABOVE FOR METHOD OF CALCULATIONS TO BE SUBMITTED.
  
 FOR EXAMPLE: SEE OTHER COMPONENTS SUCH AS THE FLOOR OF
 THE ICE RINK ITSELF BEING SHOWN WITH *CARPET AND RUBBER
 PADDING*. THIS IS NOT POSSIBLE.
  
 FOR EXAMPLE: THE IDR SHOWS *NO* EXTERIOR DOORS FROM
 CONDITIONED SPACE WHEN THE PLANS CLEARLY CONTAINS
 SEVERAL.
  
 FOR EXAMPLE: MECHANICAL/ELECTRICAL ROOMS SHOWING*CARPET
 AND RUBBING PADDING* WHEN THE ELECTRICAL ROOMS ARE NOT
 PERMITTED TO CONTAIN COMBUSTIBLES. SEE COMMENTS FROM
 OTHER TRADES ON THIS.
  
 5) NOTE: BASED ON THE PLANS SUBMITTED THIS GENERATOR
 WILL BE A LIFE SAFETY REQUIRED NEC 700 SYSTEM YET THERE
 ARE OTHER WIRING ITEMS ON THIS SAME PANEL, EQUIPMENT
 AND ATS WHICH ARE NOT LEGALLY REQUIRED AND ARE OPTIONAL
 STAND-BY. PLEASE SEE NEC 700.9 FOR WIRING REQUIRED AS
 OTHER SYSTEMS SHALL NOT BE PART OF THE EMERGENCY/LIFE
 SAFETY REQUIRED SYSTEMS. NO INFORMATION WAS SUBMITTED
 FOR THE ON-SITE REQUIRED FUEL PER 700.12B3 AND
 701.11B3. THERE ARE MANY OTHER SECTIONS INCLUDING
 SECTIONS OF NFPA-110 WHICH ALSO APPLY HOWEVER NOT EVERY
 POSSIBLE CODE SECTION IS LISTED.
 PLEASE SEE THERE WAS NO INFORMATION SUBMITTED FOR
 MANUFACTURE SPECS/CUT SHEETS OF THE ATS, GENERATOR AND
 FUEL TANKS. PLEASE SUBMIT. PLEASE SEE NFPA-110 2002,
 NEC 110.3,90.7 ETC
 ** PLEASE BE SURE TO SEE NFPA-110 CHAPTER 7 FOR
 INSTALLATION REQUIREMENTS.
 ** THERE ARE SEVERAL ITEMS NOT SUBMITTED. AS THIS UNIT
 IS BEING SHOWN AS A 700,701 SYSTEM ALL THE ABOVE AND
 CODE MUST BE MET.
  
 6) NOTE: IT IS BEING NOTED WITH RELEVANCE TO THE NOTE
 #56 ABOVE; IF THE INTENT IS FOR THE BUILDING TO BE
 OCCUPIED UNDER EMERGENCY POWER THEN BATTERY BACK UP
 LIGHTS WILL BE REQUIRED FOR ALL EGRESS PATHS. THE
 OCCUPIED BUILDING WOULD BE THEN UNDER EMERGENCY POWER
 FOR A *NORMAL OCCUPANCY*. IF THE EMERGENCY GENERATOR IS
 THEN LOST THERE WOULD BE NOT EGRESS LIGHTING FOR ANY
 OCCUPANCY PUBLIC OR OTHER WISE TO FIND THEIR WAY OUT OF
 THE BUILDING. IF THE BUILDING IS NOT GOING TO BE
 OCCUPIED UNDER GENERATOR POWER THIS OFFICE WILL
 REQUIRED AN ORIGINAL LETTER SIGNED, NOTARIZED FROM THE
 NEW BUILDING OWNER STATING THE BUILDING WILL NOT BE
 OCCUPIED UNDER EMERGENCY POWER. THIS WILL BE
 ENFORCEMENT FROM THIS OFFICE AS WELL AS THE FIRE
 MARSHAL OFFICE.
 NFPA-101 7.8.1, 7.9.1ETC
 THE OTHER OPTION WOULD BE TO INSTALL THE BATTERY BACK
 UP LIGHTS FOR MINIMUM EGRESS UNDER AN EMERGENCY
 CONDITION AND THE GENERATOR WOULD BECOME AN OPTIONAL
 STAND-BY SYSTEM. SEE THE FOLLOWING TWO COMMENTS AS
 THESE WILL ALSO AFFECT THE DESIGN.
  
 7) NOTE: PLEASE PROVIDE THE SELECTIVE COORDINATION
 STUDY FOR ALL EMERGENCY EQUIPMENT ON BOTH THE NORMAL
 AND EMERGENCY SIDE OF THE EMERGENCY SYSTEM AS SHOWN.
 PLEASE SEE 240.12,700.27, 701.18, NFPA-110 CHAPTER 6,
 6.5.
  
 8) NOTE: PLEASE SUBMIT PHOTO-METRICS FOR STAIRS TO
 INDICATE THE MINIMUM LEVELS UNDER NORMAL AND EMERGENCY
 CONDITIONS. THE NORMAL LEVELS REQUIRE A MINIMUM OF 10FT
 CANDLES AND IS PERMITTED TO 1 FT CANDLE UNDER EMERGENCY
 CONDITIONS.
 NFPA-101 7.8.1.3 , 709.2.1, .2.2
  
 9) NOTE: PLEASE SEE FBC 106.1.3 AS THE SUBMITTED PLANS
 SHALL MEET A MINIMUM OF 1/8INCH SCALE. MAY SHOW A
 LARGER VIEW OF THE ENTIRE LAYOUT AS LONG AS ALL AREAS
 ARE SHOWN ON A SEPARATE SHEET IN A LARGER VIEW MEETING
 THE MINIMUM SCALE.
  
 10) NOTE: PLEASE SEE 240.13, 230.95 FOR THE REQUIRED
 GROUND FAULT PROTECTION. PLEASE ALSO BE AWARE AS THE
 CODE REQUIRES GROUND FAULT SENSING IN 700.7D, 700.26
 AND NFPA-110 IN CHAPTER 6, 6.2.15
 THE ATS WOULD BE A 4-POLE UNIT OTHER WISE THERE WOULD
 BE A LACK OF COORDINATION.
 THIS WOULD BE A SEPARATELY DERIVED SYSTEM.
 ** NOTE #6 ABOVE AND WHETHER OR NOT THIS IS A LIFE
 SAFETY GENERATOR WILL HAVE AN AFFECT ON THIS COMMENT.
  
 11) NOTE: PLEASE SEE TRANSFORMER TWA WHICH IS SHOWING A
 NEUTRAL BEING INSTALLED ON THE LINE SIDE?
 PLEASE SEE 250.20,250.30 ETC
  
 12) NOTE: PLEASE PROVIDE A GROUNDING ELECTRODE RISER
 FOR THE ATTACHMENT OF ALL TRANSFORMERS.
 250.66,250.58,250.56. AS THE SERVICE AND INFORMATION ON
 THE ACTUAL BUILDING IS NOT KNOWN AT THIS TIME THIS MAY
 AFFECT THE SERVICE AS SHOWN.
  
  
 13) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2 AND
 .1.3. PLEASE PROVIDE INFORMATION ON THE PROPOSED
 LIGHTING CONTROL SYSTEM. TIMES OF OVER RIDES, LOCATIONS
 OF OVER RIDES, ETC. PLEASE BE SURE TO SEE THESE
 SECTIONS AS THERE ARE SEVERAL ITEMS REQUIRED NOT SHOWN.
 OCCUPANT MUST SEE ALL LIGHTING BEING OVER RIDDEN.
  
 14) NOTE: PLEASE SEE 700.12F FOR CIRCUITING OF
 EMERGENCY LIGHTING. THIS IS BASED ON NOTES ABOVE FOR
 REQUIRE BATTERY BACK UP FIXTURES.
  
 15) NOTE: PLEASE SEE FBC 11-4.28.1,.2 AND .3. PLEASE
 PROVIDE ALL MINIMUM LEVELS FOR ADA COMPLIANCE INCLUDING
 HEIGHTS, LEVELS OF DEVICES ETC.
  
 16) NOTE: ELECTRICAL SITE PLANS ARE MISSING MINIMUM
 DESIGN FOR FBC 140MPH 3 SECOND GUST/120 MPH SUSTAINED.
 PLEASE SUBMIT. THIS WILL BE UNDER THE STRUCTURAL REVIEW
 ONCE SUBMITTED.
  
 17) NOTE: PLEASE SEE 225.31-225.39 FOR DISCONNECTING
 MEANS REQUIRED FOR THE FEEDERS FROM THE GENERATOR. AS
 THE DISCONNECTING MEANS WILL NOT BE READILY ACCESSIBLE
 BASED ON POSSIBLE ZONING COMMENTS; A DISCONNECTING
 MEANS (NOT WITH OVER CURRENT PROTECTION) WILL BE
 REQUIRED.
  
 ** AS THERE ARE SEVERAL UNANSWERED COMMENTS AND
 INFORMATION NOT YET SHOWN, SUBMITTED OR IN DESIGN THERE
 MAY VERY WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW
 WHICH CAN NOT BE MADE AT THIS TIME.
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 5 Status N Date 2009-12-11 Cont ID  
Sent By efabian Date 2009-12-11 Time 14:49 Rev Time 0.00
Received By efabian Date 2009-12-11 Time 14:49 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2009-10-02 Cont ID  
Sent By dlauderm Date 2009-10-02 Time 10:47 Rev Time 0.50
Received By dlauderm Date 2009-10-02 Time 10:47 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2009-09-23 Cont ID  
Sent By mgonzale Date 2009-09-23 Time 11:43 Rev Time 1.00
Received By mgonzale Date 2009-09-23 Time 11:41 Sent To  
Notes
2009-09-23 11:42:59PASSED WITH PROVISO
 ENGINEERING WILL WAIT FOR CORRECT SIDEWALK ALIGNMENT
 REVISION AS PER PLANNING TO SIGN PLANS.
 MANUEL JULIAN GONZALEZ
 CONSTRUCTION SERVICES
 ENGINEERING REVIEW
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2009-08-31 Cont ID  
Sent By efabian Date 2009-08-31 Time 09:02 Rev Time 0.00
Received By efabian Date 2009-08-31 Time 09:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 11 Status P Date 2009-12-10 Cont ID  
Sent By mawillia Date 2009-12-10 Time 12:04 Rev Time 0.00
Received By mawillia Date 2009-12-10 Time 10:35 Sent To  
Notes
2009-12-10 12:04:38*****REVISION, W/E.S. DATE 11/10/2009, APPROVED*****
  
  
 REVISED PLAN SHEETS FP-1, FP-2, FP-3, FP-4, AND E-2C
 WERE STAMPED, INITIALED, AND DATED.
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 10 Status P Date 2009-10-08 Cont ID  
Sent By mcarsill Date 2009-10-08 Time 12:34 Rev Time 0.00
Received By mcarsill Date 2009-10-08 Time 12:17 Sent To  
Notes
2009-10-08 12:33:50PHASE TWO
  
 1. THE EXISTING FIRE HYDRANTS LOCATED ON THE SITE HAVE
 NOT BEEN REPLACED. THE NEW FIRE HYDRANTS PLANNED FOR
 INSTALLATION SHALL COMPLY WITH UTILITY AND FIRE RESCUE
 STANDARDS.
  
 2. ADEQUATE PROVISIONS ARE TO BE MADE FOR FIRE RESCUE
 PERSONNEL AND EQUIPMENT TO PASS THROUGH ANY SECURITY
 GATES. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY
 ELECTRONIC GATES. IF ELECTRIC, PROVISIONS ARE TO BE
 MADE FOR WHEN LOSS OF POWER OCCURS.
  
 3. ALL ELECTRICAL WORK TO COMPLY WITH NFPA 70, THE
 NATIONAL ELECTRIC CODE.
  
 4. ALL SYSTEMS AND DEVICE INSTALLATION TO COMPLY WITH
 THE FLORIDA BUILDING CODE, FLORIDA FIRE PREVENTION
 CODE, MECHANICAL, PLUMBING, AND FUEL GAS CODES WHERE
 APPLICABLE.
  
  
 APPROVED SUBJECT TO FIELD INSPECTION AND APPROVAL.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 WEST PALM BEACH FIRE RESCUE
 BUREAU OF FIRE PREVENTION
 500 NORTH DIXIE HIGHWAY
 WEST PALM BEACH, FLORIDA 33401
 804-4709 PHONE
 804-4774 FAX
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 9 Status P Date 2009-09-28 Cont ID  
Sent By mawillia Date 2009-09-28 Time 12:01 Rev Time 0.00
Received By mawillia Date 2009-09-28 Time 11:30 Sent To  
Notes
2009-09-28 13:31:44*****REVISION PROVISO*****
  
  
 PROVISO TO LANDSCAPING SHEET SHOWING PROPER EXIT
 CLEARANCE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 8 Status P Date 2009-09-01 Cont ID  
Sent By mawillia Date 2009-09-01 Time 12:26 Rev Time 0.00
Received By mawillia Date 2009-09-01 Time 11:53 Sent To  
Notes
2009-09-01 12:26:13*****APPROVED (PHASE 2)*****
  
 BASED UPON PREVIOUS PLAN REVIEW CONDUCTED AND APPROVED
 BY FIRE MARSHAL MIKE CARSILLO, PLAN SHEETS A210, A211,
 A212, A222, LS110, LS120, AND ES-1 WERE STAMPED,
 INITIALED, AND DATED.
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status P Date 2009-08-07 Cont ID  
Sent By mcarsill Date 2009-08-07 Time 16:14 Rev Time 0.00
Received By mcarsill Date 2009-08-07 Time 14:48 Sent To  
Notes
2009-08-07 16:14:051590 NORTH FLORIDA MANGO
 INTERIOR RENOVATION FOR PALM BEACH ICE WORKS ( PHASE II
 )
  
 1. CROWD MANAGEMENT TRAINING IS REQUIRED FOR THIS
 FACILITY. ONE CROWD MANAGER IS REQUIRED FOR EVERY 250
 OCCUPANTS. PLEASE GO THE MARYLAND STATE FIRE MARSHALS
 WEB SITE AND CLICK ON THE ICON FOR THE ON-LINE CROWD
 MANAGEMENT PROGRAM. AFTER COMPLETING THE PROGRAM A TEST
 NEEDS TO BE TAKEN AND CERTIFICATES SUBMITTED TO THIS
 OFFICE.
  
 2. CONSTRUCTION, DEMOLITION, AND RENOVATION IS TO
 COMPLY WITH NFPA 241.
  
 3. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY FIRE
 SPRINKLER SYSTEM RENOVATION.
  
 4. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY FIRE
 ALARM SYSTEM REMODEL.
  
 5. THE DOUBLE PAIRS OF DOORS LEADING FROM ICE RINK INTO
 LOBBY 116 SWING IN THE WRONG DIRECTION. THESE DOORS
 SHOULD SWING INTO LOBBY 116. DOORS 117 AND DOORS 118.
  
 6. ADDITIONAL EXIT SIGNS APPEAR TO BE NEEDED IN THE
 CORRIDORS TO LEADS PERSONS THROUGH DOORWAYS.
  
 7. TACTILE SIGNAGE REQUIRED AT ALL EXIT DOOR LOCATIONS.
  
 8. ADDITIONAL EXIT SIGNS APPEAR TO BE NEEDED ON THE
 SECOND FLOOR TO DIRECT PERSONS THROUGH DOORWAYS.
  
 9. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY HOOD,
 DUCTS, AND FIRE SUPPRESSION SYSTEMS. THESE SYSTEMS ARE
 REQUIRED FOR ANY COOKING THAT PRODUCES SMOKE OR GREASE
 LADEN VAPORS.
  
 10. PLEASE SUBMIT AN "ALL HAZARDS" EMERGENCY PLAN TO
 THIS OFFICE FOR THE FACILITY.
  
 11. ALL HANDRAILS AND GUARDRAILS SHALL MEET THE
 PRESCRIPTIVE STRENGTH REQUIREMENTS OF THE FBC AND THE
 FFPC.
  
 12. THE EXTERIOR STAIR DISPLAYED ON PAGE 722 SHALL HAVE
 A MINIMUM OF AT LEAST 10' FROM ANY OPENINGS VERTICALLY
 OR HORIZONTALLY OF THE STAIRS.
  
 13. DUCT SMOKE DETECTORS WHEN ACTIVATED SHALL CAUSE A
 GENERAL ALARM. NOTE 11 ON PAGE E-1 IS INCORRECT.
  
 14. STORAGE AREAS UNDER BLEACHERS SHALL BE FIRE
 SPRINKLER PROTECTED.
  
 15. PLEASE ENSURE THAT PROPER EXIT DISCHARGE IS
 PROVIDED TO ALL EXITS SERVING THE FACILITY.
  
 16. INTERIOR FINISH CLASSIFICATIONS FOR WALLS AND
 CEILINGS SHALL COMPLY WITH THE FBC AND THE FFPC.
  
 17. PLEASE REEVALUATE THE EXIT DISCHARGE DISPLAYED ON
 PAGE 110. NEAR THE TEMPORARY PARTITION A DOUBLE DOOR
 EXITS INTO A SINGLE DOOR. BOTH LOCATIONS HAVE SEPARATE
 OCCUPANT LOADS WHEREBY THE DOUBLE DOORS HAVE A MUCH
 HIGHER EXIT CAPACITY THAN THE SINGLE DOOR.
  
 ON AUGUST 7, 2009, A LETTER IS TO BE PROVIDED REGARDING
 THESE COMMENTS EXCEPT # 17 WHICH WAS THE LAST ONE
 DOCUMENTED.
  
  
 APPROVED PROVISO
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2009-06-01 Cont ID  
Sent By mawillia Date 2009-06-01 Time 15:42 Rev Time 0.00
Received By mawillia Date 2009-06-01 Time 13:01 Sent To  
Notes
2009-06-01 13:04:06REVISIONS, DATED 5/7,8,27/2009, APPROVED
  
  
 REVISED PLAN SHEET E2B, E-4, FP-1 & FP-2, 010 (OF 7 A),
 010 (OF 2-LS), AND 020 (OF 2-LS) WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2009-04-16 Cont ID  
Sent By mawillia Date 2009-04-16 Time 15:55 Rev Time 0.00
Received By mawillia Date 2009-04-16 Time 15:44 Sent To  
Notes
2009-04-16 15:55:20*****REVISION #5, DATED 3/18/2009, APPROVED*****
  
  
 REVISED PLAN SHEET E-4 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2009-03-06 Cont ID  
Sent By mawillia Date 2009-03-06 Time 11:20 Rev Time 0.00
Received By mawillia Date 2009-03-06 Time 10:42 Sent To  
Notes
2009-03-06 11:20:09*****APPROVED*****
  
  
 PLAN SHEETS E-1, E-3, E-4, FP-1, FP-2 WERE RESTAMPED
 FOR APPROVAL ALONG WITH NEWLY STAMPED A.04, AND LS-1
 WHICH WAS PREVIOUSLY STAMPED ON 2/13/09.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-02-13 Cont ID  
Sent By mwennerg Date 2009-02-13 Time 12:32 Rev Time 0.00
Received By mwennerg Date 2009-02-13 Time 12:32 Sent To  
Notes
2009-02-13 12:36:28FIRE PROVISOS
  
 1) NFPA 13, 2002 EDITION SHALL BE REFERENCED.
  
 2) DUCT SMOKE DETECTORS TO INITIATE A GENERAL FIRE
 ALARM.
  
 3) SEPARATE SHOP DRAWINGS/PERMITS FOR FIRE SPRINKLER
 AND FIRE ALARM.
  
 STAMPED SHEETS LS-1, E-1, E-3, E-4, FP-1 AND FP-2.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2009-01-03 Cont ID  
Sent By mawillia Date 2009-01-03 Time 14:57 Rev Time 0.00
Received By mawillia Date 2009-01-03 Time 13:06 Sent To  
Notes
2009-01-03 14:56:26*****DENIED*****
  
 *THE FOLLOWING COMMENTS FROM THE FIRST REVIEW STILL
 NEED TO BE ADDRESSED:
  
 01. THE ADDRESS NUMBER (1590) SHOWN IN THE THE TILE
 BLOCK OF EACH SUBMITTED PLAN SHEET DOES NOT CORRELATE
 WITH THE ADDRESS NUMBER (1600) AS LISTED IN OUR
 COMMUNITYPLUS DATABASE SYSTEM.
  
 04. ONLY ONE FIRE HYDRANT IS SHOWN ON SHEET SP-1, ARE
 ANY ADDITIONAL FIRE HYDRANTS PROPOSED ON THIS
 CAMPUS/SITE? IF NOT, EXPLAIN RATIONALE.
  
 06. IT APPEARS THAT THE BUILDING IS SET OFF OF THE
 ADDRESSED NORTH FLORIDA MANGO ROAD. HOW WILL EMERGENCY
 RESPONDERS AND/OR THE PUBLIC LOCATE THIS STRUCTURE?
  
 12. NFPA 13 2002 EDITION SHALL BE REFERENCED. REVISE
 NOTE 21 ON SHEET FP-1 TO REFLECT AS SUCH.
  
 * THE FOLLOWING NEW COMMENTS ARE TO BE ADDRESSED:
  
 A.) SOME SHEETS IN ONE OF THE PLAN SETS ARE NOT SEALED
 AS PER FLORIDA STATUTE 481.
  
 B.) PLEASE ADDRESS BUILING EXAMINER'S COMMENT #42 IN
 REFERENCE TO TRAVEL DISTANCES AND OTHER ASSOCIATED
 INFORMATION.
  
 C.) A DICREPANCY STILL EXISTS AS TO WHETHER THERE IS A
 MEZZANINE AREA OR NOT. ALL PLANS SHOULD REFLECT THE
 SAME FLOOR LAYOUT.
  
 D.) IF THERE IS A MEZZANINE AREA FOR THIS PROJECT,
 PROVIDE A LAYOUT OF THE FIRE SPRINKLER DEVICES FOR THIS
 AREA.
  
 E.) IF THE PROPERTY IS TO BE EQUIPPED WITH AN ACCESS
 GATE, FIRE DEPARTMENT EMERGENCY ACCESS SHALL BE
 PROVIDED THROUGH THE USE OF AN APPROVED DEVICE OR
 SYSTEM. FOR MORE INFORMATION, CONTACT WEST PALM BEACH
 FIRE PREVENTION BUREAU AT 561-804-4724.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-10-28 Cont ID  
Sent By mawillia Date 2008-10-28 Time 19:47 Rev Time 0.00
Received By mawillia Date 2008-10-28 Time 19:09 Sent To I
Notes
2008-10-28 19:47:34*****DENIED*****
  
 01. THE ADDRESS NUMBER (1590) SHOWN IN THE THE TILE
 BLOCK OF EACH SUBMITTED PLAN SHEET DOES NOT CORRELATE
 WITH THE ADDRESS NUMBER (1600) AS LISTED ON YOUR
 APPLICATION OR IN OUR SYSTEM.
  
 02. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 03. THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE
 WITH EMERGENCY ACCESS TO THE SAID PROPERTY OR THE
 VIOCINITY THEREOF INCLUDING STREETS, ALLEYS, FIRE
 LANES, ETC.
  
 04. ONLY ONE FIRE HYDRANT IS SHOWN ON SHEET LP-1, SRE
 ANY ADDITIONAL FIRE HYDRANTS PROPOSED ON THIS
 CAMPUS/SITE? IF NOT, EXPLAIN RATIONALE.
  
 05. IS THIS PROPOSED STRUCTURE A CHANGE OF OCCUPANCY?
  
 06. IT APPEARS THAT THE BUILDING IS SET OFF OF THE
 ADDRESSED NORTH FLORIDA MANGO ROAD. HOW WILL EMERGENCY
 RESPONDERS AND/OR THE PUBLIC LOCATE THIS STRUCTURE?
  
 07. SHOW/DISPLAY THE APPROPIATE EXTERIOR ELEVATION THE
 NUMERICAL ADDRESS ON THE STRUCTURE OF THE BUILDING. AS
 PER WEST PALM BEACH CODE, THE NUMBERS SHALL BE NO LESS
 THAN 6" IN HEIGHT AND NO LESS THAN 1" IN WIDTH/STROKE.
  
 08. PROVIDE THE PRESCRIPTIVE STRENGHTS FOR THE STAIRS'
 HANDRAILS/GUARDRAILS.
  
 09. SPECIFY THE INTERIOR WALL AND CEILING FINISH
 MATERIAL IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 10. FIRE DOORS AND WINDOWS SHALL COMPLY WITH NFPA 80.
  
 11. WHAT IS THE OCCUPANT LOAD FOR THE PROPOSED
 STRUCTURE?
  
 12. NFPA 13 2002 EDITION SHALL BE REFERENCED. REVISE
 NOTE 21 ON SHEET FP-1 TO REFLECT AS SUCH.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop G GAS REVIEW
Rev No 5 Status P Date 2009-09-03 Cont ID  
Sent By kstevens Date 2009-08-20 Time 16:01 Rev Time 0.00
Received By kstevens Date 2009-08-20 Time 16:00 Sent To  
Notes
2009-09-03 16:01:41REVISION FOR GAS OK -- SHT P-5 (NEW SHEET).

Review Stop G GAS REVIEW
Rev No 4 Status F Date 2009-08-11 Cont ID  
Sent By kstevens Date 2009-08-10 Time 10:23 Rev Time 0.00
Received By kstevens Date 2009-08-07 Time 18:54 Sent To  
Notes
2009-08-11 10:44:51REVISION -DENIED
 REFERENCE:
 FBC-2007 FUEL GAS
  
 ****FROM PREVIOUS REVISION REVIEW:
  
 1. SHT P-5 GAS PIPING SYSTEM (F) INDICATES 20 FEET
 DELVELOPED LENGHT. REVISION ON RISER DIAGRAM INDICATES
 33 FEET TO 35 FEET FROM THE METER TO MOST REMOTE.
 PLEASE CORRLEATE. SECTION 402.4.1.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2009-07-30 Cont ID  
Sent By kstevens Date 2009-07-30 Time 18:21 Rev Time 0.00
Received By kstevens Date 2009-07-30 Time 18:21 Sent To  
Notes
2009-07-30 18:24:52REVISION DENIED
 REFERENCE:
 FBC-2007 FUEL GAS
  
 1. SHT P-5 GAS PIPING SYSTEM (F) INDICATES 20 FEET
 DELVELOPED LENGHT. REVISION ON RISER DIAGRAM INDICATES
 33 FEET TO 35 FEET FROM THE METER TO MOST REMOTE.
 PLEASE CORRLEATE. SECTION 402.4.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2009-01-06 Cont ID  
Sent By kstevens Date 2009-01-06 Time 18:24 Rev Time 0.00
Received By kstevens Date 2008-12-24 Time 17:00 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-10-01 Cont ID  
Sent By kstevens Date 2008-10-01 Time 14:18 Rev Time 0.00
Received By kstevens Date 2008-10-01 Time 14:18 Sent To  
Notes
2008-10-01 14:22:54DENIED
 REFERENCE: FBC-2004 FUEL GAS
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL SHEETS WITH ROCAMAR ENGINEERING SERVICES INC.
 TITLE BLOCK. THE ADDRESS ON THE TITLE BLOCK DOES NOT
 REFLECT THE ADDRESS OF RECORD ON THE STATE OF FLORIDA
 DBPR WEBSITE. (SEE ATTACHED SHEET). PLEASE UPDATE THE
 TITLE BLOCKS OR THE DBPR WEBSITE PRIOR TO RESUBMITTING
 FOR REVIEW SO THE ADDRESS CORRELATES. FAC
 61G15-23.002(2) & FS 471.025.
  
 2. SHT P-1 SHOWS THE GAS LINE TO THE EMERGENCY
 GENERATOR. THE NOTE INDICATES 20 PSI REQUIRED. PLEASE
 CLARIFY. SUBMIT MANUF. SPECIFICATION SHEETS AS WELL AS
 INSTALLATION SHEETS FOR THE GENERATOR SHOWING A LISTING
 FOR THE GENERATOR, INLET PRESSURE & BTU LOAD FOR THE
 GENERATOR. SEPARATE GENERATOR PERMIT REQUIRED. FBC-2004
 FUEL GAS DOES NOT HAVE A TABLE FOR 20 PSI. PLEASE
 SUBMIT AN APPROVED GAS PIPE SIZING TABLE FOR 20 PSI.
 SECTION 402.
  
 3. SHT P-5 THE GAS PIPING, (1-1/2") TO THE GENERATOR
 DOES NOT REFLECT THE GAS PIPING SIZE INDICATED ON SHT
 P-1, (1"). PLEASE CORRELATE. SECTION 402.
  
 4. SHT P-5 SEPARATE GAS PERMIT IS REQUIRED. PLEASE
 SUBMIT THE FOLLOWING INFORMATION FOR EACH GAS SYSTEM:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. (PIPE LENGTHS NOT INDICATED).
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. (20 PSI ON SHT P-1
 BUT .5 PSI ON SHT P-5) CLARIFY EACH SYSTEM.
  
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 **PLEASE SHOW "GAS PIPING SIZED ON FOLLOWING" FOR EACH
 METER/SYSTEM.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 18 Status N Date 2009-11-17 Cont ID  
Sent By dpalmer Date 2009-11-17 Time 15:22 Rev Time 0.00
Received By dpalmer Date 2009-11-17 Time 15:18 Sent To  
Notes
2009-11-17 15:23:02C-38

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2009-10-05 Cont ID  
Sent By lmartine Date 2009-10-05 Time 15:57 Rev Time 0.00
Received By lmartine Date 2009-10-05 Time 15:56 Sent To  
Notes
2009-10-05 16:04:55C--7

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2009-09-21 Cont ID  
Sent By shill Date 2009-09-21 Time 11:55 Rev Time 0.00
Received By shill Date 2009-09-21 Time 11:55 Sent To  
Notes
2009-09-21 11:55:55REVISION TO C8
  

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2009-09-16 Cont ID  
Sent By shill Date 2009-09-16 Time 14:47 Rev Time 0.00
Received By shill Date 2009-09-16 Time 14:47 Sent To  
Notes
2009-09-16 14:48:03STRUCTURAL REVISION, SHEET S8, ROUTED TO ZONING (JR)

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2009-09-14 Cont ID  
Sent By lmartine Date 2009-09-03 Time 08:52 Rev Time 0.00
Received By lmartine Date 2009-09-03 Time 08:51 Sent To  
Notes
2009-09-14 08:57:08C-29
2009-09-14 08:52:25C-30

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2009-09-08 Cont ID  
Sent By jwitmer Date 2009-09-08 Time 11:24 Rev Time 0.00
Received By jwitmer Date 2009-09-08 Time 11:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2009-08-19 Cont ID  
Sent By lmartine Date 2009-08-19 Time 17:42 Rev Time 0.00
Received By lmartine Date 2009-08-19 Time 17:42 Sent To  
Notes
2009-08-31 11:21:08*********MOVED TO C-25******************
2009-08-19 17:44:18C-12********EXPEDITED***************

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2009-08-14 Cont ID  
Sent By lmartine Date 2009-08-14 Time 09:50 Rev Time 0.00
Received By lmartine Date 2009-08-14 Time 09:50 Sent To  
Notes
2009-08-14 09:50:40IN PLUMBING BOX

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2009-08-03 Cont ID  
Sent By lmartine Date 2009-08-03 Time 13:43 Rev Time 0.00
Received By lmartine Date 2009-08-03 Time 13:43 Sent To  
Notes
2009-08-03 13:43:36C-30

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2009-07-20 Cont ID  
Sent By shill Date 2009-07-20 Time 11:16 Rev Time 0.00
Received By shill Date 2009-07-20 Time 11:16 Sent To  
Notes
2009-07-20 11:16:27C 30

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2009-06-05 Cont ID  
Sent By lmartine Date 2009-06-04 Time 13:08 Rev Time 0.00
Received By lmartine Date 2009-06-04 Time 13:08 Sent To  
Notes
2009-06-05 13:12:05PASE 3 STRUCTURAL REVISIONS, PUT IN PLAN REVIEW ROOM
 FOR DOUG LM

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date   Cont ID  
Sent By   Date 2009-05-22 Time   Rev Time 0.00
Received By dwise Date 2009-05-11 Time 19:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2009-04-09 Cont ID  
Sent By adarroug Date 2009-04-09 Time 10:51 Rev Time 0.00
Received By adarroug Date 2009-04-09 Time 10:51 Sent To  
Notes
2009-04-09 10:51:51TO "C50"

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2009-03-24 Cont ID  
Sent By rregueir Date 2009-03-24 Time 14:01 Rev Time 0.00
Received By rregueir Date 2009-03-24 Time 14:00 Sent To E
Notes
2009-03-24 14:01:11SENT TO DVP DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-03-03 Cont ID  
Sent By adarroug Date 2009-03-03 Time 09:33 Rev Time 0.00
Received By adarroug Date 2009-03-03 Time 09:33 Sent To  
Notes
2009-03-03 09:37:19TO "COMM" BD#43

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-02-06 Cont ID  
Sent By adarroug Date 2009-02-06 Time 10:52 Rev Time 0.00
Received By adarroug Date 2009-02-06 Time 10:52 Sent To  
Notes
2009-02-06 10:54:57TO "COMM" BD#19/PLANS ON RACK/3 ROLLS AND PAPERWORK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-12-23 Cont ID  
Sent By adarroug Date 2008-12-23 Time 15:54 Rev Time 0.00
Received By adarroug Date 2008-12-23 Time 15:54 Sent To  
Notes
2008-12-23 15:59:20TO "COMM" BD#63

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-10-29 Cont ID  
Sent By adarroug Date 2008-10-29 Time 15:36 Rev Time 0.00
Received By adarroug Date 2008-09-26 Time 10:50 Sent To  
Notes
2008-09-26 10:59:32TO "COMM" BD#56

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2009-09-08 Cont ID  
Sent By shill Date 2009-09-08 Time 12:09 Rev Time 0.00
Received By shill Date 2009-09-08 Time 12:09 Sent To  
Notes
2009-09-08 12:10:34PLANS RETURNED FROM IMPACT FEE ASSESSMENT
 8178 SF, $0 DUE PER W SWOPE (PLANS STAMPED, NOTE FROM
 IMPACT FEES INCLUED)
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2009-08-06 Cont ID  
Sent By shill Date 2009-08-06 Time 12:20 Rev Time 0.00
Received By shill Date 2009-08-06 Time 12:20 Sent To  
Notes
2009-08-06 12:21:24 
  

Review Stop L LANDSCAPING
Rev No 6 Status P Date 2009-09-29 Cont ID  
Sent By rkussner Date 2009-09-29 Time 09:33 Rev Time 0.00
Received By rkussner Date 2009-09-23 Time 10:14 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 5 Status F Date 2009-04-16 Cont ID  
Sent By rkussner Date 2009-04-16 Time 10:03 Rev Time 0.00
Received By rkussner Date 2009-04-16 Time 10:03 Sent To  
Notes
2009-04-16 10:10:49***REVISION DATED 4/12/2009 FAILED LANDSCAPE REVIEW***
  
 1. CHANGES TO THE SITE LAYOUT SHOWN ON THE PHOTOMETRIC
 PLAN ARE NOT CONSISTENT WITH THE APPROVED SITE PLAN.
 ALL PLANS MUST BE CONSISTENT.
  
 2, THERE ARE CONFLICTS BETWEEN SITE LIGHTING AND
 PROPOSED TREES. ALL SITE LIGHTING LOCATIONS SHALL BE
 SHOWN ON THE LANDSCAPE PLAN TO AVOID SUCH CONFLICTS.
 LIGHT POLES SHALL BE CENTERED BETWEEN TREES AROUND THE
 PERIMETER OF THE SITE. WALL MOUNTED LIGHTING SHALL BE
 UNOBSTRUCTED.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop L LANDSCAPING
Rev No 4 Status P Date 2009-03-05 Cont ID  
Sent By rkussner Date 2009-03-05 Time 15:25 Rev Time 0.00
Received By rkussner Date 2009-03-05 Time 15:25 Sent To Z
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 3 Status F Date 2009-02-18 Cont ID  
Sent By rkussner Date 2009-02-18 Time 14:47 Rev Time 0.00
Received By rkussner Date 2009-02-18 Time 09:15 Sent To PC
Notes
2009-02-18 15:01:07***LANDSCAPE REVIEW FAILED***
  
 1. LANDSCAPE COMMENTS FOR THE FEBRUARY 11TH PPRC
 MEETING HAVE NOT BEEN ADDRESSED. PLEASE REVISE PLAN TO
 ADDRESS ALL COMMENTS AND RESUBMIT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462,

Review Stop L LANDSCAPING
Rev No 2 Status F Date 2009-01-05 Cont ID  
Sent By rkussner Date 2009-01-05 Time 15:19 Rev Time 0.00
Received By rkussner Date 2009-01-05 Time 15:19 Sent To  
Notes
2009-01-05 15:50:37***LANDSCAPE REVIEW FAILED***
  
 1. PURSUANT TO SECTION 94-442 (B)(4), ALL LANDSCAPED
 AREAS AND PLANT MATERIALS WITHIN OR ADJACENT TO
 VEHICULAR USE AREAS SHALL BE PROTECTED FROM VEHICULAR
 ENCROACHMENT BY WHEEL STOPS, CURBS OR OTHER SIMILAR
 DEVICES. THOUGH CURBING WAS SHOWN IN CERTAIN AREAS OF
 THE SITE, OTHER AREAS ARE UNPROTECTED.
  
 2. PURSUANT TO SECTION 94-443 (B)(4), AT LEAST ONE
 SHADE OR FLOWERING TREE SHALL BE PLANTED IN A REQUIRED
 BUFFER STRIP FOR EACH 30 LINEAR FEET OR PORTION
 THEREOF. IN AT LEAST ONE LOCATION ALONG THE SOUTH
 PERIMETER OF THE SITE, AN EXISTING TREE IS BEING
 REMOVED AND THE GAP LEFT BETWEEN TREES WILL BE GREATER
 THAN 30 FEET. PLEASE ADD TREES WHERE NECESSARY ON ALL
 SIDES OF THE SITE TO COMPLY WITH THIS REQUIREMENT.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT A.
 KUSSNER @ (561) 822-1462.

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2008-10-20 Cont ID  
Sent By   Date 2008-10-20 Time   Rev Time 0.00
Received By   Date 2008-10-20 Time   Sent To  
Notes
2008-10-20 13:08:55***LANDSCAPE REVIEW FAILED***
  
 1. PURSUANT TO SECTION 94-441(B), THE LANDSCAPING, TREE
 PROTECTION, AND SCREENING REQUIREMENTS OF ARTICLE XIV
 SHALL APPLY TO ALL DEVELOPMENT WITHIN THE CITY. BECAUSE
 THIS ALTERATION EXCEEDS 50 PERCENT OF THE VALUE OF THE
 STRUCTURE, THE ENTIRE SITE SHALL BE UPGRADED TO MEET
 ALL MINIUM LANDSCAPE STANDARDS.
  
 2. SUBMIT A LANDSCAPE PLAN, SIGNED AND SEALED BY A
 REGISTERED LANDSCAPE ARCHITECT, THAT SHOWS THE ENTIRE
 SITE, AS WELL AS, THE ACCESS WAYS.
  
 3. PROVIDE A XERISCAPE TABLE AND ALL LANDSCAPE
 CALCULATIONS REQUIRED TO COMPLY WITH ARTICLE XIV. THE
 PLAN SHALL INCLUDE A PLANT LIST THAT IDENITIFIES ALL
 EXISTING AND PROPOSED TREES, SHRUBS AND GROUND COVER.
 IT SHALL PROVIDE THE QUANTITY, SIZE AND SPACING OF ALL
 PROPOSED PLANT MATERIAL.
  
 4. PURSUANT TO SECTION 94-444(B), OUTDOOR INCINERATORS,
 GARBAGE OR TRASH RECEPTALCES, FUEL OIL OR PROPANE
 TANKS, AND STORAGE RACKS SHALL NOT BE PERMITTED UNLESS
 APPROPRIATE SCREENING IS PROVIDED. PLEASE INDICATE HOW
 TRASH AND GARBAGE WILL BE COLLECTED AND SHOW HOW IT
 WILL BE SCREENED. THE PROPOSED GENERATOR SHALL ALSO BE
 SCREENED.
  
  
 IF YOU HAVE QUESTIONS REGARDING THE LANDSCAPE COMMENTS,
 PLEASE CONTACT ROBERT KUSSNER @ (561) 822-1462.

Review Stop M MECHANICAL (A/C)
Rev No 11 Status F Date 2009-12-17 Cont ID  
Sent By rregueir Date 2009-12-17 Time 20:31 Rev Time 0.00
Received By rregueir Date 2009-12-17 Time 20:29 Sent To  
Notes
2009-12-17 20:31:21ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 WIND CALCULATIONS FOR OUTDOOR EQUIPMENT SUBMITTED,
 PROVIDE AT LEAST TWO ORIGINAL SIGNED AND SEALED SETS
 FOR BUILDING PLAN REVIEW TO DEMONSTRATE COMPLIANCE WITH
 FBC-M 301.13.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 10 Status P Date 2009-12-17 Cont ID  
Sent By rregueir Date 2009-12-17 Time 20:29 Rev Time 0.00
Received By rregueir Date 2009-12-17 Time 20:27 Sent To  
Notes
2009-12-17 20:29:13REVISED PLANS AS FOLLOWS:
 M-1A DELTA 7
 M-1B DELTA 7
 M-2A DELTA 6
 M-2B DELTA 7
 M-2C DELTA 5
 M-3 DELTA 7
  

Review Stop M MECHANICAL (A/C)
Rev No 9 Status P Date 2009-10-09 Cont ID  
Sent By rregueir Date 2009-10-09 Time 09:48 Rev Time 0.00
Received By rregueir Date 2009-10-09 Time 09:41 Sent To  
Notes
2009-10-09 09:48:50REVISED AS FOLLOWS:
 M1A, M2B, M3 DELTA 7
 M1B DELTA 8
 M2A DELTA 6
 M2C DELTA 3

Review Stop M MECHANICAL (A/C)
Rev No 8 Status P Date 2009-08-27 Cont ID  
Sent By rregueir Date 2009-08-27 Time 17:59 Rev Time 0.00
Received By rregueir Date 2009-08-26 Time 19:44 Sent To  
Notes
2009-08-27 18:00:22REVISED FOR PHASE 2 "PERFORMANCE REVISION"
2009-08-26 19:45:06IN PROGRESS

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2009-08-10 Cont ID  
Sent By rregueir Date 2009-08-10 Time 19:17 Rev Time 0.00
Received By rregueir Date 2009-08-10 Time 18:10 Sent To  
Notes
2009-08-10 19:17:44REVIEW #: 2ND (PHASE 2)
 ACTION: **PASSED WITH PROVISO**
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 2. SUBMITTAL FOR RECIRCULATING SYSTEMS WAS RECEIVED.
 HOWEVER, THE COMMERCIAL KITCHEN AREA STILL REQUIRES AN
 OVERALL EXHAUST RATE OF 0.7 CFM PER SQ FT IN ACCORDANCE
 WITH ASHRAE 62.1-2004 TABLE 6-4. REVISE PLANS
 ACCORDINGLY AND RESUBMIT.
  
 6. WRITTEN RESPONSE INDICATES WIND RESISTANCE FOR
 MECHANICAL APPLIANCES IS A 2007 CODE REQUIREMENT. THIS
 IS INCORRECT. THE SAME REQUIREMENTS ARE IN PLACE UNDER
 THE 2004 FBC. PROVIDE MANUFACTURERS WIND RESISTANCE
 DATA FOR ALL OUTDOOR APPLIANCES IN ACCORDANCE WITH
 FBC-M 2004 EDITION SECTION 301.13.
  
 NOTE: PREVIOUS MECHANICAL PLANS (PAGE M-1 AIR BALANCE
 SCHEDULE) SHOWED A MODULATING 100% OUTSIDE AIR
 DEHUMIDIFACTION UNIT PROVIDING 9000 CFM OUTSIDE AIR IN
 THE SKATING RINK AREA VIA DUCT SOCK. THIS UNIT SHALL
 NOT BE CONSIDERED AS ELIMINATED BASED ON THESE
 REVISIONS. ELIMINATION OF THIS UNIT WOULD LEAVE THE
 RINK AND SPECTATOR AREAS WITHOUT VENTILATION AS
 REQUIRED UNDER ASHRAE 62.1-2004. THIS UNIT IS STILL
 SHOWN ON PERMIT PLANS ON PAGE M-2-IRB.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2009-07-20 Cont ID  
Sent By rregueir Date 2009-07-20 Time 20:06 Rev Time 0.00
Received By rregueir Date 2009-07-20 Time 17:29 Sent To  
Notes
2009-07-20 20:06:00REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. 100% OUTSIDE AIR UNIT AHU-3 SHALL BE PROVIDED WITH A
 MOTORIZED VOLUME DAMPER IN THE OUTSIDE AIR INTAKE DUCT
 IN ACCORDANCE WITH FBC-B 13-409.AB 3.3.
  
 2. CONCESSION AREA REQUIRES COMMERCIAL KITCHEN EXHAUST
 HOOD IF COMMERCIAL COOKING IS TO OCCUR IN THIS AREA IN
 ACCORDANCE WITH FBC-M 507.2. PROVIDE SEPARATE PLANS AND
 PERMIT APPLICATION FOR COMMERCIAL HOOD AND HOOD
 SUPPRESSION SYSTEMS.
  
 3. EF-2 IN ZAMBONI ROOM IS NOT SERVING AS AN EXHAUST
 FAN, BUT AS A SUPPLY FAN. SMOKE DETECTORS SHALL BE
 INSTALLED IN SUPPLY AIR SYSTEMS WITH A DESIGN CAPACITY
 GREATER THAN 2,000 CFM IN ACCORDANCE WITH FBC-M
 606.2.1.
  
 4. SHOW HOW MINIMUM CONTINUOUS VENTILATION RATE OF 0.05
 CFM PER SQ. FT. IS TO BE PROVIDED IN ZAMBONI STORAGE
 ROOM PER FBC-M 404.2.
  
 5. PAGE M-2B SHOWS A 4 INCH VENT TO WALL CAP AND
 REFERENCES A DETAIL ON PAGE M-4. NO SUCH DETAIL COULD
 BE FOUND ON PAGE M-4. PLEASE CLARIFY.
  
 6. ALL OUTDOOR APPLIANCES SHALL BE DESIGNED AND
 INSTALLED FOR WIND RESISTANCE. PROVIDE DATA FROM
 OUTDOOR APPLIANCE MANUFACTURER(S) SHOWING THE OUTDOOR
 APPLIANCES ARE DESIGNED FOR WIND RESISTANCE IN
 ACCORDANCE WITH FBC-M 301.13.
  
 NOTE: THE PHASING ASPECT OF THIS PROPOSED SCOPE OF WORK
 IS NOT CLEAR. SOME AREAS INDICATE THEY ARE EXISTING
 UNDER SEPARATE PERMIT BUT THIS SCOPE IS SUBMITTED AS A
 REVISION TO EXISTING PERMIT WHICH IS STILL OPEN. ANY
 DUPLICATIVE REVIEW OF EXISTING SYSTEMS IS A RESULT OF
 THIS LACK OF CLARITY.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date   Cont ID  
Sent By   Date 2009-05-22 Time   Rev Time 0.00
Received By dwise Date 2009-05-22 Time 19:44 Sent To  
Notes
2009-05-27 19:44:55APPROVED AS NOTED ON PLANS

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2009-03-06 Cont ID  
Sent By rregueir Date 2009-03-04 Time 11:56 Rev Time 0.00
Received By rregueir Date 2009-03-04 Time 11:56 Sent To I
Notes
2009-03-06 11:57:26SENT TO LMARTINEZ FOR PROCESSING

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2009-02-13 Cont ID  
Sent By rregueir Date 2009-02-13 Time 08:00 Rev Time 0.00
Received By rregueir Date 2009-02-12 Time 20:54 Sent To  
Notes
2009-02-13 08:00:32REVIEW #: 3RD
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 PLANS HAVE BEEN REVIEWED FOR CODE COMPLIANCE AND
 STAMPED. HOWEVER, REVIEW WILL REMAIN IN FAIL STATUS
 PENDING RESOLUTION OF THE FOLLOWING:
  
 ENERGY CALCULATIONS: A SYSTEM SIZING SUMMARY HAS BEEN
 PROVIDED IN LIEU OF COOLING LOAD CALCULATIONS. THIS IS
 ACCEPTABLE BUT THE SYSTEM SIZING SUMMARY MUST BE SIGNED
 AND SEALED IN ACCORDANCE WITH FBCB 13-407.1.ABC.1.
  
 ENERGY CALCULATIONS: PLEASE SEE BUILDING AND ELECTRICAL
 COMMENTS. THIS REVIEW WILL REMAIN IN FAIL STATUS UNTIL
 ENERGY CALCULATIONS PASS ALL REVIEWS.
  
 DRYER EXHAUST: DRYER MODEL NUMBER HAS BEEN SHOWN ON
 PLANS AND INSTALLATION INSTRUCTIONS HAVE BEEN PROVIDED.
 DRYER INSTALLATION IS CODE COMPLIANT. HOWEVER, PLEASE
 RPOVIDE THREE COPIES OF THE DRYER SPECS AND
 INSTRUCTIONS TO BE INCLUDED WITH THE THREE PERMIT SETS
 OF PLANS AND SUBMITTALS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-12-28 Cont ID  
Sent By rregueir Date 2008-12-28 Time 11:54 Rev Time 0.00
Received By rregueir Date 2008-12-28 Time 11:53 Sent To  
Notes
2008-12-28 11:54:21REVIEW #: 2ND
 ACTION: DENIED
  
 REVIEWED FOR COMPLIANCE WITH THE FOLLOWING:
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 NOTE: WHILE THIS IS THE SECOND PLAN REVIEW FOR PERMIT,
 THE EXTENT OF DESIGN CHANGES FROM PREVIOUS REVIEW
 (AREAS IDENTIFIED ON PLANS WITH CLOUDS AS HAVING BEEN
 CHANGED) MAKES IT NECESSARY TO REVIEW ALL SYSTEMS AND
 DESIGNS COMPLETELY.
  
 1. ONE SET OF ARCHITECTURAL AND LIFE SAFETY PLAN WERE
 NOT SEALED BY THE ARCHITECT. PLEASE PROVIDE PROPER
 SEAL, SIGNATURE, DATE AND TITLE BLOCK INFORMATION AS
 REQUIRED IN ACCORDANCE WITH FBC 106.1 AND FS 481.
  
 2. PAGE M-4: DETAIL FOR DUCT SMOKE DETECTOR SHOWS THE
 DETECTOR BEING INSTALLED IN THE RETURN AIR SYSTEM. DUCT
 SMOKE DETECTORS SHALL BE INSTALLED IN THE SUPPLY AIR
 SYSTEM IN ACCORDANCE WITH FBCM 606.2.1.
  
 3. PAGE M-2: THERE ARE MULTIPLE UNPROTECTED DUCT
 PENETRATIONS AND AIR TRANSFER OPENINGS SHOWN ON FLOOR
 PLANS AT FIRE RATED WALL PENETRATIONS. EXAMPLES ARE IN
 AREAS SUCH AS THE ADMINISTRATIVE OFFICES, RESTROOMS AND
 ZAMBONI STORAGE ROOM. ONE SET OF PLANS HAS BEEN
 MARKED-UP TO IDENTIFY THESE LOCATIONS. SHOW HOW ALL
 DUCT PENETRATIONS AND AIR TRANSFER OPENING AT RATED
 WALL ASSEMBLIES ARE TO BE PROTECTED IN ACCORDANCE WITH
 FBCM 607.5.
  
 4. PAGES M-1 AND M-2: FLOOR PLAN CALLS FOR RUSKIN MODEL
 #DFSDR1 ROUND FIRE/SMOKE DAMPER AT SEVERAL WALL
 PENETRATIONS. THIS DAMPER IS DESIGNED AND LISTED FOR
 USE AS A CEILING DAMPER AT PENETRATIONS OF HORIZONTAL
 ASSEMBLES SUCH AS TUNNEL CORRIDOR CEILINGS OR AT
 MEMBRANE PENETRATIONS OF FLOOR/CEILING ASSEMBLIES. THEY
 ARE NOT DESIGNED OR INTENDED TO BE INSTALLED AT
 VERTICAL WALL ASSEMBLIES. THERE ARE NO INSTALLATION
 INSTRUCTIONS FOR SUCH AN APPLICATION. FIRE DAMPERS,
 COMBINATION FIRE/SMOKE DAMPERS AND CEILING DAMPERS
 LOCATED WITHIN AIR DISTRIBUTION SHALL BE INSTALLED IN
 ACCORDANCE WITH THE REQUIREMENTS OF THIS SECTION, AND
 THE MANUFACTURER?S INSTALLATION INSTRUCTIONS AND
 LISTING PER FBCM 607.2. PLEASE INDICATE ON PLANS THE
 PROPER DAMPER FOR THE PROPER APPLICATION IN ACCORDANCE
 WITH THEIR LISTING AND THIS SECTION.
  
 5. PAGE M-2: FLOOR PLAN SHOWS AT LEAST ONE DUCT
 PENETRATION BEING PROTECTED BY A FIRE/SMOKE DAMPER
 WHERE NO RATED WALL ASSEMBLY IS SHOWN. AN EXAMPLE WOULD
 BE A 4 INCH ROUND FLEX DUCT PENETRATING A WALL NEAR THE
 LAUNDRY ROOM AT THE ADJACENT CLOSET. PLEASE CONFIRM
 THAT DAMPERS ARE ONLY SHOWN AT RATED WALL ASSEMBLIES IN
 ACCORDANCE WITH THEIR LISTING PER FBCM 607.2.
  
 6. PAGE M-2: FLOOR PLAN SHOWS A 4 INCH ROUND DRYER
 EXHAUST DUCT PENETRATING A RATED WALL ASSEMBLY WITH A
 FIRE/SMOKE DAMPER AT THE PENETRATION. FIRE DAMPERS,
 COMBINATION FIRE/SMOKE DAMPERS AND ANY SIMILAR DEVICES
 THAT WILL OBSTRUCT THE EXHAUST FLOW, SHALL BE
 PROHIBITED IN CLOTHES DRYER EXHAUST DUCTS IN ACCORDANCE
 WITH FBCM 504.2. THIS DUCT PENETRATION CAN BE PROTECTED
 WITH THE THROUGH-PENETRATION FIRESTOP DETAIL WHICH IS
 ALREADY SHOWN ON THE PLANS. PLEASE REMOVE THE DAMPER
 FROM THE PLANS AT THIS LOCATION AND CALL FOR THE
 THROUGH-PENETRATION FIRESTOP SYSTEM TO BE USED AT THIS
 LOCATION.
  
 7. PAGE M-2: FLOOR PLAN SHOWS SEVERAL FLEX DUCTS
 ATTACHING DIRECTLY TO THE FIRE/SMOKE DAMPERS. ACCESS
 DOORS ARE REQUIRED AT THESE LOCATIONS. PLEASE SHOW HOW
 DUCT ACCESS TO THESE DAMPERS IS TO BE PROVIDED IN
 ACCORDANCE WITH FBCM 607.4.
  
 8. PAGE M-2 SHOWS DRYER EXHAUST DUCT EXCEEDING 25 FEET
 IN LENGTH. SHOW HOW EXHAUST DUCT IS TO BE ROUTED AND
 TERMINATED WITH A DEVELOPED LENGTH OF 25 FEET OR LESS
 IN ACCORDANCE WITH FBCM 504.6.1.
 NOTE: THE EXCEPTION TO THIS SYSTEM ALLOWS THE USE OF
 DRYER MANUFACTURER?S INSTALLATION INSTRUCTIONS TO ALLOW
 LENGTHS IN EXCESS OF 25 FEET. DRYER MANUFACTURER?S
 INSTRUCTIONS MAY BE PROVIDED TO DEMONSTRATE COMPLIANCE
 WITH THIS SECTION.
  
 9. PAGE M-2 INDICATES THAT EXHAUST FANS IN THE
 REFRIGERATION MACHINERY ROOM WILL ONLY OPERATE AT FULL
 SPEED UNDER EMERGENCY CONDITIONS. MECHANICAL
 VENTILATION SHALL BE CAPABLE OF EXHAUSTING THE MINIMUM
 QUANTITY OF AIR BOTH AT NORMAL OPERATING AND EMERGENCY
 CONDITIONS IN ACCORDANCE WITH FBCM 1105.6. PLEASE SHOW
 HOW THE REQUIRED MINIMUM VENTILATION RATE OF NOT LESS
 THAN 0.5 CFM PER SQUARE FOOT IS TO BE ACHIEVED IN THE
 REFRIGERATION MACHINERY ROOM IN ACCORDANCE WITH FBCM
 1105.6.3.
  
 10. PAGE M-1: AIR BALANCE SCHEDULE CALLS FOR 9000 CFM
 MAKEUP AIR UNIT. NO INFORMATION COULD BE FOUND ON
 PLANS, EQUIPMENT SCHEDULE OR ENERGY CALCULATIONS FOR
 THIS UNIT. PLEASE PROVIDE LOCATION, INSTALLATION
 DETAIL, INFORMATION ON EQUIPMENT SCHEDULE AND ALL
 RELEVANT INFORMATION ON PLANS AND IN ENERGY
 CALCULATIONS IN ACCORDANCE WITH FBCB 106.1.1, FBCM
 304.1 AND FBCB 13-100.2.
  
 11. PAGE M-5: NOTE 3B.3 AND 3B.4 CALL FOR EXTERIOR
 DUCTWORK ASSOCIATED WITH THE ABOVE MENTIONED MAKEUP AIR
 UNIT. NO SUCH DUCTWORK OR AIR DISTRIBUTION SYSTEM IS
 SHOWN ON PLANS. PLEASE SHOW ALL AIR DISTRIBUTION
 SYSTEMS ON THE PLANS TO DEMONSTRATE COMPLIANCE WITH
 FBCM 603.1. ALSO, PROVIDE INSTALLATION DETAIL AS
 INDICATED IN THE NOTE WITH WIND RESISTANCE INFORMATION
 IN ACCORDANCE WITH FBCM 301.13. ALSO, THIS SECTION
 REQUIRES ALL APPLIANCES AND EQUIPMENT EXPOSED TO WIND
 BE DESIGNED TO RESIST WIND PRESSURES. PROVIDE
 MANUFACTURER?S DATA SHOWING ALL OUTDOOR APPLIANCES ARE
 DESIGNED TO RESIST WIND PRESSURES IN ACCORDANCE WITH
 THIS SECTION.
  
 12. PAGE M-3: CONDENSATE TRAP DETAIL SHOWS A SECONDARY
 DRAIN FROM AN AUXILIARY DRAIN PAN. THIS DETAIL CALLS
 FOR THE SECONDARY DRAIN TO BE ROUTED TO THE ?NEAREST
 WET COLUMN.? IF A SECONDARY DRAIN IS USED, IT SHALL
 DISCHARGE TO A CONSPICUOUS POINT OF DISPOSAL TO ALERT
 OCCUPANTS IN THE EVENT OF A STOPPAGE OF THE PRIMARY
 DRAIN IN ACCORDANCE WITH FBCM 307.2.3(1). THE DETAIL
 ALSO SHOWS A FLOAT SWITCH IN THE AUXILIARY DRAIN PAN.
 THE USE OF A WATER LEVEL DETECTION DEVICE IN THE
 AUXILIARY PAN MAY BE USED IN LIEU OF THE SECONDARY
 DRAIN PER FBCM 307.2.3(3), MAKING THE SECONDARY DRAIN
 LINE UNNECESSARY. PLEASE CLARIFY THE TYPE OF AUXILIARY
 DRAIN PROTECTION TO BE USED AT THE AHUS.
  
 13. THE AREA OF THE SCOPE OF WORK ON PLANS INCLUDES AN
 UNFINISHED SHELL SPACE. THIS SPACE SHALL BE INCLUDED IN
 THE METHOD C ENERGY CALCULATIONS. ALL ASSUMPTIONS MADE
 ABOUT FEATURES NOT INSTALLED UNTIL LATER THAT ARE NOT
 ON THE BUILDING PLANS SHALL BE LISTED AND APPENDED TO
 THE COMPLIANCE FORM SUBMITTED TO THE BUILDING
 DEPARTMENT IN ACCORDANCE WITH FBCB 13-101.1.6. ALSO,
 COOLING LOAD CALCULATIONS OR A SYSTEM SIZING SUMMARY
 SHALL BE APPENDED TO THE ENERGY CALCULATIONS IN
 ACCORDANCE WITH FBCB 13-407.1.ABC.1.
 NOTE: IF A SYSTEM SIZING SUMMARY IS PROVIDED, IT SHALL
 BE SIGNED AND SEALED BY THE DESIGN PROFESSIONAL IN
 ACCORDANCE WITH THIS SECTION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-10-22 Cont ID  
Sent By tgordon Date 2008-10-22 Time 14:32 Rev Time 5.30
Received By tgordon Date 2008-10-22 Time 11:59 Sent To  
Notes
2008-10-22 12:26:39PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) MECHANICAL PLANS M-1 AND M-2 ARE SHOWING DUCTS
 PENETRATING THE 1-HR RATED EGRESS CORRIDOR (SEE PLAN
 LS.01), AT THE WEST SIDE OF THE BUILDING. PER 2004 FBC
 607.5.4 CORRIDORS/SMOKE BARRIERS. A LISTED SMOKE DAMPER
 DESIGNED TO RESIST THE PASSAGE OF SMOKE SHALL BE
 PROVIDED AT EACH POINT A DUCT OR AIR TRANSFER OPENING
 PENETRATES A SMOKE BARRIER WALL OR A CORRIDOR ENCLOSURE
 REQUIRED TO HAVE SMOKE AND DRAFT CONTROL DOORS IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, BUILDING.
 SMOKE DAMPERS AND SMOKE DAMPER ACTUATION METHODS SHALL
 COMPLY WITH SECTION 607.5.4.1. ALSO SEE 2004 FBC
 715.3.3.
  
 2) PLANS SHOW THE DUCTS ALSO PENETRATE FIRE PARTITIONS,
 PLEASE SHOW ON PLANS HOW THE PENETRATIONS ARE BEING
 PROTECTED, PER 2004 FBC/M 607.5.3.
  
 3) PLEASE PROVIDE FOR RETURN AIR TO THE FIRST AID ROOM
 AND BRAKE ROOM ON PLAN M-2, PER 2004 FBC/M 601.4.
  
 4) PLEASE SHOW ON PLANS HOW THE ZAMBONI STORAGE ROOM
 WILL COMPLY WITH 2004 FBC/M 404 ENCLOSED PARKING
 GARAGES.
  
 5) SHOW ON PLANS FOR EQUIPMENT ROOM, COMPLIANCE WITH
 2004 FBC/M 1104.2, 1105 MACHINERY ROOM AND 1106.
  
 6) THE TWO CARRIER A/C SYSTEM MODEL NUMBERS LISTED ON
 THE A/C EQUIPMENT SCHEDULE COULD NOT BE FOUND ON THE
 ARI DIRECTORY WEB-SITE, PLEASE CORRECT, SUBMIT AN ARI
 CERTIFICATE OR MANUFACTURE SPEC. SHEETS, PER 2004 FBC
 13-407.1.ABC.3.1.1 OR 13-607.1.ABC.3.1.1.
  
 7) ONLY ONE OF THE CARRIER A/C SPLIT SYSTEMS ARE LISTED
 ON THE ENERGY CAL'S. PLEASE CORRECT PER 2004 FBC
 13-103.3.
  
 8) THE ARCHITECT OR ENGINEER OF RECORD NEED TO REVIEW
 AND APPROVE THE SHOP DRAWINGS FROM BRR TECHNOLOGIES (A
 SHOP REVIEW STAMP AND SIGNATURE WILL MEET THIS
 REQUIREMENT), SEE 2004 WPB AMEND. 106.3.
  
 9) PLEASE SUBMIT PRODUCT APPROVAL OR AN NOA FOR RUSKIN
 LOUVERS, SEE FS 553.842(1) AND FAC RULE 9B-72,
 9B-72.005, AND FAC 9B-72.010(31)(H).
  
 **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG.
  
 *** PRODUCT APPROVALS SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL (A SHOP REVIEW STAMP AND
 SIGNATURE WILL MEET THIS REQUIREMENT). SEE W.P.B.
 AMEND. 106.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 12 Status F Date 2009-08-29 Cont ID  
Sent By kstevens Date 2009-08-29 Time 17:05 Rev Time 0.00
Received By kstevens Date 2009-08-29 Time 17:05 Sent To  
Notes
2009-08-29 17:10:49REVISIONS DENIED
 REFERENCE:
 FBC-2004 CHAPTER 1
  
 1. SHT P-1 HAS BEEN SUPERCEDED BY A REVISION WITH NEW
 UP TO DATE INFORMATION. SECTION 106.1.3.
  
 2. SHT P-1A IS A SHEET THAT HAS BEEN PREVIOUSLY
 SUBMITTED AND REVIEWED AND IS ON FILE. NO CHANGES
 INDICATED. SECTION 106.1.3.
  
 3. SHT P-1C IS A SHEET THAT HAS BEEN PREVIOUSLY
 SUBMITTED AND REVIEWED AND IS ON FILE. NO CHANGES
 INDICATED. SECTION 106.1.3.
  
 4. SHT P-2B INDICATES A NEW REVISION #6. NO REVISION #6
 WAS FOUND AND NO CHANGES/REVISION WERE LOCATED. SECTION
 106.1.3.
  
 5. SHT P-3A IS A SHEET THAT HAS BEEN PREVIOUSLY
 SUBMITTED AND REVIEWED AND IS ON FILE. NO CHANGES
 INDICATED. SECTION 106.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 11 Status P Date 2009-08-20 Cont ID  
Sent By kstevens Date 2009-08-20 Time 17:35 Rev Time 0.00
Received By kstevens Date 2009-08-20 Time 17:35 Sent To  
Notes
2009-08-20 17:36:38REVISIONS OK -- SHTS P-1, P-1A, P-1B, P-1C, P-2B, P-3A
 & P5

Review Stop P PLUMBING
Rev No 10 Status F Date 2009-08-10 Cont ID  
Sent By kstevens Date 2009-08-10 Time 17:39 Rev Time 0.00
Received By kstevens Date 2009-08-07 Time 18:53 Sent To  
Notes
2009-08-10 17:49:28REVISION DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 1
 FBC-2007 CAHPTER 11
  
 ****FROM PREVIOUS REVISION REVIEW:+
  
 1. OK
 2. OK
 3. OK (DELETED)
  
 4. SHT P-1 3 INCH SANITARY FROM 2ND FLOOR TO DRYWELL IS
 PROHIBITED. SECTION 301.3.
 ****RESPONSE NOTED, BUT THE PIPING STILL IS INDICATED
 AS SANITARY, NOT CONDENSATE ON SHT P-1.
  
 5. OK
 6. OK
 7. OK
  
 8. SHT P-2B INDICATE WHERE THE WATER HEATER PAN DRAIN
 LINE TERMINATES. SECTION 504.7.2.
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED.
  
 9. SHT P-3A THE SANITARY ISOMETRIC RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN, NOR DOES IT MEET CODE.
 PLEASE ADDRESS THE FOLLOWING:
 - THE CLEANOUTS REQUIRED BY SECTIONS 708.3.2 & 708.3.5
 SHOWN ON THE FLOOR PLAN ARE MISSING ON THE RISER.
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED.
 - OK
 - OK
 - OK
 - OK
 PLEASE CORRELATE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 9 Status F Date 2009-07-30 Cont ID  
Sent By kstevens Date 2009-07-30 Time 18:25 Rev Time 0.00
Received By kstevens Date 2009-07-23 Time 18:33 Sent To  
Notes
2009-07-30 18:45:32REVISION DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 1
 FBC-2007 CAHPTER 11
  
 1. SHTS P-1 & P-1B INDICATE WHERE THE SANITARY BUILDING
 DRAIN CONNECTS TO THE BUILDING SEWER FOR THE FIXTURES
 AT THE EQUIPMENT SANITARY. SECTION 701.3.
  
 2. SHTS P-1 & P-1B FITTING FOR FLOOR DRAIN DOWS NOT
 ALLOW THE SEWAGE/WASTE TO BE GUIDED IN THE DIRECTION OF
 FLOW. SECTION 706.3.
  
 3. SHTS P-1 & P-1A GREASE EATING BACTERIA. PLEASE
 SUBMIT MANUF. SPECIFICATION ON SYSTEM. SECTION 106.1.2,
 (MORE INFORMATION REQUIRED).
  
 4. SHT P-1 3 INCH SANITARY FROM 2ND FLOOR TO DRYWELL IS
 PROHIBITED. SECTION 301.3.
  
 5. SUBMIT CALCULATIONS FOR MINIMUM FACILITIES PER
 TABLES 1004.1.1, (BLDG) & 403.1, (PLMG). INDICATE THE
 SQUARE FOOTAGE & OCCUPANCY LOAD FOR ALL OCCUPANCIES,
 ASSEMBLY, BUSINESS, STORAGE ETC. INDICATE THE TOTAL
 OCCUPANCY INCLUDING ALL NEW SEATING. ALSO SHOW POTTY
 PARITY AS REQUIRED IN SECTION 403.1.1.
  
 6. SHT 310 DETAIL #6 BATHROOM TO BE ADAPTABLE. SUBMIT
 INFORMATION ON DETAIL SHOWING ALL BACKING FOR REQUIRED
 GRAB BARS IN THE SHOWER AND AT THE WATER CLOSET
 SECTIONS 11-4.16.4 & 11-4.21.4. INDICATE THE W/C TO BE
 18" OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. (FIG
 28). SHOW THE REQUIRED TURNING AREA IN THE BATHROOM.
 11-4.23.3.
  
 7. SHT P-1A DETAIL 3. INCOMPLETE INFORMATION ON THE
 LEFT SIDE OF DETAIL. PLEASE CLARIFY. SECTIONS 106.1.1 &
 106.1.2.
  
 8. SHT P-2B INDICATE WHERE THE WATER HEATER PAN DRAIN
 LINE TERMINATES. SECTION 504.7.2.
  
 9. SHT P-3A THE SANITARY ISOMETRIC RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN, NOR DOES IT MEET CODE.
 PLEASE ADDRESS THE FOLLOWING:
 - THE CLEANOUTS REQUIRED BY SECTIONS 708.3.2 & 708.3.5
 SHOWN ON THE FLOOR PLAN ARE MISSING ON THE RISER.
 - THE FITTING AT THE JUNCTION OF THE BUILDING DRAIN &
 THE BUILDING SEWER AT THE N.W. CORNER OF THE BUILDING
 DOES NOT GUIDE THE SEWAGE/WASTE IN THE DIRECTION OF
 FLOW. SECTION 706.3.
 - PIPING TO THE W/C & LAV IN THE MEN'S LOCKER ROOM DOES
 NOT REFLECT THE FLOOR PLAN. SECTION 701.1.
 - THE VENT IS MISSING IN ONE GANG SHOWER BUT IS SHOWN
 ON THE FLOOR PLAN. SECTION 901.1.
 - FLOOR DRAINS IN THE GANG BATH ON THE SECOND FLOOR ARE
 SHOWN BETWEEN THE LAST W/C & THE NEXT TO LAST W/C ON
 THE FLOOR PLAN, BUT AFTER ALL W/C'S ON THE RISER
 DIAGRAM. SECTION 701.1. PLEASE CORRELATE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 8 Status P Date   Cont ID  
Sent By   Date 2009-05-22 Time   Rev Time 0.00
Received By dwise Date 2009-05-22 Time 19:48 Sent To  
Notes
2009-05-27 19:43:42REVIEWED BY DOUG WISE. APPROVED AS NOTED ON PLANS.

Review Stop P PLUMBING
Rev No 7 Status F Date 2009-04-10 Cont ID  
Sent By kstevens Date 2009-04-10 Time 19:07 Rev Time 0.00
Received By kstevens Date 2009-04-10 Time 19:07 Sent To  
Notes
2009-04-10 19:11:39DENIED
 REFERENCE:
 FBC-2004 CHAPTER 1
  
 1. SHTS P-2B & P-8 INDICATES REVISION NUMBER 4 IN THE
 REVISION INDEX, BUT NO REVISION NUMBER 4 WAS FOUND ON
 EITHER SHEET. PLEASE CLOUD AND INDICATE THE NEW
 REVISION WITH A REVISION NUMBER. ALSO TO HELP EXPEDITE
 FUTURE REVISION REVIEWS, PLEASE TURN OFF ALL CLOUDS AND
 REVISION NUMBERS FROM PREVIOUSLY APPROVED REVISION.
 (EXAMPLE: REVISION 4 SUBMITTED SO REVISIONS 1, 2 & 3
 CLOUDS AND REVISIONS NUMBERS SHOULD BE TURNED OFF.
 SECTION 106.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 6 Status P Date 2009-04-10 Cont ID  
Sent By kstevens Date 2009-04-10 Time 19:06 Rev Time 0.00
Received By kstevens Date 2009-04-10 Time 19:06 Sent To  
Notes
2009-04-10 19:07:47REVISION OK -- SHT P-6 REVISION #4.

Review Stop P PLUMBING
Rev No 5 Status P Date 2009-03-09 Cont ID  
Sent By lmartine Date 2009-03-09 Time 15:50 Rev Time 0.00
Received By lmartine Date 2009-03-09 Time 15:50 Sent To  
Notes
2009-03-09 15:54:36COMMENTS FROM #3 REVIEW HAVE BEEN ADDRESSED, SEE PERMIT
 APPLICATION.

Review Stop P PLUMBING
Rev No 4 Status F Date 2009-03-04 Cont ID  
Sent By kstevens Date 2009-03-04 Time 17:59 Rev Time 0.00
Received By kstevens Date 2009-03-04 Time 17:59 Sent To  
Notes
2009-03-04 18:02:19PLANS APPROVED. PERMIT TO STAY IN FAILED STATUS UNTIL
 THE COMMENT ABOUT THE APPLICATION HAS BEEN ADDRESSED.

Review Stop P PLUMBING
Rev No 3 Status F Date 2009-02-07 Cont ID  
Sent By kstevens Date 2009-02-07 Time 17:34 Rev Time 0.00
Received By kstevens Date 2009-02-07 Time 17:34 Sent To  
Notes
2009-02-07 17:01:40DENIED
 REFERENCE: FBC-2004 PLUMBIING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 CITY WPB MUNICIPAL CODE
  
 ****FROM PREVIOUS REVIEW:
  
 ******FROM PREVIOUS REVIEWS:
  
 1. OK
 2. OK
  
 3. THE APPLICATION FOR PERMIT ASKS FOR GROSS SQUARE
 FOOTAGE AND WHETHER OR NOT THIS IS A CHANGE OF
 OCCUPANCY. PLEASE INDICATE BOTH ON THE APPLICATION.
 SECTION 105.1.
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED.
 ******RESPONSE NOTED, COMMENT NOT ADDRESSED.
  
 4. OK
 5. OK
 6. OK
 7. OK
 8. OK
 9. OK
 10. OK
 11. OK
 12. OK
 13. OK
 14. OK
 15. OK
 16. OK
 17. OK
 18. OK
 19. OK
 20. OK
 21. OK
 22. OK
 23. OK
 24. OK
  
 ***********NEW COMMENTS***********
 1B. ALL ARCHITECTURAL SHEETS ARE NOT SEALED ONE SET OF
 PLANS. SECTION 106.1.
  
 2B. OK
 3B. OK
 4B. OK
  
 5B. SHT P-7 SANITARY ISOMETRIC RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN AT THE SHOWER IN THE PRIVATE
 BATH, AT THE TOILET ROOM BY COL. LINE F/1 AND CLEANOUTS
 ADDED TO THE FLOOR PLAN IN THE SEWER LINES ARE NOT
 SHOWN ON THE RISER DIAGRAM. PLEASE CORRELATE. SECTION
 106.1.1 AND TABLE 710.1.1.
 ****RESPONSE NOTED, BUT THE PIPING IN THE PRIVATE BATH
 SHOW THE PIPING TO THE LAV INDICATED AT THE WATER
 CLOSET, AND THE PIPING TO THE WATER CLOSET AT THE LAV
 LOCATION. -- THE CLEANOUTS SHOWN ON THE FLOOR PLAN OF
 SHT P-1 ARE STILL NOT SHOWN ON THE SANITARY ISOMETRIC
 RISER DIAGRAM. STILL MISSING ARE THE CLEANOUT ON THE
 NORTH SEWER 100 FEET DOWNSTREAM OF THE TWO WAY CLEANOUT
 NEAR THE JUNCTION OF THE BUILDING DRAIN AND THE
 BUILDING SEWER. THE CLEANOUTS NEAR THE JUNCTIONS OF THE
 BUILDING DRAINS AND THE BUILDING SEWERS, (SECTION
 708.3.5), FOR THE GREASE LINE, THE SANITARY LINE FOR
 THE MECHANICAL FLOOR DRAINS ON THE WEST SIDE, & THE
 SANITARY DRAIN FOR THE MEN'S AND WOMEN'S LOCKER ROOMS.
 ALSO THE CLEANOUTS FOR THE BUILDING SEWER ON THE SOUTH
 SIDE OF THE BUILDING ARE NOT SHOWN, (3). -- NOTE: THE
 CLEANOUT FOR THE NORTH SEWER ON THE FLOOR PLAN SCALES
 OUT OVER 100 FEET ON SHT P-1. PER SECTION 708.3.2
 MAXIMUM 100 FEET BETWEEN CLEANOUTS ON THE BUILDING
 SEWERS.
  
 6B. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ********IMPORTANT NOTE:**********
  
 1C. PLEASE SUBMIT ONE SET OF PREVIOUSLY REVIEWED SHEETS
 AS ALL SHEETS HAVE BEEN REPLACED WITH NEW SHEETS AND IF
 THE PREVIOUSLY REVIEWED SHEETS ARE NOT SUBMITTED FOR
 COMPARISON THEN EACH SHEET WILL HAVE TO BE REVIEWED AS
 A NEW SHEET AND MORE/DIFFERENT COMMENTS MAY BE
 FORTHCOMING. PLEASE SEE PREVIOUS NOTE INDICATING THE
 REQUIREMENT FOR ONE SET OF VOIDED SHEETS.
  
 *******************************************
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2009-01-06 Cont ID  
Sent By kstevens Date 2009-01-06 Time 18:24 Rev Time 0.00
Received By kstevens Date 2008-12-23 Time 17:00 Sent To  
Notes
2009-01-06 18:55:07DENIED
 REFERENCE: FBC-2004 PLUMBIING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 CITY WPB MUNICIPAL CODE
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
 2. OK
  
 3. THE APPLICATION FOR PERMIT ASKS FOR GROSS SQUARE
 FOOTAGE AND WHETHER OR NOT THIS IS A CHANGE OF
 OCCUPANCY. PLEASE INDICATE BOTH ON THE APPLICATION.
 SECTION 105.1.
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED.
  
 4. OK
  
 5. SUBMIT CALCULATIONS FOR MINIMUM FACILITIES PER
 TABLES 1004.1.2 & 403.1. PER TABLE 1004.1.2 THE RINK IS
 50 GROSS. (SHOW GROSS SQUARE FOOTAGE FOR THE RINK.
 PLEASE INDICATE CALCULATIONS FOR OTHER OCCUPANCIES SUCH
 AS BUSINESS & STORAGE. INDICATE THE SQUARE FOOTAGE OF
 EACH AREA ON THE FLOOR PLAN AS WELL AS THE DECK AREA
 AROUND THE RINK.
 ****RESPONSE NOTED, BUT THE NUMBER OF W/C'S FOR THE
 WOMEN SHALL BE CHANGED TO 9. (347 DIVIDED BY 40 EQUALS
 8.675 WHICH SHALL BE ROUNDED UP TO 9). PLEASE CORRECT
 SHT CV.01.
  
 6. OK
 7. OK
 8. OK
  
 9. SHT A.01.1 & A.09 (DETAILS A/A.09, E/A.09, 1/A.09,
 2/A.09, 3/A.09 & 4/A.09). SHOW COMPLIANCE WITH THE
 FOLLOWING:
  
 ___FOR W/C'S:
 A. OK
 B. OK
 C. 11-4.16.5 FLUSH CONTROLS
 ****RESPONSE NOTED, BUT DETAIL 9 ON SHT A.09.1 SHOWS
 THE FLUSH CONTROLS ON THE WALL SIDE. PLEASE CORRECT.
  
 ___FOR LAVS:
 A. OK
 B. OK
 C. OK
 D. OK
  
 10. SHT A.01.1 & A.09 (DETAILS D/A.09, 8/A.09 &
 9/A.09). THE BATHROOM SHALL BE ACCESSIBLE. PLEASE SHOW
 COMPLIANCE WITH THE FOLLOWING:
 ****RESPONSE NOTED, BUT PLANS MUST SHOW THE BACKING FOR
 THE GRAB BARS IN THE SHOWER & W/C, A 5 FOOT TURNING
 AREA, W/C TO BE 18" OFF THE WALL TO THE CENTERLINE OF
 THE FIXTURE, SHOWER CONTROLS AT THE REQUIRED LOCATION &
 A DETAIL FOR THE SHOWER CURB IF INSTALLED TO BE
 ADAPTABLE. NO RESPONSE FOR DETAILS 8/A.09 & 9/A.09.
  
 11. OK
 12. OK
 13. OK
 14. OK
 15. OK
 16. OK
 17. OK
 18. OK
 19. OK
 20. OK
 21. OK
 22. OK
 23. OK
 24. OK
  
 ***********NEW COMMENTS***********
 1B. ALL ARCHITECTURAL SHEETS ARE NOT SEALED ONE SET OF
 PLANS. SECTION 106.1.
  
 2B. SHT A.01 STALL TO BE ACCESSIBLE IN TOILET ROOM AT
 JUNCTION OF COL. LINES B & 2. SECTION 11-4.17.3 & FIG
 30E.
  
 3B. SHT A.09 NOT SUBMITTED BUT STILL SHOWN ON THE INDEX
 OF DRAWINGS. PLEASE CORRELATE. (SHT A.01 REFERENCES
 DETAILS FROM SHT A.09) PLEASE CLARIFY. SECTIONS 106.1.1
 & 106.1.3.
  
 4B. SHT P-1 FITTING ON SEWER LINE FROM TOILET ROOM ON
 THE NORTH SIDE OF THE BUILDING IS SHOWN AGAINST THE
 FLOW. PLEASE CORRECT. SECTION 706.3.
  
 5B. SHT P-7 SANITARY ISOMETRIC RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN AT THE SHOWER IN THE PRIVATE
 BATH, AT THE TOILET ROOM BY COL. LINE F/1 AND CLEANOUTS
 ADDED TO THE FLOOR PLAN IN THE SEWER LINES ARE NOT
 SHOWN ON THE RISER DIAGRAM. PLEASE CORRELATE. SECTION
 106.1.1 AND TABLE 710.1.1.
  
 6. SHT P-7 SANITARY ISOMETRIC RISER DIAGRAM. THE VENT
 FOR THE WASH MACHINE SHALL VENT OFF THE TOP OF THE
 STACK, NOT OUT OF THE LAUNDRY BOX AT THE TOP OF THE
 STANDPIPE AS SHOWN. SECTION 901.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-10-31 Cont ID  
Sent By kstevens Date 2008-10-01 Time 14:58 Rev Time 0.00
Received By kstevens Date 2008-09-29 Time 16:56 Sent To  
Notes
2008-10-01 14:16:35DENIED
 REFERENCE: FBC-2004 PLUMBIING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 CITY WPB MUNICIPAL CODE
  
 1. ALL SHEETS WITH ARCHITECTURAL TITLE BLOCK SHALL
 INCLUDE THE ADDRESS AND FIRM LICENSE NUMBER,
 (CERTIFICATE OF AUTHORIZATION NUMBER), AS REQUIRED IN
 FAC 61G1-16.004(1)(2) & FS 481.219, 481.2055. (SEE
 ATTACHED SHEET).
  
 2. SHT CV.01 STATES "INTENDED TO BE USED AS A PRIVATE
 ENTERTAINMENT FACILITY". PLEASE CLARIFY. ENTERTAINMENT
 FOR WHO? IS THIS A SELECT GROUP OF PEOPLE? IS THIS TO
 BE A TRAINING FACILITY? SECTION 106.1.2 & TABLES
 1004.1.2 & 403.1.
  
 3. THE APPLICATION FOR PERMIT ASKS FOR GROSS SQUARE
 FOOTAGE AND WHETHER OR NOT THIS IS A CHANGE OF
 OCCUPANCY. PLEASE INDICATE BOTH ON THE APPLICATION.
 SECTION 105.1.
  
 4. THE ADDRESS ON THE APPLICATION & IN THE CITY WEBSITE
 IS SHOWN AS 1600 FLORIDA MANGO ROAD, BUT THE PLANS SHOW
 THE ADDRESS AS 1590 FLORIDA MANGO ROAD. THE CORRECT
 ADDRESS SHALL BE INDICATED ON EACH SHEET PER SECTIONS
 106.1.1 & 106.1.3.
  
 5. SUBMIT CALCULATIONS FOR MINIMUM FACILITIES PER
 TABLES 1004.1.2 & 403.1. PER TABLE 1004.1.2 THE RINK IS
 50 GROSS. (SHOW GROSS SQUARE FOOTAGE FOR THE RINK.
 PLEASE INDICATE CALCULATIONS FOR OTHER OCCUPANCIES SUCH
 AS BUSINESS & STORAGE. INDICATE THE SQUARE FOOTAGE OF
 EACH AREA ON THE FLOOR PLAN AS WELL AS THE DECK AREA
 AROUND THE RINK.
  
 6. SHT LP-1 IS NOT SIGNED, SEALED & DATED AS REQUIRED
 IN SECTION 106.1 & FLORIDA STATUTES.
  
 7. SHT A.01 NOTE STATES "DEMO PLAN SUBMITTED UNDER
 SEPARATE PERMIT". DEMO PERMIT NOT FOUND. PLEASE
 INDICATE THE DEMO PERMIT NUMBER FOR REFERENCE. SECTION
 106.1.2 & SECTION 704.5.
  
 8. SHTS A.01.1 & A.09 (DETAILS B/A.09 & C/A.09). SHOW
 THE 5 FOOT TURNING AREA, BACKING FOR THE GRAB BARS AT
 THE W/C AND SHOWER, INDICATE THE LOCATION OF THE
 CONTROLS IN THE SHOWER & SUBMIT A DETAIL FOR THE SHOWER
 CURB, (MAX 1/2" IF INSTALLED, NO CURB REQUIRED).
 SECTIONS 11-4.1.3(11), 11-4.16.4, 11-4.21.4, 11-4.21.5
 & 11-4.21.7.
  
 9. SHT A.01.1 & A.09 (DETAILS A/A.09, E/A.09, 1/A.09,
 2/A.09, 3/A.09 & 4/A.09). SHOW COMPLIANCE WITH THE
 FOLLOWING:
  
 ___FOR W/C'S:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.4 GRAB BARS (INDICATED AS 3'6" AFF IN
 DETAILS 2 & 4.
 C. 11-4.16.5 FLUSH CONTROLS
  
 ___FOR LAVS:
 A. 11-4.19.2 CLEARANCES
 B. 11-4.19.3 CLEAR FLOOR SPACE
 C. 11-4.19.4 EXPOSED PIPES & SURFACES
 D. 11-4.19.5 FAUCETS
  
 10. SHT A.01.1 & A.09 (DETAILS D/A.09, 8/A.09 &
 9/A.09). THE BATHROOM SHALL BE ACCESSIBLE. PLEASE SHOW
 COMPLIANCE WITH THE FOLLOWING:
  
 ___FOR W/C:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.3 HEIGHT
 C. 11-4.16.4 GRAB BARS
 D. 11-4.16.5 FLUSH CONTROLS
 E. 11-4.16.6 DISPENSERS
  
 ___FOR LAV:
 A. 11-4.19.2 HEIGHT & CLEARANCES
 B. 11-4.19.3 CLEAR FLOOR SPACE - FORWARD APPROACH
 REQUIRED (FIG 32)
 C. 11-4.19.4 EXPOSED PIPES & SURFACES
 D. 11-4.19.5 FAUCETS
 E. 11-4.19.6 MIRRORS
  
 ___FOR SHOWER:
 A. 11-4.21.2 SIZE & CLEARANCES
 B. 11-4.21.3 SEAT
 C. 11-4.21.4 GRAB BARS
 D. 11-4.21.5 CONTROLS
 E. 11-4.21.6 SHOWER UNIT
 F. 11-4.21.7 CURBS
  
 11. SHTS A.01 & P.11 (DETAILS 3/A.11 & A/A.11). TOILET
 ROOM SHALL BE ACCESSIBLE. PLEASE SHOW COMPLIANCE WITH
 THE FOLLOWING:
  
 A. 11-4.24.4 SINK DEPTH
 B. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD APPROACH
 REQUIRED - CABINET DOORS NOT APPROVED)
 C. 11-4.24.7 FAUCET
  
 12. ALL SHEETS WITH ROCAMAR ENGINEERING SERVICES INC.
 TITLE BLOCK. THE ADDRESS ON THE TITLE BLOCK DOES NOT
 REFLECT THE ADDRESS OF RECORD ON THE STATE OF FLORIDA
 DBPR WEBSITE. (SEE ATTACHED SHEET). PLEASE UPDATE THE
 TITLE BLOCKS OR THE DBPR WEBSITE PRIOR TO RESUBMITTING
 FOR REVIEW SO THE ADDRESS CORRELATES. FAC
 61G15-23.002(2) & FS 471.025.
  
 13. SHT P-1 MACERATING UNIT. SUBMIT MANUF
 SPECIFICATIONS & INSTALLATION INSTRUCTIONS. NOTE
 INDICATES SEE DETAIL ON SHEET P-3, BUT THE DETAIL JUST
 SHOWS A WEBSITE AND THE WEBSITE WILL NOT OPEN. SECTIONS
 106.1.2 & 712.4.1.
  
 14. SHT P-1 SHOWS AN OIL INTERCEPTOR. THE OIL
 INTERCEPTOR SHALL BE SIZED BY THE UTILITY DEPT.
 INDUSTRIAL PRETREATMENT. PLEASE CONTACT HOLLY MCGRATH
 LABORATORY SUPERVISOR BY PHONE, (561) 822-2271 - OR
 FAX, (561) 822-2279 - OR E-MAIL, [email protected].
 ARTICLE III SECTION 90-124(7).
  
 15. SHT P-1 SHOWS THE GAS LINE TO THE EMERGENCY
 GENERATOR. THE NOTE INDICATES 20 PSI REQUIRED. PLEASE
 CLARIFY. SUBMIT MANUF. SPECIFICATION SHEETS AS WELL AS
 INSTALLATION SHEETS FOR THE GENERATOR SHOWING A LISTING
 FOR THE GENERATOR, INLET PRESSURE & BTU LOAD FOR THE
 GENERATOR. SEPARATE GENERATOR PERMIT REQUIRED. FBC-2004
 FUEL GAS DOES NOT HAVE A TABLE FOR 20 PSI. PLEASE
 SUBMIT AN APPROVED GAS PIPE SIZING TABLE FOR 20 PSI.
 SECTION 402.
  
 16. SHT P-1 CLEANOUTS ARE REQUIRED PER SECTION 708.3.2,
 NOT MORE THAN 100 FEET IN BUILDING SEWERS AND PER
 SECTION 708.3.5 NEAR THE JUNCTION OF THE BUILDING DRAIN
 AND THE BUILDING SEWER. PLEASE SHOW ON THE FLOOR PLAN
 AND ON THE SANITARY RISER DIAGRAM.
  
 17. SHT P-1 SHOWS 1-1/2" MAKE UP WATER TO THE 2ND FLOOR
 MECHANICAL, 1-1/2" MAKE UP WATER FOR SYSTEM FILLING &
 1" HOT WATER FOR ICE MELTING. PLEASE INDICATE THE
 METHOD OF BACKFLOW PROTECTION OF EACH SUPPLY LINE PER
 SECTIONS 608.1 & 608.3. ALSO AN RPZV BACKFLOW IS
 REQUIRED ON THE WATER SERVICE TO THE BUILDING PER
 SECTION 608.13.2. PLEASE INDICATE ON THE PLANS AND ON
 THE WATER ISOMETRIC RISER DIAGRAM SHEET P-7.
  
 18. SHT P-2 PIPING ARRANGEMENT AT THE WATER HEATER.
 PLEASE INDICATE WHERE THE T&P RELIEF VALVE TERMINATES.
 SECTION 504.6.1 -- INDICATE THE MANUFACTURE AND MODEL
 NUMBER FOR THE EXPANSION TANK. SUBMIT CALCULATIONS OR
 MANUF. CHART FOR SIZING THE EXPANSION TANK. SECTION
 607.3.2.
  
 19. SHT P-3 ICE MELTING PIT DRAINAGE DETAIL. PER
 SECTION 712.2 A FULL OPEN VALVE IS REQUIRED ON THE
 DISCHARGE SIDE OF THE CHECK VALVE. -- THE DETAIL
 APPEARS TO SHOW A REDUCTION IN PIPE SIZE IN THE
 DIRECTION OF FLOW. THIS IS NOT APPROVED PER SECTION
 704.2. PLEASE CLARIFY.
  
 20. SHT P-5 INDICATE THE MANUFACTURE AND MODEL NUMBER
 FOR THE EXPANSION TANK. SUBMIT CALCULATIONS OR MANUF.
 CHART FOR SIZING THE EXPANSION TANK. SECTION 607.3.2.
  
 21. SHT P-5 THE GAS PIPING, (1-1/2") TO THE GENERATOR
 DOES NOT REFLECT THE GAS PIPING SIZE INDICATED ON SHT
 P-1, (1"). PLEASE CORRELATE. SECTION 402.
  
 22. SHT P-5 SEPARATE GAS PERMIT IS REQUIRED. PLEASE
 SUBMIT THE FOLLOWING INFORMATION FOR EACH GAS SYSTEM:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. (PIPE LENGTHS NOT INDICATED).
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. (20 PSI ON SHT P-1
 BUT .5 PSI ON SHT P-5) CLARIFY EACH SYSTEM.
  
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 **PLEASE SHOW "GAS PIPING SIZED ON FOLLOWING" FOR EACH
 METER/SYSTEM.
  
 23. SHT P-7 PLUMBING WATER ISOMETRIC RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN. THE WATER SUPPLY PIPING TO
 W/C & LAV IN THE TOILET ROOM BY THE ICE PIT ARE NOT
 SHOWN ON THE ISOMETRIC. PLEASE CORRELATE. SECTIONS
 106.1.1 & 604. -- A SHUT OFF VALVE IS REQUIRED ON THE
 SUPPLY LINE TO THE HOSE BIBB BY THE EQUIPMENT ROOM.
 SECTION 606.2(2).
  
 24. SHT P-7 PLUMBING SANITARY ISOMETRIC RISER DIAGRAM.
 THE FLOOR DRAIN IN THE ROOM ADJACENT TO THE MOP SINK
 ROOM SHALL HAVE A TRAP PRIMER. SECTION 1002.4.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 13 Status P Date 2009-12-09 Cont ID  
Sent By jroach Date 2009-12-09 Time 09:40 Rev Time 0.00
Received By jroach Date 2009-12-09 Time 09:40 Sent To  
Notes
2009-12-09 09:40:40ZONING PLAN REVIEW
  
 PERMIT NO.: 08090611
 ADDRESS: 1590 N. FLORIDA MANGO
 CONTRACTOR/CONTACT: STYLE BUILT CONSTRUCTION
 TELEPHONE NO.: 561.635.6935
 SCOPE OF REVIEW: REVISIONS TO THE FOLLOWING SHEETS:
 M-1A, M-1B, M-2A, M-2B, M-2C, M-3, FP-1, FP-2, FP-3,
 FP-4, E-1, E-2C, E-2D, E-6, ES-1, ES-2
  
 REVIEW STATUS: PASSED WITH PROVISOS
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1) THE INSTALLATION OF THE IRRIGATION PUMP SHALL NOT
 IMPEDE WITH THE INSTALLATION OF THE PROPOSED
 LANDSCAPING. ALL LANDSCAPING SHALL BE INSTALLED IN
 ACCORDANCE WITH THE APPROVED LANDSCAPE PLAN.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  

Review Stop Z ZONING
Rev No 12 Status P Date 2009-12-08 Cont ID  
Sent By jroach Date 2009-12-08 Time 17:41 Rev Time 0.00
Received By jroach Date 2009-12-08 Time 17:41 Sent To B
Notes
2009-12-08 18:41:55ZONING PLAN REVIEW
  
 PERMIT NO.: 08090611
 ADDRESS: 1590 FLORIDA MANGO ROAD
 CONTRACTOR/CONTACT: CHRIS HAIR
 TELEPHONE NO.: 561.362.0220
 SCOPE OF REVIEW: REVISIONS TO SHEETS: T, 001, 010, 212,
 222, 722 (SUBMITTED 11/19/2009)
  
 REVIEW STATUS: ALL REVISED PLANS PASSED.
  
 PLEASE NOTE THAT ALL SITE PLANS, LANDSCAPE PLANS, CIVIL
 PLANS, ETC. WILL NEED TO BE REVISED TO REFLECT THE
 NEWLY-MODIFIED SITE PLAN CONFIGURATION.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM

Review Stop Z ZONING
Rev No 11 Status P Date 2009-10-15 Cont ID  
Sent By jroach Date 2009-10-15 Time 09:16 Rev Time 0.00
Received By jroach Date 2009-10-15 Time 09:16 Sent To  
Notes
2009-10-15 09:23:50ZONING PLAN REVIEW
  
 PERMIT NO.: 08090611
 ADDRESS: 1590 FLORIDA MANGO ROAD
 CONTRACTOR/CONTACT: NAT HEALY
 TELEPHONE NO.: 561.635.6935
 SCOPE OF REVIEW: REVISIONS TO SHEETS: T, 210, 211, 220,
 221, 320, 710, 820, 910, 920, 930, 931, 932, 933, 934,
 940, 941, M-1A, M-1B, M-2A, M-2B, M-2C, M-3, E-2A,
 E-2B, E-2C, E-4B, E-5A, E-5B, ES-1
  
 REVIEW STATUS: ALL REVISED PLANS PASSED, WITH THE
 EXCEPTION TO SHEET ES-1.
  
 PLEASE NOTE THAT THIS REVIEW IS PASSED SUBJECT TO THE
 FOLLOWING PROVISOS:
  
 1) PARKING AREA TO BE INCLUDED IN THIS BUILDING PERMIT.
  
 2) PRIOR TO ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 (CO), THE SUBJECT PROPERTY SHALL BE REPLATTED.
  
 3) PRIOR TO FINAL INSPECTION, SHEETS SP1 AND LP1 SHALL
 BE AMENDED TO REFLECT THE LOCATION OF ALL A/C
 CONDENSING UNITS (I.E. NORTHEAST AND SOUTHWEST CORNERS
 OF THE BLDG).
  
 4) PRIOR TO FINAL INSPECTION, SHEET LP1 SHALL BE
 AMENDED TO PROVIDE LANDSCAPE SCREENING AROUND ALL A/C
 CONDENSING UNITS (I.E. NORTHEAST AND SOUTHWEST CORNERS
 OF THE BLDG).
  
 SHEET ES-1 HAS BEEN FAILED AS THE PROPOSED LOCATION OF
 THE IRRIGATION PUMP DISCONNECT APPEARS TO CONFLICT WITH
 THE PROPOSED LOCATION OF TREES/LANDSCAPING WITHIN THE
 LANDSCAPE ISLAND.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM

Review Stop Z ZONING
Rev No 10 Status P Date 2009-09-22 Cont ID  
Sent By jroach Date 2009-09-22 Time 18:49 Rev Time 0.00
Received By jroach Date 2009-09-22 Time 18:49 Sent To  
Notes
2009-09-22 18:50:25ZONING PLAN REVIEW
  
 PERMIT NO.: 08090611
 ADDRESS: 1590 FLORIDA MANGO ROAD
 CONTRACTOR/CONTACT: NAT HEALY
 TELEPHONE NO.: 561.635.6935
 SCOPE OF REVIEW: RETAINING WALL DETAILS.
  
 REVIEW STATUS: PASSED
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  

Review Stop Z ZONING
Rev No 9 Status P Date 2009-09-22 Cont ID  
Sent By jroach Date 2009-09-22 Time 18:41 Rev Time 0.00
Received By jroach Date 2009-09-22 Time 18:41 Sent To  
Notes
2009-09-22 18:44:32ZONING PLAN REVIEW
  
 PERMIT NO.: 08090611
 ADDRESS: 1590 FLORIDA MANGO ROAD
 CONTRACTOR/CONTACT: NAT HEALY
 TELEPHONE NO.: 561.635.6935
 SCOPE OF REVIEW: PHASE II
  
 REVIEW STATUS: PASSED WITH PROVISOS
  
 PLEASE NOTE THAT THIS REVIEW IS PASSED SUBJECT TO THE
 FOLLOWING PROVISOS:
  
 1) PARKING AREA TO BE INCLUDED IN THIS BUILDING PERMIT.
  
 2) PRIOR TO ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 (CO), THE SUBJECT PROPERTY SHALL BE REPLATTED.
  
 3) PRIOR TO FINAL INSPECTION, SHEETS SP1 AND LP1 SHALL
 BE AMENDED TO REFLECT THE LOCATION OF ALL A/C
 CONDENSING UNITS (I.E. NORTHEAST AND SOUTHWEST CORNERS
 OF THE BLDG).
  
 4) PRIOR TO FINAL INSPECTION, SHEET LP1 SHALL BE
 AMENDED TO PROVIDE LANDSCAPE SCREENING AROUND ALL A/C
 CONDENSING UNITS (I.E. NORTHEAST AND SOUTHWEST CORNERS
 OF THE BLDG).
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM

Review Stop Z ZONING
Rev No 8 Status F Date 2009-08-17 Cont ID  
Sent By jroach Date 2009-08-17 Time 13:46 Rev Time 0.00
Received By jroach Date 2009-08-17 Time 13:46 Sent To  
Notes
2009-08-17 14:59:58ZONING PLAN REVIEW
  
 PERMIT NO.: 08090611
 ADDRESS: 1590 FLORIDA MANGO ROAD
 CONTRACTOR/CONTACT: NAT HEALY
 TELEPHONE NO.: 5613.635.6935
 SCOPE OF REVIEW: PHASE II
  
 REVIEW STATUS: FAILED
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1) IT IS STAFF'S UNDERSTANDING THAT THE UPDATED SITE
 AND LANDSCAPE PLANS, SHOWING THE EXPANDED PARKING LOT,
 ETC., WERE TO BE SUBMITTED AS PART OF PHASE II. NO SUCH
 PLANS HAVE BEEN PROVIDED.
  
 2) THE PHASE II ARCHITECTURAL PLANS INDICATE 8,178
 SQUARE FEET OF MEZZANINE SPACE, WHILE THE SITE PLAN
 SUBMITTED AND APPROVED BY THE PLANNING & ZONING
 DEPARTMENT AS PART OF THE DEVELOPMENT OF SIGNIFICANT
 IMPACT (DSI) WAS ONLY APPROVED FOR 7,864 SQUARE FEET. A
 MINOR AMENDMENT TO THE DSI SHALL BE SUBMITTED TO AND
 APPROVED BY THE PLANNING & ZONING DEPARTMENT PRIOR TO
 ISSUANCE OF THE PERMIT.
  
 3) ARCHITECTURAL PLANS FOR PHASE II INDICATE THAT THE
 PARKING AREA IS UNDER SEPARATE PERMIT.....IN ACCORDANCE
 WITH THE EXISTING BUILDING PERMIT, AS WELL AS STAFF'S
 UNDERSTANDING OF PHASE II, THE PARKING AREA IS TO BE
 INCLUDED AS PART OF THIS PERMIT AND IS TO BE COMPLETE
 PRIOR TO ISSUANCE OF THE FINAL C.O. PLEASE ADJUST PLANS
 ACCORDINGLY.
  
 4) AS SEATING IS NOW BEING PROVIDED WITHIN THE RINK,
 PLEASE ADJUST ALL PARKING COUNTS ACCORDINGLY. BE SURE
 THIS IS INCLUDED AS PART OF THE MINOR DSI AMENDMENT
 DESCRIBED ABOVE.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  

Review Stop Z ZONING
Rev No 7 Status F Date 2009-06-21 Cont ID  
Sent By jroach Date 2009-06-21 Time 14:17 Rev Time 0.00
Received By jroach Date 2009-06-21 Time 14:17 Sent To  
Notes
2009-06-21 14:20:52ZONING PLAN REVIEW
  
 PERMIT NO.: 08090611
 ADDRESS: 1590 FLORIDA MANGO ROAD
 CONTRACTOR/CONTACT: NAT HEALY
 TELEPHONE NO.: 635.6935
 SCOPE OF REVIEW: PHASE III STRUCTURAL REVISIONS.
  
 REVIEW STATUS: FAILED
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1) AS THE PROPOSED ICE RINK USE IS BEING EXPANDED, A
 MINOR AMENDMENT TO THE DEVELOPMENT OF SIGNIFICANT
 IMPACT (DSI) SHALL BE SUBMITTED TO, AND APPROVED BY,
 THE PLANNING AND ZONING DEPARTMENT PRIOR TO FURTHER
 REVIEW OF THE PHASE III PLANS.
  
 2) PLEASE VERIFY WITH THE BULDING PLAN REVIEWER WHETHER
 OR NOT A HANDICAP ACCESSIBLE PARKING SPACE WILL BE
 REQUIRED AT THE ENTRANCE INTO THE NEW SPACE.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1459
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  
  

Review Stop Z ZONING
Rev No 6 Status F Date 2009-04-15 Cont ID  
Sent By jroach Date 2009-04-15 Time 10:53 Rev Time 0.00
Received By jroach Date 2009-04-15 Time 10:53 Sent To  
Notes
2009-04-15 11:00:20ZONING PLAN REVIEW
  
 PERMIT NO.: 08090611
 ADDRESS: 1590 FLORIDA MANGO ROAD
 CONTRACTOR/CONTACT: NAT HEALY
 TELEPHONE NO.: 635.6935
 SCOPE OF REVIEW: REVISION TO THE FOLLOWING SHEETS: E-4,
 E-6, ES-1, E-5, ESP-1, P-2B, P-6, P-8
  
 REVIEW STATUS: FAILED
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1) THE ELECTRICAL SITE PLAN SHOWING THE LOCATION OF THE
 SITE LIGHTING DOES NOT MATCH THAT APPROVED BY
 RESOLUTION NO. 105-09, NOR DOES IT MATCH THE SITE PLAN
 SUBMITTED WITH THE OVERALL BUILDING PERMIT. IF THE SITE
 PLAN IS BEING MODIFIED, A MINOR AMENDMENT TO THE
 DEVELOPMENT OF SIGNIFICANT IMPACT (DSI) SHALL BE
 SUBMITTED TO, AND APPROVED BY, THE PLANNING AND ZONING
 DEPARTMENT PRIOR TO THE APPROVAL OF THE BUILDING
 PERMIT. ONCE THE MINOR AMENDMENT HAS BEEN APPROVED, THE
 OVERALL BUILDING PERMIT WILL NEED TO BE REVISED TO
 REFLECT THE NEW SITE PLAN.
  
 2) SEE LANDSCAPE PLANNER'S COMMENTS REGARDING POTENTIAL
 CONFLICTS BETWEEN SITE LIGHTING AND PROPOSED
 LANDSCAPING.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.
  

Review Stop Z ZONING
Rev No 5 Status P Date 2009-04-01 Cont ID  
Sent By jroach Date 2009-04-01 Time 08:40 Rev Time 0.00
Received By jroach Date 2009-04-01 Time 08:40 Sent To  
Notes
2009-04-01 08:42:07ZONING PLAN REVIEW
  
 PERMIT NO.: 08090611
 ADDRESS: 1590 FLORIDA MANGO ROAD
 CONTRACTOR/CONTACT: NAT HEALY
 TELEPHONE NO.: 561.635.6935
 SCOPE OF REVIEW: REVISION #3 DATED 03/20/09 - SHEETS
 A.01, A01.1,A.02,A.06,A.07,A.10.1
  
 REVIEW STATUS: PASSED
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.
  

Review Stop Z ZONING
Rev No 4 Status P Date 2009-03-05 Cont ID  
Sent By jroach Date 2009-03-05 Time 15:49 Rev Time 0.00
Received By jroach Date 2009-03-05 Time 15:49 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2009-02-17 Cont ID  
Sent By jroach Date 2009-02-17 Time 18:42 Rev Time 0.00
Received By jroach Date 2009-02-17 Time 18:41 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2009-01-02 Cont ID  
Sent By jroach Date 2009-01-02 Time 13:45 Rev Time 0.00
Received By jroach Date 2009-01-02 Time 13:45 Sent To  
Notes
2009-01-02 15:26:20ZONING PLAN REVIEW
  
 PERMIT NO.: 08090611
 ADDRESS: 1590 FLORIDA MANGO ROAD
 CONTRACTOR/CONTACT: NAT HEALY
 TELEPHONE NO.: (561) 635-6935
  
 REVIEW STATUS: FAILED
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 ***FAILED***
  
 THE FOLLOWING COMMENTS WERE NOT ADDRESSED AS PART OF
 THE RESUBMITTAL:
  
 1) TWO (2) COPIES OF A CURRENT/ACCURATE SURVEY SHALL BE
 INCLUDED.
  
 2) AN EASEMENT CONSENT FORM SHALL BE SUBMITTED TO AND
 APPROVED BY THE CITY'S PUBLIC UTILITIES DEPARTMENT, AND
 THEN INCLUDED IN THE PERMIT PACKAGE, FOR THE
 CONSTRUCTION OF THE NEW FENCE. IF THE FENCE WILL BE
 LOCATED WITHIN AN EASEMENT, AN EASEMENT CONSENT FORM
 SHALL BE PROVIDED FROM ALL PRIVATE UTILITY COMPANIES.
  
 3) PLEASE CORRECT AND PROVIDE AN ACCURATE BUILDING
 FOOTPRINT ON THE SITE PLAN. BE SURE TO SHOW THE
 OUTLINES OF AWNINGS, SHUTTERS, CANOPIES, ETC. ON THE
 EXTERIOR OF THE BUILDING. PLEASE PROVIDE DIMENSIONS OF
 SUCH.
  
 THE FOLLOWING COMMENTS ARE NEW AND HAVE BEEN GENERATED
 DUE TO CHANGES TO THE PLAN UPON RESUBMITTAL:
  
 1) ON SHEET SP-1 THE TRANSFORMER ON THE EAST SIDE OF
 THE BUILDING IS LABELED, BUT NOTHING IS SHOWN.
  
 2) ALL LANDSCAPE AREAS ARE TO BE PROTECTED FROM VEHICLE
 ENCROACHMENT BY A TYPE D CURB AND/OR WHEEL STOPS. THE
 SITE PLAN IS UNCLEAR AS TO WHICH AREAS ARE CURBED,
 WHICH ARE NOT, ETC. PLEASE CLEARLY IDENTIFY THOSE AREAS
 THAT ARE CURBED, ETC.
  
 3) IN THE SITE DATA TABLE, PLEASE INDICATED UNDER
 "ADDITIONAL PARKING REQUIRED" WHAT THE ADDITIONAL
 SQUARE FOOTAGE IS AND WHAT PARKING RATIO IS BEING USED
 TO DETERMINED THE REQUIRED NUMBER OF SPACES (1 PER 250
 SQ. FT.).
  
 4) PARKING DETAIL SHALL BE PROVIDED (SEE ATTACHED).
  
 5) A DETAIL OF THE PROPOSED DUMPSTER ENCLOSURE SHALL BE
 PROVIDED. BE SURE TO DIMENSION THE ENCLOSURE ON THE
 SITE PLAN.
  
 6) THE ELECTRICAL SITE PLAN DOES NOT MATCH SHEET SP-1
 (I.E. PARKING AREAS DON'T MATCH, ETC.). ADDITIONALLY,
 SHEET ES-1 SHOWS THE INSTALLATION OF A GATE ON THE EAST
 ACCESS ROAD. THIS IS A SEPARATE PROPERTY AND
 IMPROVEMENTS SHALL NOT CROSS PROPERTY LINES. IF A GATE
 IS TO BE INSTALLED, A UNITY OF TITLE SHALL BE RECORDED
 FOR BOTH PROPERTIES. IF THIS GATE IS PROPOSED TO BE
 MOTORIZED AND OPEN-ON-DEMAND DURING BUSINESS HOURS,
 THEN AT LEAST 100 FEET OF STACKING SHALL BE PROVIDED.
  
 7) PLEASE CLEARLY IDENTIFY ON SHEET SP-1 WHAT IS
 EXISTING, WHAT IS PROPOSED, ETC (I.E. IS THE 6 FOOT
 WOOD FENCE TO THE SOUTH OF THE DRIVEWAY EXISTING? IS
 THE 6 FOOT FENCE ALONG THE WEST PROPERTY LINE EXISTING?
 IS THE 8 FOOT BLOCK WALL ALONG THE SOUTH PROPERTY LINE
 EXISTING?) SOME THINGS ARE UNCLEAR AS TO WHETHER OR NOT
 THEY ARE EXISTING OR PROPOSED. PLEASE CLARIFY
 ACCORDINGLY.
  
 IMPORTANT: THE SITE PLAN SHOULD CLEARLY SHOW WHAT THE
 FINAL PRODUCT WILL LOOK LIKE. SHEET SP-1 CURRENTLY
 SHOWS EXISTING CURBING AND ASHPALT IN AREAS WHERE
 LANDSCAPING IS TO BE PLACED, YET DOES NOT INDICATE
 THEIR REMOVAL, ETC. IDEALLY, THE SITE PLAN WILL SHOW
 THE FINAL PRODUCT WHILE A DEMOLITION PLAN WOULD SHOW
 WHAT IS BEING REMOVED. AS PROVIDED IN THE COMMENT
 ABOVE, BE SURE THE SITE PLAN CLEARLY IDENTIFIES WHAT IS
 EXISTING, PROPOSED, ETC.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2008-10-07 Cont ID  
Sent By jroach Date 2008-10-07 Time 18:52 Rev Time 0.00
Received By jroach Date 2008-10-07 Time 18:52 Sent To  
Notes
2008-10-07 19:25:53***FAILED***
  
 1) PURSUANT TO SECTION 94-441 OF THE CITY'S ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDRS), RENOVATIONS,
 REPAIRS, AND ALTERATIONS WHICH EXCEED 50% OF THE VALUE
 OF THE STRUCTURE ARE REQUIRED TO BRING THE ENTIRE SITE
 INTO CONFORMITY WITH THE CURRENT LANDSCAPE
 REQUIREMENTS. PRIOR TO THE ISSUANCE OF ANY PERMIT, A
 LANDSCAPE PLAN SHOWING COMPLIANCE WITH ARTICLE XIV OF
 THE ZLDRS SHALL BE SUBMITTED AND APPROVED.
  
 2) TWO (2) COPIES OF A CURRENT/ACCURATE SURVEY SHALL BE
 INCLUDED.
  
 3) AN EASEMENT CONSENT FORM SHALL BE SUBMITTED TO AND
 APPROVED BY THE CITY'S PUBLIC UTILITIES DEPARTMENT, AND
 THEN INCLUDED IN THE PERMIT PACKAGE, FOR THE
 CONSTRUCTION OF THE NEW FENCE. IF THE FENCE WILL BE
 LOCATED WITHIN AN EASEMENT, AN EASEMENT CONSENT FORM
 SHALL BE PROVIDED FROM ALL PRIVATE UTILITY COMPANIES.
  
 4) WITH THE INSTALLATION OF THE NEW GATES, THERE SHALL
 BE AT LEAST 100 FEET OF STACKING FROM THE PUBLIC RIGHT
 OF WAY.
  
 5) PLEASE PROVIDE THE DIMENSIONS FROM THE PROPERTY LINE
 TO THE NEW GENERATOR.
  
 6) PURSUANT TO SECTION 94-444(B) OF THE CITY'S ZLDRS,
 GENERATORS SHALL BE SCREENED. SCREENING SHALL CONSIST
 OF BRICK, DECORATIVE CONCRETE, OTHER DECORATIVE
 MASONRY, OR COMPARABLY DURABLE WOOD AND STEEL.
 SCREENING SHALL BE LANDSCAPED WITH SHRUBS AND HEDGES
 PLANTED AT 2-FOOT INTERVALS.
  
 7) PLEASE PROVIDE A DETAIL OF THE PROPOSED FENCE,
 INCLUDING THE PROPOSED HEIGHT. FENCES LOCATED WITHIN
 THE FRONT LANDSCAPE BUFFER (FIRST 5 FEET OF THE
 PROPERTY) SHALL NOT EXCEED 4 FEET IN HEIGHT.
  
 8) THE LANDSCAPE PLAN DOES NOT MATCH THE SITE PLAN
 (I.E. GENERATOR, FENCING, BUILDING FOOTPRINT, ETC.).
  
 9) THE ADDITION OF THE STAIR AND MEZZANINE INSIDE THE
 BUILDING RESULTS IN THE ADDITION OF BUILDING SQUARE
 FOOTAGE. ADDITIONAL PARKING SHALL BE PROVIDED TO
 ACCOMMODATE THE ADDITIONAL SQUARE FOOTAGE.
  
 10) PLEASE CORRECT AND PROVIDE AN ACCURATE BUILDING
 FOOTPRINT ON THE SITE PLAN. BE SURE TO SHOW THE
 OUTLINES OF AWNINGS, SHUTTERS, CANOPIES, ETC. ON THE
 EXTERIOR OF THE BUILDING. PLEASE PROVIDE DIMENSIONS OF
 SUCH.
  
 11) PLEASE PROVIDE A DETAIL OF THE SHUTTERS AND
 DIMENION THE PROJECTION OF SUCH FROM THE EXTERIOR OF
 THE BUILDING.
  
 12) THE LANDSCAPE PLAN SHALL BE SIGNED AND SEALED BY A
 REGISTERED LANDSCAPE ARCHITECT.
  
 13) ARE THE PLANTERS AROUND THE BUILDING EXISTING?
 THESE SHALL BE CURBED (TYPE "D" CURBING) TO PREVENT
 VEHICLE ENCROACHMENT INTO THE PLANTING BEDS.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.