 |
Plan Review Details - Permit 08090593
| Plan Review Stops For Permit 08090593 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
2 |
Status |
P |
Date |
2009-04-06 |
|
|
Cont ID |
|
| Sent By |
jnguyen |
Date |
2009-04-06 |
Time |
16:27 |
Rev Time |
0.00 |
| Received By |
jnguyen |
Date |
2009-04-06 |
Time |
15:23 |
Sent To |
|
|
| Notes |
| 2009-04-06 16:23:30 | I HAVE ANALYZED THE SITE PLANS & CONSULTED WITH JIM | | | WITMER TO PINPOINT THE EXACT LOCATION OF THE | | | FREE-STANDING PAVILION AREA (SLIGHTLY TO THE NORTHEAST | | | OF THE SWA OPERATIONS BUILDING AT 6880 N JOG RD) IN THE | | | EAST PARCEL BOUNDARY. UNDER PCN# 74424227000001010 - | | | SEQUENTIAL UNIT RECORD 0008, I HAVE ASSIGNED THIS | | | PAVILION THE SECONDARY ADDRESS OF 6882 N JOG RD. I | | | NOTIFIED ALL THE RELEVANT PARTIES VIA E-MAIL & HAVE | | | RETURNED THE PERMIT APPLICATION FOLDER & SITE PLANS TO | | | THE BOX. |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
P |
Date |
2008-10-22 |
|
|
Cont ID |
|
| Sent By |
jnguyen |
Date |
2008-10-22 |
Time |
14:46 |
Rev Time |
0.00 |
| Received By |
jnguyen |
Date |
2008-10-22 |
Time |
10:40 |
Sent To |
|
|
| Notes |
| 2008-10-22 14:32:50 | THIS PERMIT# 08090593 IS BEING ATTACHED TO THE WRONG | | | PCN# 74-42-42-34-00-000-1010 WHEN IT ACTUALLY SHOULD BE | | | CONNECTED TO PCN# 74-42-42-27-00-000-1010. I HAVE | | | ISSUED THE EXISTING 6880 N JOG RD TO THE PROPOSED SWA | | | OPERATIONS BUILDING BECAUSE LILI CREATED THIS ADDRESS | | | POINT IN GIS ON 12-20-2007 & LISTED IT FOR THIS | | | SPECIFIC PURPOSE (IN CP LISTED AS UNIT 0006 UNDER THE | | | CORRECT PCN# 74-42-42-27-00-000-1010). I HAVE ALSO | | | ISSUED 6890 N JOG RD FOR THE PROPOSED SWA MAINTENANCE | | | BUILDING (IN CP LISTED AS UNIT 0007 UNDER THE CORRECT | | | PCN# 74-42-42-27-00-000-1010). |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2009-06-03 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-06-03 |
Time |
10:30 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2009-06-03 |
Time |
09:45 |
Sent To |
|
|
| Notes |
| 2009-06-03 10:46:30 | OPERATIONS BUILDING - PASSED | | | 6-03-09 CONTRACTOR HAS SUBMITTED FOR SEPERATE PERMIT | | | FOR THE ; | | | | | | MAINTENACE BUILDING: 09060065 6890 N JOG RD- PASSED | | | | | | PAVILION: 09060067 6882 N JOG RD- DENIED | | | | | | NOTES : COMMENT FOR THE PAVILION FROM THE LAST REVIEW | | | WILL NOW BE TRANSFERRED TO THE NEW PAVILION PERMIT . | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2009-06-01 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-06-01 |
Time |
13:12 |
Rev Time |
0.55 |
| Received By |
jwitmer |
Date |
2009-06-01 |
Time |
13:10 |
Sent To |
|
|
| Notes |
| 2009-06-01 13:15:28 | | | | BUILDING PLAN REVIEW | | | PERMIT: 08090593 | | | ADD: 6880 N JOG RD | | | CONT:WEST CONSTRUCTION | | | TEL: (561)248-3868 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 08090593 6880 N. JOG RD. OFFICE BUILDING TYPE II-B | | | 1,800 SQ FT | | | 6890 N. JOG RD. S-2 MAINTENANCE BUILDING TYPE II-B | | | 1,000 SQ FT | | | 6882 N JOG RD. PAVILION TYPE II-B 728 SQ FT. | | | | | | THE BUILDING OFFICIAL HAS REQUESTED THAT 3 SEPERATE | | | PERMIT APPLICATIONS WITH SEPERATE TRACKING NUMBERS AND | | | ADDREESSES BE ASIGNED TO ALLOW FOR THE MULTIPLE | | | INSPECTIONS THAT WILL BE REQUIRED FOR EACH BUILDING, | | | AND SEPERATE TRACKING OF INSPECTIONS. | | | | | | THE TWO SETS OF PLANS AND BACK UP DOCUMENTATION WILL BE | | | ALL THAT IS NEEDED, THE (MASTER 08090593)) PERMIT | | | NUMBER WILL HAVE ALL THE REVIEW DOCUMENTATION. | | | | | | 1-12) COMPLIED. | | | | | | 13) THIRD REQUEST, 1ST UNDER PERMIT APPLICATION. THE | | | RESPONSE COMMENTS INDICATE THIS TO BE A PAVILION, TO BE | | | PART OF THIS PERMIT WE DO NEED INFORMATION AS FAR AS | | | COMPONENTS AND CLADDING YOU INDICATE THIS IS A | | | PRE-ENGINEERED CANOPY, EITHER IT HAS GONE THROUGH THE | | | MANUFACTURED BUILDING PROGRAM WITH THE STATE AND IS | | | APPROVED AS A MANUFACTURED MODULAR BUILDING PROGRAM | | | WITH STATE APPROVED PLANS OR IT WILL NEED PRODUCT | | | APPROVALS FOR THE ROOFING ASSEMBLY. WITHOUT PLANS THIS | | | AREA WILL BE EXEMPTED FROM THE PERMIT AND PLANS TO BE | | | SUBMITTED UNDER A SEPERATE PERMIT. | | | 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. | | | YOUR RESPONCE AS TO SECTION 503.1.1 DEALS WITH SQUARE | | | FOOTAGE OF FIRE AREA AND THERE NOT BEING REQUIREMENTS | | | FOR RATED WALLS BEING BUILDINGS AND OPENING | | | PROTECTIVES. ONE ISSUE THAT WE HAVE IS WITH NO PLANS, | | | NO STRUCTURAL COLUMNS, BEAMS NOR ROOF SHEATHING IS | | | PROVIDED. THE ROOFING PRODUCT APPROVAL SUBMITTED 2004 | | | FL 3778-R1 | | | IS FOR NON-STRUCTURAL ROOF METAL, REQUIRING | | | SUBSHEATHING DECK. 1507.4.1. | | | | | | 14-17) COMPLIED. | | | | | | 18) 3RD REQUEST. SHEET S-4 INDICATES A FOOTING TYPE A | | | BUT THE PLANS ARE LACKING COLUMN AND BEAM INFORMATION, | | | 1609.2.1 PART OFTHE MAIN WIND FORCE-RESISTING SYSTEM. | | | PLEASE PROVIDE ADDITONAL INFORMATION, 106.1..2. 106.3.5 | | | MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. | | | | | | 19) 3 RD REQUEST, SHEET A-4 ALSO INDICATES THE ROOFING | | | ASSEMBLY TO BE A PREMANUFACTRED CANOPY, PLEASE PROVIDE | | | PRODUCT INFORMATION, TO BE PART OF THIS PERMIT WE DO | | | NEED INFORMATION AS FAR AS COMPONENTS AND CLADDING YOU | | | INDICATE THIS IS A PRE-ENGINEERED CANOPY, EITHER IT HAS | | | GONE THROUGH THE MANUFACTURED BUILDING PROGRAM WITH THE | | | STATE AND IS APPROVED AS A MANUFACTURED MODULAR | | | BUILDING PROGRAM WITH STATE APPROVED PLANS OR IT WILL | | | NEED PRODUCT APPROVALS FOR THE ROOFING ASSEMBLY. | | | WITHOUT PLANS THIS AREA WILL BE EXEMPTED FROM THE | | | PERMIT AND PLANS TO BE SUBMITTED UNDER A SEPERATE | | | PERMIT. 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR | | | BUILDINGS. | | | | | | 20)2 COMPLIED. | | | | | | 21)INFORMATIONAL: GENERATOR PAD IS SHOWN ON SHEET SD-1, | | | IS THIS PAD AND GENERATOR AND ATTACHMENT TO SLAB WILL | | | BE REVIEWED UNDER A SEPERATE PERMIT. 1609.1.3 ANCHORAGE | | | AGAINST OVERTURNING, UPLIFT AND SLIDDING. ANCHORAGE | | | AGAINST OVERTURNING IS NOT THE RESPONSIBILITY OF THE | | | GENERATOR MANUFACTURER BUT THE DESIGNER OF RECORD. | | | | | | 22) STAIR DELETED, COMPLIED. | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | B |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2009-04-06 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-04-06 |
Time |
14:18 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2009-04-06 |
Time |
14:18 |
Sent To |
|
|
| Notes |
| 2009-04-06 14:29:56 | BUILDING PLAN REVIEW | | | PERMIT: 08090593 | | | ADD: 6880 N JOG RD | | | CONT:MAJOR WORKING DRAWING REVIEW | | | TEL: (772)231-4301 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 08090593 6880 N. JOG RD. OFFICE BUILDING TYPE II-B | | | 1,800 SQ FT | | | 6890 N. JOG RD. S-2 MAINTENANCE BUILDING TYPE II-B | | | 1,000 SQ FT | | | 6882 N JOG RD. PAVILION TYPE II-B 728 SQ FT. | | | | | | THE BUILDING OFFICIAL HAS REQUESTED THAT 3 SEPERATE | | | PERMIT APPLICATIONS WITH SEPERATE TRACKING NUMBERS AND | | | ADDREESSES BE ASIGNED TO ALLOW FOR THE MULTIPLE | | | INSPECTIONS THAT WILL BE REQUIRED FOR EACH BUILDING, | | | AND SEPERATE TRACKING OF INSPECTIONS. | | | | | | THE TWO SETS OF PLANS AND BACK UP DOCUMENTATION WILL BE | | | ALL THAT IS NEEDED, THE (MASTER 08090593)) PERMIT | | | NUMBER WILL HAVE ALL THE REVIEW DOCUMENTATION. | | | | | | 1-12) COMPLIED. | | | | | | 13) THIRD REQUEST, 1ST UNDER PERMIT APPLICATION. THE | | | RESPONSE COMMENTS INDICATE THIS TO BE A PAVILION, TO BE | | | PART OF THIS PERMIT WE DO NEED INFORMATION AS FAR AS | | | COMPONENTS AND CLADDING YOU INDICATE THIS IS A | | | PRE-ENGINEERED CANOPY, EITHER IT HAS GONE THROUGH THE | | | MANUFACTURED BUILDING PROGRAM WITH THE STATE AND IS | | | APPROVED AS A MANUFACTURED MODULAR BUILDING PROGRAM | | | WITH STATE APPROVED PLANS OR IT WILL NEED PRODUCT | | | APPROVALS FOR THE ROOFING ASSEMBLY. WITHOUT PLANS THIS | | | AREA WILL BE EXEMPTED FROM THE PERMIT AND PLANS TO BE | | | SUBMITTED UNDER A SEPERATE PERMIT. | | | 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. | | | YOUR RESPONCE AS TO SECTION 503.1.1 DEALS WITH SQUARE | | | FOOTAGE OF FIRE AREA AND THERE NOT BEING REQUIREMENTS | | | FOR RATED WALLS BEING BUILDINGS AND OPENING | | | PROTECTIVES. ONE ISSUE THAT WE HAVE IS WITH NO PLANS, | | | NO STRUCTURAL COLUMNS, BEAMS NOR ROOF SHEATHING IS | | | PROVIDED. THE ROOFING PRODUCT APPROVAL SUBMITTED 2004 | | | FL 3778-R1 | | | IS FOR NON-STRUCTURAL ROOF METAL, REQUIRING | | | SUBSHEATHING DECK. 1507.4.1. | | | | | | 14-17) COMPLIED. | | | | | | 18) 3RD REQUEST. SHEET S-4 INDICATES A FOOTING TYPE A | | | BUT THE PLANS ARE LACKING COLUMN AND BEAM INFORMATION, | | | 1609.2.1 PART OFTHE MAIN WIND FORCE-RESISTING SYSTEM. | | | PLEASE PROVIDE ADDITONAL INFORMATION, 106.1..2. 106.3.5 | | | MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. | | | | | | 19) 3 RD REQUEST, SHEET A-4 ALSO INDICATES THE ROOFING | | | ASSEMBLY TO BE A PREMANUFACTRED CANOPY, PLEASE PROVIDE | | | PRODUCT INFORMATION, TO BE PART OF THIS PERMIT WE DO | | | NEED INFORMATION AS FAR AS COMPONENTS AND CLADDING YOU | | | INDICATE THIS IS A PRE-ENGINEERED CANOPY, EITHER IT HAS | | | GONE THROUGH THE MANUFACTURED BUILDING PROGRAM WITH THE | | | STATE AND IS APPROVED AS A MANUFACTURED MODULAR | | | BUILDING PROGRAM WITH STATE APPROVED PLANS OR IT WILL | | | NEED PRODUCT APPROVALS FOR THE ROOFING ASSEMBLY. | | | WITHOUT PLANS THIS AREA WILL BE EXEMPTED FROM THE | | | PERMIT AND PLANS TO BE SUBMITTED UNDER A SEPERATE | | | PERMIT. 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR | | | BUILDINGS. | | | | | | 20)2 COMPLIED. | | | | | | 21)INFORMATIONAL: GENERATOR PAD IS SHOWN ON SHEET SD-1, | | | IS THIS PAD AND GENERATOR AND ATTACHMENT TO SLAB WILL | | | BE REVIEWED UNDER A SEPERATE PERMIT. 1609.1.3 ANCHORAGE | | | AGAINST OVERTURNING, UPLIFT AND SLIDDING. ANCHORAGE | | | AGAINST OVERTURNING IS NOT THE RESPONSIBILITY OF THE | | | GENERATOR MANUFACTURER BUT THE DESIGNER OF RECORD. | | | | | | 22) STAIR DELETED, COMPLIED. | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2009-01-06 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-01-06 |
Time |
08:39 |
Rev Time |
5.55 |
| Received By |
jwitmer |
Date |
2009-01-05 |
Time |
16:00 |
Sent To |
|
|
| Notes |
| 2009-01-06 09:03:04 | BUILDING PLAN REVIEW | | | PERMIT: 08090593 | | | ADD: 6880 N JOG RD | | | CONT:MAJOR WORKING DRAWING REVIEW | | | TEL: (772)231-4301 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | OFFICE BUILDING TYPE II-B 1,800 SQ FT | | | S-2 MAINTENANCE BUILDING TYPE II-B 1,000 SQ FT | | | | | | JAN 06/2009 | | | 2ND REVIEW | | | ACTION: DENIED | | | | | | 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE | | | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | | | | 1B) PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS, | | | REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR | | | REVIEW FOR PERMIT. IF YOUR PROJECT WILL REQUIRE A | | | RESIDENT INSPECTOR OR IF YOUR PROJECT IS A THRESHOLD | | | BUILDING REQUIRING A THRESHOLD INSPECTOR THEN (3) THREE | | | SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED FOR PERMIT | | | ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS WEST PALM | | | BEACH ADMINISTRATIVE CODE. | | | | | | 1C-1E) COMPLIED. | | | | | | 2) 2ND REQUEST, COMMENT RESPONSE SHEET INDICATES SOILS | | | REPORTS WERE SUBMITTED, NOT IN THIS REVIEW. 1802.2.1 | | | QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING POWER OF | | | THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING VALUE | | | SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE | | | BUILDING OFFICIAL SHALL REQUIRE THAT THE NECESSARY | | | INVESTIGATION BE MADE. SUCH INVESTIGATION SHALL COMPLY | | | WITH THE PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 . | | | | | | 3) COMPLIED, BUILDING PROVISO: 109.3.10* IMPACT OF | | | CONSTRUCTION. | | | | | | 4) COMPLIED, BUILDING PROVISO: 109.3.10.1 HURRICANE | | | PROTECTION. | | | | | | 5) COMPLIED. | | | | | | 6) ENERGY CALCULATION ARE IN THIS SUBMITTAL, BUT ARE | | | THE WRONG VERSION . PLEASE REVIEW SECTION 13-400.3..A. | | | | | | 7-10) THE COUNTY DOES NOT REQUIRE PRODUCT APPROVALS AT | | | TIME OF PERMIT SUBMISSION. THE CITY OF WEST PALM DOES | | | REQUIRE THE FULL PRODUCT APPROVAL PACKAGE, THERE ARE | | | OLD MIAMI-DADE REPORTS THAT STILL HAVE NOT HAD THEIR | | | ANCHOR CALCULATION UPDATED TO THE 2004 FBC, WHICH MEANS | | | UNDER THE 2001 FBC 1.33 INCREASES WERE TAKEN IN STEEL | | | FASTENERS, 1605.3.1.1. AS STATED IN COMMENT (1B) | | | PRODUCT APPROVAL REPORTS ARE REQUIRED AT TIME OF | | | APPLICATION. HIGHLIGHT GLAZING SYSTEM TO BE USED IF | | | THERE IS MULTIPLE GLAZING UNIT TYPES. | | | | | | 7) 2ND REQUEST,1609.1.4 PROTECTION OF OPENINGS IN | | | WIND-BORNE DEBRIS REGIONS, EXTERIOR GLAZING THAT | | | RECEIVES POSITIVE PRESSURE IN THE LOWER 60 FEET (18.3 | | | M) IN BUILDINGS SHALL BE ASSUMED TO BE OPENINGS AND THE | | | BALANCE OF GLAZED OPENINGS IN THE REST OF THE BUILDING | | | SHALL BE ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT | | | RECEIVES POSITIVE PRESSURE IS IMPACT RESISTANT OR | | | PROTECTED WITH AN IMPACT RESISTANT COVERING MEETING THE | | | REQUIREMENTS OF SSTD 12, ASTM E 1886 AND ASTM E 1996, | | | OR MIAMI-DADE TAS 201, 202 AND 203 REFERENCED THEREIN | | | AS FOLLOWS: 1. GLAZED OPENINGS LOCATED WITHIN 30 FEET | | | (9.1 M) OF GRADE SHALL MEET THE REQUIREMENTS OF THE | | | LARGE MISSILE TEST. 2. GLAZED OPENINGS LOCATED MORE | | | THAN 30 FEET (9.1 M) ABOVE GRADE SHALL MEET THE | | | PROVISIONS OF THE SMALL MISSILE TEST. | | | | | | 8)2ND REQUEST, FL BLD CODE 1609.6.2.2 COMPONENTS & | | | CLADDING, PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, | | | MISSING REPORTS ARE AS FOLLOWS: | | | 8A) FIXED WINDOWS | | | 8B) MULLIONS | | | 8C) EXTERIOR GLAZED DOORS | | | 8D) EXTERIOR METAL DOORS | | | 8E) ROLL UP DOORS | | | 8F) WALL LOUVERS | | | 8G) TRUSS ANCHORS | | | 8H) ROOF ASSEMBLIES | | | 8I) SOFFITS | | | | | | 9) 2ND REQUEST, PRODUCT APPROVALS SUBMITTED WITH PERMIT | | | APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO | | | COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR | | | INFORMATION PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE | | | APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER | | | SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, | | | SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR | | | SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT. | | | WWW.FLORIDABUILDING.ORG | | | | | | 10) 2ND EQUEST, WPB ADMIN CODE 106.3* PRODUCT | | | APPROVALS. THOSE PRODUCT WHICH ARE REGULATED BY DCA | | | RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY | | | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR | | | JURISDICTIONAL APPROVAL. | | | | | | OFFICE BUILDING TYPEII-B | | | | | | 11A) COMPLIED. | | | | | | 11B) 2ND REQUEST, SHEET A-11 & SHEET A-14 APPEAR TO | | | HAVE A 2'X2' LAY IN TILE CEILING, PLANS DO NOT PROVIDE | | | HOW THE 1 HOUR RATING OF WALLS IS TO OCCUR, THROUGH TO | | | THE ROOF DECK OR A 1HR RATED CEILING. 708.1. | | | A) YOUR RESPONCE IS CONFUSING, SHEET AD-3, THE NOTE | | | ADDED TO EXTEND DRYWALL AND INSULATION TO THE UNDER | | | SIDE OF THE ROOF DECK DOES NOT TIE TO A WALL TYPE. A | | | GENERIC WALL TYPE IS DEPICTED AND THE | | | NOTE IS NOT LOCATED NEXT TO WALL TYPE 2A A NONRATED | | | WALL NOR NEXT TO 2-1 A 1 HR RATED WALL ASSEMBLY. | | | | | | B) PLEASE PROVIDE THE DETAIL OF HOW THE RATED WALL WILL | | | FASTEN INTO THE ROOF DECK ASSEMLBY, ALSO NOTE WHAT TYPE | | | OF FLEXIBLE SEALENT SHALL BE USED.713.1 FIRE RESISTANT | | | JOINT SYSTEMS. | | | | | | C) THIS SAME CORRIDOR 111 HAS A DOOR# 107 WHICH IS PART | | | OF THE RATED CORRIDOR THE DOOR SCHEDULE DOES NOT | | | INDICATE AS SUCH TABLE 1016.1. | | | | | | D) AD-3 LIFE SAFETY SHEET WILL ALSO NEED TO BE UPDATED | | | FOR A RATED LOBBY WALL AND DOOR 107. | | | | | | E) THE RATING OF CORRIDOR 111 FOR 1 HOUR IS REQUIRED | | | BECAUSE OF THE OCCUPANT LOAD BEING GREATER THAN 30 FOR | | | TRAINING ROOM AND BREAK ROOM WHEN THE FOLDING PARTITION | | | IS NOT USED. IT BECOMES AN | | | ASSEMBLY OCCUPANCY REQUIRING THE CORRIDOR 111TO BE | | | RATED FOR 1 HR. THIS RATING WILL CONTINUE THROUGH TO | | | THE EXIT. THE LOBBY AREA WALL IS NOT INDICATED AS A | | | FIRE RATED WALL. 1016.5CORRIDOR CONTINUITY | | | FIRE-RESISTANCE-RATED CORRIDORS SHALL BE CONTINUOUS | | | FROM THE POINT OF ENTRY TO AN EXIT, AND SHALL NOT BE | | | INTERRUPTED BY INTERVENING ROOMS. EXCEPTION: FOYERS, | | | LOBBIES OR RECEPTION ROOMS CONSTRUCTED | | | AS REQUIRED FOR CORRIDORS SHALL NOT BE CONSTRUED AS | | | INTERVENING ROOMS. THE LOBBY CAN BE USED AS PART OF THE | | | MEANS OF EGRESS BUT THE WALL LABELED 2A WILL NEED TO BE | | | RATED ONE HOUR. | | | | | | F) CORRIDOR 101 IS WITHIN A BUSINESS OCCUPANCY AND WILL | | | NOT BE REQUIRED TO BE 1 HR RATED, IF THE DESIGNER | | | WISHES TO RATE THIS CORRIDOR YOU MAY DO THAT. | | | | | | 11C-D) COMPLIED. | | | | | | 12)2ND REQUEST SHEET A-8 PLEASE PROVIDE COMPLIANCE WITH | | | 11-4.22.2 DOORS. ALL DOORS TO ACCESSIBLE TOILET ROOMS | | | SHALL COMPLY WITH 11-4.13. DOORS SHALL NOT SWING INTO | | | CLEAR FLOOR SPACE REQUIRED FOR ANY FIXTURE. SEE ROOMS | | | 120,& 121. | | | 11-4.1.3(11) TOILET FACILITIES. IF TOILET ROOMS ARE | | | PROVIDED, THEN EACH PUBLIC AND COMMON USE TOILET ROOM | | | SHALL COMPLY WITH SECTION 11-4.22. OTHER TOILET ROOMS | | | PROVIDED FOR THE USE OF OCCUPANTS OF SPECIFIC SPACES | | | (I.E., A PRIVATE TOILET ROOM FOR THE OCCUPANT OF A | | | PRIVATE OFFICE) SHALL BE ADAPTABLE. IF BATHING ROOMS | | | ARE PROVIDED, THEN EACH PUBLIC AND COMMON USE BATHROOM | | | SHALL COMPLY WITH SECTION 11-4.23. ACCESSIBLE TOILET | | | ROOMS AND BATHING FACILITIES SHALL BE ON AN ACCESSIBLE | | | ROUTE. | | | | | | 13) 2ND REQUEST, THE RESPONSE COMMENTS INDICATE THIS TO | | | BE A PAVILION, TO BE PART OF THIS PERMIT WE DO NEED | | | INFORMATION AS FAR AS COMPONENTS AND CLADDING YOU | | | INDICATE THIS IS A PRE-ENGINEERED CANOPY, EITHER IT HAS | | | GONE THROUGH THE MANUFACTURED BUILDING PROGRAM WITH THE | | | STATE AND IS APPROVED AS A MANUFACTURED MODULAR | | | BUILDING PROGRAM WITH STATE APPROVED PLANS OR IT WILL | | | NEED | | | PRODUCT APPROVALS FOR THE ROOFING ASSEMBLY. WITHOUT | | | PLANS THIS AREA WILL BE EXEMPTED FROM THE PERMIT AND | | | PLANS TO BE SUBMITTED UNDER A SEPERATE PERMIT. | | | 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. | | | | | | 15-17) COMPLIED. | | | T THE CONNECTION STATES THAT WELDING OF CONNECTIONS IS | | | PROHIBITED, PLEASE PROVIDE MANUFACTURERS APPROVAL FOR | | | WELDING OF THIS TYPE OF CONNECTION. 106.1.2 ADDITIONAL | | | INFORMATION REQUIRED. | | | | | | 18) 2ND REQUEST. SHEET S-4 INDICATES A FOOTING TYPE A | | | BUT THE PLANS ARE LACKING COLUMN AND BEAM INFORMATION, | | | 1609.2.1 PART OFTHE MAIN WIND FORCE-RESISTING SYSTEM. | | | PLEASE PROVIDE ADDITONAL INFORMATION, 106.1..2. 106.3.5 | | | MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. | | | | | | 19) 2ND REQUEST, SHEET A-4 ALSO INDICATES THE ROOFING | | | ASSEMBLY TO BE A PREMANUFACTRED CANOPY, PLEASE PROVIDE | | | PRODUCT INFORMATION, TO BE PART OF THIS PERMIT WE DO | | | NEED INFORMATION AS FAR AS COMPONENTS AND CLADDING YOU | | | INDICATE THIS IS A PRE-ENGINEERED CANOPY, EITHER IT HAS | | | GONE THROUGH THE MANUFACTURED BUILDING PROGRAM WITH THE | | | STATE AND IS APPROVED AS A MANUFACTURED MODULAR | | | BUILDING PROGRAM WITH STATE APPROVED PLANS OR IT WILL | | | NEED PRODUCT APPROVALS FOR THE ROOFING ASSEMBLY. | | | WITHOUT PLANS THIS AREA WILL BE EXEMPTED FROM THE | | | PERMIT AND PLANS TO BE SUBMITTED UNDER A SEPERATE | | | PERMIT. 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR | | | BUILDINGS. | | | | | | 20)2ND REQUEST, STRUCTURAL SHEETS S-4, S-6 AND S-8 ROOF | | | PRESSURE ZONES FAIL TO INDICATE PRESSURE ZONE 3 FAIL TO | | | INDICATE CORNER ZONE# 3 AND THE ASSOCIATED PRESSURES, | | | PLEASE REVIEW FIGURE 1609.6.2.2 COMPONENTS AND | | | CLADDING. WITH THE RESPONSE FOR THIS COMMENT IT APPEARS | | | THAT YOUR CODE BOOK HAS NOT BEEN UPDATED. IN 2006 | | | SUPPLEMENTS( BLUE PAGES) THE TABLE 1609.6C HAS BEEN | | | ELIMINATED. PLEASE REVISE SHEET S-6 FOR PRESSURES IN | | | ZONE 3. | | | | | | 21) 2ND REQUEST, GENERATOR PAD IS SHOWN ON SHEET SD-1, | | | IS THIS PAD GOING TO BE PART OF THIS PERMIT OR JUST | | | INFORMATIONAL, THE GENERATOR AND ATTACHMENT TO SLAB | | | WILL BE REVIEWED UNDER A SEPERATE PERMIT. PLEASE | | | PROVIDE SIZE OF GENERATOR PAD, IF STELL REINFORCEMENT | | | IS TO BE INSTALLED AND ANCHORS TO RESIST THE MOMENT OF | | | OVER TURNING. 1609.1.3 ANCHORAGE AGAINST OVERTURNING, | | | UPLIFT AND SLIDDING. | | | | | | 22) STAIR DELETED, COMPLIED. | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-10-10 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-10-10 |
Time |
09:41 |
Rev Time |
8.55 |
| Received By |
jwitmer |
Date |
2008-10-10 |
Time |
09:41 |
Sent To |
|
|
| Notes |
| 2008-10-10 12:15:00 | BUILDING PLAN REVIEW | | | PERMIT: 08090593 | | | ADD: 6880 N JOG RD | | | CONT:MAJOR WORKING DRAWING REVIEW | | | TEL: (772)231-4301 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | OFFICE BUILDING TYPE II-B 1,800 SQ FT | | | S-2 MAINTENANCE BUILDING TYPE II-B 1,000 SQ FT | | | | | | OCT 10,2008 | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE | | | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS, | | | PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR | | | SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL | | | REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A | | | THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN | | | (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED | | | FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS | | | WEST PALM BEACH ADMINISTRATIVE CODE. | | | | | | 1C) INFORMATIONAL 106.1.1* W.P.B. ADMINISTRATIVE | | | CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN | | | INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO | | | THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO | | | CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION | | | SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE | | | CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR | | | ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC | | | INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE | | | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND | | | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT | | | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS | | | DETERMINED BY THE BUILDING OFFICIAL. | | | | | | 1D ) BOTH THE ARCHITECTURAL AND STRUCTURAL PLANS | | | INDICATE A PAVILION NEST TO THE ADMINISTRATIVE OFFICE | | | THE PLAN REVIEW SHEET SUBMITTED ONLY INDICATES A REVIEW | | | FOR THE OPERATIONS BUILDING AND MAINTENACE BUILDING . | | | IS THIS STRUCTURE TO BE PERMITTED WITH THIS WORK? IN | | | THE MINIMUM BUILDING CLASSIFICATION TYPE, IS THIS | | | STRUCTURE TO BE CONSIDERED IN THE SQ FT OF THE | | | OPERATIONS BUILDING UNDER SECTION 503.1.3 OR TWO | | | SEPERATE STRUCTURES WHERE TABLE 602 AND 704.8 WILL NEED | | | TO BE CONSIDERED? ADDITIONAL INFORMATION REQUIRED, | | | 106.1.2. | | | | | | 1E) I PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) | | | AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC | | | BUILDING WITH THE 2007 SUPPLEMENTS, PLEASE REVISE. | | | | | | 2) 1802.2.1 QUESTIONABLE SOIL. WHERE THE | | | SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE | | | A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS | | | CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE | | | THAT THE NECESSARY INVESTIGATION BE MADE. SUCH | | | INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF | | | SECTIONS 1802.4 THROUGH 1802.6 . | | | | | | 3) 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION | | | ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A | | | MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF | | | ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO | | | AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY THE | | | APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS | | | AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS | | | INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST, | | | NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE | | | STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION | | | ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE | | | WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY | | | REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH | | | ENGINEERING STANDARDS TO PRESERVE THE | | | POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY, | | | DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW | | | RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS, | | | PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING | | | PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ | | | FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A | | | PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED | | | DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS | | | PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A | | | CERTIFICATION FROM A LICENSED ENGINEER SHALL BE | | | SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL | | | OF THE FINAL INSPECTION. | | | | | | 4) 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE | | | UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED | | | MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR | | | OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS. | | | AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE | | | HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH | | | CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE | | | EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN | | | SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH | | | CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING | | | DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY | | | PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE | | | CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24 | | | HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE | | | SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION TO | | | THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS | | | SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO | | | SECTION 113 OF THIS CHAPTER. | | | | | | 5) NOTE SHEET CD-6 IS NOT SIGNED NOR SEALED, PLEASE | | | CORRECT. SHEET PLANS, SPECIFICATIONS, REPORTS OR OTHER | | | DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING | | | FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND | | | SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE | | | DOCUMENT. | | | FL ADMIN CODE 61G15-23.002 ENGINEERS | | | | | | 6) PLANS DO NOT ENCLUDE ENERGY CALCULATIONS 106.3.5.1.4 | | | AND INPUT ENERGY CALCULATIONS. | | | | | | 7) 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE DEBRIS | | | REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE | | | PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS | | | SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF | | | GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE | | | ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES | | | POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH | | | AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS | | | OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE | | | TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1. | | | GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE | | | SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST. | | | 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M) | | | ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL | | | MISSILE TEST. | | | | | | 8) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, | | | PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING | | | REPORTS ARE AS FOLLOWS: | | | 8A) FIXED WINDOWS | | | 8B) MULLIONS | | | 8C) EXTERIOR GLAZED DOORS | | | 8D) EXTERIOR METAL DOORS | | | 8E) ROLL UP DOORS | | | 8F) WALL LOUVERS | | | 8G) TRUSS ANCHORS | | | 8H) ROOF ASSEMBLIES | | | 8I) SOFFITS | | | | | | 9) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION | | | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE | | | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE | | | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. | | | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT | | | IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT | | | HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR | | | LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE | | | 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 10) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE | | | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | | | | OFFICE BUILDING TYPEII-B | | | | | | 11A) SHEET A3 INDICATES THE CORRIDOR# 111 TO BE ONE | | | HOUR RATED, THERE IS NO DOOR BETWEEN THE CORRIDOR AND | | | LOBBY 100, PLEASE INDICATE HOW OPENING PROTECTIVE | | | (715.3) ARE ACHIEVED IN THIS AREA. | | | | | | 11B) SHEET A-11 & SHEET A-14 APPEAR TO HAVE A 2'X2' LAY | | | IN TILE CEILING, PLANS DO NOT PROVIDE HOW THE 1 HOUR | | | RATING OF WALLS IS TO OCCUR, THROUGH TO THE ROOF DECK | | | OR A 1HR RATED CEILING. 708.1. | | | | | | 11C) SHEET A-4 INDICATES WALL TYPE AS 1 HOUR RATED | | | WALLS WITH WALL TAG (AD3) WITHIN THE CORRIDORS, SHEET | | | AD-1 INDICATES WITHIN THE DOOR LEGOND 45 MINUTE OPENING | | | PROTECTION FOR THE DOORS, DOOR D114 & D115 INDICATE THE | | | WRONG TYPE OF FRAMES, PLEASE CORRECT. | | | | | | 11D) SHEET A-4 CORRIDORS ARE INDICATED AS A 1 HOUR FIRE | | | RATED CORRIDORS BUT THERE IS NO SEPERATION OF THE 1 | | | HOUR RATED CORRIDOE AND THE FILE STORAGE ROOM# 107. | | | | | | 12) SHEET A-8 PLEASE PROVIDE COMPLIANCE WITH 11-4.22.2 | | | DOORS. ALL DOORS TO ACCESSIBLE TOILET ROOMS SHALL | | | COMPLY WITH 11-4.13. DOORS SHALL NOT SWING INTO CLEAR | | | FLOOR SPACE REQUIRED FOR ANY FIXTURE. | | | SEE ROOMS 117, 120, 121, & 1124. | | | | | | 13) SHEET A-14 THE REFLECTED CEILING PLAN INDICATES A | | | LARGE SQUARE TO THERIGHT OF THE RIGHT OF THE KITCHEN | | | AND MECANICAL ROOM 24'X30' WITH 3 LIGHT FIXTURES? SHEET | | | E-5 THIS AREA APPEARS EITHER AS ANOTHER | | | BUILDING OR A OPEN PAVILION,(SHEET S2-S3) IS THIS | | | STRUCTURE TO BE PART OF THIS PERMIT? ARE THEY TO | | | REQUIRE FIRE SEPERATION BETWEEN THE TWO BUILDINGS TABLE | | | 602, OR ARE THEY TO BE CONSIDEREDAS ONE BUILDING AS | | | UNDER SECTION 503.1.3 TWO BUILDINGS ON THE SAME LOT. | | | | | | 14) SHEET A-7 INDICATES A BRICK VENNEER PLEASE PROVIDE | | | DOCUMENTATION AS HOW THE VENEERS ARE TO BE ADHERRED. | | | PLEASE SEE SECTION 2114.2 CONCRETE BEARING LEDGE. | | | BRICK, STONE OR OTHER VENEER SHALL BE SUPPORTED BY A | | | CONCRETE BEARING LEDGE AT LEAST EQUAL TO THE TOTAL | | | THICKNESS OF THE BRICK, STONE OR OTHER VENEER, WHICH IS | | | POURED INTEGRALLY WITH THE CONCRETE FOUNDATION. NO | | | SUPPLEMENTAL CONCRETE FOUNDATION POURS WHICH WILL | | | CREATE A HIDDEN COLD JOINT SHALL BE USED WITHOUT | | | SUPPLEMENTAL TREATMENT IN THE FOUNDATION UNLESS THERE | | | IS AN APPROVED PHYSICAL BARRIER. AN APPROVED PHYSICAL | | | BARRIER SHALL ALSO BE INSTALLED FROM BELOW THE WALL | | | SILL PLATE OR FIRST BLOCK COURSE HORIZONTALLY TO EMBED | | | IN A MORTAR JOINT. IF MASONRY VENEER EXTENDS BELOW | | | GRADE, A TERMITE PROTECTIVE TREATMENT MUST BE APPLIED | | | TO THE CAVITY CREATED BETWEEN THE VENEER AND THE | | | FOUNDATION, IN LIEU OF A PHYSICAL BARRIER. | | | EXCEPTION: VENEER SUPPORTED BY A SHELF, ANGLE OR LINTEL | | | SECURED TO THE FOUNDATION SIDEWALL IN ACCORDANCE WITH | | | ACI 530/ASCE 5/TMS 402, PROVIDED AT LEAST A 6-INCH (152 | | | MM) CLEAR INSPECTION SPACE OF THE FOUNDATION SIDEWALL | | | EXTERIOR EXIST BETWEEN THE VENEER AND THE TOP OF ANY | | | SOIL, SOD, MULCH OR OTHER ORGANIC LANDSCAPING | | | COMPONENT, DECK, APRON, PORCH, WALK OR ANY OTHER WORK | | | IMMEDIATELY ADJACENT TO OR ADJOINING THE STRUCTURE. | | | | | | 15) SHEET S-2 DOES NOT INDICATE COMPLIANCE WITH 1816.1 | | | TERMITE PROTECTION. | | | | | | 16) SHEET S-3 INDICATES THE TYPE OF CONNECTION TO BE | | | USED AT EACH TRUSS LOCATION BUT THE FORCES THE | | | CONNECTION NEEDS TO RESIST IS NOT PROVIDED, VERTICAL, | | | HORIZONTAL AND LATERALL LOADS. 1609.2.1. | | | PART OF THE MAIN WINDFORCE-RESISING SYSTEM. NOTE | | | CONNECTION TYPE TS1WTCS INFORMATION COULD NOT EVEN BE | | | ACCESSED ON THE TRUSSTEEL WEBSITE. | | | | | | 17) SHEET S-3 TRUSS NOTE# 5 INDICATES TO SEE TRUSSSTEEL | | | STANDARD DETAIL TS027A FOR THE WELDING OF TRUSS | | | CONNECTION TO STEEL BEAM, NO SUCH DETAILS HAVE BEEN | | | PROVIDED. NOTE IN MANY CASES | | | THE MANUFACTURER OF THE CONNECTION STATES THAT WELDING | | | OF CONNECTIONS IS PROHIBITED, PLEASE PROVIDE | | | MANUFACTURERS APPROVAL FOR WELDING OF THIS TYPE OF | | | CONNECTION. 106.1.2 ADDITIONAL INFORMATION REQUIRED. | | | | | | 18) SHEET S-4 INDICATES A FOOTING TYPE A BUT THE PLANS | | | ARE LACKING COLUMN AND BEAM INFORMATION, 1609.2.1 PART | | | OFTHE MAIN WIND FORCE-RESISTING SYSTEM. PLEASE PROVIDE | | | ADDITONAL INFORMATION, 106.1..2. | | | | | | 19) SHEET A-4 ALSO INDICATES THE ROOFING ASSEMBLY TO BE | | | A PREMANUFACTRED CANOPY, PLEASE PROVIDE PRODUCT | | | INFORMATION, WILL NEED TO MEET THE REQUIREMENTS OF | | | COMMENT NUMBER 8,9 & 10. | | | | | | 20) STRUCTURAL SHEETS S-4, S-6 AND S-8 ROOF PRESSURE | | | ZONES FAIL TO INDICATE PRESSURE ZONE 3 FAIL TO INDICATE | | | CORNER ZONE# 3 AND THE ASSOCIATED PRESSURES, PLEASE | | | REVIEW FIGURE 1609.6.2.2 COMPONENTS AND CLADDING. | | | | | | 21) GENERATOR PAD IS SHOWN ON SHEET SD-1, IS THIS PAD | | | GOING TO BE PART OF THIS PERMIT OR JUST INFORMATIONAL, | | | THE GENERATOR AND ATTACHMENT TO SLAB WILL BE REVIEWED | | | UNDER A SEPERATE PERMIT. | | | | | | 22) SD-3 PLANS INDICATE STAIRS BUT THE STAIR LOCATION | | | IS NOT SHOWN ON THE ARCHITECTURAL PLANS NOR THE | | | STRUCTURAL PLAN INDICATES THEY ARE TO BE LOCATED WITHIN | | | THE OPERATIONS AND MAINTENANCE BUILDING, WHERE / | | | | | | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A | | | RESULT OF THE ADDITIONAL INFORMATION REQUESTED | | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | | THIS REVIEW. | | | | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2009-05-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-05-29 |
Time |
10:13 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-05-29 |
Time |
10:13 |
Sent To |
|
|
| Notes |
| 2009-05-29 10:14:04 | *** NOTES/ REDLINES**** | | | | | | 1) NOTE: MANUFACTURES SPECS/CUT SHEETS WERE SUBMITTED | | | FOR THREE COMPLETELY DIFFERENT TRANSFER SWITCHES. | | | A) ONE AS AUTOMATIC NON SERVICE ENTRANCE RATED. | | | B) ONE FOR NON-AUTOMATIC, MTS. | | | C) ONE FOR SERVICE ENTRANCE RATE AUTOMATIC TRANSFER | | | SWITCH. | | | | | | AS THE RISER INDICATES AND REQUIRES THE SWITCH TO BE | | | SERVICE ENTRANCE RATED ONLY *(C) * ABOVE MEETS AND | | | COORDINATES WITH RISER. | | | | | | THE SPECS/CUT SHEETS FOR BOTH A AND B WAS REMOVED FROM | | | SETS TO ALLEVIATE ANY CONFUSION. | | | | | | 2) NOTED FOR INFORMATION. THE NEW BUILDING OFFICIAL | | | WILL BE REQUIRING THE MAINTENANCE/OPERATION BUILDING TO | | | BE UNDER SEPARATE PERMIT. THE SAME PLANS WILL BE USED , | | | HOWEVER WILL NEED SEPARATE APPLICATION. PLEASE CONTACT | | | DOUGLAS WISE FOR ANY QUESTIONS. 561-805-6654 | | | | | | 3) NOTE: GATE SHALL BE UNDER SEPARATE FENCE PERMIT | | | ALONG WITH PLANS. | | | | | | 4) NOTE: LOW VOLTAGE SYSTEMS SUCH AS DATE, PHONE, AND | | | CAMERAS ALL SHALL BE UNDER SEPARATE PERMITS. ** MAY | | | REFERENCE THESE PLANS IF NO CHANGES ARE MADE. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2009-03-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-03-30 |
Time |
10:48 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-03-30 |
Time |
10:48 |
Sent To |
|
|
| Notes |
| 2009-03-30 10:48:38 | ** DENIED REVIEW ** | | | 3RD REVIEW, 1ST REVIEW UNDER PERMIT APPLICATION. | | | | | | | | | 1) NOTE: PLEASE BE SURE ALL INFORMATION ON THE INPUT | | | DATA REPORT OF THE SUBMITTED ENERGY CALCULATIONS | | | COORDINATES WITH THE PLANS. THIS HAS BEEN NOTED FOR THE | | | THIRD TIME. 13-415.2, 13-415.2.ABC.1.1, .1.2 AND .1.3. | | | PREVIOUS REVIEW GAVE SOME EXAMPLES OF ITEMS ON PLANS | | | WHICH WERE NOT IN THE IDR. THE EXTERIOR LIGHTING WAS | | | NOTED AS AN EXAMPLE; HOWEVER THERE IS A SUBSTANTIAL | | | AMOUNT OF EXTERIOR FIXTURES ON PLANS WHICH ARE STILL | | | NOT IN THE IDR. | | | FOR EXAMPLE: WHAT ABOUT ALL THE LIGHTING ON SHEET E-2? | | | | | | FOR EXAMPLE: THE IDR SHOWS MANUAL CONTROLS FOR ALL | | | INTERIOR LIGHTING. PLANS DO NOT SHOW THE SAME. | | | | | | FOR EXAMPLE: THE M FIXTURE ON THE FIXTURE LEGEND IS | | | SHOWN WITH 2-42WATT BULBS YET THE IDR ONLY INDICATES | | | ONE -42WATT BULB IN EACH FIXTURE. | | | THE M FIXTURES ON E-8 ARE MISSING IN THE COUNT ALSO. | | | | | | FOR EXAMPLE: THE KW RATING OF THE WATER HEATER ON PLANS | | | IS GREATER THAN THAT OF THE IDR. | | | | | | PLEASE BE SURE THE ENERGY CALCULATIONS CERTIFICATION | | | SHEET IS SIGNED, DATED AND SEALED. THE COVER SHEET IS | | | NOT COMPLETE AS AN EXCEPTION FOR COVER SHEETS OF | | | REPORTS. FS 471.025, FAC 61G15-23.002 | | | 13-101, 13-103.1.1.1, 13-400.A.3 | | | | | | 2) NOTE: PLEASE SEE 13-415.1.ABC.1.1, .1.2 FOR SPACE | | | CONTROLS REQUIRED IN ROOMS 114/115. THE RESPONSE SEEMS | | | TO MAKE NOTE OF POLE SWITCHES. WHERE IS THE OCCUPANCY | | | SENSORS/DEVICES LOCATED? SEE SECTION 13-415.1.ABC.1.2 | | | FOR CONFERENCE ROOMS AND BREAK ROOMS WHICH REQUIRE | | | OCCUPANCY SENSORS OF SOME TYPE. LIGHTING NEEDS TO BE | | | TURNED OFF WITHIN 30MINS. IT IS NOT CLEAR HOW THE | | | DEVICES AND THE NOTES PROVIDED WILL ACCOMPLISH THIS | | | REQUIREMENT. | | | BASED ON THE SYMBOL LEGEND THESE ARE STANDARD DEVICES. | | | | | | 3) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT | | | SHEETS FOR THE SERVICE ENTRANCE RATED MAIN/ATS. THE | | | RESPONSE MENTIONS THIS WILL BE DONE BY CONTRACTOR | | | HOWEVER NO SUBMITTAL WAS IN THE SUBMITTED | | | PLANS/PACKAGE. | | | THE RESPONSE LETTER GOES INTO DETAIL WITH RESPECT TO | | | THE MANUFACTURE WHICH IS NOT KNOWN AT THIS TIME BASED | | | ON THE BID PROCESS ETC. PLEASE SUBMIT ANY LISTED SE | | | RATE MAIN/ATS WHICH MEETS LISTING REQUIREMENTS AND | | | MINIMUM CODE REQUIREMENTS. AS LONG AS A PRODUCT IS | | | CHOSEN WHICH MEETS CODE THE, SUBMITTAL MAY ALWAYS BE | | | CHANGED AT A LATER DATE. | | | 110.3, 90.7, 230.70, 230.76, 230.79. | | | | | | ** AN EXAMPLE WOULD BE JUST LIKE A WINDOW PRODUCT | | | APPROVAL: A WINDOW IS REQUIRED TO BE CHOSEN MEETING | | | MINIMUM WIND LOADS, IMPACT RATINGS ETC AND HAVE FLORIDA | | | PRODUCT APPROVAL/MIAMI-DADE APPROVAL. THAT WINDOW MAY | | | NOT BE THE ONE CHOSEN FOR THE BID HOWEVER IT MEETS CODE | | | AND MINIMUM DESIGN CRITERIA. THEY OFTEN ARE REVISED AT | | | A LATER DATE WHICH IS ONLY A SUBMITTAL TO CHANGE THE | | | PRODUCT. | | | | | | | | | | | | ** IMPORTANT ** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED | | | INTO TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2009-01-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-01-05 |
Time |
13:55 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-01-05 |
Time |
13:55 |
Sent To |
|
|
| Notes |
| 2009-01-05 13:55:32 | ** DENIED 2ND REVIEW ** | | | | | | ** SOME NOTES FROM PREVIOUS REVIEW STILL NEED TO BE | | | ADDRESSED. | | | | | | 1) NOTE: PLANS STILL ONLY SUBMITTED FOR PLAN REVIEW AND | | | PERMIT APPLICATION HAS YET TO BE MADE. PLEASE KEEP IN | | | MIND THE NEW FLORIDA BUILDING CODE IS SET TO GO INTO | | | EFFECT ON MARCH 1ST, 2009. | | | VERIFICATION OF SEVERAL ITEMS INCLUDING LICENSING WILL | | | BE DONE ONCE PERMIT APPLICATION IS MADE. | | | *** PLEASE BE SURE ALL DOCUMENTATION CONTAINS THE | | | CORRECT ADDRESS. | | | | | | 2) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENT WITH | | | RESPECT TO LIGHTING CONTROLS. ROOMS/AREAS 114 AND 115 | | | SHOW SWITCHES HOWEVER THESE ARE NOT THE SAME SYMBOLS AS | | | USED IN THE OTHER ROOMS. THERE IS A NOTE #2 WHICH LENDS | | | TO POSSIBLE USE OF A SINGLE OCCUPANCY SENSOR TYPE | | | DEVICE HOWEVER THIS IS NOT CLEAR AT THIS TIME. | | | PLEASE SHOW THE SAME SYMBOL AS USED ON OTHER LOCATIONS. | | | 13-415.1.ABC.1.1,.1.2 AND .1.3. | | | | | | 3) NOTE: THE PREVIOUS SUBMITTED WERE NOT SUBMITTED WITH | | | THE REQUIRED ENERGY CALCULATIONS PER FBC 13-101, | | | 13-400, 13-415.2 ETC | | | THE SPECIFIC SECTIONS WERE GIVEN HOWEVER THESE WILL BE | | | NOTED ONCE MORE. PLEASE SEE 13-400.3.A FOR VERSION | | | WHICH WAS ADOPTED ON DECEMBER 8TH, 2006. THE CURRENT | | | FLA COM VERSION AS NOTED IN THIS SECTION TO BE USED AT | | | A MINIMUM IS VERSION 2.5. THE SUBMITTED CALCULATIONS | | | ARE VERSION 2.11 WHICH IS NO LONGER AN ADOPTED VERSION | | | IN THE STATE OF FLORIDA. | | | PLEASE BE SURE ALL ITEMS ON PLANS COORDINATES WITH THE | | | SUBMITTED INPUT DATA REPORT. THIS INCLUDES OTHER TRADES | | | AS WELL. | | | 13-415.2,13-415.2.ABC.1.1,.1.2 AND .1.3 FOR LIGHTING. | | | SEE THE EXTERIOR LIGHTING ON THE IDR ONLY INDICATES 4 | | | FIXTURES. THIS IS NOT POSSIBLE WHEN THE PLANS SHOW A | | | CONSIDERABLE AMOUNT OF MORE FIXTURES THAN THE FOUR | | | NOTED. | | | PLEASE SEE 13-401- 13-412 FOR OTHERS. | | | ITEMS SUCH AS FLOORS WHICH ARE ALL SHOWN AS | | | CARPET/RUBBER PADDING IS NOT CORRECT AS THERE ARE | | | SEVERAL AREAS WHICH ARE NOT THIS FINISH ARE SOME WHICH | | | ARE NOT PERMITTED TO CONTAIN THIS TYPE OF FINISH. (ELEC | | | ROOM, MECH ROOM ETC). | | | SEE COMMENTS FROM OTHER TRADES. | | | | | | ** PLEASE SEE THE COVER SHEET FOR THE PLANS INDICATES | | | THE ADDRESS AS 7501 N JOG RD ALTHOUGH THE APPLIED | | | LOCATION IS 6880. PLEASE COORDINATE ALL PLANS AND | | | SUPPORTING DOCUMENTATION. | | | | | | 4) NOTE: ON THE PREVIOUS REVIEW THE PHOTO-METRIC LEVELS | | | FOR THE LIFE SAFETY EGRESS WERE REQUESTED. THE RESPONSE | | | MENTIONS TO SEE ENCLOSED PLANS. THIS INFORMATION NEEDS | | | TO BE PART OF THE PLANS, WITH TITLE BLOCKS ALONG WITH | | | BEING SIGNED, DATED AND SEALED BY THE RESPONSIBLE | | | DESIGNER. | | | NFPA-101 7.8, 7.9. | | | FS471.003, 471.025, FAC 61G15-23.002 | | | FBC 106.1.1, 106.5. ADDITIONAL INFORMATION, CLARITY ON | | | RECORD PLANS. | | | | | | 5) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT | | | SHEETS ON THE GENERATOR, ATS ETC. THE ATS IS AN | | | INTEGRAL PART OF THE ELECTRICAL RISER AND COULD NOT BE | | | UNDER A SEPARATE PERMIT. | | | 110.3,90.7 | | | | | | 6) NOTE: NOW THAT THE LOADS FOR MDP-OP ARE SHOWN PLEASE | | | PROVIDE A GENERATOR WHICH WILL SERVE THE CAPACITY OR | | | PLEASE PROVIDE ALL LOAD SHEDDING WHICH WOULD BE NEEDED | | | TO DECREASE LOAD ON SYSTEM. AS SHOWN AT THIS TIME THE | | | GENERATOR WILL FEED ALL LOADS. | | | 220, 215.3, 702.5 ETC | | | | | | 7) NOTE: PLEASE PROVIDE WIND LOADS FOR LIGHT POLES PER | | | FBC TABLE 1609. RESPONSE MENTIONS THE INFORMATION WAS | | | ADDED TO SHEET E-10. HOWEVER THIS INFORMATION AS SHOWN | | | IS NOT CORRECT AND HAS BEEN CONFIRMED WITH THE BUILDING | | | REVIEWER. | | | | | | 8) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS FOR ALL | | | ITEMS. PLEASE SEE SHEET E-7, ROLL UP DOOR FOR EXAMPLE: | | | 408.4. | | | | | | 9) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO LOAD | | | CALCULATIONS. PLEASE SUBMIT THE LOAD CALCULATIONS | | | SHOWING HOW THE LOADS WERE DERIVED. THERE ARE NO NOTES | | | ON WHETHER OR NOT THE CONTINUOUS LOADS SUCH AS THE | | | LIGHTING AND WATER HEATER WAS ALREADY FIGURED AT 125% | | | OR IF THEY STILL NEED TO BE. | | | THE TYPICAL WATER HEATER SHOWN ON PLANS INDICATE 4500 | | | VA HOWEVER NO INDICATE OF THE 125% COULD BE LOCATED. | | | 220.12,220.14,220.42,220.44, ETC CONTINUOUS LOADS PER | | | 215.3,230.42. SEE 422.13 FOR STORAGE TYPE WATER | | | HEATERS. THIS WAS A CHANGE IN THE 2005 NEC. | | | | | | 10) NOTE: PLEASE CLARIFY THE FOUNDATION STEEL BEING | | | PART OF THE GROUNDING ELECTRICAL SYSTEMS AT BOTH | | | STRUCTURES. THE PLANS NOTES *BUILDING STEEL* HOWEVER IT | | | IS NOT CLEAR IF THIS IS FOR *FOUNDATION STEEL*. | | | 250.50 | | | THIS COMMENT WAS NOT MADE ON THE PREVIOUS REVIEW. | | | | | | ** AS NOTED ON PREVIOUS REVIEW AS THERE IS SOME | | | INFORMATION NOT YET SUBMITTED A COMPLETE REVIEW FOR | | | CODE COMPLIANCE CAN NOT BE DONE AT THIS TIME. | | | | | | ** IMPORTANT ** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED | | | INTO TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2008-10-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-10-22 |
Time |
09:06 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-10-22 |
Time |
09:06 |
Sent To |
|
|
| Notes |
| 2008-10-22 09:06:59 | | | | ** DENIED REVIEW** | | | | | | | | | | | | | | | 1) NOTE: PLANS HAVE ONLY BEEN SUBMITTED FOR PLAN REVIEW | | | AND NOT FOR PERMIT. EVEN ONCE ALL COMMENTS HAVE BEEN | | | ADDRESSED AND PERMIT APPLICATION BY A LICENSED | | | CONTRACTOR HAS NOT BEEN MADE THE REVIEW WOULD STILL | | | REMAIN IN A FAILED STATUS. THERE ARE SEVERAL ITEMS FOR | | | LICENSING WHICH IS VERIFIED AT A LATER DATE WHEN | | | APPLICATION HAS BEEN MADE. | | | | | | 2) NOTE: THE PROJECT INFORMATION HAS BEEN SENT TO | | | ADDRESSING FOR REVIEW. THE PLANS DO NOT INDICATE ANY | | | ADDRESS ON THE TITLE BLOCKS AND TWO SEPARATE BUILDINGS | | | ARE BEING CONSTRUCTED. KEEP IN MIND IF THESE TWO | | | SEPARATE STRUCTURES ARE SUBMITTED ON THE SAME PLANS | | | UNDER ONE PERMIT A CERTIFICATE OF OCCUPANCY, | | | INSPECTIONS FINALS ETC WOULD BE FOR BOTH. IT WOULD NOT | | | BE POSSIBLE TO CO ONE WITH OUT THE OTHER. IF TWO PERMIT | | | APPLICATIONS ARE MADE, ONE FOR EACH BUILDING THIS WOULD | | | ALLOW EACH TO CONTAIN A CO ETC. | | | PLEASE BE SURE ONCE THE ADDRESS FOR EACH BUILDING IS | | | ASSIGNED THE TITLE BLOCKS REFLECT EACH. | | | 61G15-23.002, 61G1-16.004 | | | FBC 106.1, 106.5 | | | | | | 3) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS AND LIGHTING | | | PERFORMANCE CALCULATIONS IN COMPLIANCE WITH THE FBC | | | 13-415.2.ABC.1.1, .1.2 AND .1.3. PLEASE SEE 13-400, | | | 13-415 ETC | | | AS NO CALCULATIONS OR PERFORMANCE CALCULATIONS WERE | | | SUBMITTED NO REVIEW OF THESE ITEMS COULD BE DONE. | | | | | | 4) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE LISTED | | | ON THE ELECTRICAL PLANS. | | | 2004 FBC W/2007 REVISIONS. | | | 2005 NFPA-70 | | | 2003 NFPA-101 | | | 2002 NFPA-110 | | | | | | 5) NOTE: PLEASE KNOW THAT ALL LOW VOLTAGE SYSTEMS ARE | | | REQUIRED TO BE UNDER A SEPARATE PERMIT. IF THE PLANS | | | SHOW ALL OF THE EQUIPMENT THEN THEY MAY BE REFERENCED | | | FOR A TURN AROUND PERMIT ONCE THE BASE BUILDING | | | PERMIT(S) ARE ISSUED. | | | | | | 6) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT | | | SHEETS FOR THE GENERATOR, ATS AND OTHER EQUIPMENT SUCH | | | AS THE FUEL TANK. THE FUEL TANKS WILL BE UNDER THE | | | REVIEW OF OTHER TRADES. | | | 110.3, 90.7 | | | FBC 106.1.2 | | | | | | 7) NOTE: PLEASE PROVIDE INFORMATION ON PLANS THAT THE | | | MOTORIZED GATES HAVE A FAIL SAFE OR BACK UP FOR | | | OPERATION IN THE EVENT OF POWER FAILURE. SEE FIRE | | | MARSHAL REVIEW. THIS IS NOTED AS THIS WILL AFFECT THE | | | ELECTRICAL PLANS. | | | | | | 8) NOTE: PLEASE PROVIDE A GROUNDING ELECTRODE | | | RISER/ATTACHMENT LOCATION FOR ALL TRANSFORMERS. | | | 250.66,250.50.250.58 ETC | | | | | | 9) NOTE: PLEASE SEE THE LIGHTING CONTROLS TO MEET FBC | | | 13-415.1.1, .1.2 AND .1.3 ARE IN QUESTION FOR MORE | | | INFORMATION. WHAT DOES THE SWITCH 1 DO? THE NOTE ON THE | | | PLANS MENTIONS OPERATION HOWEVER DOES THIS DEVICE STILL | | | CONTAIN AN AUTOMATED OPERATION TO TURN LIGHTING OFF | | | ONCE AN OCCUPANT IS NO LONGER IN THE SPACE? | | | PLEASE SEE THE BREAK ROOMS AND OTHER ROOMS SUCH AS | | | TRAINING ROOMS MUST MEET 13-415.1.ABC.1.2. ( AREAS 114, | | | 115 ETC) | | | IN LOCATIONS SUCH AS MULIT0GNAG BATH ROOMS PLEASE | | | INDICATE THE AUTOMATED DEVICES FOR LIGHTING CONTROLS | | | WITH DUAL TECHNOLOGY. IF DEVICE WAS MOTION ONLY THIS | | | WOULD AFFECT OTHER AREAS IN THE SAME BATHROOMS WHICH | | | MAY BE OCCUPIED YET NO MOTION COULD BE DETECTED. | | | | | | 10) NOTE: PLEASE INDICATE THE CIRCUITING FOR THE | | | EMERGENCY BATTERY BACK UP IN ROOM 117 (LADIES | | | BATHROOM). 700.12F | | | | | | 11) NOTE: PLEASE SUBMIT PHOTO-METRICS FOR EGRESS PATHS | | | UNDER EMERGENCY BACK UP CONDITIONS. THE LIGHTING LEVELS | | | UNDER NORMAL ARE NOT NEEDED AS THEY ARE CLEARLY | | | SUFFICIENT HOWEVER THE LIGHTING LEVELS UNDER EMERGENCY | | | IN SOME AREAS ARE IN QUESTION. PLEASE SEE NFPA-101 | | | 7.9.1 WHICH PERMITS 1FT CANDLE UNDER EMERGENCY | | | CONDITIONS. | | | FBC 106.1.1, 106.1.2 FOR ADDITIONAL INFORMATION AND | | | CLARIFICATION. | | | | | | 12) NOTE: PLEASE VERIFY ALL DISCONNECTING MEANS AT THE | | | DETACHED ROOF STRUCTURE PER 225.31-225.39. | | | ( MAY BE A SNAP SWITCH) | | | GROUNDING REQUIRED PER 250.32 ALREADY SHOWN. | | | | | | 13) NOTE: PLEASE CLARIFY THE SERVER ROOM. IF THIS IS AN | | | IT ROOM PLEASE BE SURE ALL ITEMS LISTED IN 645.2 ARE | | | MET IN ORDER FOR WIRING METHODS PERMITTED IN 645 TO BE | | | USED. IF THESE ITEMS ARE NOT MET THE WIRING METHODS | | | WHICH ARE PERMITTED IN 645 ARE NOT PERMITTED TO BE USED | | | AND THIS MAY AFFECT FUTURE EQUIPMENT INSTALLATION AND | | | WIRING. PLEASE PLACE NOTE ON PLANS THAT WILL STATE: | | | *THIS IS NOT AN IT ROOM AND WIRING METHODS OF NEC 645 | | | ARE NOT PERMITTED*. OR WORDS TO THAT AFFECT. | | | | | | 14) NOTE: PLEASE BE SURE LIGHT POLES ARE STATING THE | | | WIND LOAD RATINGS AS NOTED IN THE FBC. THE LIGHT POLE | | | CALCULATIONS WILL BE UNDER BUILDING/STRUCTURAL REVIEW. | | | THIS IS NOTED FOR INFORMATION ONLY. | | | | | | 15) NOTE: PLEASE COMPLETE ALL ROOM AND AREA | | | DESIGNATIONS ON PLANS. THIS MAY BE ALPHA OR NUMERIC. | | | MOST AREAS SHOW BOTH AT THIS TIME. | | | PLEASE BE SURE THE PANEL SCHEDULES ARE SPECIFIC TO | | | ROOMS AND AREAS IN WHICH THEY FEED. FOR EXAMPLE SIMPLY | | | STATING *RECEPTACLES* OR * LIGHTING* IS NOT ACCEPTABLE. | | | PLEASE SEE THE CHANGE IN THE 2005 NEC (HANDBOOK) WHICH | | | EXPLAINS THE CHANGE IN 408.4 FOR MORE SPECIFIC | | | DESIGNATIONS. THIS IS NOT ONLY FOR ON-SITE HOWEVER ALSO | | | FOR RECORD PLANS. | | | THIS WOULD INCLUDE THE CIRCUIT FOR ROLL UP DOOR AT | | | MAINT BUILDING. | | | FBC 106.1.1, 106.5 | | | | | | 16) NOTE: PLEASE SEE THE PLANS SHOW A CIRCUIT TO | | | GENERATOR ENCLOSURE HOWEVER BUT NOT FOR A PARTICULAR | | | PURPOSE. THE PLANS ALSO SHOW AT THE GENERATOR A | | | DESIGNATION TO THE PANEL HOWEVER NOT THE CIRCUIT. IF | | | THIS CIRCUIT IS FOR A BATTERY CHARGER, BLOCK HEATER ETC | | | PLEASE CHECK WITH THE MANUFACTURE OF ANY PARTICULAR | | | GENERATOR AS THEY ARE USUALLY DEDICATED CIRCUITS. BLOCK | | | HEATERS CAN BE AS HIGH AS 1500WATTS WHICH WOULD NOT | | | PERMIT THE BATTERY CHARGER TO BE ON THE SAME CIRCUIT. | | | 408.4, 220 ETC | | | FBC 106.1.2, 106.1.1 | | | | | | 17) NOTE: PLEASE SEE ELECTRICAL ROOM 109 AS THIS STATES | | | A LINE NOTE FROM THE TRANSFORMER TO *LP-OP2* HOWEVER | | | BASED ON RISER AND DESIGNATION ALREADY USED FOR | | | TRANSFORMER IN ROOM 113 THIS IS CONFUSING. | | | PLEASE CLARIFY HOW BOTH HAVE THE SAME DESIGNATION? | | | FBC 106.1.1, | | | NEC 230,450,215 ETC GENERAL COORDINATION | | | | | | 18) NOTE: PLEASE SUBMIT LOAD CALCULATIONS FOR THE | | | MDP-OP. AS NO LOADS ARE SHOWN IT IS NOT POSSIBLE TO | | | DETERMINE CODE COMPLIANCE FOR ALL EQUIPMENT INCLUDING | | | THE LOAD ON THE GENERATOR AND WHETHER OR NOT THE | | | GENERATOR IS OF SUFFICIENT SIZE. | | | 220, 702.5 ETC | | | FBC 106.1.1, 106.1.2 | | | PLEASE BE SURE TO INDICATE ALL CONTINUOUS LOADS AND | | | LARGEST MOTOR LOADS AT 125%. | | | 215.3,230.42 | | | | | | 19) NOTE: PLEASE KNOW AS THERE IS INFORMATION NOT YET | | | SUBMITTED FOR REVIEW THERE MAY VERY WELL BE NEW | | | COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE MADE | | | AT THIS TIME. | | | | | | | | | | | | | | | | | | **IMPORTANT** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | | TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2009-03-02 |
|
|
Cont ID |
|
| Sent By |
mgonzale |
Date |
2009-03-02 |
Time |
|
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
2009-03-02 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2008-11-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-12-15 |
Time |
09:13 |
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
2008-11-06 |
Time |
16:13 |
Sent To |
ENG |
|
| Notes |
| 2008-11-06 16:42:22 | APPROVED WITH PROVISO: | | | | | | EOR MUST SUPPLY NPDES PLAN AT TIME OF PRECONSTRUCTION | | | WITH CITY'S ENGINEERING DEPT. | | | | | | ALL UTILITIES HAVE BEEN COORDINATED WITH THE CITY OF | | | WPB. | | | | | | MANNY GONZALEZ | | | (561) 494-1085 | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2009-06-16 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2009-06-16 |
Time |
10:14 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2009-06-16 |
Time |
10:13 |
Sent To |
|
|
| Notes |
| 2009-06-16 10:14:50 | SENT TO L. MARTINEZ FOR PROCESSING. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2009-04-09 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-04-09 |
Time |
17:29 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-04-09 |
Time |
16:22 |
Sent To |
|
|
| Notes |
| 2009-04-09 17:29:47 | *****UNSAT**** | | | | | | THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN | | | REVIEW STILL NEED TO BE ADDRESSED: | | | | | | | | | 07. AS PER WEST PALM BEACH CODE, THE ADDRESS NUMBERS ON | | | THE BUILDING SHALL BE NO LESS THAN 6" IN HEIGHT AND NO | | | LESS THAN 1" IN WIDTH PLAINLY VISBLE FROM THE ROADWAY | | | TO APPROACHING VEHICLES. | | | | | | 14. IN REFERENCE TO NFPA 241 BEING ADDED TO THE PLANS, | | | PLEASE CONTACT THIS OFFICE IN THIS MATTER. | | | | | | | | | (ALL OTHER COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS | | | HAVE BEEN SATISFIED; THE APPROPROPITE PLAN SHEETS ARE | | | TO BE FIRE-STAMPED WHEN THE ABOVE ITEMS AS WELL AS | | | OTHER PLAN EXAMINERS' COMMENTS HAVE BEEN ADDRESSED.) | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722; PLAN REVIEW OFFICE | | | 561-804-4724; FIRE PREVENTION BUREAU | | | 561-644-7326; BUSINESS CELLULAR |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2009-01-14 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2009-01-14 |
Time |
11:11 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2009-01-14 |
Time |
11:11 |
Sent To |
|
|
| Notes |
| 2009-01-14 11:23:21 | ***DENIED*** | | | | | | MOST OF THE PREVIOUS COMMENTS HAVE BEEN ADDRESSED. | | | PLEASE SEE THE FOLLOWING AND NOTE THAT THE PLANS WILL | | | REMAIN IN FAILED STATUS UNTIL REVIEWED AND APPROVED FOR | | | PERMIT. | | | | | | 1) PLEASE ADD TO CODE ANALYSIS ON SHEET A-3. NFPA 1, | | | 2003 CHAPTER-18 | | | | | | 2) TYPICALLY DEAD END WATER LINES THAT ARE CONNECTED TO | | | FIRE PROTECTION EQUIPMENT IS AN UNACCEPTABLE | | | ARRANGEMENT, PARTICULARLY IF FUTURE EQUIPMENT IS | | | PROPOSED. PLEASE PROVIDE FURTHER EXPLANATION. | | | | | | 3) PLEASE PROVIDE VERIFICATION THAT EQUIPMENT | | | ILLUSTRATED ON SHEET CD-5 IS A DOUBLE CHECK DETECTOR | | | ASSEMBLY. THE RESPONSE SEEMS TO SUGGEST A DEVICE THAT | | | IS TIED TO THE DOMESTIC WATER SUPPLY INDICATING A | | | BACKFLOW DEVICE. | | | | | | 5) OK PLEASE VERIFY THE ACTUAL DISTANCES ON THE | | | DRAWINGS AS CODE ANALYSIS INDICATES THAT DISTANCES | | | VARY. | | | | | | 7) THE ADDRESS IS SHOWN ON PLANS. PLEASE INCLUDE | | | INFORMATION SHOWING CODE COMPLIANCE PER THE CITY OF | | | WEST PALM BEACH REQUIREMENTS FOR COMMERCIAL BUILDINGS. | | | | | | 14) PLEASE ADD NOTE TO PLANS. NFPA 241 | | | | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2008-10-29 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-10-29 |
Time |
14:04 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-10-29 |
Time |
14:04 |
Sent To |
|
|
| Notes |
| 2008-10-29 14:22:49 | ***DENIED*** | | | | | | 1) PROPERTY ACCESS AND WATER SUPPLY TO COMPLY WITH NFPA | | | 1, 2003, CHAPTER-18. | | | | | | 2) FIRE LINE APPEARS TO DEAD END AT FIRE HYDRANT. ARE | | | THERE ANY OTHER FIRE HYDRANTS ON THE PROPERTY? | | | | | | 3) SHEET CD-5 ILLUSTRATES A DOUBLE CHECK DETECTOR | | | ASSEMBLY. IN ADDITION TO ELECTRONIC SUPERVISION, DEVICE | | | SHALL BE SECURED WITH CHAIN AND LOCK. SUBJECT BUILDINGS | | | ARE NOT FIRE SPRINKLER PROTECTED. WHAT BUILDING IS | | | PROTECTED BY DOUBLE CHECK DETECTOR ASSEMBLY? | | | | | | 4) IN ADDITION TO APPLICABLE BUILDING CODES, LIFE | | | SAFETY SHALL COMPLY WITH NFPA 101, 2003. | | | | | | 5) PLEASE INDICATE ACTUAL MAXIMUM TRAVEL DISTANCES ON | | | DRAWINGS. (LIFE SAFETY PLAN) | | | | | | 6) DOORS SHALL SWING IN DIRECTION OF TRAVEL WHERE | | | SERVING AREAS WITH (50) OR MORE OCCUPANTS. | | | | | | 7) ADDRESSES ARE REQUIRED ON BUILDINGS THAT SHALL BE | | | MINIMUM OF 6" IN HEIGHT, 1" WIDTH AND CONTRASTING WITH | | | BACKGROUND. | | | | | | 8) PROVIDE MINIMUM INTERIOR FINISH CLASSIFICATION FOR | | | WALLS AND CEILING IN TERMS OF CLASS A,B OR C. ADD NOTE | | | TO ELEVATIONS | | | | | | 9) 2A-10B,C RATED FIRE EXTINGUISHERS ARE REQUIRED TO BE | | | MOUNTED AT LOCATIONS NOT TO EXCEED 75" TRAVEL DISTANCE | | | REQUIREMENT. OK ON SHEET A-17. | | | | | | 10) KNOX BOX ENTRY REQUIRED FOR BUILDINGS. CONTACT | | | BUREAU OF FIRE PREVENTION AT (561) 804-4724 FOR | | | ASSISTANCE. | | | | | | 11) FIRE DAMPERS TO BE TESTED FOR CLOSURE IN ACCORDANCE | | | WITH UL 555 REQUIREMENTS PRIOR TO FINAL INSPECTION. | | | | | | 12) MOTOR OPERATED GATES TO BE PROVIDED WITH FAIL SAFE | | | MECHANISM IN THE EVENT OF POWER LOSS. | | | | | | 13) SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR | | | GENERATOR AND ASSOCIATED EQUIPMENT. | | | | | | 14) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY | | | WITH NFPA 241. | | | | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2010-08-09 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2010-08-09 |
Time |
10:13 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2010-08-09 |
Time |
10:12 |
Sent To |
|
|
| Notes |
| 2010-08-09 10:12:58 | SENT TO FIRE BOX. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2009-05-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-05-21 |
Time |
13:28 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-05-21 |
Time |
13:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2009-02-26 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2009-02-26 |
Time |
16:10 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2009-02-26 |
Time |
16:10 |
Sent To |
|
|
| Notes |
| 2009-02-26 16:14:12 | TO "COMM" BD#5--PLANS ON RACK--3 ROLLS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-12-15 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-12-15 |
Time |
09:40 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-12-15 |
Time |
09:40 |
Sent To |
|
|
| Notes |
| 2008-12-15 09:40:20 | TO "COMM" BD#43 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-12-15 |
|
|
Cont ID |
|
| Sent By |
mgonzale |
Date |
2008-11-06 |
Time |
16:42 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-09-25 |
Time |
10:38 |
Sent To |
ENG |
|
| Notes |
| 2008-09-25 10:38:28 | TO "COMM" BD#48 |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
P |
Date |
2009-05-26 |
|
|
Cont ID |
|
| Sent By |
rkussner |
Date |
2009-05-26 |
Time |
17:39 |
Rev Time |
0.00 |
| Received By |
rkussner |
Date |
2009-05-26 |
Time |
17:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2009-06-12 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-06-12 |
Time |
14:50 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-06-12 |
Time |
14:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2009-03-27 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-03-27 |
Time |
17:08 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-03-27 |
Time |
15:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2009-01-24 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-01-24 |
Time |
15:31 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-01-24 |
Time |
15:15 |
Sent To |
|
|
| Notes |
| 2009-01-24 15:30:58 | REVIEW #: 2ND ***PLAN CHECK ONLY*** | | | ACTION: DENIED | | | | | | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH | | | PREVIOUS REVIEW COMMENTS FOR THE PURPOSE OF CONTINUITY: | | | | | | 1. OK. SEPARATE PERMIT FOR GENERATOR REQUIRED. SUBMIT | | | PLANS FOR THAT PERMIT WHICH HAVE BEEN REVIEWED AND | | | APPROVED BY PBC DERM. FOR MORE INFORMATION PLEASE | | | CONTACT PBC DERM AT: 561-233-2400 OR | | | HTTP://WWW.PBCGOV.COM/ERM/ | | | | | | 2. *PREVIOUS COMMENT* PAGE H-1 REFERS TO FORM 400A FOR | | | ENERGY CODE COMPLIANCE. NO SUCH FORM WAS PROVIDED WITH | | | THIS SUBMISSION. WITHOUT SUCH FORM, AN OVERALL ENERGY | | | CODE COMPLIANCE REVIEW CAN NOT BE PERFORMED. PROVIDE A | | | COMMERCIAL ENERGY CODE COMPLIANCE FORM IN ACCORDANCE | | | WITH FBCB 13-400.0. ALSO, COOLING LOAD CALCULATIONS | | | SHALL BE APPENDED TO THE ENERGY CODE COMPLIANCE FORM IN | | | ACCORDANCE WITH FBCM 13-407.1.ABC.1. AS A RESULT OF | | | THIS INFORMATION NOT BEING PROVIDED, RELATED ADDITIONAL | | | COMMENTS ARE LIKELY IN SUBSEQUENT REVIEWS. | | | *PARTIALLY ADDRESSED* FORM 400A VERSION 2.11 WAS | | | SUBMITTED WITH COOLING LOAD CALCULATIONS. AN ACCURATELY | | | COMPLETED FORM 400A-04R (GENERATED BY THE FLA/COM-2004 | | | COMPUTER PROGRAM, VERSION 2.5) DEMONSTRATING THAT CODE | | | COMPLIANCE HAS BEEN ACHIEVED SHALL BE SUBMITTED TO THE | | | BUILDING OFFICIAL FOR METHOD A COMPLIANCE IN ACCORDANCE | | | WITH FBCB 13-400.3.A. METHOD A VERSION 2.11 HAS NOT | | | BEEN IN EFFECT SINCE THE DECEMBER 8, 2006 REVISIONS TO | | | THE FBC. REVIEW FOR COMPLIANCE WITH FBCB CHAPTER 13 IS | | | NOT POSSIBLE AT THIS TIME. | | | | | | 3. *PREVIOUS COMMENT* PAGE H-2: MULTIPLE DUCTS ON FLOOR | | | PLAN DO NOT HAVE A SIZE DESIGNATION. EXAMPLES: OUTSIDE | | | AIR DUCTS IN MECHANICAL ROOMS, RETURN TRUNK AND BRANCH | | | LINES. PLEASE CHECK ALL DUCTS ON FLOOR PLAN AND PROVIDE | | | MISSING SIZE INFORMATION. DUCTS SHALL BE DESIGNED AND | | | INSTALLED TO PROVIDE THE REQUIRED DISTRIBUTION OF AIR | | | IN ACCORDANCE WITH FBCM 603.1. | | | *PARTIALLY ADDRESSED* SOME DUCTS ON PLANS ARE STILL | | | MISSING SIZES, SUCH AS THE OA DUCTS IN MECHANICAL ROOM | | | 113 AND THE RETURN BRANCH IN THE KITCHEN. PLEASE | | | PROVIDE ALL MISSING INFORMATION. ALSO, PLEASE SEE FBCM | | | 407.1 FOR REQUIREMENTS RELATED TO RETURN AIR INTAKES IN | | | KITCHENS. | | | | | | 4. OK | | | | | | 5. OK | | | | | | 6. OK | | | | | | 7. *PREVIOUS COMMENT* PAGE HD-2: THERE IS NO DETAIL | | | PROVIDED FOR INSTALLATION OF GRAVITY HOOD, ASSOCIATED | | | ROOF CURB OR ROOF JACKS FOR WIND RESISTANCE. MECHANICAL | | | EQUIPMENT SHALL BE DESIGNED AND INSTALLED TO RESIST | | | WIND PRESSURES IN ACCORDANCE WITH FBCM 301.13. | | | *PARTIALLY ADDRESSED* DETAIL ON HD-3 CALLS FOR EYEBOLT | | | EMBEDDED 3 INCHES WITH EPOXY GROUT. HOW IS THIS | | | POSSIBLE ON A METAL STANDING SEAM ROOF? THIS DETAIL | | | APPEARS TO BE FOR A CONCRETE DECK, WHICH DOES NOT APPLY | | | TO THIS PROJECT. PLEASE CORRECT FOR THE APPROPRIATE | | | ROOF ASSEMBLY. | | | | | | 8. OK | | | | | | NOTE: THE 2007 FLORIDA BUILDING CODE IS SCHEDULED TO | | | BECOME EFFECTIVE ON MARCH 1, 2009. IF A PERMIT | | | APPLICATION FOR THIS PROJECT IS SUBMITTED AFTER THIS | | | DATE, THESE PLANS WILL NEED TO BE REVIEWED FOR | | | COMPLIANCE WITH THE NEW CODE PRIOR TO PERMIT ISSUANCE. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2008-10-25 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-10-25 |
Time |
12:18 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-10-25 |
Time |
12:15 |
Sent To |
|
|
| Notes |
| 2008-10-25 12:18:21 | REVIEW #: 1ST ***PLAN CHECK ONLY*** | | | ACTION: DENIED | | | | | | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. PAGE A-3 INDICATES TWO 1,000 GALLON DIESEL FUEL | | | STORAGE TANKS, ONE FOR EACH BUILDING. PAGE E-2 SHOWS | | | ONLY ONE GENERATOR WITH DIESEL STORAGE TANK. WHICH IS | | | CORRECT? NO INFORMATION WAS PROVIDED REGARDING THE | | | DIESEL GENERATOR OR FUEL STORAGE SYSTEM TO BE USED. | | | PROVIDE SUBMITTAL DOCUMENTATION FOR EACH TO DEMONSTRATE | | | COMPLIANCE WITH FBCM SECTION 915. ALSO, ABOVE GROUND | | | FUEL STORAGE TANKS GREATER THAN 550 GALLONS SHALL BE | | | SUBMITTED TO PALM BEACH COUNTY DERM FOR APPROVAL PRIOR | | | TO PERMIT ISSUANCE. INCORPORATE DERM APPROVED PLANS | | | INTO THESE PERMIT DOCUMENTS. FOR MORE INFORMATION | | | PLEASE CONTACT PBC DERM AT: 561-233-2400 OR | | | HTTP://WWW.PBCGOV.COM/ERM/ | | | | | | 2. PAGE H-1 REFERS TO FORM 400A FOR ENERGY CODE | | | COMPLIANCE. NO SUCH FORM WAS PROVIDED WITH THIS | | | SUBMISSION. WITHOUT SUCH FORM, AN OVERALL ENERGY CODE | | | COMPLIANCE REVIEW CAN NOT BE PERFORMED. PROVIDE A | | | COMMERCIAL ENERGY CODE COMPLIANCE FORM IN ACCORDANCE | | | WITH FBCB 13-400.0. ALSO, COOLING LOAD CALCULATIONS | | | SHALL BE APPENDED TO THE ENERGY CODE COMPLIANCE FORM IN | | | ACCORDANCE WITH FBCM 13-407.1.ABC.1. AS A RESULT OF | | | THIS INFORMATION NOT BEING PROVIDED, RELATED ADDITIONAL | | | COMMENTS ARE LIKELY IN SUBSEQUENT REVIEWS. | | | | | | 3. PAGE H-2: MULTIPLE DUCTS ON FLOOR PLAN DO NOT HAVE A | | | SIZE DESIGNATION. EXAMPLES: OUTSIDE AIR DUCTS IN | | | MECHANICAL ROOMS, RETURN TRUNK AND BRANCH LINES. PLEASE | | | CHECK ALL DUCTS ON FLOOR PLAN AND PROVIDE MISSING SIZE | | | INFORMATION. DUCTS SHALL BE DESIGNED AND INSTALLED TO | | | PROVIDE THE REQUIRED DISTRIBUTION OF AIR IN ACCORDANCE | | | WITH FBCM 603.1. | | | | | | 4. PAGE H-2: SEVERAL BRANCH DUCTS SHOW CONTROL DAMPERS | | | ABOVE GYPSUM BOARD CEILINGS. SHOW HOW THESE DAMPERS ARE | | | TO BE ACCESSED FOR TESTING AND BALANCING IN ACCORDANCE | | | WITH FBCB 13-410.1.ABC.4. | | | | | | 5. PAGE H-2: THE OUTSIDE AIR INTAKE LOUVER FOR AHU-3 | | | AND AHU-4 IS SHOWN TO BE APPROXIMATELY 5 FEET FROM THE | | | PARKING LOT FOR THE OPERATIONS BUILDING. MECHANICAL | | | OUTSIDE AIR INTAKE OPENINGS SHALL BE LOCATED A MINIMUM | | | OF 10 FEET FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT, | | | SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS, STREETS, | | | ALLEYS, PARKING LOTS AND LOADING DOCKS IN ACCORDANCE | | | WITH FBCM 401.5.1. | | | | | | 6. PAGE H-2: THE RETURN DUCT PENETRATING A RATED WALL | | | ASSEMBLY AT BREAK ROOM 106 SHOW NO FIRE DAMPER AT THE | | | DUCT PENETRATION BUT SHOWS THE FIRE DAMPER AT ANOTHER | | | LOCATION IN THE WALL, AWAY FROM THE DUCT. PLEASE SHOW | | | THE DUCT PENETRATION TO BE PROTECTED IN ACCORDANCE WITH | | | FBCM 607.5 AND SHOW THE CORRECT LOCATION OF THE DAMPER | | | IN ACCORDANCE WITH FBCM 607.8. | | | | | | 7. PAGE HD-2: THERE IS NO DETAIL PROVIDED FOR | | | INSTALLATION OF GRAVITY HOOD, ASSOCIATED ROOF CURB OR | | | ROOF JACKS FOR WIND RESISTANCE. MECHANICAL EQUIPMENT | | | SHALL BE DESIGNED AND INSTALLED TO RESIST WIND | | | PRESSURES IN ACCORDANCE WITH FBCM 301.13. | | | | | | 8. PAGE HD-2: NO INFORMATION SHOWN ON PLANS OR IN | | | DETAIL REGARDING AUXILIARY OR SECONDARY DRAIN | | | PROTECTION FOR CONDENSATE DRAIN SYSTEMS. PROVIDE | | | AUXILIARY OR SECONDARY DRAIN PROTECTION IN ACCORDANCE | | | WITH FBCM 307.2.3. | | | | | | NOTE: THE 2007 FLORIDA BUILDING CODE IS SCHEDULED TO | | | BECOME EFFECTIVE ON MARCH 1, 2009. IF A PERMIT | | | APPLICATION FOR THIS PROJECT IS SUBMITTED AFTER THIS | | | DATE, THESE PLANS WILL NEED TO BE REVIEWED FOR | | | COMPLIANCE WITH THE NEW CODE PRIOR TO PERMIT ISSUANCE. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
P |
Date |
2009-06-01 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-06-01 |
Time |
15:29 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-06-01 |
Time |
15:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2009-04-14 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-04-14 |
Time |
15:53 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-04-14 |
Time |
15:53 |
Sent To |
|
|
| Notes |
| 2009-04-14 15:54:49 | | | | | | | PASSED/PROVISO: | | | | | | WATER HAMMER ARRESTORS SHALL BE LOCATED NEAR THE | | | FIXTURES IN AN "EFFECTIVE RNAGE" NOT IN THE CEILING. | | | PDI-WH 201. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2009-04-13 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-04-13 |
Time |
16:36 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-04-13 |
Time |
16:36 |
Sent To |
|
|
| Notes |
| 2009-04-13 16:44:42 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | | | | ****FROM PREVIOUS REVIEW: | | | | | | ******FROM PREVIOUS REVIEWS: | | | | | | ********FROM PREVIOUS REVIEWS: | | | | | | 1. OK | | | 2. OK | | | 3. OK | | | 4. OK | | | | | | 5. OK | | | | | | ___FOR SINKS: | | | A. OK | | | B. OK | | | C. 11-4.24.4 SINK DEPTH (PROVISO) | | | D. OK | | | E. OK | | | F. OK | | | G. OK | | | | | | 6. SHT P-3 MORE INFORMATION IS REQUIRED. PLEASE | | | INDICATE WHAT THE HOSE REELS WILL BE WASHING OFF. WHAT | | | WILL HAPPEN TO THE WATER USED TO WASH OFF WHATEVER IS | | | BEING WASHED OFF? WILL THERE BE ANY CHANCE OF GREASE OR | | | OIL WASHED OFF? PLEASE CLARIFY. SECTIONS 106.1.2 & | | | 301.2. MORE COMMENTS MAY FOLLOW DEPENDING TO THE | | | COMMENT RESPONSES TO THESE QUESTIONS. | | | ****RESPONSE NOTED, COMMENT NOT ADDRESSED. | | | ******RESPONSE NOTED, BUT THE SECTION OF THE COMMENT | | | ABOUT WHAT WILL HAPPEN TO THE WATER, (AND NOW THE MUD), | | | HAS NOT BEEN ADDRESSED. THERE IS NO INDICATION OF HOW | | | THE WALLS WILL BE PROTECTED FROM THE STANDING WATER IN | | | THE MAINTENANCE BUILDING, NO INDICATION OF SLOPING OF | | | THE FLOORS AWAY FROM THE WALLS, NO WALL FINISH SCHEDULE | | | INDICATING WATER PROOFING OF WALLS ETC. SECTION 301.2 | | | SYSTEM INSTALLATION. PLUMBING SHALL BE INSTALLED WITH | | | DUE REGARD TO PRESERVATION OF THE STRENGHT OF | | | STRUCTURAL MEMBERS AND PREVENTION OF DAMAGE TO WALLS | | | AND OTHER SURFACES THROUGH FIXTURE USAGE. PLEASE | | | CLARIFY. | | | ********NO WRITTEN RESPONSE. COMMENT TO BE ADDRESSED | | | WITH A SIGNED, SEALED COMMENT RESPONSE TO THE ABOVE | | | COMMENT. THE FINISH SCHEDULE FOR THE MAINTENANCE | | | BUILDING INDICATE P-1 FININSH. PLEASE INDICATE WHAT P-1 | | | FINISH IS AND WHERE IN THE PLANS THIS CAN BE FOUND. THE | | | ARCHITECT OR ENGINEER OF RECORD WILL BE REQUIRED TO | | | TAKE RESPONSIBILITY FOR THE CODE SECTION 301.2. | | | | | | 7. OK | | | | | | 8. SHT P-4 WATER RISER DIAGRAM. WATER HAMMER ARRESTORS | | | SHALL BE LOCATED NEAR THE FIXTURE IN AN "EFFECTIVE | | | RANGE" NOT IN THE CEILING AS SHOWN. PDI-WH 201. WATER | | | HAMMER ARRESTORS ARE REQUIRED AT THE REFRIGERATOR ICE | | | MAKER LINES. SECTION 604.9. -- A SHUT OFF VALVE IS | | | REQUIRED ON THE SUPPLY LINE TO THE WALL HYDRANT NEAR | | | OFFICE ROOM 102. SECTION 606.2(2). | | | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. MOST | | | WATER HAMMER ARRESTORS DO NOT REQUIRE ACCESS AND THE | | | PDI-WH 201 GUIDLINES SHOW THE WATER HAMMER ARRESTORS | | | NEAR THE FIXTURES, NOT IN THE CEILING. | | | ******RESPONSE NOTED, BUT THE WATER HAMMER ARRESTORS | | | ARE STILL SHOWN IN THE CEILING AND NOT DOWN NEAR THE | | | FIXTURES IN AN "EFFECTIVE RANGE" AS REQUIRED. | | | ********NO RESPONSE, COMMENT NOT ADDRESSED. | | | | | | 9. OK | | | 10. OK | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2009-03-26 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-03-26 |
Time |
08:36 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-03-25 |
Time |
17:12 |
Sent To |
|
|
| Notes |
| 2009-03-26 08:47:38 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | | | | ****FROM PREVIOUS REVIEW: | | | | | | ******FROM PREVIOUS REVIEWS: | | | | | | 1. OK | | | 2. OK | | | 3. OK | | | 4. OK | | | | | | 5. OK | | | | | | ___FOR SINKS: | | | A. OK | | | B. OK | | | C. 11-4.24.4 SINK DEPTH (PROVISO) | | | D. OK | | | E. OK | | | F. OK | | | G. OK | | | | | | 6. SHT P-3 MORE INFORMATION IS REQUIRED. PLEASE | | | INDICATE WHAT THE HOSE REELS WILL BE WASHING OFF. WHAT | | | WILL HAPPEN TO THE WATER USED TO WASH OFF WHATEVER IS | | | BEING WASHED OFF? WILL THERE BE ANY CHANCE OF GREASE OR | | | OIL WASHED OFF? PLEASE CLARIFY. SECTIONS 106.1.2 & | | | 301.2. MORE COMMENTS MAY FOLLOW DEPENDING TO THE | | | COMMENT RESPONSES TO THESE QUESTIONS. | | | ****RESPONSE NOTED, COMMENT NOT ADDRESSED. | | | ******RESPONSE NOTED, BUT THE SECTION OF THE COMMENT | | | ABOUT WHAT WILL HAPPEN TO THE WATER, (AND NOW THE MUD), | | | HAS NOT BEEN ADDRESSED. THERE IS NO INDICATION OF HOW | | | THE WALLS WILL BE PROTECTED FROM THE STANDING WATER IN | | | THE MAINTENANCE BUILDING, NO INDICATION OF SLOPING OF | | | THE FLOORS AWAY FROM THE WALLS, NO WALL FINISH SCHEDULE | | | INDICATING WATER PROOFING OF WALLS ETC. SECTION 301.2 | | | SYSTEM INSTALLATION. PLUMBING SHALL BE INSTALLED WITH | | | DUE REGARD TO PRESERVATION OF THE STRENGHT OF | | | STRUCTURAL MEMBERS AND PREVENTION OF DAMAGE TO WALLS | | | AND OTHER SURFACES THROUGH FIXTURE USAGE. PLEASE | | | CLARIFY. | | | | | | 7. OK | | | | | | 8. SHT P-4 WATER RISER DIAGRAM. WATER HAMMER ARRESTORS | | | SHALL BE LOCATED NEAR THE FIXTURE IN AN "EFFECTIVE | | | RANGE" NOT IN THE CEILING AS SHOWN. PDI-WH 201. WATER | | | HAMMER ARRESTORS ARE REQUIRED AT THE REFRIGERATOR ICE | | | MAKER LINES. SECTION 604.9. -- A SHUT OFF VALVE IS | | | REQUIRED ON THE SUPPLY LINE TO THE WALL HYDRANT NEAR | | | OFFICE ROOM 102. SECTION 606.2(2). | | | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. MOST | | | WATER HAMMER ARRESTORS DO NOT REQUIRE ACCESS AND THE | | | PDI-WH 201 GUIDLINES SHOW THE WATER HAMMER ARRESTORS | | | NEAR THE FIXTURES, NOT IN THE CEILING. | | | ******RESPONSE NOTED, BUT THE WATER HAMMER ARRESTORS | | | ARE STILL SHOWN IN THE CEILING AND NOT DOWN NEAR THE | | | FIXTURES IN AN "EFFECTIVE RANGE" AS REQUIRED. | | | | | | 9. OK | | | 10. OK | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2009-01-27 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-01-27 |
Time |
10:19 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-01-27 |
Time |
10:19 |
Sent To |
|
|
| Notes |
| 2009-01-27 10:44:07 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | | | | ****FROM PREVIOUS REVIEW: | | | | | | 1. OK | | | 2. OK | | | 3. OK | | | 4. OK | | | | | | 5. SUBMIT DETAILS FOR THE ACCESSIBLE FIXTURES SHOWING | | | COMPLIANCE WITH THE FOLLOWING: | | | | | | ___FOR DRINKING FOUNTAIN: | | | A. OK | | | | | | ___FOR W/C'S: | | | A. 11-4.16.2 CLEAR FLOOR SPACE | | | ****RESPONSE NOTED, BUT THE CLEAR FLOOR SPACE IS NOT | | | SHOW IN TOILET ROOMS 120 & 121. | | | B. 11-4.16.5 FLUSH CONTROLS | | | ****RESPONSE NOTED, BUT NO INDICATION OF THE | | | REQUIREMENT FOR CONTROLS TO THE WIDE SIDE OF THE | | | TOILET. | | | C. W/C TO BE 18" OFF THE WALL TO THE C/L OF THE | | | FIXTURE. FIGURES 28 AND 30E. | | | ****RESPONSE NOTED, BUT THE W/C'S IN TOILET ROOMS 120 & | | | 121 NOT ADDRESSED. | | | | | | ___FOR URINALS: | | | A. OK | | | B. OK | | | | | | ___FOR LAVS: | | | A. 11-4.19.3 CLEAR FLOOR SPACE | | | ****RESPONSE NOTED, BUT THE CLEAR FLOOR SPACE IS NOT | | | SHOW IN TOILET ROOMS 120 & 121. | | | B. 11-4.19 4 EXPOSED PIPES & SURFACES | | | ****NO RESPONSE, COMMENT NOT ADDRESSED. | | | C. OK | | | D. LAVS TO BE A MINIMUM 15" OFF WALL TO C/L OF FIXTURE. | | | FIG. 32. | | | ****RESPONSE NOTED, BUT THE LAV'S IN TOILET ROOMS 120 & | | | 121 NOT ADDRESSED. | | | | | | ___FOR SHOWERS: | | | A. 11-4.21.2 SIZE & CLEARANCES | | | ****NO RESPONSE, COMMENT NOT ADDRESSED | | | B. 11-4.21.3 SEAT | | | ****HEIGHT NOT INDICATED. | | | C. 11-4.21.4 GRAB BARS | | | ****NOT SHOWN AS REQUIRED IN FIGURE 37. ALSO SHOW THE | | | HEIGHT. | | | D. 11-4.21.5 CONTROLS | | | ****THE LOCATION OF THE CONTROLS NOT SHOWN. | | | E. 11-4.21.6 SHOWER UNIT | | | ****NO RESPONSE, COMMENT NOT ADDRESSED. | | | F. 11-4.21.7 CURBS | | | ****NO RESPONSE, COMMENT NOT ADDRESSED. | | | | | | ___FOR TOILET ROOMS: | | | A. 11-4.22.2 DOOR SWING | | | ****NO RESPONSE, COMMENT NOT ADDRESSED FOR TOILET ROOMS | | | 120 & 121. | | | B. 11-4.22.3 TURNING AREA | | | ****NO RESPONSE, COMMENT NOT ADDRESSED FOR TOILET ROOMS | | | 120 & 121. | | | | | | ___FOR BATHROOMS: | | | A. OK | | | B. OK | | | | | | | | | ********** NOTE: PER SECTION 11-4.1.3(11) IF TOILET | | | ROOMS ARE PROVIDED, THEN EACH PUBLIC AND COMMON USE | | | TOILET ROOM SHALL COMPLY WITH SECTION 11-4.22. COMMENT | | | RESPONSE "IT SHOULD BE NOTED THAT TOILET ROOMS 120 & | | | 121 ARE NOT INTENDED TO ACCOMMODATE THE PHYSICALLY | | | DISABLED" IS NOT ACCEPTABLE. PLEASE SHOW COMPLIANCE. | | | | | | ___FOR SINKS: | | | A. 11-4.24.2 HEIGHT | | | B. 11-4.24.3 KNEE CLEARANCE | | | C. 11-4.24.4 SINK DEPTH | | | D. 11-4.24.5 CLEAR FLOOR SPACE. FORWARD APPROACH | | | REQUIRED. CABINET DOORS NOT APPROVED. | | | E. 11-4.24.6 EXPOSED PIPES & SURFACES | | | F. 11-4.24.7 FAUCETS | | | G, 11-4.2.3 AN UNOBSTRUCTED TURNING AREA | | | ****NO RESPONSE TO A THRU G AND COMMENTS NOT ADDRESSED. | | | THIS IS FOR THE KITCHEN/BREAK ROOM. SUBMIT AN ELEVATION | | | DETAIL SHOWING ALL INFORMATION REQUIRED. | | | | | | 6. SHT P-3 MORE INFORMATION IS REQUIRED. PLEASE | | | INDICATE WHAT THE HOSE REELS WILL BE WASHING OFF. WHAT | | | WILL HAPPEN TO THE WATER USED TO WASH OFF WHATEVER IS | | | BEING WASHED OFF? WILL THERE BE ANY CHANCE OF GREASE OR | | | OIL WASHED OFF? PLEASE CLARIFY. SECTIONS 106.1.2 & | | | 301.2. MORE COMMENTS MAY FOLLOW DEPENDING TO THE | | | COMMENT RESPONSES TO THESE QUESTIONS. | | | ****RESPONSE NOTED, COMMENT NOT ADDRESSED. | | | | | | 7. OK | | | | | | 8. SHT P-4 WATER RISER DIAGRAM. WATER HAMMER ARRESTORS | | | SHALL BE LOCATED NEAR THE FIXTURE IN AN "EFFECTIVE | | | RANGE" NOT IN THE CEILING AS SHOWN. PDI-WH 201. WATER | | | HAMMER ARRESTORS ARE REQUIRED AT THE REFRIGERATOR ICE | | | MAKER LINES. SECTION 604.9. -- A SHUT OFF VALVE IS | | | REQUIRED ON THE SUPPLY LINE TO THE WALL HYDRANT NEAR | | | OFFICE ROOM 102. SECTION 606.2(2). | | | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. MOST | | | WATER HAMMER ARRESTORS DO NOT REQUIRE ACCESS AND THE | | | PDI-WH 201 GUIDLINES SHOW THE WATER HAMMER ARRESTORS | | | NEAR THE FIXTURES, NOT IN THE CEILING. | | | | | | 9. SHT PD-1 EWH-1 WATER HEATER DETAIL STATES "EXPANSION | | | TANK SEE SPECIFICATIONS". SPECIFICATIONS WERE NOT | | | SUBMITTED. PLEASE SUBMIT CALCULATIONS OR MANUF. CHART | | | INDICATING THE MODEL AND CORRECT SIZING OF THE | | | EXPANSION TANK. SECTION 607.3.2. | | | ****RESPONSE NOTED, BUT THE ATTACHED MANUFACTURER'S | | | SIZING GUIDELINES WERE NOT FOUND. PLEASE INDICATE WHERE | | | THE GUIDELINES WERE ATTACHED AND CAN BE LOCATED. | | | | | | 10. SHT PD-1 A FLOOR DRAIN IS NOT AN APPROVED INDIRECT | | | WASTE RECEPTOR. A FLOOR SINK OR HUB DRAIN IS REQUIRED | | | FOR THE P&T RELIEF VALVE AND EMERGENCY PAN DRAIN LINES. | | | SECTIONS 504.6.1, 504.7.2, 802.3 & 802.3.2. THE | | | INDIRECT WASTE RECEPTOR SHALL BE LOCATED NEAR THE WATER | | | HEATER SO THE RELIEF AND PAN DRAIN LINES DO NOT PRESENT | | | A TRIPPING HAZARD. | | | ****RESPONSE NOTED, BUT THE FLOOR DRAIN IS STILL NOT AN | | | APPROVED INDIRECT WASTE RECEPTOR. COMMENT NOT COMPLETLY | | | ADDRESSED. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2008-10-03 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-10-03 |
Time |
11:12 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-10-02 |
Time |
15:57 |
Sent To |
|
|
| Notes |
| 2008-10-03 14:03:52 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | | | | 1. SHT CD-6 IS NOT SIGNED, SEALED & DATED AS REQUIRED | | | IN SECTION 106.1, THE FLORIDA ADMINISTRATIVE CODE & | | | FLORIDA STATUTES. | | | | | | 2. SHT A-1 BARRIER-FREE FIXTURE MOUNTING HEIGHT SHOWS | | | THE GRAB BAR FOR THE W/C ON THE SIDEWALL TO BE 40". | | | MINIMUM LENGTH IS 42" PER FIG 29 & SECTION 11-4.16.4. | | | | | | 3. SHT A-3 BUILDING CODE ANALYSIS FOR OPERATIONS & | | | MAINTENANCE BLDGS SHALL INCLUDE THE 2005, 2006 & 2007 | | | REVISIONS/AMENDMENTS. PLEASE INDICATE ON PLANS. SECTION | | | 106.1.1. | | | | | | 4. SHT A-3 MAINTENANCE BUILDING FIXTURE REQUIREMENTS | | | PER TABLE 403.1 ARE NOT INDICATED. IF USING THE | | | EXCEPTION TO SECTION 403.4, THEN THIS MUST BE STATED ON | | | THE PLANS AS WELL AS THE DISTANCE FROM THE MAINTENANCE | | | BUILDING TO THE OPERATIONS BUILDING FACILITIES. SECTION | | | 106.1.1. | | | | | | 5. SUBMIT DETAILS FOR THE ACCESSIBLE FIXTURES SHOWING | | | COMPLIANCE WITH THE FOLLOWING: | | | | | | ___FOR DRINKING FOUNTAIN: | | | A. 11-4.15.5 CLEAR FLOOR SPACE | | | | | | ___FOR W/C'S: | | | A. 11-4.16.2 CLEAR FLOOR SPACE | | | B. 11-4.16.5 FLUSH CONTROLS | | | C. W/C TO BE 18" OFF THE WALL TO C/L OF FIXTURE. | | | FIGURES 28 & 30E | | | | | | ___FOR URINALS: | | | A. 11-4.18.3 CLEAR FLOOR SPACE | | | B. 11-4.18.4 FLUSH CONTROLS | | | | | | ___FOR LAVS: | | | A. 11-4.19.3 CLEAR FLOOR SPACE | | | B. 11-4.19 4 EXPOSED PIPES & SURFACES | | | C. 11-4.19.5 FAUCETS | | | D. LAVS TO BE A MINIMUM 15" OFF WALL TO C/L OF FIXTURE. | | | FIG. 32. | | | | | | ___FOR SHOWERS: | | | A. 11-4.21.2 SIZE & CLEARANCES | | | B. 11-4.21.3 SEAT | | | C. 11-4.21.4 GRAB BARS | | | D. 11-4.21.5 CONTROLS | | | E. 11-4.21.6 SHOWER UNIT | | | F. 11-4.21.7 CURBS | | | | | | ___FOR TOILET ROOMS: | | | A. 11-4.22.2 DOOR SWING | | | B. 11-4.22.3 TURNING AREA | | | | | | ___FOR BATHROOMS: | | | A. 11-4.23.2 DOOR SWING | | | B. 11-4.23.3 TURNING AREA | | | | | | ___FOR SINKS: | | | A. 11-4.24.2 HEIGHT | | | B. 11-4.24.3 KNEE CLEARANCE | | | C. 11-4.24.4 SINK DEPTH | | | D. 11-4.24.5 CLEAR FLOOR SPACE. FORWARD APPROACH | | | REQUIRED. CABINET DOORS NOT APPROVED. | | | E. 11-4.24.6 EXPOSED PIPES & SURFACES | | | F. 11-4.24.7 FAUCETS | | | G, 11-4.2.3 AN UNOBSTRUCTED TURNING AREA | | | | | | 6. SHT P-3 MORE INFORMATION IS REQUIRED. PLEASE | | | INDICATE WHAT THE HOSE REELS WILL BE WASHING OFF. WHAT | | | WILL HAPPEN TO THE WATER USED TO WASH OFF WHATEVER IS | | | BEING WASHED OFF? WILL THERE BE ANY CHANCE OF GREASE OR | | | OIL WASHED OFF? PLEASE CLARIFY. SECTIONS 106.1.2 & | | | 301.2. MORE COMMENTS MAY FOLLOW DEPENDING TO THE | | | COMMENT RESPONSES TO THESE QUESTIONS. | | | | | | 7. SHT P-4 SANITARY RISER DIAGRAM. THE VENT FOR THE | | | CLEANOUTS AT THE END OF EACH GANG BATH IS NOT APPROVED. | | | THESE ARE HORIZONTAL DRY VENTS. SECTION 905.3. (VENTS | | | ARE NOT REQUIRED FOR CLEANOUTS AND CAN BE DELETED). | | | | | | 8. SHT P-4 WATER RISER DIAGRAM. WATER HAMMER ARRESTORS | | | SHALL BE LOCATED NEAR THE FIXTURE IN AN "EFFECTIVE | | | RANGE" NOT IN THE CEILING AS SHOWN. PDI-WH 201. WATER | | | HAMMER ARRESTORS ARE REQUIRED AT THE REFRIGERATOR ICE | | | MAKER LINES. SECTION 604.9. -- A SHUT OFF VALVE IS | | | REQUIRED ON THE SUPPLY LINE TO THE WALL HYDRANT NEAR | | | OFFICE ROOM 102. SECTION 606.2(2). | | | | | | 9. SHT PD-1 EWH-1 WATER HEATER DETAIL STATES "EXPANSION | | | TANK SEE SPECIFICATIONS". SPECIFICATIONS WERE NOT | | | SUBMITTED. PLEASE SUBMIT CALCULATIONS OR MANUF. CHART | | | INDICATING THE MODEL AND CORRECT SIZING OF THE | | | EXPANSION TANK. SECTION 607.3.2. | | | | | | 10. SHT PD-1 A FLOOR DRAIN IS NOT AN APPROVED INDIRECT | | | WASTE RECEPTOR. A FLOOR DRAIN OR HUB DRAIN IS REQUIRED | | | FOR THE P&T RELIEF VALVE AND EMERGENCY PAN DRAIN LINES. | | | SECTIONS 504.6.1, 504.7.2, 802.3 & 802.3.2. THE | | | INDIRECT WASTE RECEPTOR SHALL BE LOCATED NEAR THE WATER | | | HEATER SO THE RELIEF AND PAN DRAIN LINES DO NOT PRESENT | | | A TRIPPING HAZARD. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2009-05-26 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2009-05-26 |
Time |
17:24 |
Rev Time |
0.50 |
| Received By |
eschneid |
Date |
2009-05-26 |
Time |
17:23 |
Sent To |
|
|
| Notes |
| 2009-05-26 17:25:13 | PASSED | | | | | | SIGNAGE AND ANY NEW FENCING REQUIRE SEPARATE PERMITS. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2009-04-20 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2009-04-20 |
Time |
15:55 |
Rev Time |
0.25 |
| Received By |
eschneid |
Date |
2009-04-20 |
Time |
15:55 |
Sent To |
|
|
| Notes |
| 2009-04-20 16:01:36 | FAILED - REVIEW COMPLETED ON 3/12. | | | | | | THE FOLLOWING CONDITIONS FROM THE 3/12/09 SITE PLAN | | | APPROVAL LETTER HAVE NOT BEEN ADDRESSED: | | | | | | A. THE BICYCLE RACK SHOWN ON ALL PLANS SHALL MATCH THE | | | DETAIL SHOWN ON SHEET CD-2, INCLUDING ALL DIMENSIONS. | | | B. THE WHEEL STOP DETAIL ON SHEET CD-2 SHALL CONFORM TO | | | THE CITY OF WEST PALM BEACH STANDARD WHEEL STOP SHOWN | | | ON FIGURE XIV-2 OF CHAPTER 94 OF THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS. | | | C. WHEEL STOPS SHALL BE PROVIDED AT ALL PARKING SPACES | | | SINCE THE PARKING SPACES DO NOT MEET THE OVERHANG | | | REQUIREMENTS SHOWN ON FIGURE XIV-2 OF CHAPTER 94 OF THE | | | ZONING AND LAND DEVELOPMENT REGULATIONS. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1435. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2008-12-18 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2008-12-18 |
Time |
15:54 |
Rev Time |
0.00 |
| Received By |
eschneid |
Date |
2008-12-18 |
Time |
15:54 |
Sent To |
|
|
| Notes |
| 2008-12-18 16:01:12 | FAILED | | | | | | ALL REPEAT COMMENTS. | | | | | | 1) THE CITY STAFF COMMENTS PROVIDED AS PART OF THE | | | FORMAL SITE PLAN HAVE NOT BEEN SUFFICIENTLY ADDRESSED | | | AND THEREFORE THE FORMAL SITE PLAN IS NOT APPROVED. | | | | | | 2) THE PLANS SUBMITTED WITH THIS PLAN REVIEW ARE THE | | | SAME AS THE PLANS THAT WERE INSUFFICIENT DURING THE | | | FORMAL SITE PLAN REVIEW. | | | | | | 3) ZONING WILL NOT REVIEW PLANS SUBMITTED TO THE | | | CONSTRUCTION SERVICES DEPARTMENT UNTIL THE FORMAL SITE | | | PLAN HAS BEEN APPROVED. NOTE THE PLANS REVIEWED AS PART | | | OF THE BUILDING PERMIT APPLICATION SHALL BE THE SAME AS | | | THOSE APPROVED DURING THE FORMAL SITE PLAN PROCESS. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1435. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2008-10-01 |
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
eschneid |
Date |
2008-10-01 |
Time |
08:44 |
Sent To |
|
|
| Notes |
| 2008-10-01 08:46:53 | FAILED | | | | | | THIS PROJECT IS REQUIRED TO HAVE APPROVAL OF A FORMAL | | | SITE PLAN REVIEW BY THE PLANNING AND ZONING DEPARTMENT | | | PRIOR TO THE SUBMITTAL FOR BUILDING PERMIT. CODE | | | COMPLIANCE WILL BE REVIEWED AT THE TIME OF FORMAL SITE | | | PLAN APPLICATION. | | | | | | CONTACT KELLY FREEMAN @ (561) 822-1435 FOR APPLICATION | | | PROCEEDURE. |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |